Manning Systems AirAlert 96d Operating Manual

Multi-Channel Gas Monitoring System
Manning AirAlertTM96d
Instruction and Installation Manual
07/09
Release C Draft
Honeywell Confidential & Proprietary
This work contains valuable, confidential, and proprietary information. Disclosure, use
or reproduction outside of Honeywell Inc. is prohibited except as authorized in writing.
This unpublished work is protected by the laws of the United States and other countries.
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 1
Notices and Trademarks
Copyright 2009 by Honeywell International Inc.
Release C July 2009
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Manning is a registered trademark of Honeywell International Inc.
Other brand or product names are trademarks of their respective owners.
Honeywell Analytics 405 Barclay Blvd. Lincolnshire, IL 60069 USA
1-800-538-0363
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 2
About This Document
World Wide Web
The following Honeywell web sites may be of interest.
Honeywell Organization WWW Address (URL)
Corporate www.honeywell.com
Honeywell Analytics www.honeywellanalytics.com
Manning Gas Detection www.manningsystems.com
Telephone
Contact us by telephone at the numbers listed below.
Organization Phone Number
United States Honeywell Analytics Inc. 1-800-538-0363 1-913-712-5576 1-913-712-5580 Fax
Canada Honeywell Analytics Inc. 1-888-749-8878
Europe Honeywell PACE +44 (0)1202 676161
Asia Pacific Honeywell Asia Pacific Inc. +82 (0)2 2025 0307
Middle East Honeywell Analytics Inc. +971 4 3458 338
Sales Information
Contact us at detectgas@honeywell.com
Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol Definition
ATTENTION: Identifies information that requires special consideration.
TIP: Identifies advise or hints for the user, often in terms of performing a task.
REFERENCE-EXTERNAL: Identifies an additional source of information outside of this bookset.
REFERENCE-INTERNAL: Identifies an additional source of information within this bookset.
WARNING: Indicates a potentially hazardous situation, which, if not avoided, could result in injury or death.
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 3
Contents Serial number:
Section Title Page
1 Introduction 6 A Safety Information — Read First 6 B Getting Started 6 2 Installation 7 A Guidelines 7 B Mounting Installation 7 3 Wiring 8 A Power 10 B Communication 10 C Relay Outputs 11 D Jumper Instructions 11 4 Initial Startup 12 A Datalogger (SDcard) 12 B User Interface 12 5 Operation 13 Normal, Single Tx, Debug, and Simulation Modes 13 6 Programming Menus 14
Controller Information 14 Sensor Information 14 Relay and Annunciator Information 14 Event Information 14
7 Configuration 15 A Main Menu 15 B Acquisition Mode 18 8 Specifications 24 9 Maintenance 24 Periodic Inspections and Calibration 24 Replacement Parts 24 Cleaning 24 Battery Disposal 24 10 Relay Module (optional) 25 11 Limited Warranty 27
Figure Title Page
1 Manning AirAlertTM96d 6 2 Installation 7 3 System Wiring 8 4 Sample Network Wiring 9 5 Power Wiring 10 6 Communications Wiring 10 7 Relay Outputs 11 8 Datalogger 12 9 User Interface 12 10 Tx Log 19 11 Manning AirAlert 12 Relay Module PCB 26
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 4
TM
96d-RMS 25
Introduction
This manual has been prepared to help in the use and installation of the Manning AirAlertTM96d Multi-Channel Gas Monitoring System. This manual will convey the operating principles of the sensor, ensure proper installation, and demonstrate start-up and routine maintenance procedures.
ATTENTION: This manual must be carefully followed by all individuals who have or will have the responsibility for using or servicing the Manning AirAlert
Honeywell Analytics with respect to this equipment will be voided if the equipment is not used and serviced in accordance with the instructions in this manual. If in doubt about a procedure, please contact Honeywell Analytics before proceeding.
TM
96d gas monitor. Warranties made by
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 5
1 Introduction
Warning
To ensure your personal safety, read “Safety Information” (below) before you use the controller.
The Manning AirAlert
TM
96d system sets new standards in gas detection and in the measurement of environmental parameters.
Acting as the nerve center of a modular gas detection network, the Manning AirAlert
TM
96d provides continuous monitoring of up to 96 connected units on three distinct channels.
The Manning AirAlert
TM
96d provides a full array of displays. At a glance, it is possible to determine the status of the entire network. Field modifications are straightforward. A menu driven program allows for minor fine-tuning of the sequence of operation all the way to the reconfiguration of the entire network.
Since no two projects are alike, the Manning AirAlert
TM
96d is designed to be highly customized. Combined with ease of installation, this unit represents the most affordable gas monitoring solution for institutional, commercial and light industrial applications.
For more advanced applications, the Manning AirAlert
TM
96d controller provides datalogging capacity within a cast aluminum enclosure. The perfect solution for even the most complex of industrial applications.
A Safety Information — Read First
Use the controller only as specified in this manual, otherwise the protection provided by the controller may be impaired.
Warning: To prevent ignition of flammable
or combustible atmospheres, disconnect power before servicing.
Do not use the controller if it is damaged. Before you use the controller, inspect the case.
If the controller is damaged or something is missing, contact Honeywell Analytics immediately.
To avoid possible damage to the controller:
Do not expose the controller to electrical shock and/or severe continuous mechanical shock.
Do not attempt to disassemble, adjust, or service the controller unless instructions for that procedure are contained in the manual and/or that part is listed as a replacement part. Use only Manning replacement parts.
The controller Warranty could be voided if customer personnel or third parties damage the controller during repair attempts.
B Getting Started
Intended Use
The Manning AirAlert around the clock monitoring of the gas detection network. Moreover, a log of all the sensors concentrations and alarms will be created for analysis with the datalogger option. Also, the grouping/zoning capabilities will result in energy cost savings.
Figure 1. Manning AirAlertTM96d
TM
96d controller will provide
Read the Warnings and Cautions on the following pages before using the controller.
