Mantracourt UAB User Manual

Page 1
UAB
Universal Amplifier/Digitiser
User Manual
MICRON METERS
www.micronmeters.com
metersinfo@micronmeters.com
Page 2
1
Chapter 1 Introduction To The Universal Process Amplifier System ......................................................... 4
Chapter 2 Installation ................................................................................................................... 5
Environmental Requirements ........................................................................................................... 5
Terminal Connections .................................................................................................................... 6
Section 1 -The Rack (RUA) Variant .................................................................................................... 7
Figure 2.1 - Rear view of Rack (RUA2) ................................................................................................ 7
Figure 2.2 UAB Rear Connection Terminals ......................................................................................... 7
Figure 2.3 The 32 Way A & C (DIN41612) Connections ............................................................................. 7
Figure 2.4 Rack Module Layout ......................................................................................................... 8
Figure 2.5 LP2 Hand Held Programming Unit ........................................................................................ 8
Figure 2.6 RUA1 for External Programmer (LP2) .................................................................................. 8
Figure 2.7 RUA2 On-Board Programmer .............................................................................................. 8
Section 2 - The Surface Mount (SMP) Variant ........................................................................................ 8
Figure 2.8 The IP65-ABS Case (LAB) Dimensions & Mounting Points ............................................................. 9
Figure 2.9 The DIN Rail Mounting (D2) Dimensions ................................................................................. 9
Figure 2.10 Stainless Steel Panel Mount & Programming Display Module, Dimensions & Mounting Points ................ 9
Figure 2.11 LCS Stainless Steel Panel Cut Out ...................................................................................... 10
Figure 2.12 Connection & Fitting Details for the Surface Mounted Amplifier (UAB) ......................................... 10
Programmers for Surface Mount Variants ........................................................................................... 11
Figure 2.13 LP1 On-Board Programmer Unit ........................................................................................ 11
Figure 2.14 LP2 Remote hand Held Programmer Unit (UAB) ..................................................................... 11
Chapter 3 Power Supplies ............................................................................................................ 12
Section 1 - The Rack Version (RS1) ................................................................................................... 12
Table 3.1 .................................................................................................................................. 12
Table 3.2 .................................................................................................................................. 12
Section 2 - The Surface Mount Versions (LS1 and LS3) ............................................................................ 12
Figure 3.1 Power Supply LS1 Connections ........................................................................................... 13
Figure 3.2 LS3 Connections ............................................................................................................ 13
Chapter 4 Input Modules .............................................................................................................. 14
Table 4.1 UADCV1 and UADCA1 Switch Configuration ............................................................................. 14
Figure 4.1 The UADC1 & UADCA1 Modules .......................................................................................... 14
Figure 4.2 The UALV1 - LVDT Module Rear Panel Connections .................................................................. 14
Figure 4.3 LVDT Switch Settings ...................................................................................................... 15
Figure 4.4 Rear Panel Connections ................................................................................................... 15
Figure 4.5 UAT1 & 2 ..................................................................................................................... 16
Figure 4.6 Thermocouple Connectors ................................................................................................ 16
Figure 4.7 RTD Module UAPT .......................................................................................................... 16
Figure 4.8 RTD Connections ............................................................................................................ 17
Fast Strain Gauge The (UAFLC) Module .............................................................................................. 18
Figure 4.9 UAFLC Module ............................................................................................................... 18
Figure 4.10 UAFLC Connections ....................................................................................................... 18
Figure 4.11 the UADIA Modules ........................................................................................................ 18
Figure 4.12 UADIA Connections ....................................................................................................... 18
Chapter 5 Output Modules ............................................................................................................ 19
Section 1 - General Description ....................................................................................................... 19
Figure 5.1 Showing the Potentiometer for Gain & Offset Adjustment ......................................................... 19
Figure 5.2 UAFAO Connections ........................................................................................................ 19
Section 2 - Digital Output Modules ................................................................................................... 20
Figure 5.3 RR1 Module .................................................................................................................. 21
Figure 5.4 LR1 Module .................................................................................................................. 21
Figure 5.5 Installation of LR1 .......................................................................................................... 22
Figure 5.6 Connection to the Surface Mount/DIN Rail Version UAI²C (S) ...................................................... 22
Section 3 - The Communications Port Modules ..................................................................................... 22
Figure 5.7 LC1 Current Loop ........................................................................................................... 23
Figure 5.8 IF25 Connecting Multiple Process Amplifiers .......................................................................... 23
LC3 Isolated RS232/485 Communications Module .................................................................................. 23
Figure 5.9 LC3 Isolated RS232/485~Mode Connections ........................................................................... 23
Page 3
Mantracourt Electronics Limited UAB User Manual
2
Figure 5.10 Connecting Multiple Units on RS485 ................................................................................... 24
Figure 5.11 LC3 RS232 Mode Connection to PC ..................................................................................... 24
Figure 5.12 LC3 RS232 Mode Connection to Printer ............................................................................... 24
RC1 Communications Current Loop Module Connections ......................................................................... 25
Figure 5.13 RC1 Communication Connections ...................................................................................... 25
Figure 5.14 RC1 Baud Rate Selection................................................................................................. 25
Figure 5.15 Connecting Multiple Process Amplifiers ............................................................................... 26
RC3 RS232/485 Communication Connectors ........................................................................................ 26
Figure 5.16 RC3 RS232/485 Communication Connections ........................................................................ 26
Figure 5.17 - RC3 Baud Rate Selection ............................................................................................... 27
Section 4 Serial Communication Protocol ........................................................................................... 27
Fast MANTRABUS - selected when CP is 128 ........................................................................................ 27
Communications Commands ........................................................................................................... 28
Data Transmitted To Process Amplifier For Command 1 ......................................................................... 28
Table 5.1 .................................................................................................................................. 33
Process Amplifier Printer Format ..................................................................................................... 33
Chapter 6 The Amplifier Displays ................................................................................................... 35
Figure 6.1 Programmer Unit Panel Layout (RUA2) ................................................................................ 35
Figure 6.2 LP2 Remote Hand Held Programmer Unit ............................................................................. 35
Figure 6.3 Programmer Unit Panel Layout (LP1) ................................................................................... 35
Control Panel Guide ..................................................................................................................... 36
Figure 6.4 Programmer Unit Panel Layout .......................................................................................... 36
Figure 6.5 Display Module Connections and Switch Settings ..................................................................... 37
Table 6.1 .................................................................................................................................. 37
Chapter 7 Programming The Amplifiers ........................................................................................... 38
Section 1 - Display & Programming Mnemonics .................................................................................... 38
Table 7.1 Configurable Parameters for Process Input ............................................................................. 38
Table 7.2 Configurable Parameters for Dual Input Modules ...................................................................... 41
Configurable Parameters for UAFLC - Fast Strain Gauge Input Module ........................................................ 41
Table 7.3 Configurable Parameters .................................................................................................. 42
Section 2 - Setting the Conditions for Linear Inputs ............................................................................... 42
Figure 7.1 Linear Input Scaling ........................................................................................................ 42
Method of Calculating IPL and IPH from any known input values ............................................................... 42
Input Calibration Routine .............................................................................................................. 43
Section 3 - The Temperature Input Modules (UAT1 & UAT2) ..................................................................... 43
Table 7.4 - Thermocouple Input Codes ............................................................................................. 44
Table 7.5 .................................................................................................................................. 44
Section 4 - The Rate/Totaliser Input Module (UARTL)............................................................................ 45
Setting up the Input ..................................................................................................................... 45
Table 7.6 .................................................................................................................................. 45
Table 7.7 Input Configuration ......................................................................................................... 45
Setting the Prescaler .................................................................................................................... 45
Table 7.8 .................................................................................................................................. 46
Rate Measurement ....................................................................................................................... 46
Period (Time measurement between pulses) ...................................................................................... 46
Input Code ................................................................................................................................ 46
Table 7.9 .................................................................................................................................. 46
(i) Period in mSeconds ................................................................................................................. 46
Table 7.10 Period mS Fixed Scale .................................................................................................... 46
(ii) Period in µSeconds .................................................................................................................. 46
Table 7.11 Period µS Unity Scale (IPSF 1.0000) .................................................................................... 46
Frequency ................................................................................................................................. 46
Table 7.12 ................................................................................................................................. 47
Figure 7.2 Frequency Unity Scale Inputs ............................................................................................ 47
RPM ......................................................................................................................................... 47
Table 7.13 RPM Unity Scale ............................................................................................................ 47
Figure 7.3 RPM Unity Scale Range .................................................................................................... 48
Count/Rate Scaling & Scaling/Rate .................................................................................................. 48
Page 4
Mantracourt Electronics Limited UAB User Manual
3
Scaling Example: - ....................................................................................................................... 48
RTL Module Inputs ....................................................................................................................... 49
Figure 7.4 RTL Module Inputs .......................................................................................................... 49
Section 5 - Programming the Output Functions .................................................................................... 49
Hysteresis (HYS) .......................................................................................................................... 49
Latching Outputs (OL) .................................................................................................................. 50
Table 7.14 Output Latch Codes (OL) ................................................................................................. 50
Output Action (OA) ...................................................................................................................... 50
Table 7.15 Output Action Codes (OA) ................................................................................................ 50
Delay Timers .............................................................................................................................. 50
Delay On Timer ........................................................................................................................... 50
Delay Off Timer .......................................................................................................................... 50
PID Functions ............................................................................................................................. 50
PID Empirical Tuning .................................................................................................................... 51
Section 6 - Scaling the Analogue Outputs ........................................................................................... 51
Output Scaling ............................................................................................................................ 51
Figure 7.5 Analogue Output ............................................................................................................ 51
Method of Calculating OPL & OPH from any known Output & Display Values ................................................. 52
Calibration ................................................................................................................................ 52
Figure 7.6 Showing the Potentiometers for Gain and Offset Adjustment ..................................................... 52
Figure 7.7 Showing the Potentiometers for Gain & Offset Adjustment ........................................................ 53
Chapter 8 Order Codes ................................................................................................................ 54
RUA Rack Mounted Universal Input Process Amplifier ............................................................................. 54
UAB Universal Amplifier ................................................................................................................ 54
SMP Surface Mount Process Indicator & Controller ................................................................................ 55
CE Approvals .............................................................................................................................. 56
Instrument Setup Record Sheet ....................................................................................................... 57
W A R R A N T Y .......................................................................................................................... 57
Page 5
Mantracourt Electronics Limited UAB User Manual
4
Chapter 1 Introduction To The Universal Process Amplifier System
The Mantracourt Electronics Universal Process Amplifier System is based upon a concept of modular construction. By adopting such a concept, it is possible to offer a great deal of flexibility of construction, to meet the wide and varying needs of system building. The system is centred on a Eurocard sized amplifier PCB, which consists in its standard form of, Central Processing, and voltage and current Analogue output ports. Facilities are provided to connect a series of ‘plug in ’ option boards for inputs, relay and communications outputs together with mains and low voltage DC power supply options. A special Fast Analogue output module is also available to complement a Fast Strain Gauge input option. The modular concept offers the opportunity for assembly in Surface Mount, DIN Rail and 19-inch Rack variants. The system concept is described in diagrammatic form with the range of options listed. The options will be described under the various Chapters as follows:
1. Introduction
2. Installation requirements
3. Power Supplies
4. Input Modules
5. Output Modules & Communications Information
6. The Amplifier Displays
7. Programming the Amplifier including essential INPUT CALIBRATION ROUTINES, which must be actioned. See Chapter 7
8. Order Codes
9. Specifications
Page 6
Mantracourt Electronics Limited UAB User Manual
5
Chapter 2 Installation
In order to maintain compliance with the EMC Directive 2004/108/EC the following installation recommendations should be followed.
