Maple Systems Graphic HMIs Information Sheet

CONTROLLER INFORMATION SHEET
Maple Model(s) PLC or Controller
Graphic HMIs Siemens S7-200 SMART (PPI)
WARNING If your communications cable is not wired exactly as shown in our cable
assembly instructions, damage to the HMI or loss of communications can result.
The PLC station number cannot be the same as the HMI station number.
Summary
Maple Systems Graphic HMIs communicate with Siemens S7-200 SMART modules via PPI.
When configured with EZware, the Graphic HMI is the master in a point-to-point single master, single slave format. Please refer to the Installation and Operations Manual for information on connecting multiple Graphic HMIs to a single PLC port.
Communications
The Graphic HMI should be connected to the controller’s PPI port. A list of communications cables offered by Maple Systems as well as cable assembly instructions to assist you in assembling your own communications cable are available on our website at www.maplesystems.com.
PLC Controller Settings
Cab
le
. Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 – www.maplesystems.com
1036-0203 Page 1 of 4 Rev. 01, 10/11/2015
Accessible
PLC Register Type
Address Range
Format
PLC Register Description
MW
0-30
dd
Word Memory
VW
0-20478
ddddd
V Memory
SMW
0-1534
dddd
Special Memory
T
0-255
ddd
Timer
C
0-255
ddd
Counter
AIW
0-110
ddd
Analog Input
AQW
0-110
ddd
Analog Output
VD
0-20476
ddddd
V Memory (Double Word)
PLC Bit Type
Address Range
Format
PLC Bit Description
I
00-317
ddo
Input Bit (Read Only)
Q
00-317
ddddo
Output Bit
M
00-317
dddddo
Bit Memory
V
00-204797
dddddo
V Memory Bit
S
00-317
ddo
SCR
SM
00-15357
ddddo
Special Memory Bit
Timer
0-255
ddd
Timer
Counter
0-255
ddd
Counter
PLC
Mem
ory
Register Memory The following table lists the PLC’s register memory ranges that the Graphic HMIs are able to access. Please note that your PLC’s memory range may be smaller or larger than that supported by these HMIs. The following register memory can be displayed in 16-bit or 32-bit format on the Maple HMI.
(Note: d=decimal )
Discrete Memory The following table lists the PLC’s discrete memory ranges that the Graphic HMIs are able to access. Please note that your PLC’s memory range may be smaller or larger than that supported by these HMIs. The following discrete memory is displayable in single-bit format
on the Maple HMI.
(Note: d=decimal, o=octal)
Phone: 425/745-3229 • Fax: 425/745-3429 • Email: support@maplesystems.com • www.maplesystems.com 1036-0203 Page 2 of 4 Rev. 01, 10/11/2015
EZware Settings
Name
Recommended Settings
Options
Important Notes
Name:
Siemens S7-200 Smart (PPI)
Description label HMI or PLC
PLC
Location
Local
Local, Remote
Select Local if PLC directly connected to HMI, Remote if PLC connected thru another HMI.
PLC type:
Siemens S7-200 Smart (PPI)
PLC I/F:
RS485 2W
RS-232, RS-485 2W, RS-485 4W
Must match the controller port setting.
PLC default station no.:
2
1-126
Must match the node address assigned to the PLC.
Setting: COM:
COM1
COM1-COM3
Serial port of the HMI connected to the controller.
Settings: Baud rate
9600
9600, 19200,
187.5K
Must match the PPI port setting. Use the fastest baud rate supported by the controller.
Settings: Data Bits
8
7 or 8
Must match the PPI port setting.
Settings: Stop Bits
1
1 or 2
Must match the PPI port setting.
Settings: Parity:
Even
Even, Odd, None
Must match the PPI port setting.
The following table lists the communications settings that must be configured in EZware. These settings can be found in the Edit-System Parameters menu under the Device Properties tab. Please note:
The Recommended Settings column provides the recommended setting
based upon the default settings most commonly used in Siemens modules.
The Options column lists EZware’s options; your PLC may not support
every option
. Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333
1036-0203 Page 3 of 4 Rev. 01, 10/11/2015
Name
Recommended Settings
Options
Important Notes
Settings: Timeout (sec)
1.0
0.1 to 25.5
Adjust if longer timeout is required.
Settings: Turn around delay (ms):
5
0-1000
Timeout period between HMI polls.
Settings: Send Ack Delay :
30 Settings: Reserved 1:
0 Not Applicable
Settings: Reserved 2:
0 Not Applicable
Settings: Reserved 3:
0 Not Applicable
Interval of block pack (words):
5
0-512
Max. read-command size (words):
16 Not Adjustable
Max. write-command size (words):
2 Not Adjustable
Phone: 425/745-3229 • Fax: 425/745-3429 • Email: support@maplesystems.com • www.maplesystems.com
1036-0203 Page 4 of 4 Rev. 01, 10/11/2015
Loading...