Note: This instrument contains a lithium battery. Do not mix with the solid waste stream. Spent batteries should be disposed of by a qualified recycler or hazardous materials handler.
Caution
To avoid possible personal injury:
Manning AirA lert 96d
Enter ESC Silence
Warn
Alarm
High Alarm
Power
Fault
TX
RX
Warning: Substitution of components may
impair intrinsic safety.
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 6
2 Installation
A Guidelines
These guidelines must be strictly observed to assure that the equipment will work properly. If they are not applied, Honeywell Analytics will not recognize any liability in case of improper operation.
Make sure to locate all units easily accessible
for proper service.
Avoid any location where units could be
subject to vibrations.
Avoid any location close to any electro-
magnetic interference.
Avoid any location where there are large
temperature swings.
Verify local requirements and existing
regulations, which may affect the choice of location.
Warning
A cable with more than one pair of wires is unacceptable for communication use.
B Mounting Installation
The suggested height for controller installation is 5 feet from the floor.
Figure 2. Installation
Manning AirA lert 96d
5’
13.2”
Enter ESC Silence
Warn
Alarm
High Alarm
Power
Fault
TX
RX
0.28” diameter
6.25”
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 7
3 Wiring
Figure 3. System Wiring
In Out
J22
V+ V-
V+
EOL2
V-
RC
R
J23
A1 B1 SHLDA2B2
EOL3
SD card datalogger
RC
R
Pushbutton
EOL4
RC
R
J24
SHLD A3 B4B3A4
EOL1
RC
R
End-of-line jumper position
Relay 4
Relay 3
Warn
Alarm
System status LEDs
High Alarm
Power
Relay 1 Relay 2
Fault
TX
RX
NO NC NO NC
J26
J3
J7
NC
NO
NC
NO
J25
Relay Outputs (J3-J7-J25-J26) 5A, 30 Vdc or 120 Vac (resistive load)
Previous
Channel 2
Channel 1
Channel 4
642
Channel 3
531
Next
Power Requirements (J22): Communication Requirements (J23 - J24):
24 Vdc, 500 mA 24 AWG twisted pair, shielded (Belden 9841 or equivalent)
14 AWG, 2 conductor, stranded cable (Belden 5100UE or equivalent)
Up to 10 sensors per power supply
Up to 1,000 feet max power cable length per power supply
Larger power cable and/or additional power supplies may be required for longer cable runs and/or increased number of sensors
Contact Honeywell Analytics for help with all power requirements.
Network can be up to 2,000 feet per channel
Avoid “T-taps” if possible
Do not exceed 65 feet per T-tap
Do not exceen 130 feet total of all T-taps
Communication wire shield must be connected to shield terminal(s) of controller (J23-J24)
Channels 1-2-3: Modbus protocol — Communicates only with Modbus devices
Channel 4: Modbus output only — No sensor can be connected to Channel 4
Normally open
Normally closed
3+5 4+6
1+3 2+4
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 8
3 Wiring continued
Example of system wiring with network devices:
Figure 4. Sample Network Wiring
Supply
V+ V-
AirAlert 96d
V+
V-
A1 B1 SHLDA2B2
SHLD A3 B4B3A4
Power cable (V+)
Power cable (V-)
Channel 1 (A1 and B1 twisted pair)
Power Supply
IRIM IMPower
VL
EC EC EC EC EC EC
VL
EC EC EC ECEC EC EC EC EC EC
Relay
Module
RS-485 comm cable; Twisted pair, 24 AWG, shielded (Belden 9841)
Power cable; Two conductor, 14 AWG (Belden 5100UE)
4/20 mA comm cable; Three conductor, 18 AWG, shielded, stranded (Belden 8770)
VL sensor cable; Four conductor, 16 AWG, non-shielded
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 9
3 Wiring continued
r
A Power
B Communication
The power requirement range for the Manning AirAlert
TM
96d controller is 24 Vdc, 500 mA. The system must be grounded to the power supply. A dedicated circuit breaker should be used. Use 14 AWG two conductor, stranded cable (Belden 5100UE or equivalent), up to 1,000 ft.
If the controller is sharing a power supply
with multiple sensors on the network, care must be taken to observe voltage drops (line loss) on the power cable. Supply voltages less than 17 Vdc can render some network devices inoperable. Any supply voltage less than 17 Vdc requires the installation of an additional power supply at that point on the power cable.
Depending on total power consumption, avoid powering more than 10 network devices with one power supply. Additional power supplies and/or
decreased number of network devices may be required to compensate for line loss. Contact Honeywell Analytics for help with all power requirements.
Note: Terminal J27 must be grounded to
mechanical ground.
Figure 5. Power Wiring
The communication cables have to be grounded using the shield terminal. Up to 32 network devices can be installed on each channel.
Use 24 AWG two conductor, twisted and shielded cable (Belden 9841 or equivalent) for the connection. The network can be up to 2,000 feet per channel. The length of a T-tap can be a maximum of 65 feet (20 m). A maximum of 130 feet (40 m) for all the T-taps must be respected.
The communication cables have to be grounded using the shield terminal. Use twisted and shielded cable #24/2 AWG (Belden 9841) for the connection.
Note: Channel 4 is the slave communication channel to retransmit the MODBUS signal to
PLC. No sensor can be connected to this channel.