Inputs:
Comms Port:
Analogue Output:
Use individually screened twisted multipair cable. (e.g. FE 585 - 646) The pairs should be : pins 1 & 6 pins 2 & 5 pins 3 & 4 Terminate all screens at pin 1 of the input. The screens should not be connected at the transducer end of the cables.
Use individually screened twisted multipair cable. (e.g. FE 118-2117) The pairs should be:
-Tx & +Tx
-Rx & +Rx Terminate screens at pin 1 of the input . The screens should not be connected at the host port.
Use screened twisted pair cable. (e.g. RS 626-4761)
Terminate screen at pin 1 of the input. The screen should not be connected at the host port.
Pin 1 of the input should be connected to a good Earth. The Earth connection should have a cross-sectional area sufficient enough to ensure a low
impedance, in order to attenuate RF interference.
Country
Supplier
Part No
Description
UK
Farnell
118-2117
Individually shielded twisted multipair cable (7/0.25mm)- 2 pair
Tinned copper drain. Individually shielded in polyester tape. Diameter: 4.1mm
Capacitance/m: core to core 115 pF & core to shield 203 pF
UK
Farnell
585-646
Individually shielded twisted multipair cable (7/0.25mm)- 3 pair
Tinned copper drain. Individually shielded in polyester tape. Diameter: 8.1mm
Capacitance/m: core to core 98 pF & core to shield 180 pF
UK RS 626-4761 Braided shielded twisted multipair cable (7/0.2mm)- 1 pair
Miniature- twin -round Diameter: 5.2 mm
Capacitance/m: core to core 230 pF & core to shield 215 pF
Environmental Requirements
UAB units can operate in any industrial environment provided the following limits are not exceeded at the point of installation:
Operating
Temperature:
-10 ºC to 50 ºC
Humidity:
95 % non condensing
Storage Temperature:
-20ºC to +70ºC
Page 7
Mantracourt Electronics Limited UAB User Manual
6
Units can operate from any one of the following:
or
or
220/240V AC, 50/60Hz
110V AC, 50/60Hz
9-30V DC, 50/60Hz (Not RUA)
Terminal Connections
Connection between the UAB modules and input/output signals, are made via screw connections to the rear of the rack, or edge of the UAB in Surface Mount Versions. (See Figure 2.1)
Page 8
Mantracourt Electronics Limited UAB User Manual
7
Section 1 -The Rack (RUA) Variant
Figure 2.1 - Rear view of Rack (RUA2)
Figure 2.2 UAB Rear Connection Terminals
Figure 2.3 The 32 Way A & C (DIN41612) Connection s
Page 9
Mantracourt Electronics Limited UAB User Manual
8
Figure 2.4 Rack Module Layout
Figure 2.5 LP2 Hand Held Programming Unit
Figure 2.6 RUA1 for External Programmer (LP2)
Figure 2.7 RUA2 On-Board Programmer
Section 2 - The Surface M o unt (SMP) Variant
The surface mount variant of the Universal Amplifier is offered in a number of different configurations dependant upon the system installation requirements, to which any of the input, output and communications modules can be fitted as described in the diagram in Section 1. Each description is followed by the order coding for ease of identification.
1.The surface mount IP65 ABS cased version with a large LCD display and programming module mounted in the lid,
where local programming and control is required. - (SMP/C).
2.The DIN rail mounted version with a remotely connected large LCD display and programming module fitted with a
stainless steel panel mounting fixture which will operate up to 2 metres from the amplifier. (SMP/D) A version of the (SMP/D) above is offered with a driver package (LCDR) where there is a requirement for the remote display and programming module to operate over distances greater than 2 metres, and up to 100 metres from the amplifier. Where order codes are required for individual items, please refer to the order code list in the rear of the manual at Chapter 8.
3.ABS Cased Versions are available without a display and programming module mounted on the lid. Programmed
through the internal FCC socket on the UAB, (using an LP2 Hand Held Programmer see Figure 2.13) or the remote LP1 On Board Programmer see Figure 2.14
Page 10
Mantracourt Electronics Limited UAB User Manual
9
Figure 2.8 The IP65-ABS Case (LAB) Dimensions & Mounting Points
Case Depth = 75mm
Figure 2.9 The DIN Rail M o u n ting (D2) Dimensio ns
Max height above
DIN Rail Mounting surface = 100mm. Fits ALL carrier rails DIN/EN 35
Figure 2.10 Stainless Steel Panel Mount & Programming Display Module, Dimensions & Mounting Points
4mm M4 studs x 12mm for mounting. Sealing is provided by a Neoprene gasket For LCD max cable length = 2 meters. For LCDR max cable length = 100 meters
Page 11
Mantracourt Electronics Limited UAB User Manual
10
Figure 2.11 LCS Stainless Steel Panel Cut Out
Where there is a requirement for the stainless steel fixture to be mounted in a panel please note the details of the ‘Cut Out’ are as described in the following drawing.
Figure 2.12 Connection & Fitting Details for th e Surface Mounted Amplifier (UAB)
Display & Keypad FCC68 Connector (For Surface Mounted Display or Hand
Held Programmer LP2 for Non Display Versions.)
The standard (100mS) strain gauge input is contained within the LCB module & therefore has no separate input module
15 Way field screw connection for input, contacts & AN-OP
For DIN mounting cut off
PCB on white line
WATCHDOG LED
Page 12
Mantracourt Electronics Limited UAB User Manual
11
Programmers for Surface Mou n t V arian ts Figure 2.13 LP1 On-Board
Programmer Unit
Figure 2.14 LP2 Remote hand Held
Programmer Unit (UAB)
Page 13
Mantracourt Electronics Limited UAB User Manual
12
Chapter 3 Power Supplies
There are three types of power supply available within the UAB system. The rack versions RUA1 and RUA2 are served by a common power supply, which offers power to the 12 channels in the case of the RUA1 and 8 channels for the RUA2. The Surface Mount versions are offered with mains an AC version or a low voltage DC version.
Section 1 - The Rack V ersion (RS1)
The RS1 supplies power to the channels within the rack via the common back plane, offering 220/240VAC at 50/60 Hz or 110VAC at 50/60 Hz. The 110/240 is selected by a switch on the rear of the power supply module. A green LED on the front panel indicates when power is applied
A 5-Ampere protection fuse is fitted within the power input socket.
The maximum power rating for a full rack is 100 Watts.
Connection to the rack is made via a flying lead with a shrouded and earthed IEC mains connector
Note: Inputs are not intended to be connected to voltages above 50 VAC or 120Vdc
Tables 3.1 and 3.2 show details of the connections and voltages for the various supply rails.
Table 3.1
SUPPLY CONNECTION
TO DIN 41612
MIN V MAX V MAX ac V CURRENT
per channel
COMMENTS
0V 15a, 15c - - - - Common for
processor supplies
-5V 17a, 17c -4.80 -5.2 1mV 110Ma Power supply
-14V UNREG
19a, 19c
-11
-18V
150mV
2mA
Used to detect power fail
-9V8 20a, 20c -9.1 -10.2 1mA 200mA Provides excitation for stain gauges and
relays
Table 3.2
SUPPLY
CONNECTION TO DIN 41612
MIN V
MAX V
MAX ac V
CURRENT per channel
COMMENTS
+24V ISO
25a
+20
+32
240mV
32mA
Only required if AN­OP to be used
-5V ISO
26a
-4.75
-5.25
1mV
5mA
Only required if AN­OP to be used
0V ISO
27a - - - -
Only required if AN­OP to be used
Section 2 - The Surface Mount Versions (LS1 and LS3)
The LS1 power supply is a ‘plug in’ module supplying 110 Volts AC at 50/60 Hz or 220/240 Volts AC at 50/60 Hz.
A maximum power rating of 10 Watts is available, with this module.
The running current for each amplifier is between 250 and 480 milliamps dependant upon module configuration, with a start up current of 3 Amps for 20 milliseconds. Earthing (or shield)- If the amplifier is not earthed elsewhere, an earth should be made to the screen (SC) of the 15 way connector.
PROC-
ESSOR SUPPLIES
ANALOGUE
OUTPUT ISOLATED SUPPLY
Page 14
Mantracourt Electronics Limited UAB User Manual
13
Figure 3.1 Power Supply LS1 Connections
Figure 3.2 LS3 Connections
The LS3 module should be protected on installation by an in line fuse.
The LS3 power supply is a 'plug in' module supplying 9 to 30 Volts DC. Similar in characteristics to the LS1 with regard to power and current ratings. The module is not reverse polarity protected and will require similar protection at installation.
Page 15
Mantracourt Electronics Limited UAB User Manual
14
Chapter 4 Input Modules
The following DC Voltage & Current input modules are available:
-
UADCV1 -
UADCA1 ­UADCV2 ­UADIA -
UADIV -
0 to 10 Volts
0 to 20mA ± 200mV Dual Input - 4 to 20mA
Dual Input - 0 to 10 Volts
Table 4.1 UADCV1 and UADCA1 Sw itc h Configuration
SW1
±200mV
0-10V
0-20mA
1 2 3 4 5 6 7
8
10V Excite 24V Excite 5-25V VAR Excite ON OFF OFF OFF
OFF
10V Excite 24V Excite 5-25V VAR Excite OFF ON ON OFF
ON
10V Excite 24V Excite 5-25V VAR Excite OFF ON ON ON
OFF
Figure 4.1 The UADC1 & UADCA1 Modu l es
Figure 4.2 The UALV1 - LVDT Module Rear Panel Connections
Page 16
Mantracourt Electronics Limited UAB User Manual
15
Figure 4.3 LVDT Switch Settings
The UARTL - Rate/Totaliser Module
Figure 4.4 Rear Panel Connections
Note: See Chapter 7 Section 4 for details of input and pre scaler settings.
UAT1 ­UAT2 -
Thermocouple Type K Modules Thermocouple Type J Modules
Connecting the Thermocouple
WARNING: ENSURE POWER IS SWITCHED OFF BEFORE MAKING CONNECTION TO THE UAB
1. Connect the thermocouple to the UAB terminal as shown in Figure 4.6 Note: If the thermocouple has a floating input, connect terminal 1 to ground.
2. The external cold junction sensor is always connected between input terminals 4 and 6. If no external sensor is used, link terminals 4 & 6.
Page 17
Mantracourt Electronics Limited UAB User Manual
16
3. Normally, thermocouple burnout is indicated by upscale over range. If downscale indication is required, link terminals 2 & 3.
Figure 4.5 UAT1 & 2
Figure 4.6 Thermocouple Connectors
The UAPT Connecting the Resistance Thermometer Module
Connect the resistance thermometer to the UAB terminals as shown in Figure 4.8 using the terminals appropriate to 2, 3 and 4 wire connections.
Note: It is recommended that 4 core-screened cable be used for this connection with terminal 6 used for screen and ground. If however, this is not practical, terminal 2 may be used for guard and ground.
Figure 4.7 RTD Module UAP T
Page 18
Mantracourt Electronics Limited UAB User Manual
17
Figure 4.8 RTD Connections
UAFLC Fast Strain Gauge
The UAFLC offers a direct connection to most low level (foil) strain gauge sensors. A 10-volt excitation is provided and it is monitored to compensate for any variation due to supply drift, load regulation or voltage drop in the cable between the sensor and the UAFLC. The maximum supply current is 150mA, which allows for the connection of 4 x 350 Ohm strain gauges. Strain gauge sensitivity is preset via DIL switches to 0.5, 0.8, 1.0, 1.25, 1.5, 2.0, 2.5, 3.5, 5, 10, 20, 50, 100 and 200 mV/V. Select the next value higher than the strain gauge output maximum.
