Manning Systems Airscan IRF9 Quick Start Guide

Manning AirscanTM IRF9 SPECIFICATIONS
Refrigerant, Ammonia and Carbon Dioxide Detector
General Specification
Use Infrared (diffusion) type sensor that works in conjunction with any Honeywell Analytics Manning readout or alarm unit.
Common Operation
Gases Monitored R-404a, R-22, R-507, R-134a, R-407a, R-410a, R-422d, NH
Gas Sampling Diffusion method with no moving parts, real time continuous monitoring of all points
Output Linear 4/20 mA output into a load resistor of 500 ohm maximum
Accuracy +/- 3% full scale
Repeatability +/- 1% full scale
Operational
Humidity 0-100% RH (condensing)
Operating Temperature -40°C to +60°C / -60°F to +140°F
Storage Temperature -28°C to +60°C / -20°F to +140°F
Common Module
Cable Recommendation Three conductor, stranded shielded cable with drain wire, all enclosed in a vinyl jacket. For cable runs up to 200 feet,
use 18# AWG (Belden #8770 or equivalent).
Power Source 24 Volts DC regulated, 1.2 amp max.
Repeatability +/- 1% full scale
Sensor Specifications
Response Time T90 = 10 seconds
with full-scale calibration gas @ .75 litres/min. flow rate
Ranges R Gases: 0-500 ppm, 0-1,000 ppm, 0-3,000 ppm CO
Sensor Viability Test SensorCheck, an internal microprocessor determines the sensor’s electrical viability every 24 hours. If the viability test fails a 0.5 mA signal will indicate a fault. An internal light will show if a sensor is dried up or disconnected.
Enclosure 16 gauge painted steel or stainless steel. NEMA 4, UL 508 listed, CSA certified for use with industrial control equipment.
Weight 4.4 lbs.
: 0-1%, 0-3%; NH3: 0-2%, 0-4%
2
, CO
3
2
© 2010 Honeywell Analytics