Figure 6. Communications Wiring
RC
R
J23
A1 B1 SHLDA2B2
EOL3
RC
R
EOL4
RC
R
J24
SHLD A3 B4B3A4
EOL1
RC
R
End-of-line jumper position
Powe
Fault
TX
RX
EOL3
A1 B1
RC
R
Channel 2
A2
Channel 1
Communication Requirements:
24 AWG twisted pair, shielded (Belden 9841 or equivalent)
Network can be up to 2,000 feet per channel
Avoid “T-taps” if possible
End-of-line specification:
The E.O.L. jumper for channels 1-2-3-4 must alwaysbe in E.O.L. position
Channel 4
Channel 3
RC
R
J23
Previous
J22
V+ V-
In Out
V+
EOL2
V-
Do not exceed 65 feet per T-tap
Do not exceen 130 feet total of all T-taps
Next
Communication wire shield must be connected to shield terminal(s) of controller (J23-J24)
Channels 1-2-3: Modbus protocol — Communicates only with Modbus devices
Channel 4: Modbus output only — No sensor can be connected to Channel 4
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 10
3 Wiring continued
C Relay Outputs
The relay outputs will withstand up to 5 amps at 30 Vdc (resistive load only). They can be used to activate horns and strobes. Refer to Figure 7 for proper wiring. Each relay can be configured in the PROGRAMMING MENU.
Default setting is:
Relay 1 (J25) = Warn Relay 2 (J26) = Alarm Relay 3 (J3) = High Alarm Relay 4 (J7) = Fault
Relay rating: 5 A, 30 Vdc (resistive load)
D Jumper Instructions
Figure 7. Relay Ouputs
Relay 4
Relay 3
Warn
Alarm
System status LEDs
High Alarm
J3
J7
NC
NO
NC
NO
The different jumpers on the PCB enable the user to make different operations manually.
Jumper EOL1, EOL2, EOL3, EOL4
: Enable the user to add an END-OF-LINE jumper to improve the communication signal. Two positions are possible, R or RC. It can vary in accordance with the system constraints. See the wiring detail for the EOL position.
Jumper RELAY J29, J30, J31, and J32 used to test the relay. Short pins to test.
: They are
Power
Relay 1 Relay 2
Fault
TX
RX
NO NC NO NC
Relay Outputs (J3-J7-J25-J26) 5A, 30 Vdc or 120 Vac (resistive load)
J26
642
531
J25
Normally open
Normally closed
Relay Jumpers:
Short jumper to test relay
End-of-line specification:
The E.O.L. jumper for channels 1-2-3-4 must always be in E.O.L. position
3+5 4+6
1+3 2+4
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 11
4 Initial Startup
Be sure to connect the system as shown in the wiring detail before powering up the unit. Apply power to the controller and all network devices. Then remove the SHDN jumper to start the unit.
A Datalogger (SDcard)
The DLC option for the controller collects data automatically and stores it on a digital flash Multi­MediaCard (SDcard). If the SDcard becomes full:
The information logging is stopped
No Sdcard flag is displayed on the screen
The Sdcard LED blinks
Note: For log activation or deactivation, please refer to the Acquisition section.
Warning
Always deactivate datalogging function before removing the SDcard. Never
remove the SDcard when the red LED is on.
B User Interface
The main display indicates the firmware revision number, time and date, number of sensor/events/ groups programmed in the controller, etc.
LED Definition:
Warn, Alarm and High Alarm — Red LEDs indicate that one or more sensors have reached the corresponding alarm level. If LED Warn is blinking, an Event is activated (no alarm).
Power: Green LED indicates that the controller is powered on and functioning properly.
Fault: Yellow LED indicates a fault (communication problem with a network device).
TX: Yellow LED will blink when the controller is sending information on the communication channel.
RX: Green LED will blink when a sensor sends information to the controller.
Figure 9. User Interface
Figure 8. Datalogger
SD card
Card in use
LED1
Keypad The keypad is used to move the cursor into the various programming fields (up, down, left and right) or to adjust the display contrast.
Enter key The enter key is used to access the programming menu [which requires a password (default password is 9935)] and to modify the programming fields.
Manning AirAlert 96d
Enter ESC Silence
ESC key
The escape key is used to exit the programming menu or to cancel an input.
Warn
Alarm
High Alarm
Power
Fault
TX
RX
Silence key
Will turn off the buzzer of AirAlert 96d (see latching option).
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 12
5 Operation
The available system operations are based on four different modes: normal mode, single Tx mode, debug mode, and simulation mode. These system modes enable the user to use, analyze, debug, and simulate actions that can be taken by the system. Password is needed to access the different programming menus. The system services might be interrupted by some menu operations.
A Normal Mode
When the system is in Normal Mode, some values can be changed without interrupting the system service. After changing a value in the menu fields, the new value will take effect right after the user gets back to the MAIN MENU. The Normal Mode is the normal system operation.
Note: Entering the EVENT MENU will disable
Event evaluation and reset their status — during that time, the system is out of service until the user goes back to the MAIN MENU.
Normal Mode Menu
1 Tx Info
2 Groups
3 Events (block Event evaluation if acceded)
5 Copy
7 Network
Warning
Any actions taken in these menus reset
the Event status.
C Debug Mode
This mode is very helpful to evaluate the system, test the system operation without stopping any system services and calibrate the connected sensors. In fact, everything stays in operation except that no actions are taken by the Event. This way no relay is activated.
Note: If one of these modes is accessed, the system will automatically return to Normal
Mode after 15 minutes.
D Simulation Mode
The Simulation Mode deactivates information update from the network communication.
This mode simulates the gas concentration over associated scale range for each sensor, one after the other.
The alarm level (A, B, C) are evaluated in accordance to the gas concentration simulated.
Events are evaluated and actions are taken.
During the simulation, the controller is unaware of the current status of the network device.
Simulation Mode can be stopped in the TEST MENU at any time.
Note: Simulation Mode can be combined
with any of the three previous ones (i.e., Normal Mode, Single Tx Mode, or Debug Mode). No other combinations are possible.
Note: Displays details in the following pages.
B Single Tx Mode
The Single Tx Mode doesn’t prevent Event evaluation. By entering this mode, the user is able to analyse one sensor at a time. Only the displayed device is interrogated by the controller, thus has its information updated.