Note: It is important that the UAFLC is powered up with the strain gauge connected to the input as the A/D performs an Autocal of its own on power up.
SW1 mV/V
1 2 3 4 5 6 7 8 0.5 x - - x - x x x
0.8
- x x - - x x x 1.0 - x - x - - x -
1.25
- x - - - - - x 1.5 - - x x x - - -
2.0 - - x - x - - x
2.5 - - x - - - - -
3.5 - - - x x - - -
5.0
- - - x - - - x 10.0
- - - - x - - x 20.0
- - - - - x - x 50.0
- - - - - - x x 100.0
- - - - - - - x 200.0
- - - - - - -
-
x = ON - = OFF mV/V = ±mV/V nominal full range gain within ±3%
Page 19
Mantracourt Electronics Limited UAB User Manual
18
Fast Strain Gauge The (UAFLC) Mo d ul e
Figure 4.9 UAFLC Module Figure 4.10 UAFLC Connections
Dual Input Modules
Provide two non-isolated inputs either 4 to 20mA or 0 to 10 volts (This should be specified at time of order) as:
• UADIA = 4/20mA
• UADIV = 0/10 volts
These inputs have independent scaling factors IPLA and IPHA for input 'A' and IPLB and IPHB for input 'B'.
The display can be selected from the list of 'A' and 'B' functions as follows, and can be selected under the mnemonic 'Ab'
0 = 1 = 2 = 3 = 4 =
A + B A - B A x B A/B A = process input, B = setpoint (SP1)
Scale factors can be applied to this function using a scale factor 'SF', a division factor 'DF' and a display offset 'OFFS'. The analogue output, relays and printer take their value from the function selected at 'Ab’.
Figure 4.11 the UADIA Modules Figure 4.12 UADIA Connectio ns
Page 20
Mantracourt Electronics Limited UAB User Manual
19
Chapter 5 Output Modules
Section 1 - General Description
Analogue outputs of 4 to 20mAmps and 0 to 10 volts are standard features and an integral part of the Universal Amplifier pcb. Further output modules are available offering alarm/control, printer and communications facilities. Analogue outputs are fully scaleable, opto-isolated and digitally generated. The analogue output signals are generated by the CPU from the displayed input variable, so that output signals are normally related to displayed input values except where the PID function is selected. The 4 to 20 mA output is pre calibrated to an accuracy of within 0.15% of the range. The 0-10V outputs are accurate to within 2% of the 4 to 20mA output.
Notes:
1. Maximum current load on voltage modules is 2mA
2. Maximum drive voltage available in current modules is 20V
The PID function is an option selectable within the standard software program and provides, where required an analogue output so that outputs are related to the PID power levels and not the displayed input signal. Note: In this mode the analogue output cannot be scaled.
A fast analogue output module (UAFAO) is available for use with the fast strain gauge (10msec) input (UAFLC), where a fast capture facility is a requirement.
The digital output modules consist of two single pole change over relays with ON/OFF or PID control. If required, latching outputs may be selected via the keypad, reset action being achieved by a contact closure or via the communications module, where a program has been written via an appropriate protocol. Set points and hysterisis are also set via the keypad or from a communications input. Relay outputs may also be inverted via the keypad. Relay operations are controlled by set point and hysterisis values, output inversion, time delays or by the PID time proportioning output on set point 1.
Figure 5.1 Showing th e Potentiometer for Gain & Offset Adjus tment
Figure 5.2 UAFAO Connections
Fast Analogue The (UAFAO) Module
Important Note 1: The output action mnemonic OA must be set to 32 when operating with this module. Important Note 2: When changing the value of OA to, or from ’32; it is necessary to power the unit off and back on
again as a restart.
See Note with regard to calibrations on Chapter 7 ‘Method of Calculating OPL & OPH from any known output and Display’
Page 21
Mantracourt Electronics Limited UAB User Manual
20
Section 2 - Digital Output Modules
Module Functions
The Universal Amplifier can be programmed so that the relay output module reacts to all or any of the following functions:
• Set points
• In Flight compensation
• Hysteresis
• Relay inversion
• Latching
Set Points (SP)
Set points are used to produce output signals at any required value so that the operation of the monitored process can be maintained to preset levels. Any excursion beyond set points will activate the relay or relays, to provide alarm or initiate control as required. Two set points (SP1) and (SP2) can be programmed to suit different applications. The actions of either or both set points can inverted if required. For normal operation the set point output is active until the input reaches the set point level. In this condition when the input value is less than the set point, the SP indicator is on and the output relay is energised producing a closed circuit on a normally open contact. When the set point value is reached, the SP indicator is off and the relay is de­energised producing an open circuit output.
For an inverted operation the reverse conditions apply. Normal and inverted action is determined by the direction of the input value as it changes. For example: In alarm applications.
A High-High operation allows for a rising input value to operate on two set points to define an acceptable quantity, weight or band of operation.
A Low-Low operation operates on a falling value.
A High-Low operation will operate on a rising or falling value, setting a 'band' by one set point operating normally and the other being an inverted action.
Hysteresis (HYS) Once a Hysteresis value has been set, it will be applied to both set points entered. It is effective for both normal and inverted action. When Hysteresis is applied to set points with normal output action, the input is allowed to rise to the set point value and the output is then turned off. The output is held off until the input value has dropped to the set point minus the Hysteresis value. For inverted action the input drops to the set point and the output goes off and comes on again when the input rises to the set point plus the Hysteresis value.
Output Action (OA) The Output Action facility allows the user to determine whether set points produce normal or inverted and latched or unlatched output operation. If an analogue output module is also fitted, the Output Action function determines whether the module's output is inverted or not. For programming details refer to Chapter 7 Table 7.15
Latching Output (OL) The latching facility allows the relay module output to held until the reset externally Latching is applied to the status of the relay SP1 or SP2. For programming details refer to Chapter 7 Table 7.14
Page 22
Mantracourt Electronics Limited UAB User Manual
21
Digital Output Modules - (LR1) Surface Mount and (RR1) Rack Mount There are two relay modules available, which function in a similar way. The ‘plug in’ module LR1 used with the surface mount version is fitted with relay status LEDs, connections being made directly on to the module terminal block
The RR1, which is used with the rack version, is not fitted with relay status LEDs, these being brought out for observation, to the front of the rack channel. Connections to the module are made to a 4 way field terminal at the rear of the rack channel.
RR1 - 2 SPCO relays, SP1 and SP2
Relay contact rating - 50V @ 500mA
LR1 - 2 SPCO relays, SP1 and SP2,
Relay contact rating - 240V @ 5A AC
Figure 5.3 RR1 Module Figure 5.4 LR1 Module
The Remote Driver Modules - UAI ²C
The module offers a general I/O facility for connection to Relays, Real Time Clock and Remote Displays, and is a direct 'plug in' replacement for the RR1 or LR1 Relay Module.
Two versions of the module are available one for the Rack and the other for the Surface Mount versions of the Universal Amplifier Board.
Connection to the Rack version - UA1²C (R)
The Channel 4 Way Screw
NO 1 Com 1 NO 2
Com 2
Wire Colour from REMC1 Violet & Yellow Red Black
Blue
Signal GND +5V CLK
DATA
Connection to the Surface Mount/DIN Rail version - UAI ²C(S)
Page 23
Mantracourt Electronics Limited UAB User Manual
22
Figure 5.5 Installa tion of LR1
To meet the Specified EMC Fast transient requirements it is important that the ferrite ring supplied is fitted as per the following instructions.
Illustration showing ferrite ring FEC 323-4940 fitted to the LR1 relay wiring.
Two turns of the wiring are passed through the ring positioned 12cm from the LR1 end of the cable to improve immunity to electrical fast transients and bursts.
Figure 5.6 Connection to the Surface Mount/DIN Rail Version UAI²C (S)
Section 3 - The Communications Port Modules
A series of communications modules in both surface mount and rack versions, provide for two way data links to an intelligent host such as a Personal Computer, Main frame or PLC, which are able to acquire displayed values and read or modify the user configurable parameters, using any of the following: -
A 20mA current loop usually connected through an IF25 current loop to RS232 interface unit for multiple amplifier connection. - (LC1) for the surface mount and (RC1) for the rack version.
An RS232 for a one to one communication, usually where a printer connection is required. (RC2) for the rack version.
A RS232/485 (link selectable) for one to one or multi-drop applications - (LC3) for the surface mount and (RC3) for the rack version.
Three communication formats, FAST MANTRABUS, ASC11 and PRINTER are selected from the mnemonic CP via the keypad of the display/programmer.
Integrity is ensured by pre-programmed default parameters, should a loss of communications with the host unit occur.
Connection and Baud rate setting details are shown in the following module diagrams: -
Page 24
Mantracourt Electronics Limited UAB User Manual
23
Figure 5.7 LC1 Current Loop
Figure 5.8 IF25 Connecting Multiple Process Amplifiers
Connecting Multiple Process Amplifiers to the IF25 Interface Notes
1. Maximum loop voltage is 50V dc.
2. Loop is isolated from host and Process Amplifiers. Loop should be earthed via Rx - on IF25/254
3. IF25 used for up to 25 Process Amplifiers.
4. At 19,200 Baud, max. cable length is 100m metres, using cable type BICC H8085.
LC3 Isolated RS232/485 Co m munications Modul e Figure 5.9 LC3 Isolate d RS232/ 485~M ode Connection s
Note: When multi dropping in RS485 mode, the last device should be fitted with LK2, which acts as a 120R­terminating resistor.
Page 25
Mantracourt Electronics Limited UAB User Manual
24
Figure 5.10 Connec tin g M u l tiple Units on RS485
Figure 5.11 LC3 RS232 Mode Connection to PC
Note: LK1 must be fitted for RS232 operation
Figure 5.12 LC3 RS232 Mode Connection to Printer
Note 1: LK1 must be fitted for RS232 operation Note 2: If no RTS is available from the printer, fit LK2
NOTE: When using an RS232 to RS485 converter, which has a non-biased receiver, the following actions are recommended:
-
To bias the device:
1. Terminate the receiver with 140R in place of the usual 120R
2. Fit a 1.5K from the receive negative to the receiver +5V supply, or a 3K3 to the +12V supply.
3. Fit a 1.5K from the receive positive to the receiver supply Ground.
Page 26
Mantracourt Electronics Limited UAB User Manual
25
RC1 Communications Current Loop Module Connections
RC1 used in connection with an IF25 to provide a high noise immunity 20mA current loop. RC1 modules are supplied with a BLUE 9 way bus-terminating header. One of these headers must be connected to each channel fitted with an RC1 module, apart from Channel 1, which is terminated by links, LK1 & LK2 on back plane.
Figure 5.13 RC1 Commun ica tio n Connections
9 way ‘D’ type socket with (RED) identifier
9 way ‘D’ type socket (BLUE) for channels 2-12 supplied with RC1
Figure 5.14 RC1 Baud Rate Selection
Baud rate is selected by a link header
(SW1)
Page 27
Mantracourt Electronics Limited UAB User Manual
26
Figure 5.15 Connecting Multiple Process Amplifiers
IF25 To Multi Rack System
Notes:
1. Maximum loop voltage is 50V dc.
2. Loop is isolated from host and RCA15s. Loop should be earthed via Rx - on IF25/254
3. IF25 used for up to 25 RCA15s.
4. At 19,200 Baud, max. cable length is 100m meters, using cable type BICC H8085.
RC3 RS232/485 Communication Connectors
Providing isolated multi-drop RS485 for up to 25 RCA15 Channels.
