Product Data Sheet
17XX STD
Replace XX with 02 thru 12 for number of poles
1700 Series
30 Amps, 600 Volts AC/DC
(Unprepared Wire)
or
75 Amps, 600 Volts AC/DC when
wired with crimp type ring, spade or
fork terminal
/8” Line to Line Spacing
5
Wire Range (with unprepared wire):
#10 - #18 AWG Copper
See tables below for wire sizes.
Electrical Ratings:
• 30A (unprepared wire) (Based on NEC Table 310-16, 75°C columns)
• 75A (when wired with crimp type ring, spade or fork terminal) (Based on NEC Table
310-16, 75°C columns)
• 600 Volts AC/DC (UL 1059 Class C, User Group - General Industrial)
• Short Circuit Current Rated for 10,000 Amps.
• Factory and Field Wiring
Mechanical Ratings:
• Maximum insulator base temperature: 125°C (257°F) UL RTI
• Storage and transportation temperature range: -35°C to 110°C (-31°F to 230°F)
• Flammability rating of insulator base: UL 94 V-0
• Use outside these ratings needs to be judged in the end-use application.
Materials:
Copper Wire Stranding Classes - Number of Strands
• Connector: Brass, nickel plated
• Insulator base: Glass-filled polycarbonate (thermoplastic)
• Screws: Brass, nickel plated, 10-32
• Marking Strip: Vinyl (white)
• Marking strip anchor screws: Steel, zinc plated
Agency Approvals:
• UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E62806
• CSA Certified, CSA C22.2 No. 158, File No. LR19766
• CE compliant to IEC 60947-7-1
• RoHS Compliant
Wire Approvals:
• Panel mountable: #10 fastener, torque to 25-30 in. lbs.
Accessories:
• Cover: Clear PVC snap on cover, sized to fit and protect, CC17 XX (substitute XX for
number of poles)
• Din Rail Adapter: Din R-1
• Din Rail Channel: MN 35 (6’6” max, but can be cut to length)
• Printing Available on Marking Strip