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 13
6 Programming Menus
G
r
t
y
Controller Information
Number of Sensors
Accessible Memory Card
Number of Groups Product Name Firmware Version
AirAlert-96d ver 2.016
Ad:12 Gr:1
Ev:1
Date Number of Events Time
Sensor Information
Label Type of Gas Unit of Measuremen
Engine Room
NH3 0 PPM
Address Gas Concentration
Status:
-COMM (no communication)
-A (Warn)
-B (Alarm)
-C (High Alarm)
-Normal
Relay and Annunciator Information
Label
uard Shack
Active Relays
- - 2 - - 4 ­ AD:85
Address
Active Relays
Status
Event Information
Event Source
Event Numbe
EVENT
001
-Sources- ­Action-
Activated Rela
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 14
7 Configuration
s
EC-
F
A Main Menu
To access the MAIN MENU, press the Enter key and enter the password. The MAIN MENU offers the following eight programming fields:
1. Tx Info
3. Events
5. Copy
Men
Men
7. Network
The cursor to the left of a field on the display indicates that this field is accessible. The arrows in the upper left and right corners indicate that a window is accessible at the left and right of the active window respectively. The keypad’s four arrows serve to move the pointer in the MAIN MENU, and the Enter key is used to access the selected field.
Tx INFO (Programming the Parameters of a Sensor)
Sensor parameters are programmed via several different windows. There is also an additional information window indicating sensor life available for some sensors.
• Ident • Alarm A
• Com • Alarm B
• Detection • Alarm C
• Display • Servicing
The upper right-hand corner of each window indicates the address of the first sensor. When the Tx INFO field is accessed, the pointer is located to the left of the sensor address, thus signifying that the address could be put into editing mode in order to access the parameters of another sensor. The sensor address is put into editing mode using the Enter key, and the address begins to flash when it is editable. The key­pad’s Up and Down arrows are used to increment or decrement the address value. Once the correct value is obtained, the Enter key validates the address. The address then leaves the editing mode and stops flashing.
The following windows are accessible with the Left and Right arrows.
Ident (Identification of the Network Component)
1. Tx Info 001
-Ident-
The identification of the network component is comprised of two parameters: the sensor name and the sensor type. A pre-programmed list of sensors is available for both.
Com (Communication Protocol)
1. Tx Info
9
001
O-C M-
Mdbs RTU 8D 2S
Each sensor’s communication protocol is auto­matically established by the Manning AirAlert controller.
If a sensor is compatible with several protocols, it can be modified by the programmer in accordance with one of the following four choices.
1 Vulbus
2 Mdbs ASCII 7D 2S NP 9600 bauds
3 Mdbs RTU 8D 2S NP 9600 bauds
4 Mdbs RTU 1S EP 9600 bauds
Note: For MODBUS equipped sensors, the controller
must be put into Vulbus mode to allow configuration. Once configuration is complete, return to MODBUS mode for normal operation. MODBUS sensors should be set at even parity, one bit-stop.
Detection (Detection Range and Unit of Measure)
1. Tx Info 001
TM
96d
-Detection-
The DETECTION MENU does not appear for an Manning AirAlert AirAlert
cale: 0-100.0
TM
TM
96d-AP annunciator panel.
96d-RM8 relay module or Manning
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 15
7 Configuration continued
(
E
<
[
---]
Display (programming the label)
1. Tx Info 001
-Display-
edit
The “label” is a descriptive message of up to 20 characters appearing on the display for a network component. It applies to sensors, relay modules and annuciators panels and is located on the first line of the display. For a MODBUS sensor, the default label is composed of the name of the sensor or network component followed by the sensor type (if applicable) and the component address.
Alarm A (Programming Warning Levels)
1. Tx Info 001
20
-Alarm A-
MIN
The MAX value is the level at which Alarm A (Warn) is activated (set). The MIN value is the level at which Alarm A (Warn) is deactivated (rest).
Alarm B (Programming Alarm Levels)
1. Tx Info 001
-Alarm B-
MIN
The MAX value is the level at which Alarm B (Alarm) is activated (set). The MIN value is the level at which Alarm B (Alarm) is deactivated (rest).
Alarm C (Programming High Alarm Levels)
Erase Current Tx (Erase Current Displayed Tx Configuration)
1. Tx Info 001
Groups (Programming Groups of Sensors)
The programming of groups of sensors serves to combine several units in order to be able to take actions (events) based on a series of units rather than each individual one at a time. It is possible to program 126 distinct groups. Another group (GrAII) contains all the sensors within a network by default.
rase
2. Group 001
[001] [004]
end>
A group is comprised of a stack containing the address of each sensor included in the group. The pointer is represented in the stack by the flashing triangular brackets < >. The address within these brackets is editable. When the Enter key is pressed, the address begins to flash, and the brackets stop flashing. The address can then be modified using the up and down arrows. The address of each sensor programmed in 1. Tx INFO is available. The <DEL> function can be used to delete a particular sensor.
The <END> indicator represents the bottom of the stack. To add a sensor to the group, simply move the pointer towards that position and replace <END> with the address of the new sensor. The end of the stack will then move over one position.
1. Tx Info 001
The EMPTY ALL GROUPS function deletes all groups programmed in the Manning AirAlert
TM
96d controller.
-Alarm C-
MIN
The MAX value is the level at which Alarm C (High Alarm) is activated (set). The MIN value is the level at which Alarm C (High Alarm) is deactivated (reset).
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 16
7 Configuration continued
B
g
Event (Programming Events)
Default event configuration (EVENT MENU):
Relay #1 will be activated when alarm A is reached.
Alarm B will trigger relay #2.
The buzzer will also be activated for any sensors that reach alarm B.
Relay #3 will be activated when alarm C is reached.
Pressing the silence key will acknowledge the latched Events and silence the buzzer.
Relay #4 will be activated for any fault status.