For each RC3 module a GREEN 9 way bus terminating header is supplied. One of these must be connected to each channel fitted with an RC3 module. Channel 1 is terminated by links LK1 & LK2 on back plane.
Figure 5.16 RC3 RS232/485 Communication Connections
Note: The last device may be terminated by 120R resistor by fitting LK2 on RC3 module. LK1 on RC3 must not be fitted for multi-drop applications.
Page 28
Mantracourt Electronics Limited UAB User Manual
27
Figure 5.17 - RC3 Baud Rate S election
Baud Rate is selected by a link header (J3)
Do not change baud setting with power on
NOTE:
When using an RS232 to RS485 converter, which has a non-biased receiver, the following actions are recommended:
- To bias the device:
1. Terminate the receiver with 140R in place of the usual 120R
2. Fit a 1.5K from the receive negative to the receiver +5V supply, or a 3K3 to the +12V supply.
3. Fit a 1.5K from the receive positive to the receiver supply Ground.
Section 4 Serial Communication Protocol
General
Incoming data is continually monitored by the Process Amplifier on its serial input line. Each byte of data is formatted as an eight bit word without parity, proceded by one start bit and followed by one stop bit. Transmission and reception of data up to 19.2K Baud is possible, the actual rate being selected by six position header links on the communications module. The Baud rate depends upon the communications, hardware specification, distance and cable type.
Fast MANTRABUS - selected when CP is 128
To signify commencement of a new 'block' of data, the HEX number FFH is used as a 'frame' character, followed by the station number of the unit under interrogation. This is entered via the Process Amplifier keypad under mnemonic SDSt and ranges from 0-254). The Process Amplifier acts upon incoming data only if its own station number immediately follows the FFH character.
New data must be received as a string of four nibbles (bits 7-4 set to zero), which are assembled into two bytes, and written into the variables store within the Process Amplifier. The most significant nibble must be received first and the last nibble must have the most significant bit (bit 7) set to indicate the end of data. This is followed by the checksum. The data transmitted from the Process Amplifier is always sent as complete bytes. The station number precedes the data and the checksum follows the data. The data format used is signed 15 Bit. The most significant Bit of the most significant Byte is set for negative numbers.
Operation
There are two modes of operation, namely data requests by the host controller and data changes. Data requests from the Process Amplifier consist of either a complete dump of the data variables stores in RAM or the display reading. Data changes consist of writing new data to Process Amplifier variables, thus changing parameters such as Set Points, in flights etc. An acknowledgement message is returned to the Process Amplifier to indicate that the new data has been acted upon.
Updating The station number followed by the command byte determines the required mode or variable to be updated. An EXOR checksum consisting of the station number command byte and any following data must be appended to the received data. It is most important that the byte preceding the checksum must have its most significant bit set to signify the end of data. The Process Amplifier works out its own checksum and, if it disagrees with the received one, a not acknowledge (NAK) message is returned.
Page 29
Mantracourt Electronics Limited UAB User Manual
28
Communications Commands
The following is a list of commands available for reading to or writing from the Process Amplifier.
Command No.
DEC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
22
HEX
1 2 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15
16
Description
REQUEST ALL DATA INCLUDES PROCESS VARIABLE INPUT REQUEST DISPLAY DATA SET POINT 1 SET POINT 2 HYSTERESIS OUTPUT LATCH OUTPUT MODE SELECT PROPORTIONAL BAND INTEGRAL TIME DIFFERENTIAL TIME CYCLE TIME INPUT LOW INPUT HIGH OUTPUT LOW OUTPUT HIGH INPUT RANGE SELECT DECIMAL POINT POSITION STATION NO. EEPROM ENABLE/DISABLE FLAG OUTPUT RELAY RESET TOTALISER COUNT RESET
PEAK HOLD RESET
SP1 SP2 HYS OL OA PB IT (ont) DT (oFFt) CT(da) IPL IPH OPL OPH IP DP-r SDSt
-
-
-
-
Command 1 Request for All Data:
Data Transmitted To Process Amplifier For Command 1
0FFH, Station Number, 081H, Chksum
Where Chksum = Station number EXOR with 081H. Example: To obtain a complete dump of the variables in the Process Amplifier whose Station number is 47 send the following Data:-
0FFH, 02FH, 081H, 0AEH
Note MS Bit Set
Page 30
Mantracourt Electronics Limited UAB User Manual
29
Response to Command 1 From Process Amplifier
Byte
1 2,3 4,5 6,7 8,9 10,11 12,13 14,15 16,17 18,19 20,21 22,23 24,25 26,27 28,29 30,31 32,33 34,35 36 37
38
STATION NUMBER DISPLAY SET POINT 1 IN FLIGHT 1 SET POINT 2 IN FLIGHT 2 HYSTERESIS OUTPUT ACTION A/D COUNTS FOR LOW CALIBRATION POINT A/D COUNTS FOR HIGH CALIBRATION POINT DISPLAY LOW CALIBRATION VALUE DISPLAY HIGH CALIBRATION VALUE AUTO TARE DISPLAY AVERAGING OUTPUT LOW OUTPUT HIGH DECIMAL POINT POSITION STATION NUMBER EEPROM ENABLE/DISABLE FLAG RELAY STATUS
EXOR CHECKSUM OF THE ABOVE DATA
NOTE: Most significant byte precedes least significant byte for data sent by Process Amplifier
Command 2 Request Display Data
DATA transmitted to Process Amplifier for Command 2. 0FFH, Station number, 082H, Chksum
Where Chksum = Station number EXOR with 082H Example: To obtain the display reading of an Process Amplifier whose station number is 47 send the following Data:
0FFH, 02FH, 082H, 0ADH
Note MS Bit Set
Response to Command 2 from Process Amplifier Byte
1. Station No.
2. Display reading M.S. Byte.
3. Display reading L.S. Byte.
4. EXOR checksum of above data and Station No.
If, when using commands 1 or 2, an error is detected by the Process Amplifier then the Not Acknowledgement string is transmitted by the Process Amplifier.
Commands 3 To 18: Write data to Process Amplifier parameter
Commands 3 to 18 all have the same format. Format for data transmitted to Process Amplifier for Commands 3 to 18: ­0FFH, Station No, Command No, MSN, NMSN, NLSN, LSN, CHKSUM Where MSN NMSN NLSN LSN CHKSUM
= Most significant nibble of data = Next most significant nibble of data = Next least significant nibble of data = Least significant nibble of data with MSBIT set = The following EXOR’d with each other, Station number, command
number, MSN, NMSN, NLSN, LSN with MSBIT set
Example: To change SP1 to 200.0 on a Process Amplifier whose station number are 47. The following data is sent.
Page 31
Mantracourt Electronics Limited UAB User Manual
30
Please note the following points apply: -
1. The decimal point is ignored i.e. 200.0 equals 2000 digits
2. The data is sent in Hex nibbles so 2000 = 00H, 07H, 0DH, 00H
0FFH, 02FH, 03H, 00H, 07H, 0DH, 80H, 0A6H
Note MS BIT SET
Response to Command 3 to 22 If the data has been accepted by the Process Amplifier then the following acknowledgement string is transmitted by the Process Amplifier.
Station number, 015H (NAK)
If there are any errors with the data received by the Process Amplifier then the following Not Acknowledgement (NAK) string is transmitted by the Process Amplifier: -
Station number, 06H (ACK)
Command 19: EEPROM ENABLE / DISABLE The EEPROM disable facility can be used for any of the following: I. To limit the number of write cycles to EEPROM reducing degradations. II. Change data in the Process Amplifier RAM only, allowing EEPROM to hold power up values. III. Leave base constants in the EEPROM for later update to RAM, which allows manipulation of the RAM before
writing to the EEPROM.
Writing new data from the RAM to the EEPROM. EEPROM disable is achieved by writing 0100H to the Process Amplifier via command 19. In this state all writing to, or reading from the EEPROM is inhibited.
The EEPROM can be re-enabled in 2 ways: By writing 0200H via command 19. This writes the current contents of the variables store in the Process Amplifier into the EEPROM
By writing 0400H via command 19. This updates the variables store from the current contents of the EEPROM.
Examples
To disable the EEPROM on an Process Amplifier whose Station number is set to 47
0FFH 02FH 013H 00H 01H 00H 080H 0BDH
To re-enable the EEPROM and update the RAM with the old EEPROM constants:
0FFH 02FH 013H 00H 04H 00H 080H 0B8H
To re-enable the EEPROM and update it with the new RAM data:
0FFH 02FH 013H 00H 02H 00H 080H 0BEH
For response see 'Response to Command 3 to 22'.
Command 20: Output Relay Reset DATA transmitted to Process Amplifier for Command 20
OFFH, Station number, 094H, CHKSUM
Where CHKSUM = Station Number EXOR with 094H Example: To output a relay reset to an Process Amplifier whose Station Number is set to 47
0FFH, 02FH, 094H, 0BBH
Note MS BIT SET
For response by Process Amplifier see 'Response to Commands 3 to 22'
Page 32
Mantracourt Electronics Limited UAB User Manual
31
Command 21: Auto Tare DATA transmitted to Process Amplifier for Command 21
OFFH, Station number, 095H, CHKSUM Where CHKSUM = Station Number EXOR with 095H Example: To output an Auto Tare command to an Process Amplifier whose Station Number is set to 47
0FFH, 02FH, 095H, 0BAH
Note MS BIT SET
For response by Process Amplifier see 'Response to Commands 3 to 22'
Command 22: Peak Hold Reset DATA transmitted to Process Amplifier for Command 22
OFFH, Station number, 096H, CHKSUM
Where CHKSUM = Station Number EXOR with 096H Example: To output a Peak Hold reset to an Process Amplifier whose Station Number is set to 47
0FFH, 02FH, 096H, 0B9H
Note MS BIT SET
For response by Process Amplifier see 'Response to Commands 3 to 22'
Example of a Basic C ode to Communicate wit h M ANTRABUS
open the serial port with no handshaking
OPEN"COM2:4800,N,8,1,RS,DS,BIN" FOR RANDOM AS#1
request display from device 1
Frame FF
Station No
1
Command 2
And add 80 hex to this byte as it is the last before as the checksum
Checksum of
all bytes except frame
talk$=CHR$(&HFF)+CHR$(&H1)+CHR$(&H82)+CHR$(&H1 XOR&H82)
print the string to t h e port
PRINT#1,talk$;
(must add semicolon after string to stop transmitting a carriag e ret urn) wait for a while (this depends on how many bytes you are expecting and the baud rate!) input all the bytes in the serial buffer
input.from.uab$=INPUT$(LOC(1),#1)
ASCII Format - selected when CP is 129 The serial data to and from the Process Amplifier is formatted as eight bit words with no parity preceded by one start bit and followed by one stop bit. The baud rate (up to 9.6k Baud) is selected on the COMMS module. All communications are carried out using the standard ASCII character set. Incoming line feeds and spaces are ignored; upper and lower case letters are permitted. The incoming data is continually monitored for Carriage Return characters (Chr$13D). If one is received the next three characters (000 - 999) are compared with the Process Amplifier station number (SDST) previously entered via the keypad. N.B. leading zeros must be included. If no match is found the data that follows is ignored.
