TECHNICAL DATA
ELECTRICAL
CATALOGUE PERFORMANCE FAN POWER MAX OPERATING SOUND WEIGHT*
NUMBER SPEED WATTS TEMPERATURE POWER LEVEL
MAN100M 180m3/hr
50 litres per second 2500 r.p.m 32W 60ºC 43.0 dB(A) 2kgs
MAN125M 220m
MAN150M 420m
MAN200M 720m
MAN250M 730m
MAN280M 1200m
MAN315M 1300m
*PACKED IN OUTERS OF 1
60 litres per second 2490 r.p.m 31W 60ºC 38.0 dB(A) 2kgs
115 litres per second 2350 r.p.m 80W 50ºC 51.0 dB(A) 3kgs
200 litres per second 2520 r.p.m 110W 60ºC 56.0 dB(A) 4kgs
205 litres per second 2520 r.p.m 110W 60ºC 57.0 dB(A) 5kgs
335 litres per second 2400 r.p.m 200W 45ºC 57.0 dB(A) 6kgs
360 litres per second 2410 r.p.m 200W 45ºC 57.0 dB(A) 6kgs
3
3
3
3
/hr
/hr
/hr
/hr
3
/hr
3
/hr
DIMENSIONS
MODEL Ød mm ØD mm A mm B mm C mm E mm
MAN100M 100 (4") 250 272 136 50 72
MAN125M 124 (5") 250 272 147 60 60
MAN150M 149 (6") 340 283 154 53 76
MAN200M 199 (8") 340 283 177 53 55
MAN250M 249 (9") 340 283 177 53 55
MAN280M 280 (11") 405 320 177 82 55
MAN315M 315 (12") 405 320 177 82 55
220-240V- AC. 50Hz IP44. All wiring must comply with current IEE regulations.
A double pole isolating switch, having contact separation of at least 3mm in all poles,
must be used with a 3 amp fuse fitted.
MOTOR
4 pole single phase induction motor with ball bearings fitted for a long, maintenancefree life and protected by a thermo-auto resetting cut-out approved totally
enclosed for protection against dirt and dust.
Motors are continually rated.
GUARANTEE
Two year ‘no quibble’ guarantee.
INSTALLATION
Induct fans suitable for in-line systems and designed for use with suspended ceiling
systems.
CONSTRUCTION
Strong impact, light grey plastic casing. Manufactured from high impact flame
retardant ABS.
SNAP ON MOUNTING BRACKETS
ØD
CATALOGUE NUMBER
MB100 (4”)
Ød
C
B
E
A
(available separately)
MB125 (5”)
MB150 (6”)
MB200 (8”)
MB250 (9”)
MB280 (11”)
MB315 (12”)

PERFORMANCE GRAPH
IINSTALLATION INSTRUCTIONS FOR THE
MAN RANGE OF INDUCT FANS
The MAN range of induct fans can be fitted anywhere into ducting system and
installed in a vertical or horizontal position.
A special snap-in mounting bracket plus a full range of ducting and accessories are
available separately for easy of installation. Please see our catalogue for full details.
Always try to keep the ducting runs as straight as possible for the best performance.
The fans must be securely fixed to a solid surface.
TYPICAL INSTALLATION
Please dispose of
your fan at your
local civic amenity
site. DO NOT dispose
in domestic waste.
ELECTRICAL SUPPLY
This fan requires a live and neutral supply and if required an earth.
The terminal connections inside the electrical cover are:
1. Earth supply in
2. Neutral supply in
3. Live supply in
WIRING
The fan can either be operated from a separate pullcord switch fitted to the ceiling of
the room or can be connected to the light switch so that the fan wil start when the
light is switched on. A double pole fused spur having a contact separation of at least
3mm in all poles must be used and fitted with a 3 amp fuse, and must be situated
outside any room containing a shower or fixed bath.
IMPORTANT
The fan must not be accessible to any person using either the shower or bath.
Manrose Manufacturing Limited
1 Albion Close, Slough
Berkshire SL2 5DT
077343 0506
Telephone: 01753 691399
Facsimile: 01753 692294
Email: sales@manrose.com