Event programming serves to define particular actions. The following specific windows are used for such programming:
• Action
Delay (Condition 1) (Condition 2)
• Delete
Action (Definition of Actions)
3. Event 001
-Action-
Tar
Actions are comprised of two parameters. TARGET identifies the component that will perform the action. The following three components may be programmed:
Tx (Transmitter (sensor))
Re (Relay Pack/Annunciator Panel)
• Ctrl (Controller)
RELAY identifies the output, which will be activated when the event is true. The output may be one of the following three:
et:
Delay (Programming of Delays)
BEFORE and AFTER delays are used to retard the
activation or deactivation of an action. The BEFORE delay retards the activation of an action. When an event becomes true, the action will only be activated after the indicated delay. The AFTER delay retards the action’s deactivation. When the event is no longer true, the action remains until after the delay period.
3. Event 001
-Delays-
efore: -- - -
The BEFORE and AFTER delays may be programmed at 30 seconds, 45 seconds, or from 1 to 99 minutes by increments of 1 minute. The five dashes (- - - - -) indicate that no delay had been programmed. The AFTER delay can also be put into latch mode.
Latch Mode
The latch function is executed on an EVENT state.
It is possible to select the latch mode by editing the after-delay to the latch value.
The EVENT stays activated until the SILENCE key is pressed.
The silence key has two functions: silence the buzzer and unlatch the Event.
When the silence key is pressed, events in latch mode are unlatched and re-evaluated. If the Event conditions are still true, the given Event stays activated and returns into latch mode. If not, the Event is deactivated.
#XX (Activation of the component’s relay #XX)
Buzzer (Activation of the component’s audible alarm)
ALL (activation of all the component’s relays and audible alarm)
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 17
7 Configuration continued
S
Conditions
Conditions serve to define which premises make an event true.
Each condition is defined by four elements, and two conditions may be combined to provide for greater flexibility.
The element in the lower right-hand corner of a condition indicates the source of the event. The source may be a sensor (Tx001), a group (Gr001), all sensors (GrAll), or the controller’s clock (Time). The magnifying glass appearing to the right of the group number provides quick access to this group in order to view or edit it. Access to the GROUP MENU with the magnifying glass symbol. The ESC key returns the display to the condition’s window.
3. Even
t
001
(
= Alarm
TX010
)
3. Event 001
Clock
(
AND sta:
)
B Acquisition (Programming
the Acquisition Mode)
Note: Only available with Datalogging option.
4. Acquisition 10 s delay mode
tart Tx logging
Acquisition Mode for Tx Logging
The ACQUISITION MENU is only accessible when an SDcard is present. This menu is used to enable or disable the logging of the system event or sensor information. This information is stored on the SDcard, however, the acquisition interval or condition must be defined first.
Acquisitions delay mode may be made at intervals of 10 to 59 seconds or 1 to 60 minutes. A threshold mode acquisition may also be made when a sensor’s reading varies by 3% or more, 5% or more or 10% or more of its detection range.
Note: Due to system latency, threshold values can be greater (but never less) than
the selected one.
The element in the lower left-hand corner indicates the quantifier of the source (applicable only to groups). The quantifier may be indicated as the average (mean), (max), (min), (3/4), (2/3), (1/2), (1/3), (1/4), (1or+) or (all) — applicable only to groups.
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 18
3. Event 001
Enable event
Erase current
10 to 59 seconds interval
1 to 60 minute interval
3% threshold (acquisition if variation of 3% of the scale from the last logged value)
5% threshold (acquisition if variation of 5% or more of the scale from the last logged value)
10% threshold (acquisition if variation of 10% or more of the scale from the last logged value)
Example of Threshold Log Mode
2006-01-22 11:05:20;1;NH3;0;ppm;-normal-; 2006-01-22 11:06:02;1;NH3;12;ppm;-normal-; 2006-01-22 11:06:15;1;NH3;18;ppm;-normal-; 2006-01-22 11:06:28;1;NH3;6;ppm;-normal-; 2006-01-22 11:06:39;1;NH3;0;ppm;-normal-; 2006-01-22 11:30:45;1;NH3;15;ppm;-normal-; 2006-01-22 11:30:57;1;NH3;23;ppm;-normal-; 2006-01-22 11:31:08;1;NH3;20;ppm;-normal-;
7 Configuration continued
Start/Stop Tx Logging
When the display indicates Start log Tx, the acquisition mode is inactive. Acquisition will start by pressing Enter. The log message displays on the screen in accordance to the Mode that has been choose. LED1 turns ON.
Start log Tx (starts sensor acquisition) Opens an ad1_48.log and ad49_96.log file.
Stop log Tx (stops sensor acquisition)
The ad1_48.log and ad49_96.log files contain a record of sensors 1 to 48 (ad1_48.log) and 49 to 96 (ad49_96.log). This register includes the date, time and address of the sensor(s), the sensor type, the concentration read, as well as the alarm status. See example in Figure 10 below.
Start/Stop Event Logging
In addition, event information may also be acquired. As it is the case for sensor acquisition, the display indicates the function of the ENTER key.
Start log even. (starts event acquisition) Opens an events.log file.
Stop log even. (stops event acquisition)
The events.log file contains a record of the controller’s events and key entries.
Example:
2006-01-21 16:27:51; Event logging enabled 2006-01-21 16:27:53; Menu exited 2006-01-21 16:28:11; Event accessed 2006-01-21 16:28:43; Event 1 setup modified 2006-01-21 16:28:45; Menu exited
The event file indicates the date and time, menu access and modifications, as well as events that were activated.
