Product Data Sheet
0987 RZ TC XX
Replace XX with 02 thru 12 for number of poles
0987 Series
Deadfront Type
50 Amps, 600 Volts AC/DC
ire Range:
W
#8 - #24 AWG Copper Wire Only
.475” Centerline spacing
See tables below for wire sizes.
(7 Pole shown)
Electrical Ratings:
• 50A (Based on NEC Table 310-16, 75°C columns)
• 600 Volts AC/DC (UL 1059 Class C, User Group - General Industrial)
• Short Circuit Current Rated for 10,000 Amps.
• Factory and Field Wiring
Mechanical Ratings:
• Maximum insulator base temperature: 125°C (257°F) UL RTI
• Storage and transportation temperature range: -35°C to 110°C (-31°F to 230°F)
• Flammability rating of insulator base: UL 94 V-0
• Protection rating: IP-20 (IEC standard 60529)
• Use outside these ratings needs to be judged in the end-use application.
M
aterials:
• Connector: Copper Alloy, Nickel plated
• Insulator base: Glass-filled Polycarbonate (Thermoplastic)
• Terminal set screws: Steel, nickel plated
Agency Approvals:
• UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E47811
• CSA Certified, CSA C22.2 No. 158, File No. LR19766
• CE compliant to IEC 60947-7-1
• RoHS Compliant
Copper Wire Stranding Classes - Number of Strands
Wire Approvals:
*
Multiple conductors can be used for these sizes. NOTE: When using multiple
conductors, the torque must be increased to 20 in.lbs.
* May also combine (1) #12 AWG wire with (1) #14 AWG wire
• Wire strip length – 7/16”
• Panel mountable: #6 fastener, torque to 10-15 in. lbs.
Accessories:
• Printing Available: