![](/html/55/5533/5533e4ef9d8c5ae1c794d6e8efd9650e1bf74c780b4028127386057564a83805/bg1.png)
Product Data Sheet
3XX Series SP
Replace “XX” with 01 through 24 for number of poles
Terminal Block– Closed Back
With Sems Pressure Saddle Screw
30 Amps, 600 Volts (AC/DC)
Copper Wire Only
Wire Range with Wire Binding Screw: #10 - #22 AWG
(stranded wire only)
Application torque: 20 in. lbs
9/16” Centers
Electrical Ratings:
• 30A with Listed ring lug or unprepared wire, (Based on NEC Table 310-16, 75°C columns)
• 600 Volts AC/DC (UL 1059 Class C, Use Group - General Industrial)
• Short Circuit Current Rating: 10,000A (Default)
• Factory and Field Wiring.
NOTE: Use outside these ratings must be judged in end-use application
Mechanical Ratings:
• Insulator base temperature rating: -40° C/F to 150°C (302°F) UL RTI
• Flammability rating of insulator base: UL 94V-0
Materials:
• Connector (Contact): Brass, tin plated.
• Insulator base: Phenolic
• Drive screw (Rivet): Stainless steel
• Screw, #8-32 saddle plate, phil-slot: Steel, nickel plated
Agency Approvals:
• UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E62806
• CSA Certified, CSA C22.2 No. 158, File No. LR19766
• CE compliant, IEC 60947-7-1
• RoHS Compliant
![](/html/55/5533/5533e4ef9d8c5ae1c794d6e8efd9650e1bf74c780b4028127386057564a83805/bg2.png)
Wire Range:
Copper Wire Stranding Classes - Number of Conductors
Wire Size Torque Solid Class B Class C
Mounting:
Suggested product mounting hardware: #8 fastener, torque to 15-20 in. lbs.
Accessories: