![](/html/14/14c7/14c764403d00b8522a20a75edb5cc6066849a43287658ab622bb9a93fe504a23/bg1.png)
POWER DISTRIBUTION BLOCK
1343595
Wire Range
• Line: (1) 600kcmil - #2 AWG (300mm2 - 25mm2)
• Load: (12) #4 - 14 AWG (16mm2 - 2.5mm2)
Electrical Ratings
• 420 Amps
• 600V per UL 1059 & CSA 22.2 No.158, class B & C requirements
• Short circuit current ratings (SCCR): See SCCR section for specifications.
• CU7AL - 75°C connector terminal rating with copper or aluminum wire
• Factory & Field Wiring
Agency Compliance
• UL Listed, Investigated to UL 1953, File QPQS7.E309401
Material Information
• Insulator base:
• Thermoplastic
• Flammability rating of insulator base UL94V0
• Insulator base temperature rating: -40°C to 125°C (UL RTI)
• Connector: aluminum, tin plated
• Line terminal set screw: aluminum, tin plated
• Load terminal set screws: steel, nickel plated
• Connector mounting screws: steel, zinc plated
• RoHS compliant
1
![](/html/14/14c7/14c764403d00b8522a20a75edb5cc6066849a43287658ab622bb9a93fe504a23/bg2.png)
Product Data Sheet
Termination Specications
Line Side
Wire Size
(CU Stranded)
Torque
600 - 500 kcmil 42.4 N·m (375 lbf·in) 1 B, C
400 - 2 42.4 N·m (375 lbf·in) 1 B, C, G, H
• Aluminum stranded wire range: 600 kcmil - #2 AWG
• Wire strip length: 1 9/16in. (40mm)
• Terminal screw drive: 1/2in. hex
Load Side
Wire Size
(CU Stranded)
Torque
4 AWG 4 N·m (35 lbf·in) 1 B, C
6 - 8 4 N·m (35 lbf·in) 1 B, C, G, H, I (DLO)
Wires /
Terminal
Wires /
Terminal
Wire Class (UL)
Wire Class (UL)
1
1
10 4 N·m (35 lbf·in) 1-2 B, C, G, H, I (DLO)
12 - 14 4 N·m (35 lbf·in)
• Solid copper wire range: #10 - 8 AWG
• Aluminum stranded wire range: #4 - 6 AWG
• Wire strip length:
• top row: 1/2 in. (13mm)
• middle row: 11/16 in. (18mm)
• bottom row: 15/16 in. (24mm)
• Terminal screw drive: 1/8 in. hex
1-4 B, C
1-2 G, H,
I (DLO)
2 05/17/2018