Marathon Special Products 602 GP XX Data Sheet

Product Data Sheet
30 Amps, 300 Volts
602 GP XX
Replace “XX” with 01 through 26 for number of poles
Terminal Block– Open Back
Insulator Strip Required for Voltage Rating
Copper Wire Only
Wire Range with Wire Binding Screw: #10 - #18 AWG Solid 9/16” Centers Application torque: 16 in. lbs
30A with Listed ring lug or unprepared wire, (Based on NEC Table 310-16, 75°C columns)
300 Volts AC/DC (UL 1059 Class B, User Group – Commercial Appliances)
Short Circuit Current Rating: 10,000A (Default)
Approved for Factory and Field Wiring.
(AC/DC)
(6 Pole shown)
Mechanical Ratings:
nsulator base temperature: -40°C to 150°C (302°F)* UL RTI
I
Flammability rating of insulator base: UL 94V-1
* Use outside these ratings needs to be judged in the end-use application.
Materials:
Connector (Eyelet): Brass, nickel plated.
Insulator base: General Phenolic
Screw, #8-32 Binder head, Phil-Slot: Steel, nickel plated Agency Approvals:
UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E47811
CSA Certified, CSA C22.2 No. 158, File No. LR19766
CE compliant, IEC 60947-7-1
RoHS Compliant
Wire Range:
Wire Size
Torque
Solid
Class B
Class C
10
16 in. Lbs
1
14
16 in. Lbs
11616 in. Lbs
1
Copper Wire Stranding Classes - Number of Conductors
12 16 in. Lbs 1
18 16 in. Lbs 1
M
ounting: #8 fastener, torque to 15 - 20 in. lbs.
Accessories:
J (GDI-30F) Material available. Glass-fiber filler, diallyl ortho-phthalate. UL-94 V0. Certifiable to
J Military Specifications MIL-M-14 and MIL-P-19833.
Printing (for printing options, see Terminal Block Printing on website)
Marking strips - sub mounted, black only (FB) (For Printing Options, see
section on website)
Marking strips – top mounted, white only (SW)
Insulator strips - sub mounted, black only (BB) (Printing Unavailable).
Insulator Strip will be the same width as the molding.
Cover – top mounted. Order CW (white) or CB (Black). Can be printed. See website.
Phil-Slot Brass Screw (PSB)
Loading...