19
Simple Zero Test 19
4/20 mA Output Loop Integrity Check 19
F
Troubleshooting
Electrical Interfer
ence21
Figure 10: Troubleshooting the AirScan
TM
iR 21
21
Sensor On-Board Diagnostic System 21
Error on 4/20 mA Output 22
Sensor Output at 0 mA 22
Sensor Output at .5 mA 22
Gas Concentration Indicated with No Refrigerant Present 22
IR Source Failure 22
This manual has been prepared to help in the use and installation of the Manning Systems
AirScan
principles of the sensor, ensure proper installation, and demonstrate start-up and routine
maintenance procedures.
This manual must be carefully followed by all individuals who have or will have the
responsibility for using or servicing the AirScan
Manning Systems, Inc. with respect to this equipment will be voided if the equipment is
not used and serviced in accordance with the instructions in this manual. If in doubt
about a procedure, please contact Manning Systems, Inc. before proceeding.
TM
iR (Infrared Refrigerants) Sensor. This manual will convey the operating
Gas detection by the infrared method is based on the
principle that most gases absorb infrared energy at a
characteristic frequency. In this instrument, a broad
band infrared source emits energy which is then bandpass filtered to produce a narrow range of frequencies
characteristic of the refrigerants’ (CFC/HCFC/HFC)
absorption spectra. Any refrigerant in the gas sample cell
selectively absorbs energy reaching the detector. This
reduction in energy is detected, amplified and sent to the
signal processing portion of the system.
TM
The Manning Systems AirScan
iR Sensor line is a threewire, 4/20 mA sensor for two bands of refrigerants
available in a range of 0–3,000 ppm, but can be adjusted
for lower ranges, if required. The low-band or R-404a
infrared sensor reacts to R-123, R-134a, R-404a and R-507.
The high-band or R-22 AirScan
TM
iR sensor reacts to R-22.
Its solid, high-mass metal bench provides structural and
thermal stability, greater immunity to vibration, as well as
superior EMI/RFI shielding of the detector and source.
Internal compensation for environmental changes allows
the sensor to automatically adapt to fluctuating
temperature and humidity conditions. The unit exhibits
extremely high reliability with no moving parts.
Every two seconds SensorCheckTM technology monitors
the AirScan
TM
iR source and ensures that the dual
channels are functioning properly. A notification signal
will be transmitted if any of several performance
parameters is not met.
Monitoring equipment must be configured to indicate a
fault if the signal is less than 1.5 mA. All signals over
20 mA must be considered a high gas concentration.
Manning Systems infrared sensors are normally longlived (5 years plus), unless physically damaged or wetted
with water or other liquid.
System Specifications
Electrical Power: 24 Volts DC regulated, 1.0 amp.
Output: Linear 4/20 mA output into a load resistor of
500 ohms maximum
Cable Length to Sensor: 1,000 feet maximum
Cable Recommendation: Three conductor, stranded,
shielded cable with drain wire, all enclosed in a vinyl
jacket. For cable runs up to 200 feet use, #18 AWG
(Belden #8770 or equivalent). For cable runs up to 1,000
feet, use #16 AWG (Belden #8618 or equivalent).
Unit Enclosure: NEMA 4, gasketed, molded fiberglass
reinforced polyester. Non-painted, non-rusting
construction appropriate for food areas. UL 508 listed,
CSA certified for use with industrial control equipment.
source strength evaluation, incoming voltage monitor,
IR source integrity check, operating temperature monitor,
“zero” down drift monitor, and internal circuitry check.
Accuracy: ± 3% of full scale
Repeatability: ± 1% of full scale
Cross Sensitivity: Not affected by moisture, food odors,
floor cleaners, temperature changes, etc.
Operating Humidity: 0–100% RH (condensing)
Operating Temperatures: –20° F to +140° F
Storage Temperature: –20° F to +140° F
Gas Sampling: Diffusion method with no moving parts
Sampling Frequency: Real time continuous monitoring
Because each sensor can only “report” what it is
seeing at the moment,
sensor be located where leaks are most likely to
occur.
CFC/ HCFC/HFC vapor is heavier than
ambient air, so in a room with no air movement it will
tend to settle. For quickest detection, mount the
sensor about one to two feet from the floor, close to
the potential leak source.
If the primary application is the fastest possible leak
detection, mount the sensor near the potential leak
sources. In doing this, be aware that the indicated
concentration may not be representative of personnel
exposure and easy access for the required calibration
and maintenance could be compromised.
General Mounting Considerations:
•Must be easily accessible for calibration and
maintenance.