List of Events
List of Events English
Power-up “System Power-up”
Power-down “System Power-down”
Menu accessed “Menu accessed”
Menu exited “Menu exited”
Event logging enabled “Event logging enabled”
Event logging disabled “Event logging disabled”
Transmitter logging “Transmitter logging enabled enabled”
Transmitter logging “Transmitter logging disabled disabled”
Transmitter info setup “Transmitter X setup”
Alarm setup “Tx X alarm level setup”
Event setup “Event X setup”
Group setup “Group X setup”
Clock setup “Clock setup”
Language setup “Language setup”
Scroll mode setup “Scroll mode setup”
Silence activated “Silence activated”
Event status changed “Event X now True/False”
Alarm A, B, C, Fault, and “Transmitter X X status changed Alarm X True/False”
Figure 10. Tx Log
Example:
2004-01-23 17:54:25; 001; NH3; 0: ppm:--------;002; CL2; 1.5; ppm;AL:-A;003; NH3; 0 ppm--------;004; CL2; 0.0; ppm;--------;005; NH3; 0; ppm;--------; 2004-01-23 17:55:25; 001; NH3; 0: ppm:--------;002; CL2; 7.5; ppm;AL:-A;003; NH3; 0 ppm--------;004; CL2; 0.0; ppm;--------;005; NH3; 0; ppm;--------; 2004-01-23 17:56:25; 001; NH3; 0: ppm:--------;002; CL2; 6.5; ppm;--------;003; NH3; 0 ppm--------;004; CL2; 0.0; ppm;--------;005; NH3; 0; ppm;--------; 2004-01-23 17:57:25; 001; NH3; 0: ppm:--------;002; CL2; 0.5; ppm;--------;003; NH3; 0 ppm--------;004; CL2; 0.0; ppm;--------;005; NH3; 0; ppm;--------; 2004-01-23 17:58:25; 001; NH3; 0: ppm:--------;002; CL2; 0.0; ppm;--------;003; NH3; 130; ppm;AL:-A-;004; CL2; 0.0; ppm;--------;005; NH3; 0; ppm;--------;
Note: In this case, there is a reference to five sensors (addresses #1 to #5) — three NH3 and two CL2. We can see that the CL
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 19
at address #2 goes in alarm A and a few minutes later it’s the NH3 at address #3 that goes in alarm A.
2
7 Configuration continued
Copy (Transferring Data and Copying Parameters)
The COPY function serves to transfer data and copy parameters within the following windows:
• Configuration
• Parameters
Configuration (Data Transfer)
-configuration-
5. Copy
Controller to SDcard
This section of the COPY MENU is only accessible if an SDcard is present. Data can be transferred from the controller to the SDcard, or from the SDcard to the controller. Thus, an image of the controller’s programming may be transferred and stored on a computer. Similarly, the controller’s programming may be executed on a computer and then transferred to the controller.
Controller to SDcard (transfer from the controller to the SDcard)
SDcard to controller (transfer from the SDcard to the controller)
Moreover, at card insertion, the controller system looks for an existing ‘config.ini’ file containing a tag named “autoload” equal to ‘1’ (meaning true). If so, the system will automatically load the content of the file and set “autoload” to ‘0’ (meaning false). This feature is useful when you edit the file on a computer and want to avoid “menu manipulations” on the controller.
On a closer look, ‘config.ini’ is a text editable Windows .ini-style file. It can be accessed by any word processing software, but the simpler Notepad should be favored. The content of the file has the following format:
[section 1]
tag 1 = “string value 1” tag 2 = “string value 2” tag 3 = 53
[section 2]
tag 1 = true tag 2 = -12.3 […]
See example on the next page.
In order, the first command enables the user to save the controller configuration and parameters into a file named ‘config.ini’. The second command enables the user to load the configuration and parameters from the same file. Keep in mind that the content of the ‘config.ini’ file can always be edited on a computer.
Before saving the current configuration and parameters, the system will look for the existence of any previous configuration. The following steps will be performed:
1 If a file named ‘config.ini’ already exists, the
system looks for a file named ‘config.bak’;
2 If a file named ‘config.bak’ is found, it is
deleted;
3 Then, the existing ‘config.ini’ file is renamed
‘config.bak’, thus keeping a backup of the previous configuration;
4 At last, a new ‘config.ini’ file with the current
configuration is created.
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 20
7 Configuration continued
g
C
6
S
Example of saving a controller configuration
AirAlert96d = “Configuration” Date = “2006-01-09 13:51:57:”
[CONFIG] language = 1 scrollmode = 0 relaymode = 0 password = "2967" cie = 0 priority = 0 autoload = 1 [SLAVE] address = 1 protocol = 1 baudrate = 38400 databits = 8 stopbits = 2 parity = 0
[ADDRESS_1] txtype = 1 display = "ECF9 NH3 AD:01" protocol = 1 baudrate = 9600 databits = 8 stopbits = 2 parity = 0 sensortype = 65 fullscale = 102.000000 unit = 0 alarmAmin = 20.1000003 alarmAmax = 25.0000000 alarmBmin = 45.000000 alarmBmax = 50.000000 alarmCmin = 85.000000 alarmCmax = 90.000000
Parameters (Copying Parameters)
5. Copy 001
-parameters Tx info to Tx
[ADDRESS_2] txtype = 17 display = "ECF9 NH3 AD:02" protocol = 1 baudrate = 9600 databits = 8 stopbits = 2 parity = 0 sensortype = 2 fullscale = 250.000000 unit = 1 alarmAmin = 20.0000000 alarmAmax = 25.0000000 alarmBmin = 180.000000 alarmBmax = 200.000000 alarmCmin = 218.000000 alarmCmax = 225.000000 databits = 7 stopbits = 2 parity = 0
Event to Event
Event to Event source #001 target #002
[GROUP_1] tx_0 = 1 tx_1 = 2 tx_2 = 0 [EVENT_1] actiontarget = 14 actionrelay = 1 delaybefore = 0 delayafter = 0 cond1source = 1 cond1logic = 1 cond1alarm = 0 [EVENT_2] actiontarget = 0 actionrelay = 1 delaybefore = 255 delayafter = 255 cond1source = 129 cond1stat = 9 cond1logic = 7 cond1min = 10.0000000 cond1max = 15.0000000 [FIN]
OPY
The copying of parameters serves to transfer one sensor’s configuration to another, or one event to a second event. This function accelerates programming on the display when two entities have identical or close properties. Tx Info to Tx Info copies a sensor’s parameters, and Event to Event copies the parameters of one event to another.
