Product Data Sheet
15XX DJSV
Replace XX with 02, 04, 06, 08 or 12 for number of poles
1500 Series
30 Amps, 600 Volts AC/DC
(Unprepared Wire)
or
75 Amps, 600 Volts AC/DC when
wired with crimp type ring, spade or
fork terminal
8 pole shown
/8” Line to Line Spacing
5
Wire Range (with unprepared wire):
#10 - #16 AWG Copper
Wire Range will vary with Lug size
S
ee tables below for wire sizes.
Electrical Ratings:
• 30A (unprepared wire) (Based on NEC Table 310-16, 75°C columns)
• 75A (when wired with crimp type ring, spade or fork terminal) (Based on NEC Table
310-16, 75°C columns)
• 600 Volts AC/DC (UL 1059 Class C, User Group - General Industrial)
• Short Circuit Current Rated for 10,000 Amps.
• Factory and Field Wiring
Mechanical Ratings:
• Maximum insulator base temperature: 150°C (302°F) UL RTI
• Storage and transportation temperature range: -35°C to 125°C (-31°F to 257°F)
• Flammability rating of insulator base: UL 94 V-0
• Use outside these ratings needs to be judged in the end-use application.
Removable Connector
with Brass Insert
Removable Cover
aterials:
Copper Wire Stranding Classes - Number of Strands
M
• Connector: Brass, nickel plated
• Insulator base: phenolic
• Screws: Brass, nickel plated, 10-32
• Marking Strip: Vinyl (white)
• Marking strip anchor screws: Steel, zinc plated
Agency Approvals:
• UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E62806
• CSA Certified, CSA C22.2 No. 158, File No. LR19766
• CE compliant to IEC 60947-7-1
• RoHS Compliant
Wire Approvals (with unprepared wire):
• Panel mountable: #10 fastener, torque to 25-30 in. lbs.
Accessories:
• MCJ (Multi-Circuit Jumper) Bar Available: Only sold loose and the
marking strip must be removed to assemble MCJ bar on part.
• Clear cover: Thermoplastic, UL Recognized QMFZ2 - order CC 15XX (XX
representing number of poles). See Data Sheet CC 15XX
• Sems Pressure Saddle Screw with External Lock Washer (SPSE)
• Printing Available
Consult factory for custom printed applications