The next characters received (up to 4 max) are decoded as the 'label', i.e. which variable in the Process Amplifier is to be acted upon. If the label is received incorrectly and cannot be decoded the Process Amplifier will return a '?' followed by a C.R. character. If the received label is followed by a C.R. the Process Amplifier will return the current value of the variable in question. Because there is no hardware handshaking, all transmission from the Process
Amplifier is performed one character at a time upon receiving a Null character (Chr$0) prompt from the Host system. Thus for every character transmitted by the Process Amplifier a prompt character is required from the host. The output from the Process Amplifier is an ASCII string of sixteen characters the last one being C.R. The
first four characters are the Station No. (with leading zeros if necessary) followed by a space. The label then follows
Page 33
Mantracourt Electronics Limited UAB User Manual
32
with spaces added if required to make a total of four characters. The next seven characters is the numerical value of the required variable with polarity, spaces, d.p. and leading zeros added as required.If the received label is followed by an '=' character the Process Amplifier accepts the following numerical data (which must be terminated by a C.R.) and updates the variable in question and returns a C.R. character to the host when prompted. Data input is reasonably flexible. If all five digits are entered, no decimal point need be included. If less than five digits are entered with no decimal point then the last digit is assumed to be the units.
Under normal circumstances the EEPROM in the Process Amplifier continually refreshes the working RAM. However, it can be disabled via the serial input, by sending the instruction 'DROM = 256' after the Station No. In this condition all read/write operations to or from the EEPROM are inhibited. There are two instructions which will re-enable the EEPROM:
1. 'ERRD' - this performs a read from the EEPROM and updates the working RAM with the contents of the EEPROM.
2. 'ERWR' - this instruction writes the new RAM values into the EEPROM.
In both cases the EEPROM continues to refresh the RAM.
Instruction Set for ASCII Serial Communications
Request for data:
DATA sent to Process Amplifier Data returned from Process Amplifier
CR xxx
Station No.
CR xxx
Station No.
DISP CR
label
DOSP CR
incorrect label
xxx 'SPACE'
Station No.
xxx 'SPACE'
Station No.
DISP
label
DOSP
incorrect
label
YYYYYY CR
numerical value
'SPACE' ? CR
DATA sent to Process Amplifier Data returned from Process Amplifier
CR xxx
Station No..label
CR xxx Station No.,
SP1 = 100.0
numerical value
SP3 = 100.0 incorrect label
numerical value
CR
?CR
Page 34
Mantracourt Electronics Limited UAB User Manual
33
Table 5.1
Labels
DISP SP1 IF1 SP2 IF2 HYS OA At DA OPL OPH DP SDST DROM ERRD ERWR RLYS RES TARE
PKR
Description
REQUEST DISPLAY READING SET POINT 1 (SP1) IN-FLIGHT 1 (IF1) SET POINT 2 (SP2) IN-FLIGHT 2 (IF2) HYSTERESIS (HYS) OUTPUT ACTION (OA) AUTO TARE (At) DISPLAY AVERAGES (dA) OUTPUT LOW (OPL) OUTPUT HIGH (OPH) DECIMAL POINT (dP r) CAN NOT BE WRITTEN TO (SDST/CP) DISABLE EEPROM (DROM = 256) ENABLE EEPROM AND READ FROM IT ENABLE EEPROM AND WRITE TO IT OUTPUT RELAY STATUS ( 0 = BOTH OFF, 1 = RELAY 1 ON, 2 = RELAY 2 ON, 3 = BOTH RELAYS ON) OUTPUT RELAY RESET AUTO TARE
PEAK HOLD RESET
Process Amplifier Printer Format
(CP must be set between 0 - 127) Printer selection enables the Process Amplifier to print its current display value to a printer via its communications port. This display value can either be assigned a date and time stamp and/or a log number depending on the user set options entered under mnemonic 'CP'. The log number can be reset or preset using the mnemonic 'Ln'. This value is not saved on power fail. A label can be suffixed to the printed display value using the mnemonic 'LAb'. A large range of labels are available to the user. The time and date are set in the TDP printer itself using its own menu. The printer allows the entry of an additional custom text message.
Three connections are required between the Process Amplifier communications port and the printer with a maximum cable length of 100 meters. (See Chapter 5 Figure 5.11 for Details)
All standard Process Amplifier options are available with the exception of the communications modules, which cannot be connected when the printer option is used.
Additional Mnemonics for the Printer Operation:
When the printer option is fitted further mnemonics are included in the normal range. After the dP r mnemonic are the following: -
Page 35
Mantracourt Electronics Limited UAB User Manual
34
CP
0
1
2
3
At this mnemonic the printer type and print format number is selected. This number being appropriate to the type of printer used. Details are advised with each type of printer selected. Present types available are: - For the ITT IPP-144-40E printer the following numbers apply
Prints a sequential log number with the current display and unit of measure e.g. 00014 0011.3 tonne
Prints date and time with a sequential log number, current display and unit of measure e.g. 00015 0001.7 tonne
05.03.2007 05:06
Prints a sequential log number, current display, unit of measure with customer text message No 1 e.g. MANTRACOURT ELECTRONICS PROCESS AMPLIFIER PRINTER
00012 00023. tonne
Prints date and time with a sequential log number, current display, unit of measure and a customer text message No.1 e.g. MANTRACOURT ELECTRONICS PROCESS AMPLIFIER PRINTER
00013 0023. tonne
05.03.2007 12:03:04
4-7
8,9 10
12 127
Digitec 6700 series
Amplicon AP24 and AP40 Eltron LP2142 - (The label file must be called 'MEL' and the label must contain a LOG NUMBER, THE DISPLAY VARIABLE & a LABEL (not zero). LOG NUMBER, THE DISPLAY VARIABLE & a LABEL (not zero) ASCII string on print command
Continuous ASCII stream of the display data, transmitted on every display update
Note: 1 Note: 2
9 gives an inverted print out It is anticipated that further types of printer will be added, and additional numbers
will be allocated as appropriate
Lab
Label Number
A number can be selected for the appropriate unit of measure. See table below:
Note: 0 = NO LABEL
0 BLANK 1 Deg R 2 Deg C 3 Deg F 4 Kelvin 5 Ib/in 2 6 bar 7 mbar 8 kPa 9 atm 10 mmHg 11 inHg 12 inH2O 13 cmHg
14 mm 15 Wh 16 Db 17 tonne 18 m 19 in 20 ft 21 degrees 22 L/s 23 L/min 24 L/h 25 gals/s 26 gal/min 27 gal/h
28 %RH 29 gram 30 kg 31 lb 32 kWh 33 mile/h 34 % 35 ton 36 %Dev 37 W 38 kW 39 MW 40 pH 41 ppm
42 uS 43 Ohms 44 m/s 45 ft/min 46 RPM 47 RPMx10 48 RPMx100 49 cos @ 50 km/h 51 ms 52 RPM1000 53 Hz 54 kHz 55 V DC
56 mV DC 57 A DC 58 mA DC 59 V AC 60 mV AC 61 A AC 62 N 63 spare 64 spare 65 spare 66 spare 67 knots 68 s
Ln Log Number A range of numbers 0 to 19,999 is available. Any sequential number logging activity can be preset as desired, between these numbers. The number will reset to zero after 19,999. The log number is not saved on power fail and resets to zero on power up.
Page 36
Mantracourt Electronics Limited UAB User Manual
35
Chapter 6 The Amplifier Displays
A range of display /keypad variants are offered to accommodate both surface mount and rack versions of the Process Amplifiers.
Rack Amplifiers The two versions of the rack amplifier RUA1 and RUA2, have different display fixture requirements. The RUA1 is provided with an FCC type shuttered socket on the front of each channel, into which a hand held programmer (LP2) is inserted and latched and which can be removed, once programming is complete. In common with all amplifier displays a 4.5 digit LCD display and keypad is provided to allow for common programming procedures. The RUA2 is fitted with an On-Board front panel mounted display and programming facility of similar layout to the (LP2). However in this case the programming is achieved by inserting a probe through the 2.2mm holes in the front panel.
Figure 6.1 Programmer Unit Pane l Layout (RUA2)
Figure 6.2 LP2 Remote Ha n d H e ld Programmer Unit
When in the programming mode, a Flashing bar symbol ‘-’ is indicated in the top left hand corner of the display. Surface Mount Amplifiers A security link option on the rear of the display pcb, is available to prevent the change of data where required. Where surface mount amplifiers are used, options are available to program with the (LP2), from the FCC socket mounted on the main pcb, or by fitting an On-Board display module (LP1) with nylon stand off pillars, onto the main pcb, using the same FCC socket. The layout of the keypad remains similar throughout.
Figure 6.3 Programmer Unit Panel Layout (LP1)
Page 37
Mantracourt Electronics Limited UAB User Manual
36
Control Panel Guide
d
Used to scroll through and change the set up data by displaying mnemonics for each
configurable parameter, followed by the appropriate data. When in programming mode it should be noted that the first digit in the display might not be visible, but the program indicator --- will be flashing to indicate that the instrument is in programming mode, even though no digits can be seen to be flashing.
b
Selects the display digit required. Selection value is indicated by a flashing digit
and flashing program indicator.
c
Increments each selected display digit 0-9.
Pressing the c key under programming conditions will display the leading digit as
either 1, -1, or a blank display for zero.
a
Resets the display to the input variable and enters new data in the LCA15 memory.
Returns the display to the current value after Hold.
If during the programming sequence, selection is not completed, the display will revert to the input variable after 2 minutes.
The display and controls on the front panel mounted version (RL2) operate in a similar way to the remote display/programmer described above, with program
buttons being accessed through 2.2mm holes in the panel.
A Large Keypad Panel Mount Display is also available which can be mounted to the lid of the ABS case of the surface mount amplifier, or with the necessary driver hardware, can be fitted to a stainless steel panel and used remotely.
Figure 6.4 Programmer Unit Pane l L ay o ut
Page 38
Mantracourt Electronics Limited UAB User Manual
37
Figure 6.5 Display Module Connections and Switch Settings
Table 6.1
Position ON
Function
Factory Settings
1
Enables Keys b and c
ON
2
Enables all Program Keys
d b c & a
ON
3
Enables e and f Function Keys
ON
4
Enables g and h Function Keys
ON
5
Forces display to always be GROSS VALUE only
OFF 6 Forces display to always be NET VALUE only
OFF
Page 39
Mantracourt Electronics Limited UAB User Manual
38
Chapter 7 Programming The Amplifiers
Section 1 - Display & Programming Mnemonics
As described in the previous chapter, there is common symbol and keypad layout for programming all the variants whether it be rack or surface mounting units.
Table 7.1 Configurable Parameters for Process Input
The standard range of programming mnemonics is show in the following table: -
Display Function
(In order of Display)
Range
Function
PASS
SP1
SP2
HYS
OL
OA
1111
Set Point 1
Set Point 2
Hysteresis
Output Latch
Output Action (Inversion) of SP1 & SP2
±19999
2000
ADCL ADCH
-19999 to +19999
-19999 to +19999
0 to +19999 in real display units
Latch set by code in range 0-3 as shown in Table 5.1
Action set by code in range 0-15 as shown in Table 5.2
Security Password. Correct value required proceeding
further (special numbers on request). Password for Analogue Input Calibration routine giving access to: A to D Calibration Low value A to D Calibration High value Sets first output trip or control (Chapter 5 refers)
Sets second output trip or control (Chapter 5 refers)
Sets hysteresis applied to SP1 and SP2 when used for ON/OFF control units (Chapter 5 refers)
Allows SP1 and/or SP2 to be latched until reset externally, from the keypad or via communications port.