TxINFO to TxINFO (copies the parameters of a sensor)
Tx info to Tx info
Config (Programming Display Parameters and the Access Code)
Manual scroll
. Config
mo de
The CONFIG MENU is used to program the display mode, adjust the time and date, select the display language in the first window, and to edit the password in the second window.
et Date and
source tx001 tar
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 21
et tx002
7 Configuration continued
7
R
7
The scroll mode is used to set the scroll interval of the information pages displayed on the screen. Scroll mode may be set to at three or five seconds, or it may be set to manual only. The information page displayed can always be controlled manually using the arrow keys. The display will remain on the last component selected only in manual mode.
• 3-Second Scroll
• 5-Second Scroll
• Manual Scroll
The date and time are displayed in the following format:
yyyy-mm-dd hh:mm:ss (ISO 8601 standard, 24 hours format)
The desired display language is selected via Menu Francais and English Menu. The selection is made with the Enter key. When the display shows Menu Francais, the current display language is English. The language may be changed by pressing the Enter key.
The user password can be edited and comes with a default value of 9935 (last four digits of Manning’s toll free phone number).
Set User Passwor
The Config window also features an option to configure the slave port.
Address: 00
6. Conf d
-9935-
Slave Port Cnfg1
ig
38400 bauds
Mdbs RTU 8D 2S
Network (Auto-Programming of Network­Related Parameters)
The functions of the Network menu serve to reset or program information related to the network devices.
Reset Database (Resets all Tx Info database — network device)
Network Scan (Auto detection of the network devices)
Reset & Scan (Resets all Tx info database and auto detection of the network devices)
o
Resetting the network device affects only the Tx information: groups and events are not affected by these function.
Network scan serves as an auto detection service of network devices to configure the Tx information database.
St
. Network
Scan Netw rk
eset and Scan
. Networ
k
atistics
e Reset Databas
The statistics function allows the user to view details about the 16 last entries such as:
• Valid responses
• Communication errors
Timeouts (no response)
Relay configuration allows the relays to be set to normal or failsafe mode. In the event of loss of power to the controller, relays will change states if set to failsafe mode.
Relay Co i
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 22
6. C
nf guration AP Brdcst: auto
onfig
7 Configuration continued
8
q
Tests (Sequential Test Mode)
Test Sequence
This simple test sequence enables the user to activate each output and validate the operation of each controller key and all display pixels, as well as the different communication protocols.
Start Sim. Sequ. & Stop Sim. Sequ. (Stop Simulation)
8. Tests ce Test Sequen
Start Sim Se
uence
See Simulation Mode section on page 13 for more details.
The simulation mode allows for the simulation of gas concentration over associated scale range on all sensors. The simulated gas concentration values are local to the controller.
Start with Tx00X (simulation starts with sensor 00X)
• Confirm (simulation activation)
Maximum Load (Activation of All Controller Components)
Oprt Mode (Controller Operating Mode)
Oprt Mode:
. Tests
normal
1 Normal (normal controller operating mode)
2 Single Tx (activation of interrogation mode for a
single sensor)
3 Debug (activation of service mode to allow for
calibration without affecting events)
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 23
8 Specifications
Power Requirements:
Operating Environment: Ordinary location
Operating Temperature Range: —4°F to 122°F
(—20°C to 50°C)
Operating Humidity Range: 0 to 95% RH,
(non condensing)
Operating Altitude: Up to 9843 ft. (3,000 m)
Network Capacity:
Up to 96 sensors, 32 per channel
Channel 1, 2, and 3: MODBUS
Channel 4: Modbus output to PLC
Communication (length of lines):
Up to 2,000 feet (600 m) per channel 24 AWG #9841 Belden Cable
T-tap: 65 feet (20 m) maximum per t-tap,130 feet (40 m) total
User Interface:
Graphic 122 x 82 dot matrix backlit display
User friendly keypad
24 Vdc, 500 mA
Visual Indicators:
Power On Green LED
Warn Red LED (blinking upon an event)
Alarm Red LED
High Alarm Red LED
Fault Yellow LED
Tx Amber LED (blink when used)
Rx Green LED (blink when used)
Outputs:
4 DPDT relays
5A, 30 Vdc or 250 Vac (resistive load)
Time Delays: 0, 30, and 45 seconds, and1 to 99
minutes before and after alarm
Battery: Lithium battery, 3 volts
Enclosure: NEMA 4x, cast aluminium #A356.0T6
Overvoltage Category: II
Dimensions: 9.50” (W) x 14.00” (H) x 3.50” (D)
Weight: 11.4 lbs (5.2 kg)
9 Maintenance
The Manning AirAlert controller. Only the sensors need periodic inspection and calibration (see sensor manual).
Periodic Inspections and Calibration
Honeywell Analytics provides its customers with specialized gas detection equipment. Beyond the warranty period, the systems must be maintained and calibrated on a regular basis (normally two times a year).
Honeywell Analytics will not assume responsibility for the interruption of service or malfunctioning of its equipment as a result of the discontinuance of maintenance and calibration services.
If unit span or zero cannot be adjusted, the sensor may be approaching its end-of-life and must be replaced. Keep an operation log of all maintenance, calibrations and alarm events.
TM
96d is a maintenance free
Replacement Parts
A replacement 3V lithium battery is also available. If the memory card option is present, spare SDcards are also available.
Due to continuous evolution of our products, please contact our service department for ordering parts or for more details.
Cleaning
Clean the exterior with a soft, damp cloth. Do not use solvents, soaps or polishers.
Battery Disposal
This instrument contains a lithium battery. Do not mix with the solid waste stream. Spent batteries should be disposed of by a qualified recycler or hazardous materials handler.
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 24
10 Relay Module (optional)
The Manning AirAlert an output to the Manning AirAlert
TM
96d-RM8 relay module acts as
TM
96d controller. The relay module provides eight programmable relays for the activation of ventilation and audible/visual alarm output devices at programmable alarm levels. Since the relay module is an output to the controller, it can be located at any point within the gas detection network.
