Maple Systems HMI5056T, Silver Plus, HMI5104T, HMI5104X, HMI5121T Installation Manual

...
Installation Guide
808 134th Street SW Suite 120 u Everett WA 98204u (425) 745-3229
www.maplesystems.com umaple@maple-systems.com
1010-1006, Rev 01
2 Sil ver Plus Se ries
1010-1006, Rev 01
Thank you for purchasing a Maple Systems Silver Plus Series OIT. You have selected a rugged, reliable, and powerful operator interface for your application. This booklet describes the steps necessary to ensure easy installation of your Silver Plus Series OIT.
Please read this booklet carefully.
Static Aware ness
It is best NOT to remove the rear cover on the OIT. When the rear cover is removed the circuitry inside is exposed to possible damage by electrostatic discharge during handling. Minimize the possibility of electrostatic discharge by:
Discharging personal static by grounding yourself prior to handling the OIT.
Handling the OIT at static-free, grounded work station.
Connecting the chassis of the OIT to a clean ground.
Placing the OIT into an anti-static bag during transport.
Un pack ing the Unit
Carefully unpack the OIT. Please read any instructions or cautions that appear on the shipping container. Check all material in the container against the enclosed packing list. Maple Systems, Inc., will not accept responsibility for shortages against the packing list unless notified within 30 days. The equipment and its accessories were inspected and tested by Maple Systems before shipment; all of the equipment should be in good working order. Examine the equipment carefully; if any shipping damage is evident, notify the carrier immediately. You are responsible for claim negotiations with the carrier. Save the shipping container and packing material in case the equipment needs to be stored, returned to Maple Systems, or transported for any reason.
War ranty
Maple Systems warrants each product to be free from electrical and mechanical defects in materials and workmanship for a period of two years from the date of shipment. This warranty does not apply to defects in the Products caused by abuse, misuse, accident, casualty, alteration, negligence, repair not authorized by Maple Systems, use on current or voltages other than specified by Maple Systems, or application or installation not in accordance with published instruction manuals. This warranty is in lieu of any other warranty either expressed or implied.
Maple Systems’ liability is limited to the repair or replacement of the Product only, and not costs of installation, removal, or damage to user’s property or other liabilities. If Maple Systems is unable to repair or replace a nonconforming Product, it may offer a refund of the amount paid to Maple Systems for such Product in full satisfaction of its warranty obligation. Maximum liability of Maple Systems is the cost of the Product.
Information furnished by Maple Systems, Inc., is believed to be accurate and reliable. However, no responsibility is assumed by Maple Systems for the use of this information nor for any infringements of patents or other rights of third parties which may result from its use. No license is granted by implication, or otherwise, under any patent or patent rights of Maple Systems, Inc. Maple Systems retains the right to revise or change its products and documentation at any time without notice.
In stal la tion Guide 3
1010-1006, Rev 01
Installation of OITs
CE Com pli ance
The Silver Plus Series OITs have been tested to conform to European CE requirements per Council Directive 89/336/EEC. The European Union created these requirements to ensure conformity among products traded in those countries. Specifically, the Silver Plus Series OITs meet or exceed the noise emissions and immunity requirements as set forth in the EN50081 (Emissions) and EN50082 (Immunity) standards. These products are designed to withstand electrical noise in harsh industrial environments. They also conform to requirements that limit electrical emissions. However, this does not guarantee that the products will be totally immune from possible malfunction in cases where severe electrical noise occurs. Therefore, we strongly recommend that you follow the guidelines outlined in this chapter for proper wire routing and grounding to insure the proper operation of the Silver Plus Series OIT.
NEMA Rat ing
The Silver Plus Series OITs are rated for NEMA 4/12 (indoor) or IP65 installations. This means that when the OIT is properly mounted to a panel or other enclosure, the front enclosure of the OIT will provide protection to the inside of the panel from splashing water, wind blown dust, rain, or hose-directed water. The OIT must be installed according to the instructions in this manual to be properly sealed.
En vi ron men tal Con sid er ations
The Silver Plus Series is designed to operate in temperatures from 0-45° C. It is intended for indoor installations and not designed for outdoor applications. Avoid installing the Silver Plus Series in environments with severe mechanical vibration or shocks. Do not install the OIT in enclosures with rapid temperature variations or high humidity. Either will cause condensation of water inside the device and eventual damage to the OIT.
Safety Pre cau tions
Please observe the following precautions when installing the Silver Plus Series OIT. Failure to comply with these restrictions could result in loss of life, serious personal injury, or equipment damage.
Warning: Do not operate the OIT in areas subject to explosion due to flammable gases,
vapors, or dusts.
Warning: Do not connect the OIT to an AC power source. You will cause permanent
damage to the OIT.
4 Sil ver Plus Se ries
1010-1006, Rev 01
Warning: Do not attempt to use a DC power supply that does not meet OIT power
requirements. You may cause malfunction or permanent damage to the OIT.
Warning: Do not power the OIT with a DC power supply used for inductive loads or for
input circuitry to the programmable logic controller. Severe voltage spikes caused by these devices may damage the OIT.
Con trol Panel De sign Guide lines
Pay careful attention to the placement of system components and associated cable routing. These items can significantly enhance the performance and integrity of your control application.
Con trol Panel Ground ing
The control panel should be connected to a good, high-integrity earth ground, both for safety considerations and shielding purposes. Maple Systems cannot overemphasize the importance of good grounding. If you fail to use good grounding procedures during installation, sporadic malfunction of the OIT may occur:
Connect the OIT’s chassis ground terminal to a reliable earth ground with a
low-resistance path.
Route all earth ground wires that lead from the OIT, the PLC, the power supply, and the
line filter to a central earth ground point such as a barrier strip. This will ensure that no ground current from one device influences the operation of the other devices.
Connect the OIT chassis ground terminal to the control panel door using a heavy-gauge
short braided cable or ground wire to minimize resistance.
5 Sil ver Plus Se ries
1010-1006, Rev 01
I / O control lines
PLC/Host
Ground wires
(rear side)
OIT is grounded to control panel
Ground strap
Power line filter
Quiet ground (isolated)
Quiet ground
Line
Filter
OIT
Power
Supply
Shielded power cable
Shielded communication cable
Control panel is tied to a reliable earth ground
Silver Plus
SeriesOIT
24V
GND
COM1 [RS-485 2/4W]
PLC [RS-232]
COM3 [RS-485] COM3 [RS-232]
COM1 [RS-232] COM2 [RS-232]