Sets output relay action. Can be set to ‘normal’ or ‘inverted’ operation for either or both set points. Gives fail safe operation of any alarm combination, High-High, High-Low, Low-High & Low­Low. (Chapter 5 refers) Also selects whether analogue outputs controlled by display module or PID element in CPU Inversion of the analogue output.
Page 40
Mantracourt Electronics Limited UAB User Manual
39
Pb
Ont
(It)
OFFt
(dt)
dA
Proportional Band
Output on delay
Integral
Output off delay
Derivative Time
Display Averaging & Peak Hold
0 to 1024
0 to 255
0 to 6000
0 to 255
0 to 255
0 to 15
'O' Selects 'Ont'.'Offt' or 'da' function 1-1023 Selects PID mode and value of proportional band, in displayed units. 1024 Selects Integral 'It' only control
When PID is not used, (PB=0) the mnemonic (Ont) sets a delay on time for SP1 & SP2. Set in seconds. Or Selects integral value for PID control in seconds/repeat. 0= Proportional only control. When PID is not used, (PB=0) the mnemonic (Offt) sets a delay off time for SP1 & SP2 set in seconds. Or
Selects derivative value for PID control. 0 = OFF (no derivative)
When PID is not used, (PB=0) the mnemonic (dA) sets a display averaging update rate. Readings may be averaged over a number of updates and can be set as follows: Display update time 0 = 1 readings (standard) approx. 0.4S 1 = 2 readings approx. 0.8S 2 = 4 readings approx. 1.6S 3 = 8 readings approx. 3.2S 4 = 16 readings approx. 6.4S 5 = 32 readings approx. 12.8S 6 = 64 readings approx. 25.6S 7 = Fast update mode approx. 0.1S A peak hold function, which will display the highest recorded value of the measured input, can be set by adding 8 to any of the above settings. To reset Peak Hold press the b key, then within 1 second, press the c key. Can also be reset externally or via comms.
Or
(ct)
IPL
(IpOf)
IPH
Cycle time
Input Low
Offset Factor
Input High
1 to 255
-19999 to 19999
-19999 to 19999
-19999 to +19999
Set time in seconds for one
complete power cycle output of PID power (time proportioned through SP1).
For linear analogue inputs, used to set the required display reading when an analogue input is at its minimum value. Also provides an OFFSET for value for non linear analogue Inputs.Or
For rate/totaliser inputs, the value provides an offset or for totaliser, a count reset value.
For linear analogue inputs, used to set the required display reading when an analogue input is at its maximum value.Or
Page 41
Mantracourt Electronics Limited UAB User Manual
40
(IpSf)
OPL
OPH
Scale Factor
Output Low
Output High
0 - 1.9999
-19999 to+19999
-19999 to+19999
Applies a variable gain to the rate /totaliser reading 1.0000 for unity (0.5000 to halve the display value.)
Used to set the display value at which the minimum analogue output is required.
Used to set the display value at which the maximum analogue output is required.
IP
Input Select
0 to 65
Used to set up the UAB for the input
to be monitored. (See Sections 2-4 of this Chapter)
dP-r Decimal
Point & Reset
range 0 to 61 Code dP Position 0 19999 1 1.9999 2 19.999 3 199.99 4 1999.9 5 19999.
8 16
32
To set the required position of the decimal point on the display and to set the rear contact actions for count reset &/or peak hold &/or latched relay reset &/or print. Or any combination of these.
To make reset input active on any or all of the following add to dP-r No. as follows: Reset totaliser count Reset latched relays or peak hold
Activate print
(Note: Latched relays are not available with peak hold)
cP Comms
Protocol
0-129 Comms Protocol (see Chapter 5) (0
to 127 = Printer 127 = Continuous ASCII stream of display data transmitted on every display update. 128 = 'Fast' MANTRABUS 129 = 'ASCII'
SdSt
(Lab)
Serial Device
Station
Option 0-75
Set by code in range 0 to 254
Used to set individual address of
each UAB when communications port is used. NB: changes can only be made via the keypad (Chapter 5 refers).
Label number to print engineering units. (See Chapter 5)
Ln Log Number 0-19,999 To set Log number. Reset on power
up.
Inp
Input
Variable
Automatically returns the UAB to
the input again after scrolling sequence is completed and updates permanent memory.
Page 42
Mantracourt Electronics Limited UAB User Manual
41
RS Display
Resolution
0-255 Sets display resolution
0 & 1 = Resolution of 1 least significant digit. 2-255 = Resolution setting of last
digits.
Note: Invalid parameter values - Should an invalid figure be entered against any parameter, it will be rejected and the display will return to show the parameter. * This number range will increase as new printer options become available.
Table 7.2 Configurable Parameters for Dual Input Modules
Mnemonic
InPA InPb SP1 SP2 PASSWORD HYS OL OA Pb Ont or It OFFt or dt dA or ct IPLA IPHA IPLb IPHb SF DF OFFS
OPL
Descriptions
Live display of input 'A' Live display of input 'B' As for single channel inputs, except when Ab = 4, when SP1 = value set by input 'b' As for single channel inputs 1111 As for single channel inputs As for single channel inputs As for single channel inputs As for single channel inputs As for single channel inputs As for single channel inputs As for single channel inputs except add 400mS to all display update time Input low scale factor for 'A' input (no IPOF) Input high scale factor for 'A' input (no IPSF) Input low scale factor for 'B' input Input high scale factor for 'B' input Scale factor, unity being 1.0000 except when AB = 3, then unity = 001.00 Division factor, divides result of function x scale factor, by the value set Offset provides a display offset
As for single channel inputs
dPB
Cp SdSt/Lab Ln rS
dis
Sets decimal point position for 'B' input display (for display purposes only)
For single channel inputs For single channel inputs For single channel inputs For single channel inputs
Returns to A, B, function display
Ab
0 1 2 3 4
Function
A + B A - B A x B A/B
Display = Input A, SP1 = Input B
Display =
(Result of A, B Function) x SF
DF
Configurable Parameters fo r UAFLC - Fast Strain Gauge Input Module
Note: Password Protection To prevent unauthorised changes to parameters, other than Set Points and In-Flight compensation settings, a 4 digit password number must be entered. Scrolling through the Set Points and In Flight settings until ‘PASS’ is displayed accesses the number. At this point, it is necessary to enter either the factory set number 1111 in D2 - D5 positions, or the password number specifically ordered by the customer.
Page 43
Mantracourt Electronics Limited UAB User Manual
42
Table 7.3 Configurable Parameters
CODE
VALUE
FUNCTION
Inp P
t
±19999 ±19999
±19999
Live input reading Peak reading
Trough (valley) reading
Section 2 - Setting the Conditions for Linear Inputs
To monitor the analogue input, the unit must be programmed for the appropriate input module and select the required resolution.
Linear Input Code Selection The two input code (IP) options offer scaling of the input for: IP = 0. Scaling between -19999 to +19999 IP = 1. Scaling divide by 10, -1999 to +1999 Linear Input Scaling Input scaling factors are set by the user a nd determine the di splay ra nge over w hich the ana logue mo dule operates . (IPL) Input Low - This sets the displayed value at the modules minimum input. (IPH) Input High - This sets the displayed value at maximum input. If the calculated display is outside the range defined by IPL and IPH, the analogue input will be over-ranged. Example: Assume a 4-20mA input module is required to provide an input of 4mA at 100 and 20mA at 1500. Set IPL at 100 and IPH at 1500 It will be necessary to determine IPL and IPH by gra phic al o r ma thema ti ca l means i f t he know n displa y values do not coincide with the minimum and/or maximum analogue input.
Figure 7.1 Linear Inpu t Sc aling
Method of Calculating IPL and IPH from any known input values
IPL= Low - (Display span) (Low input - Min input)
Display (High input - Low input)
IPH= High + (Display Span) (Max input - High input)
Display (High input - Low input) High input = Known high input value Low input = Known low input value Min input = Lowest measurable value of input PCB fitted Max input = Highest measurable value of input PCB fitted Display span = Highest required display value -minus lowest required display value. Example: Using a 4.20mA input PCB requiring a display of 200 at 6mA and 8000 at 12mA
Page 44
Mantracourt Electronics Limited UAB User Manual
43
Min
Known Low
Known High
Max
Display Value Input Value
IPL 0mA
200 6mA
8000 12mA
IPH 20mA
IPL= 200
-((7800) (6 - 4)) (12 -6)
= 200-(7800 x 2)
(6)
IPL= 200 - 2600 IPL = -2400
IPH = 8000
+ (7800) (20 - 12)
(12 - 6)
= 8000+ (7800 x 8)
(6)
IPH = 8000 + 10400 IPH = 18400
Note 1: If IPL or IPH are greater than ±19999 then divide both IPL and IPLH by 10, this will give less resolution. Note 2: Decimal point can be placed anywhere to suit reading.
Input Calibration Rou tine
Note: It is of the utmost importance that this routine is followed carefully when setting up the instrument with Analogue Inputs.
Most analogue inputs have predetermined calibration constants, which have been written into the software at the time of manufacture; the details of these calibration values are written on a pre-printed white label on each input board against ADCL and ADCH. The values shown on the labels are to be entered in the following manner: -
Scroll to the PASSWORD mnemonic and enter the number - 2000. Press the scroll key, the display will then show the mnemonic ‘ADCL’ (A to D Calibration Low value), this prompts the entry of the value written on the label. Once this value has been entered, scroll to the mnemonic ‘ADCH’ (A to D Calibration High value), which again prompts the entry of the value written on the label.
Note: It is important that the c key is used during this procedure; otherwise the software will attempt to calculate new values for ADCL and ADCH.
Section 3 - The Temperature Input M o d ules (UAT1 & UAT2)
The UAB provides very accurate temperature measurement from thermocouple or resistance thermometer inputs. The microprocessor line arises the input signal with accuracy ensured by the application of a polynomial expression. This arrangement provides a high-resolution digital readout in units of Centigrade, Fahrenheit or Kelvin, as required. Resolution of either 0.1 or 1.0 degrees can be selected from the keypad. The input type must be selected on ordering as detailed in the ordering codes shown above (also see Chapter 8).
Setting Up Codes for Thermocouples To monitor temperature inputs from a thermocouple, set the (IP) code to select the precalibrated analogue input module, together with the required display value and resolution (See Table 7.2).
Page 45
Mantracourt Electronics Limited UAB User Manual
44
Thermocouple Cold Junction Compensation The UATx modules are supplied with a cold junction sensor. For maximum accuracy the cold junction sensor should be placed as close as possible to the junction of copper or non-thermocouple connector cables. This sensor requires to be matched to the UATx otherwise a maximum offset error or ± 2.5% at room temperature may be incurred. To calibrate this offset follow the procedure below: -
1. Short the thermocouple input connection 1 & 2
2. Connect the cold junction sensor across connections 3 & 4
3. Ensure that IPL is at zero
4. Using a reference thermometer, placed so that it is measuring the cold junction sensor temperature, allow the sensor & thermometer to reach thermal equilibrium. Note this temperature.
5. Note the temperature that the UAB display is reading, the difference between the two noted values should be entered into IPL.
6. After entering this value the reading of the reference thermometer & UAB should be similar.
Any further changes to IPL for introducing a system offset to compensate for minor temperature discrepancies between cold junction and the thermocouple cable for example should be added to the value.
Should a display be required in degrees Kelvin, it will be necessary to select the (IP) on 0ºC and set the (IPL) to +273ºC.