Manning AirAlert
Fully compatible with the Manning AirAlert
TM
96d-RM8 Features:
TM
96d
controller
Equipped with 8 programmable DPDT relays
RS-485 daisy chain installation
LED visual indication status of each relay
Specifications
Power Requirements: 17 to 27 Vdc, 250 mA
Operating Temperature Range: 32°F to 100°F
Operating Humidity Range: 0 to 95% RH
(non-condensing)
Outputs:
8 DPDT relays; 5A
30 Vdc or 250 Vac (resistive load)
Maximum Distance between Relay Module and Controller: 2,000 feet
Enclosure: NEMA 4x, cast aluminium #A356.0T6
Figure 11. Manning AirAlertTM96d-RM8
Manning AirAlert 96d
Relay Module
Power
TX ModBus
Dip Switches
The DIP switches are used to change the relay module addresses. The address ranges available begin at 81.
Modbus address
081
082
083
084
Position of the DIP switches
Dip 1 Dip2 Dip 3 Dip 4
Off
On
Off
On
Off Off Off
Off Off Off
On Off Off
On Off Off
Dimensions: 9.50” (W) x 14.00” (H) x 3.50” (D)
Weight: 11.4 lbs (5.2 kg)
LEDs
Two LEDs indicate the status of the relay module. The Power LED (green) indicates that the relay module is powered on. The Tx Modbus LED blinks when there is a data transfer between the relay module and the controller. If the communication breaks down, that LED will turn off.
085
086
087
088
089
090
091
092
093
094
095
096
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 25
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off On Off
Off On Off
On On Off
On On Off
Off Off On
Off Off On
On Off On
On Off On
Off On On
Off On On
On On On
On On On
10 Relay Module (optional) continued
Wiring Details
Power Supply Cable
14 AWG stranded cable or larger (see your network
diagram provided by Honeywell Analytics sales department).
Communication Cable
24 AWG twisted pair (Belden # 9841 or equivalent).
Figure 12. Relay Module PCB
off
1 2
DIP switches
3 4
End of Line Resistor On the last device of the communication network, a jumper must be installed as shown.
From +24VDC terminal
of power supply
From Ground terminal
of power supply
EOL1
RC
R
J10
J10
V+ V- SHLDAB
Relay 8
J8
NO NC
From “B” terminal of controller to “B” terminal of next device
From “A” terminal of controller to “A” terminal of next device
Relay 7 Relay 5
J7
NO NC
Relay 6
Power
Tx Modbus
Relay 4
NO NCNO NC
NO NC
Relay 3 Relay 1
NO NC
Relay Outputs (J1-J8) 5A, 30 Vdc or 120 Vac (resistive load)
Power and TX status LEDs
Relay 2
J2
642
531
J1
NO NCNO NC
Normally open
Normally closed
3+5 4+6
1+3 2+4
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 26
11 Limited Warranty
1. Limited Warranty
Honeywell Analytics, Inc. warrants to the original purchaser and/or ultimate customer (“Purchaser”) of Manning products (“Product”) that if any part thereof proves to be defective in material or workmanship within eighteen (18) months of the date of shipment by Honeywell Analytics or twelve (12) months from the date of first use by the purchaser, whichever comes first, such defective part will be repaired or free of charge, at Honeywell Analytics’ if shipped prepaid to Honeywell Analytics at 405 Barclay Blvd., Lincolnshire, IL 60069, in a package equal to or in the original container. The Product will be returned freight prepaid and repaired or replaced if it is determined by Honeywell Analytics that the part failed due to defective materials or workmanship. The repair or replacement of any such defective part shall be Honeywell Analytics’ sole and exclusive responsibility and liability under this limited warranty.
2. Exclusions
A. If gas sensors are part of the Product, the
gas sensor is covered by a twelve (12) month limited warranty of the manufacturer.
B. If gas sensors are covered by this limited
warranty, the gas sensor is subject to inspection by Honeywell Analytics for extended exposure to excessive gas con­centrations if a claim by the Purchaser is made under this limited warranty. Should such inspection indicate that the gas sensor has been expended rather than failed prematurely, this limited warranty shall not apply to the Product.
C. This limited warranty does not cover consum-
able items, such as batteries, or items subject to wear or periodic replacement, including lamps, fuses, valves, vanes, sensor elements, cartridges, or filter elements.
replaced,
discretion
3. Warranty Limitation and Exclusion
Honeywell Analytics will have no further obligation under this limited warranty. All warranty obligations of Honeywell Analytics are extinguishable if the Product has been subject to abuse, misuse, negligence, or accident or if the Purchaser fails to perform any of the duties set forth in this limited warranty or if the Product has not been operated in accordance with instructions, or if the Product serial number has been removed or altered.
4. Disclaimer of Unstated Warranties
THE WARRANTY PRINTED ABOVE IS THE ONLY
WARRANTY APPLICABLE TO THIS PURCHASE. ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
5. Limitation of Liability
IT IS UNDERSTOOD AND AGREED THAT HONEYWELL ANALYTIC’S LIABILITY, WHETHER
IN CONTRACT, IN TORT, UNDER ANY WARRANTY, IN NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE AMOUNT OF THE
PURCHASE PRICE PAID BY THE PURCHASER FOR THE PRODUCT AND UNDER NO CIRCUMSTANCES SHALL HONEYWELL
ANALYTICS BE LIABLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES. THE PRICE STATED FOR THE PRODUCT IS A CONSIDERA-
TION LIMITING HONEYWELL ANALYTICS’ LIABILITY. NO ACTION, REGARDLESS OF FORM, ARISING OUT OF THE TRANSACTIONS UNDER
THIS WARRANTY MAY BE BROUGHT BY THE PURCHASER MORE THAN ONE YEAR AFTER THE CAUSE OF ACTIONS HAS OCCURRED.
Manning AirAlert-96d Gas Monitor 19546 AIRALERT96D 07/09 Prelim REVC Copyright © 2009 Honeywell Analytics. All Rights Reserved. 27
Loading...