Always mount the sensor vertically.
•
•Mount the sensor clos
sour
ce for fastest possible leak detection.
•If personnel protection is the primary
application, moun
Protect sensor from water, excessive hu
•
and
wash-dow
Take air movement and ventilation patterns into
•
account.
Figure 1: Mounting Dimensions for the AirScanTMiR Sensor
it is very important that the
e to the potential leak
t in the “breathing zone.”
midity,
n.
•
To prevent electrical interference, keep sensor
and wire runs away from mercury vapor lights
var
iable speed drives, and radio repeaters.
,
•Protect sensor from physical damage (fork lifts,
etc.).
•Do not mount the sensor over a door in a
refrigerated area.
•For highly critical locations more than one
sor should be installed in each room.
sen
Very Important:
• Sensor must be mounted vertically
Never mount sensor flat on a ceiling
•
• E
nter enclosure
bottom of
Always make a drip loop in the conduit
•
Never mount sensor on a vibrating surface.
•
only through existing hole in
enclosur
e
Mount sensor enclosures through the flange holes as
shown in Figure 1, and
Penthouses: Multi-Coil (defrost one coil at a time) –
always mount vertically.
In this case the best location is usually in the center of
the penthouse four or five feet above the grate.
Single Coil (or when all coils defrost at the same time)
In this case high moisture conditions can occur and the
sensor should be mounted one foot above the grate.
Engine Rooms: The AirScan
TM
iR sensor should be
mounted in a cool part of the room, if possible. Keep
the sensor away from hot air exhausting from electric
motors or other machinery.
–
MOUNT ENCLOSURE T HIS END UP. DO NOT BLO CK PERFOR ATED VEN T HOLES.
iR
sensors near evaporators, mount the sensor no higher
than two feet below the top of the evaporator coil.
Do not mount in high air flow (1,200 feet/minute
maximum).
Never mount the sensor on evaporators as
vibration can damage the sensor.
Other Locations: When mounting AirScan
TM
iR sensors
in locations such as roof top air units, ductwork, attic
spaces, makeup air intakes, etc., contact Manning Systems
for application assistance and recommendations.
B Wiring
Electrical wiring must comply with all applicable codes.
Plant equipment that may be involved and operating conditions should be discussed with local operating personnel
to determine if any special needs should be considered.
Nearly all start-up problems are due to improper wiring
or monitor configuration. Please follow these guidelines
carefully.
Always use three conductor, insulated, stranded,
shielded copper cable. Use
not two cables of two conductor wire (see Figure 2).
If the AirScan
TM
iR is to be used with the AirAlertTM96d,
please call Manning Systems for specific wiring instructions.
Do not pull sensor wiring with AC power cables. This will
cause electrical interference. Be sure there are no breaks
or splices in sensor wiring runs. If cable runs cannot be
made without a splice, all connections must be soldered.
Soldering should be done using a rosin flux to tie the
connecting ends of sensor wires to ensure a positive and
long-lasting contact.
only three conductor cable,
Ground the shield at the main control panel. Connect
the shield wire in the sensor terminal block labeled
shield. Tape all exposed shield wire at the sensor to
insulate it from the enclosure.
All penetrations into a refrigerated room should be
sealed to prevent condensate from forming in the
conduit and dripping into the sensor enclosure.
Make drip loops for cables going into sensor housings
(see Figure 1). Follow the special mounting instructions
on the enclosure (…This End Up).
Electrical Power: 24 VDC regulated, 1.0 amp.
Output: Circuit board mounted sensor provides a linear
4/20 mA output. Monitoring equipment may have a
maximum input impedance of 500 ohms.
Contact Manning Systems for specific wiring
instructions when using AirScanTMiR sensors with an
AirAlert
Cable Recommendation: Use #18/3 (Belden #8770)
TM
96d readout unit.
for cable runs up to 200 feet. Use #16/3 (Belden
#8618) for cable runs up to 1,000 feet. Use only the
existing punched holes for connections to the sensor.
Monitoring: The AirScan
TM
iR Refrigerant Sensor may be
monitored by any Manning Systems Readout/Alarm unit
or other appropriately configured system. Monitoring
equipment must be configured to indicate a fault if the
signal is below 1.5 mA. All signals above 20 mA must be
considered a high gas concentration. A failed sensor will
output a 0.5 mA signal.
Figure 2: Wiring Diagram for the AirScanTMiR Sensor
White connects to signal input of
monitoring equipment
including two normal run modes, two 4/20 mA loop
check modes and five calibration modes. These will be
explained in Operation, Section C, Modes of Operation.