Table 7.4 - Thermocouple Input Codes
Thermocouple Type
Range
Readout
Resolution
Code Module
Inputs
J
K
-170ºC to +760ºC
-230ºC to +1300ºC
Centigrade
Fahrenheit
Centigrade
Fahrenheit
0.1
1.0
0.1
1.0
0.1
1.0
0.1
1.0
30 31 46 47
32 33 48 49
UAT2
UAT1
Resistance Thermometers This is normally a PT100 type of RTD. Resistance thermometer connections to the UAB depend upon the lead configuration, which is itself determined by the required level of accuracy.
For applications where a high accuracy measurement is not required a 2 or 3 wire installation is adequate. For high accuracy, a 4-wire connection should be used to compensate for lead resistance and connector losses.
Setting up Codes for Resistance Thermometers To monitor temperature inputs from an RTD, set the IP code to select the pre calibrated analogue input module, together with the required display value and resolution as summarised below.
Table 7.5
Display Units
Resolution
Code
Centigrade
Centigrade Fahrenheit
Fahrenheit
0.1
1.0
0.1
1.0
60
61 58
59
IPL must be set to zero fo r any of these display options, however, if any offset factor is required e.g. to co mpensate for minor temperature discrepancies between cold junction and thermocouple cable, set the (IPL) to the required offset value.
Should a display be required in degrees Kelvin, it will be necessary to select the (IP) on 0ºC and set the (IPL) to+273ºC.
Page 46
Mantracourt Electronics Limited UAB User Manual
45
Section 4 - The Rate/Totaliser Input Module (UARTL)
General Description The module allows the monitoring of frequency, RPM, period or pulse totalising from a wide range of transducers, the details of which are shown in Table 7.5
The module can be configured for any of the functions referred to in Table 7.5 and transducer types, by DIL switches keypad set parameters and connections. See Table 7.6
Setting up the Input
The types of input chosen will depend upon the sensor requirements and can be determined from the table below:
Table 7.6
Type
High Pulse Level
Threshold
Hysteresis
Input Impedance
Excitation
DCV
ACV1
ACV2
AC/DCmV
NAMUR
5-30V
±30mV to 35V
±3V to 35V
±15mV - 5V
2.5 to 17mA
2.5V
*20mV-2V
*2.5V-35V
8mV
1.6mA
1.0V
*5mV to 180mV
*120mV- 2.0V
2mV
90µA
100K min or 5K6
5K min
5K min
10M
680R
5V, 50mA
5V, 50mA
5V, 50mA
5V, 50mA
8.3V, 50mA
*Adjustable by potentiometer. When selecting the type of input required by the sensor, from Table 7.3, set the DIL switches on SW1, as shown in Table 7.4 (The RTL layout diagram Chapter 4 Figure 4.4 refers).
Table 7.7 Input Co n fig u ra tio n
Type SW1) Switch Settings
Legend
ACV1 ACV2 AC/DC mV NAMUR DCV (pull up for volt free or contact type inputs) DCV (pull down for voltage fed inputs up to 30V) DCV (Standard CMOS type input)
* *
1 2 3 4 5 6 7 8 1 0 1 0 1 x 0 1 1 1 0 0 1 x 0 1 0 0 1 0 1 x 0 1 1 1 0 0 1 x 0 1
1 0 0 1 0 x 0 1
1 0 0 0 1 x 0 1 1 0 0 0 0 x 0 1
1 - Switch ‘on’
0 - Switch ‘off’
x - See Note 1
- See Note 2
Note 1: Switch 6 selects a low pass filter with a 10uS time constant on DCV Input only Note 2: For totalising, set switch 7 'on' and 8 'off' on all ranges
Setting the Prescaler
Depending upon the rate of the frequency, RPM or period to be measured or the maximum desired count of the totaliser, it will be necessary to select the prescaler by setting the DIL switches on SW2 as shown in the Table 7.7 below. (See the UARTL layout Figure 4.4)
Page 47
Mantracourt Electronics Limited UAB User Manual
46
Table 7.8
Prescaler
(SW2) Switch Settings
Legend
Divide x 1 Divide x 10 Divide x 100 Divide x 1,000
Divide x 10,000
1 2 3 4 5 6
x 1 0 0 0 0 x 0 1 0 0 0 x 0 0 1 0 0 x 0 0 0 1 0
x 0 0 0 0 1
1 - Switch ‘on’
0 - Switch ‘off’ x - Not used
Note 1: Select only one switch to the ‘on’ position Note 2: It will be necessary to increase the prescale divide factor by setting the switch to a higher position if the input is over range.
Rate Measurement
Rate measurements are achieved by measuring the period between input signals. From this, period measurements, frequency and RPM can be derived. These measurements can be scaled to any desired display range by setting scale and offset factors from the keypad together with a prescaler set from DIL switches on the module. SW1 7 off, 8 on, and IP set by keypad to Table 7.8
Period (Time measurement between pulses)
Period measurements from 20µS to 1999.9mS can be monitored by means of prescaler and is divided into 2 ranges:
Input Code
The input code (IP) sets the type of rate measurement required i.e. Period, Frequency, and RPM and is selected from the table below: -
Table 7.9
Type
Code
Divide by 10
Frequency RPM High Resolutio n RPM Period in mS
Period in µS
12 14 16 2
6
13 15 17 3
7
(i) Period in mSeconds Table 7.10 Period mS Fixed Scale
Prescale
Divide by 1
Divide by 10
Divide by 100
Divide by 1000
Divide by 10000
Input
Resolution
Noise
0.2mS to
1999.9mS
0.1mS
0.1mS
0.02mS to199.99mS
0.01mS
0.01mS
0.02mS to19.999mS
0.001mS
0.001mS
20µS to1999.9µS
0.1µS
0.1µS
20µS to 199.99µS
0.01µS
0.01µS
(ii) Period in µSeco nds Table 7.11 Period µS Unity Sca le (IPSF 1.0000)
Prescale
Divide by 1
Divide by 10
Divide by 100
Input
Resolution
Noise
150µS to 19999µS
1.0µS
3.0µS
20µS to
999.9µS
0.1µS
0.3µS
20µS to
199.99µS
0.01µS
0.03µS
NB: These tables only apply when the scale factor is set to unity and the offset is zero.
Frequency
Frequency measurements from 0.48Hz to 50KHz can be monitored be means of prescaler.
Page 48
Mantracourt Electronics Limited UAB User Manual
47
Table 7.12
Prescale Range
Divide by 1
Divide by 10
Divide by 100
Divide by 1000
Full input
Range Optimum
Input Range
0.48Hz
to199.99Hz
0.48Hz
to100.00Hz
4.8Hz
to1999.9Hz
4.8Hz to
1KHz
48Hz
to19.999KHz 48Hz to
10KHz
480Hz
50KHz 480Hz
50KHz
Figure 7.2 Frequency Unity Scale I n p uts
Worst noise level = 3 x resolution for the same i nput frequency
Note: This applies when th e scale factor is s et to unity and the offset is z ero.
RPM
RPM measurements from 28.8 to 3 million can be monitored be means of prescaler and high-resolution range and represented by 1 pulse per revolution.
Table 7.13 RPM Unity Scal e
Prescale
Range
Divide by 1
High (0.1)
Resolution
Divide by 1
Divide by 10
Divide by 100
Divide by 1000
Full Input Range
Optimum
28.8 to
1999.9
28.8 to 500
29 to 19999
29 to 7000
28.8 to 19999 x 10
28.8 x 10 to
700 x 10
28.8
100
19999 x100
28.8 x100 to 7000 x100
28.8
x 1000
3000 x 1000
28.8 x 1000 3000 x 1000
Page 49
Mantracourt Electronics Limited UAB User Manual
48
Figure 7.3 RPM Unity Scale Ra n ge
Worst Noise Level = 3 x resolution for the same input Input RPM
Count/Rate Scaling & Scaling/Rate
The count/rate input can be represented over any display range by applying keypad set parameters known as scale and offset factors. The actual count/rate would be displayed when the scale factor is unity (1.0000) and offset factor is zero. The scale factor applies a variable gain to the count/rate and is set by the mnemonic (IPSF)
IPSF is calculated as follows:
IPSF = Required change in display digits Change in count/rate value
IPSF has a range of 0.0001 to 1.9999
The offset factor is added to or subtracted from zero offset displayed value and is set by the mnemonic (IPOF).
IPOF is calculated as follows: IPOF = required display digits - (IPSF x required count/rate value)
IPOF has a range from -12767 to +19999
Scaling Example: -
For a low frequency input of 139Hz, a display of 46 litres per minute is required for a high frequency input of 710Hz; a display of 250 litres per minute is required.
Scale Factor - IPSF = 250 - 46 204 710 - 139 = 571 = 0.3573 Therefore IPSF = 0.3573
Offset Factor - IPOF = 250 - (0.3573 x 710) = -3.683 Therefore IPOF = - 3.683
Page 50
Mantracourt Electronics Limited UAB User Manual
49
RTL Module Inputs Figure 7.4 RTL Module Inputs
The RTL module can accept four types of input as follows: -
Notes: Minimum period equals 20µS : For ACV2 inputs over 6V with greater than 50% 'Mark' use ACV1.
Section 5 - Programmin g th e O utp ut Fun ctio ns
Set Points (SP)
Set points are used to produce output signals at any required value so that the operation of the monitored process can be maintained to preset levels. Any excursion beyond set points will activate the relay or relays, to provide alarm or initiate control as required. Two set points (SP1) and (SP2) can be programmed to suit different applications. The actions of either or both set points can inverted if required. For normal operation the set point output is active until the input reaches the set point level. In this condition when the input value is less than the set point, the SP indicator is on and the output relay is energised producing a closed circuit on a normally open contact. When the set point value is reached, the SP indicator is off and the relay is de­energised producing an open circuit output. For an inverted operation the reverse conditions apply. Normal and inverted action is determined by the direction of the input value as it changes. For example: In alarm applications.
A High-High operation allows for a rising input value to operate on two set points to define an acceptable quantity, weight or band of operation.
A Low-Low operation operates on a falling value.
A High-Low operation will operate on a rising or falling value, setting a 'band' by one set point operating normally and the other being an inverted action.
Hysteresis (HYS)
Once a Hysteresis value has been set, it will be applied to both set points entered. It is effective for both normal and inverted action.
Page 51
Mantracourt Electronics Limited UAB User Manual
50
When Hysteresis is applied to set points with normal output action, the input is allowed to rise to the set point value and the output is then turned off. The output is held off until the input value has dropped to the set point minus the Hysteresis value.
Latching Outputs (O L )
The latching facility allows the relay module output to be held until reset either by keypad, external remote or via the communications port. Latching is applied to the off status of the relay SP1 or SP2.
Table 7.14 Output Latch Codes (OL)
SP1
SP2
Code
Unlatched
Latched Unlatched
Latched
Unlatched
Unlatched Latched
Latched
0
1 2
3
Display OL and enter required code using the keypad as detailed in Chapter 3.
Output Action (OA)
The output action facility allows the user to determine whether set points produce normal or inverted output operation. If an analogue output module is also fitted, the output action function determine whether the modules output is inverted or not and if PID power level is also directed to the analogue output. The output action (OA) is entered by a code to suit the requirements of the user.
