Maple Systems cMT3071, cMT3072 Installation Manual

NEMA Rating
Electrical Environment
Environmental Considerations
Cleaning Considerations
cMT3071/3072 series
Installation Instruction
6
3 5 4
1
2
Installation and Startup Guide
This document covers the installation of cMT3071/3072 Series HMI, for the detailed specifications and operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all warnings, precautions, and instructions on the device carefully before use.
Install Environment:
Installation Instructions
Use a control box that provides enough stiffness. Cutout Dimension: 192 mm x 138 mm. Secure the operator panel in position, using all the fastening holes and the provided brackets and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and preventing the panel from being deformed.) Plan for adequate space around the unit and inside the enclosure, for ventilation and cables. Consider the
heat from other devices inside the enclosure. The ambient temperature around the unit must be 0 ~ 50°C Minimum required clearances (along the overlay): Top / Bottom / Sides 15 mm Maximum panel thickness: 4.5 mm The aluminum flat-sheet at the back of the unit is a heat sink. Please be careful not to touch the heat sink since its heat can rise to 70°C in maximum when the unit is running. Planning for a 3cm space between the back of the unit and other devices is recommended.
Power Connections
Power Connector Specifications: Wire AWG: 28~12 Operating Temperature: -40°C ~105°C Screw Torque: 3.47 lbf-in (max.)
NOTE:
1. Connect positive DC line to the ‘+’ terminal and the DC ground to the ‘-’ terminal.
2. When downloading project using a USB cable, do not connect HMI with PLC and PC simultaneously, for electric potential difference may result in damage to HMI or PC.
Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
The package includes: (1) Installation Instruction, 2-sided A4 *1 (2) Human Machine Interface *1 (3) Power Connector *1 (4) Brackets & Screws *1 pack (5) Fuse 3.15A/250V 5*20mm *1 (6) USB Stick Clamp & Tying Strap *1
USB Stick Clamp Usage
Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting with HMI when strong vibration is present.
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.
System Settings
When HMI is powered up and displays image, press the round Start Button in the upper-left corner of the screen to open the Setting dialog box. Tap the lock icon and log in. (Default System Password:
111111) Go to the Network tab, and setup your network. In Setting dialog box you can see device information, configure general settings, set HMI Time/Date/Name, and more.
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download dialog box: Select Ethernet > IP tab > Enter your HMI IP > Click Download to download this project file to HMI. Using screensaver and backlight saver is recommended in order to avoid image persistence caused by displaying the same image on HMI for a long time. (Please refer to EasyBuilder Pro User Manual for software operation details.)
Communication Connections
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Power
Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be powered by DC power only, voltage range: 10.5~28VDC, compatible with most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a switching power supply. The peak starting current can be as high as 3.15A.
Fusing Require­ments
High Voltage
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with ICS Safety Recommendations.
Supply Voltage Condition
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same power supply. Note: The 12 or 24 VDC output from some controllers may not have enough current to power the unit.
Wire Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded). b. Please use twisted pair cables for power wire and signal wire and conform to the
impedance matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression
devices. d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires. e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency
dissipation. Typical values to use are 1M Ohm and 4700pF
Hardware Considerations
The system designer should be aware that devices in Controller systems could fail and thereby create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to equipment start-up, which could result in property damage and/or physical injury to the operator. If you use any programmable control systems that require an operator, be aware that this potential safety hazard exists and take appropriate precautions. Although the specific design steps depend on your particular application, the following precautions generally apply to installation of solid-state programmable control devices, and conform to the guidelines for installation of Controllers recommended in NEMA ICS 3-304 Control Standards.
Programming Considerations
To conform to ICS Safety Recommendations, checks should be placed in the controller to ensure that all writable registers that control critical parts of plant or machinery have limit checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
DANGER
CAUTION
Limited Warranty
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products. (b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse. (c) Product has been repaired or taken apart by unauthorized technicians. (d) Products whose identification markings have been removed or damaged.
PIN#
COM1
[RS232]
COM3
[RS232]
1
2
RxD 3 TxD
4
5
GND
6
7
RTS
TxD 8 CTS
RxD
9
PIN#
COM2
[RS485]2W
COM2
[RS485]4W
COM3
[RS485]
CAN
Bus
1
Data-
Rx-
2
Data+
Rx+ 3 Tx-
4
Tx+
5
GND
6
Data-
7
CAN_L
8
CAN_H
9
Data+
NOTE:
1. COM2 and COM3 [RS485] 2W support MPI 187.5K, please use one at a time.
2. Only Tx & Rx (no RTS/CTS) may be used for COM1 RS232 when COM3 RS-232 is also used.
7
8
NOTE:
Make sure that all local and national electrical standardsare met when installing the unit. Contact your local authorities to determine which codes apply.
NOTE:
Make sure that all local and national electrical standardsare met when installing the unit. Contact your local authorities to determine which codes apply.
SW1
SW2
SW3
SW4
Mode
ON
OFF
OFF
OFF
Touch Screen Calibration Mode & Reset HMI to Default
OFF
ON
OFF
OFF
Hide Start Button
OFF
OFF
ON
OFF
Boot Loader Mode
OFF
OFF
OFF
ON
Reserved
OFF
OFF
OFF
OFF
Normal
9
Con.B Con.A
COM1/COM3 [RS232] 9 Pin, Male, D-sub COM2/COM3 [RS485]/CAN Bus 9 Pin, Female, D-sub
Touchscreen Calibration & Restore Factory Default
Restore Factory Default: Apart from flipping DIP SW 1 to ON position, restoring factory default can be carried out by following Step 5 to open the Setting dialog box. Go to Reset Options tab and press the button of Reset HMI to default. Please note that the projects and data stored in the unit are all cleared after pressing this button. Another way to enter touch screen calibration mode: Press and hold anywhere on the screen for more than 2 seconds when HMI starts.
Fuse min. rating: 3.15A/250V. Use the fuse only in DC circuit. If the display does not come on within 5 seconds of power up, remove power. An internal fuse will prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections and try to power up again. Replacing fuse shall be performed by qualified personnel only.
Battery Replacement
Battery replacement shall be performed by qualified personnel only and care must be taken when handling lithium batteries. For more information on battery replacement and disposal considerations.
1010-1062_rev02_180410
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Maple's discretion.
This warranty shall not cover any product which is
Loading...