Modes are entered by properly activating pushbuttons
located on the circuit board, shown in Figure 4.
Sensor operation status is indicated by the blink
pattern of seven LEDs located in a vertical row on the
right side of the sensor circuit board (see Figure 4).
LED status is differentiated by color and duration/
pattern of blink(s). LED Indicators and Blink
Sequences are shown in Figure 6, followed by an
explanation of blink patterns.
AStart-Up Procedure
Before applying power, make a final check of all wiring
for continuity, shorts, grounds, etc. It is usually best to
disconnect external alarms and other equipment from the
sensor until the initial start-up procedures are completed.
Check the power supply voltage to the sensor with a
digital volt meter set to VDC. Place the black lead on
sensor terminal GND and the red lead on +24 (see
Figure 4, Note 1). Voltage should be between 21 and 28
VDC. If voltage is outside this range, check power supply
and wiring.
After power-up, ensure the LEDs below are operational
as follows (see Figure 3):
TM
IMPORTANT: The AirScan
iR sensor is factory
calibrated and should require minimal adjustments after
installation.
CARB Compliance: To ensure continued compliance
with CARB performance guidelines, calibrate the unit
in the environment in which it will be used. Frequency
of calibration can improve accuracy; Honeywell
Analytics recommends calibration every 6 months.
Environmental factors such as temperature, humidity,
and pressure can affect accuracy. Consider these factors
when establishing a maintenance program .
Allow the sensor to operate for 12 hours with the
enclosure sealed prior to testing the sensors. This will
give the sensor time to reach thermal equilibrium to the
external and internal temperatures while in operation.
Because sensors are normally located at a distance from
the main unit, the test time required and accuracy of the
response checks will be improved if two people perform
the start-up procedures and use radio contact.
Start-Up Test:
1)
One person exposes each sensor to a small amount
of the gas that is being monitored.
2)
The second person stays at the control unit to
determine that each sensor, when exposed to the
gas fumes, is connected to the proper input and
responds, causing appropriate alarm functions.
•Green “Power” LED continuous ON
•Both Fault LED’s are OFF
•Green “source” LED is blinking once every
2 seconds
NOTE: For cold/humid adverse environmental conditions
the “ATMOS” LED may be turning on and off periodically. In addition, the “system” LED may be blinking or
continuous ON, also described in later sections.
The AirScanTMiR has two internal pushbuttons, and two
adjustment pots that are utilized for navigation of test
functions, calibrations, and operating modes. In addition,
a pair of test points is also provided that assist in the
connection to standard meter leads for use in the
upcoming calibration and diagnostic procedures (see
Figure 4).
Figure 4: Board Component Layout
Serial PortICSP Programming Port
Zero Adjust
Span Adjust
Note 1: Checking
voltage to sensor
at +24 and GND
24
VDC
Black-Red
Note 2: Reading
signal at TEST+
and TEST-
+
40-200
mVDC
JP1
TEST +
TEST -
ZERO
SPAN
SIG
+24
GND
SHLD
Pushbutton S2
JP3
S1
S2
Chamber
Draw
Rx LEDPushbutton S1
Tx LED
JP2
CALIBRATE
mA FAULT
IR SOURCE
POWER
SYSTEM
FAULT
ATMOS
ACTIVE
“Zero” adjustment pot – adjusts output calibration
•
of the 4 mA nominal resting point
•“Span” adjustment pot – adjusts the 20 mA
concentration level or unit span/sensitivity.
•Pushbutton S1 – used to initiate the auto-zero
f
unction, program the 4 mA output calibration,
and initiate the 4/20 mA loop test.
•Pushbutton S2 – used to program the span setting.
•Test(+) and Test(–) for connection to a DC Volt
me
ter (see Figure 4, Note 2)
IMPORTANT: The pushbutton(s) must be pressed the
correct number of times and at the correct rate.
•When a multi-press sequence must be performed,
the button must be pressed rapidly and evenly,
lifting one’s finger completely from the actuator
for each consecutive press.
•For press and hold activations, one’s finger must
always be applying a down pressure withou
ruption for the sp
dis
ecified time in order to
activate the desired mode.
•
See complete details of each operation in other
parts of the manual.
TM
The AirScan
iR also has a group of LED’s (see Figure 5)
that blink in specific sequences (see Figure 6 on next
page) to indicate sensor operation and programming
modes. A summary of sensor operation and
programming modes with corresponding LED blink
sequences is shown in Figure 7 on page 10.