Output Action options are available. The value of the OA to be entered in the algebraic sum of the following components:
Table 7.15 Output Action Codes (OA)
SP1 Inverted
SP2 Inverted PID on Analogue Output
AN-OP Inverted
= 1
= 2 = 4
= 8
Example 1: If SP1 requires to be inverted and PID on the analogue output, enter 4 + 1 = 5. Example 2: To invert the analogue output and invert SP2, enter 8 + 2 = 10
Delay Timers
For applications where PID is not used (PB=0) and time delayed outputs are specified, 'ON' and delay 'OFF' times can be set via the keypad.
Delay On Timer
The delay on timer applies to SP1 and SP2 and initiates a delay before either set point can turn on. The delay timer will be reset if the off state is called for during the delay time. This is set by ‘ont’ code in seconds ranging from 0 to
255.
Delay Off Timer
The delay off timer applies to SP1 and SP2 and initiates a delay before either set point can turn off. The delay timer will be reset is the on state is called for during the delay time. This is set by ‘oFFt’ code in seconds ranging from 0 to 255.
PID Functions
The four components of a PID function are proportional band (Pb), integral time (It) and derivative time (dt). The cycle time is set by input code (ct). To set the proportional band, display (Pb) and enter the required operating band in terms of the displayed units as described in Chapter 3.
When PB is selected, the Relay 1 (SP1) is used by the PID as a time proportional output.
Page 52
Mantracourt Electronics Limited UAB User Manual
51
PID Empirical Tuning
1. Set Pb to the max 1023 and ct to a low value consistent with the mechanical constraints and system requirements.
2. Vary the input or the set point and note the system response, reduce the Pb by half and repeat, continue to reduce Pb until the process starts to oscillate, then increase Pb until it is stable.
3. Set the integral time to max (6000) and reduce it in stages until the proportional offset is eliminated. There should be a slow oscillation around set point.
4. Set a low value of dt and gradually increase this until the slow oscillation ceases.
5. Lower the value of Pb and increase the value of dt after each change, disturb the process and check that control is maintained. The final setting will be that which gives satisfactory control in the presence of these small disturbances.
6. The following equation must be applied to ensure that the system operates correctly
ct
Pb x it
must be greater than the constant .00012255 where Pb is expressed in whole numbers, ignoring any decimal point setting. i.e. 100.0 will be taken as 1000
Section 6 - Scaling th e Analogue Outp uts Output Scaling
Output scaling factors are set by the user and determine the display range over which the analogue module operates. (OPL) Output Low - This sets the displayed value at the modules minimum output. (OPH) Output High - This sets the displayed value at maximum output. If the display is outside the range defined by OPL and OPH, the analogue output will remain constant at its minimum or maximum output value.
Example: Assume a 4-20mA output module is required to provide an output of 4mA for 1000Kg and 20mA for 6500Kg. Set OPL to 1000 and OPH to 6500 It will be necessary to determine OPL and OPH by graphical or mathematical means if the known display values do not coincide with the minimum and/or maximum analogue output.
Figure 7.5 Analogue Output
Page 53
Mantracourt Electronics Limited UAB User Manual
52
Method of Calculating OP L & O PH fro m any known Output & Display Values
OPL = Low -(Display span) (Low output - Min output)
Display (High output - Low output)
OPH = High + (Display Span) (Max output - High output)
Display (High output - Low output)
Low output = Known low output High output = Known high output Min output = Lowest measurable value of output module Max output = Highest measurable value of output module Display span = Highest required display value minus lowest required display value.
Example: Using a 4.20mA output module where it is required to produce 6mA at a display value of 400 and 18mA at a display value of 1100.
OPL = 400
-( (700) (6 - 4) ) (18 -6)
= 400-(1400)
12 OPL = 400 - 116.66 OPL = 283.34
OPH = 1100
+700) (20 - 18)
(18 - 6)
=1100+(700 x 2)
12
OPH =1100 +116.66
OPH =1216.66
Note 1: OPH must be greater than OPL Note 2: If OPL or OPH are greater than ±19999 then divide both OPL and OPH by 10, this will give less resolution. Decimal point can be placed anywhere to suit reading. Decimal point can be placed anywhere to suit reading.
Calibration
Re calibration can be made by adjusting the gain and offset potentiometers, or by adjusting the values of OP LO and OP Hi. An offset can be achieved by increasing the values of both OP LO and OP Hi, and the gain by increasing the range between OP LO and OP Hi.
Figure 7.6 Showing th e Potentiometers for Gain and Offse t Adj u stment
As described in Chapter 5 the Fast Analogue Output module is specifically designed to be used when the fast strain gauge input module, (UAFLC) is fitted. (However due to physical constraints the module can be used with the Universal Amplifier in its surface mount configuration only.) Although output scaling follows a similar procedure to that of the standard analogue outputs, the re calibration adjustments required to the fast analogue output module are shown in the following diagram:
Page 54
Mantracourt Electronics Limited UAB User Manual
53
Calibration
Re calibration can be made by adjusting the gain and offset potentiometers, or by adjusting the values of OPL and OPH. An offset can be achieved by increasing the values of both OPL and OPH, and the gain by increasing the range between OPL and OPH.
Figure 7.7 Showing th e Potentiometers for Gain & Offset Adjustment
Page 55
Mantracourt Electronics Limited UAB User Manual
54
Chapter 8 Order Codes
RUA Rack Mounted Universal Input Process Amplifier
Inputs 0 to 10Volts 0-20mA DC Volts LDVT Input Temperature Input Type K Type J PT100 Rate/Totaliser Dual Channel LVDT Input Dual Channel 4 to 20mA Input Dual Channel 0 to 10V Input
Fast Strain Gauge
UADCV1 UADCA1 UALV1 UAT1 UAT2 UAPT UARTL UALV2 UADIA UADIV
UAFLC
Comms/Printer Port
Communications 20mA Current Loop RS232/485
RC1 RC3
Relay Module
Relay Output Module (2 x SPCO 500mA50V)
RR1
Amplifier/Display
Universal Amplifier for Remote Programmer (LP2)
Universal Amplifier with internal Programmer
Universal Amplifier for Remote Programmer (LP3)
RUA1
RUA2
RUA1-EX
Accessories
Rack PSU for RF1 & RF2 Rack for 12 Channels with Remote Programmer Rack for 8 Channels with Internal Programmer Blanking Panels for RF1 Blanking Panels for RF2 Remote Programmer for Standard & Fast Input Module Programmer for Hi Res Input Modules VisualLink SCADA Software Full Version VisualLink Runtime Key
VisualLink SCADA Software Demo
RS1 RF1 RF2 RB1 RB2
LP2 LP3 VLA VLR
VDL
UAB Universal Amplifier
Description
Order Code
Universal Amplifier with 4-20mA/0-10V Analogue for either ABS Case or DIN Rail Mounting
UAB
Inputs
0 to 10Volts
0-20mA DC Volts LDVT Input Temperature Input Type K Type J PT100 Rate/Totaliser Fast Strain Gauge
UADCV1
UADCA1 UALV1 UAT1 UAT2 UAPT UARTL UAFLC
Page 56
Mantracourt Electronics Limited UAB User Manual
55
Comms/Printer Port
Communications 20mA Current Loop RS232/485
LC1 LC3
Relay Module
Relay Output Module (2 x SPCO 500mA50V)
LR1
Power Supplies AC & DC
AC Power Supply 110/120V or 220/240V AC
DC Power Supply 9-32V DC
LS1
LS3
Amplifier/Display
Display PCB for fitting to LAC ABS Case
LP1
Mounting & Cases
ABS Case with plain ABS Lid
Stainless Steel Case 220 x 160 x 85mm Die Case 220 x 160 x 85mm DIN Rail Mounting fixture for the LCB/UAB Transparent Plastic Case Lid for ABS Case
LAB
LSS LDC D2 LTL
Accessories
Conformal Coating of PCBs Remote Hand Held Programmer Programmer for Hi Res Input Modules VisualLink SCADA Software Full Version VisualLink Runtime Key
VisualLink SCADA Software Demo
LCC LP2 LP3 VLA VLR
VDL
SMP Surface Mount Process Indicator & Controller
Inputs
0 to 10Volts
0-20mA DC Volts LDVT Input Temperature Input Type K Type J PT100 Rate/Totaliser Dual Channel LVDT Input Dual Channel 4 to 20mA Input Dual Channel 0 to 10V Input
Fast Strain Gauge
UADCV1
UADCA1 UALV1 UAT1 UAT2 UAPT UARTL UALV2 UADIA UADIV
UAFLC
Comms/Printer Port
Communications 20mA Current Loop
RS232/485
LC1
LC3
Relay Module
Relay Output Module (2 x SPCO 500mA50V)
LR1
Power Supplies AC & DC
AC Power Supply 110/120V or 220/240V AC
DC Power Supply 9-32V DC
LS1
LS3
Page 57
Mantracourt Electronics Limited UAB User Manual
56
Amplifier/Display
Display PCB for fitting to LAC, ABS Case
As above (LCD) with backlight Display PCB fitted with a driver for extended distance working - 100 metres ABS Case
As (LCDR) with backlight
LCD
LCD/BL
LCDR
LCDR/BL
Mounting & Cases
ABS Case prepared for PCB with front label (no PCB
fitted) DIN Rail Mounting fixture for the LCB/UAB
Stainless Steel mounting for display PCB
LAC D2
LCS
Accessories
Conformal Coating of PCBs
VisualLink SCADA Software Full Version VisualLink Runtime Key
VisualLink SCADA Software Demo
LCC
VLA VLR
VDL
CE Approvals
European EMC Directive
Low Voltage Directive
2004/108/EC BS EN 61326-1:2006 BS EN 61326-2-3:2006
2006/95/EC BS EN 61010-1:2001 Rated for Basic Insulation Normal Condition Pollution Degree 2 Permanently Connected
Insulation Category lll
Page 58
Mantracourt Electronics Limited UAB User Manual
57
Instrument Setup Record Sheet
Product
Product Code
Serial No
Tag No
Date
Location
Measurement type, range & engineering units
Communication / Baud Rate
UAB/RUA/SMP
Value
PASS
SP1
SP2
HYS
OL
OA
Pb
Ont (It)
OFFt (dt)
dA (Ct)
IPL (IPOF)
IPH (IPSF)
OPL
OPH
IP
dP r
CP
SdSt or LAb
Ln (for printer)
rS
W A R R A N T Y
All UAB products fro m Mantracourt Electronics Ltd. ('Mantraco urt') are warranted a gainst defective materi al and workmanship for a period of (3) three years from the date of dispatch. If the 'Mantracourt' product you purchase appears to have a defect in material or workmanship or fails during normal use within the period, please contact your Distributor, who will assist you in resolving the problem. If it is necessary to r eturn the product to 'Mantracourt' please include a note stating name, company, address, phone number and a detailed description of the problem. Also, plea se indicate if it is a warranty repair. The sender is responsi ble for shipping charges, freight insurance and proper packaging to prevent breakage in transit.
'Mantracourt' warr anty does not apply to defects resulting from actio n of the buyer such as mishandling, improper interfacing, operation outside of design limits, improper repair or unauthorised modification. No other warranties are expressed or implied. 'Mantracour t' specifically disclaims any implied warranties of merchantability or fitness for a specific purpose. The remedies outlined above are the buyer ’s only remedies. 'Mantracourt' will not be liable for direct, indirect, special, incidental or conseq uential damages whether based on the contract, tort or other legal theory.
Any corrective maintenance required after the warranty period should be performed by 'Mantracourt' approved pers onnel only.
In the interests of continued product development, Mantracourt Electronics Limited reserves the right to alter product specifications without prior notice.
Code No. 517-098 Issue 2.5 11.04.14
Loading...