Man Roland IPS.LBA-1 Operating Instructions Manual

Operating Instructions
IPS.LBA-1
RIEE B. Burkhard 12/00 16.86902-0029 B / en
Operating Instructions - IPS.LBA-1
Table of Contents
1. General 1
1.1. Various Subassembly Designs/Indexes 1
1.2. Brief Description 1
1.4. Technical Data 2
1.4.1. Programming Data / Identification on the INTERBUS 2
1.4.2. General Technical Data 2
1.4.3. Technical Data of Remote Bus Interfaces 3
1.4.4. Technical Data of Loop Interface (DT+, DT-, DR+, DR-) 3
1.4.5. Mechanical Data 3
1.5. Front View of Module 4
2. Block Diagram 5
3. Diagnostics LEDs 6
3.1. Subassemblies with Index A, B 6
3.2. Subassemblies from Index D onwards 7
4. Pin Configuration 8
4.1. Connector Pin Assignment of X1 Remote In 8
4.2. Connector Pin Assignment of X2 Remote OUT 8
RIEE B. Burkhard 12/00 16.86902-0029 B / en
Operating Instructions - IPS.LBA-1

1. General

1.1. Various Subassembly Designs/Indexes

Subassemblies from Index D onwards are a compatible further development. You can see this by the three additional LEDs at the top edge of the subassembly.
This description applies to both designs. The differences are described in the appropriate topics.
Subassemblies with Index C were never delivered.

1.2. Brief Description

• The IPS.LBA-1 (INTERBUS-Based Press I/O System . Loop Bus Adapter - Type 1) is an INTERBUS remote bus node (bus terminal) and is for linking an INTERBUS loop spur.
• Localizes interruptions in the connected loop spur.
• The INTERBUS IN and OUT remote bus interfaces are executed in two-wire technology (9-pin Sub-D) in accordance with the Interbus specification.
• Separate supply feed for loop and bus terminal logic, which are also galvanically isolated but can be connected externally.
• integrated mains unit for the I/O subassemblies that are connected to the loop – supplies 28.5 V DC.
• Functions only in I
• Diagnostics LEDs for the status of the INTERBUS and supply voltages
• No need to set DIL switches or jumpers
• ID code: 4 (04 hex)
• Number of data words: 0
• MAN Item Number: 16.86958-0022
NTERBUS systems that are controlled by master firmware of Version G4 and above

1.3. Important Note!

When using this subassembly you must also use the general system description (Item No.: T16.86902-0016) and the "Allgemeine Information - Interbus-Loop" [General Information on Interbus Loop](Item No.:T16.86902-0028)! This contains guides to configuration, assembly, commissioning and servicing.
When configuring the loop, you must observe the permissible line lengths, the maximum loop current (1.8A) and the voltage drop in the loop! For optimum functioning of the loop equipment, e.g. the brightness of bulbs, a voltage must be available at every location in the loop of between 23.5V and 30.0V DC. Bus operation (cyclical data traffic) is guaranteed from 15.5V.
RIEE B. Burkhard 12/00 16.86902-0029 B / en
Operating Instructions - IPS.LBA-1
1

1.4. Technical Data

1.4.1. Programming Data / Identification on the INTERBUS

ID code: 04
hex
(04
dec
)
Data length: 0 bytes

1.4.2. General Technical Data

Climatic environmental conditions
Operating temperature range: 0 ..+ 60°C with horizontal installation 0 ..+ 40°C with vertical installation
Relative humidity: 75% at 25°C, no condensation
Mechanical environmental conditions
Vibrations according to IEC 60068-2-6: 5 g
Shock according to IEC 60068-2-27: 15 g
Type of protection: IP 20 according to IEC 529
EMC
Emitted interference according to EN 55011 Class A
Immunity to interference according to IEC
Class 3, assessment criterion 2
61000-4-2 (ESD)
Immunity to interference according to IEC
10 V / m, assessment criterion 1
61000-4-3 (HF)
Immunity to interference according to IEC
Class 4, assessment criterion 2
61000-4-4 (Burst)
Immunity to interference according to IEC
Class 2, assessment criterion 3
61000-4-5 (Surge)
Immunity to interference according to IEC
10 V, assessment criterion 1
61000-4-6 (HF conductor)
Supply for IPS.LBA-1 internal logic (+24V
Rating: 24 V DC
Permissible range: 20 .. 30 V (including ripple)
Ripple 1.2 V
Polarized: yes by diode in series
Current consumption: Index A, B: 100 mA
Stored energy time in case of supply voltage
failure:
Galvanic isolation to internal logic: 500V AC (test voltage)
Supply for loop (+24V
/ 0VSL)
SL
Rating: 24 V DC
Permissible range: 20 .. 30 V (including ripple)
Ripple 1.2 V
RIEE B. Burkhard 12/00 16.86902-0029 B / en
Operating Instructions - IPS.LBA-1
/ 0VL)
L
SS
Index D onwards: 130 mA
10 ms