Dual-Flo
The Dual-Flo unit cooler is designed for use in
walk-in coolers and freezers to increase storage
space. Its extra-low profile and two-way discharge
permits mounting above aisle areas without
sacrificing either headroom or proper air circulation.
Walls are thus free for maximum utilization of shelving.
It is ideal for convenience stores, supermarkets,
restaurants and other low-ceiling-type installations.
Two-Way Discharge
Air Defrost Models – 6,400 through
25,000 BTUH @ 10 Degree T.D.
Electric Defrost Models – 4,800 through
21,800 BTUH @ 10 Degree T.D.
Now available with EC Motors
High Efficiency / High Reliability
Performance and Electrical Data
Air Defrost Models
Model Number
AMC38-75 7,500 11,250 1,455 3.6 1.4 1.10 .54 1.2 0.6
AMC38-88 8,800 13,200 1,305 3.6 1.4 1.10 .54 1.2 0.6
AMC38-98 9,800 14,700 1,200 3.6 14 1. 10 .54 1.2 0.6
AMC48-112 11 ,200 16,800 2,120 4 .8 1.8 1.44 .75 1.6 0.8
AMC48-130 13 ,000 19,500 1,920 4 .8 1.8 1.44 .72 1.6 0.8
8 FPI
AMC48-10 15,000 22,50 0 1,760 4.8 1.8 1.44 .75 1.6 0.8
AMC58-162 16 ,200 24,300 2, 320 6.0 2.3 1.80 .90 2.0 1.0
AMC48-210 21 ,000 31,500 1, 820 4.8 1.8 1.44 .72 1.6 0.8
AMC58-230 23 ,000 34,500 2, 650 6.0 2.3 1.80 .90 20 1.0
AMC68-250 25 ,000 37,500 2, 970 7.2 2.8 2.16 1.1 2.4 1.2
AMC36-64 6,400 9,600 1,560 3.6 1.4 1.10 .54 1.2 0.6
AMC36-82 8,200 12,300 1,425 3.6 1.4 1.10 .54 1.2 0.6
AMC3 6-93 9,300 13,950 1,30 5 3.6 1.4 1.10 .54 1.2 0.6
AMC46-100 10 ,000 15,000 2, 160 4.8 1.8 1.44 .72 1.6 .08
AMC46-123 12 ,300 18,450 2, 040 4.8 1.8 1.44 .72 1.6 0.8
6 FPI
AMC46-140 14 ,000 21,000 1, 920 4.8 1.8 1.44 .72 1.6 0.8
AMC56-157 15 ,700 23,500 2, 360 6.0 2.3 1.80 .90 2.0 1.0
AMC46-190 19 ,000 28,500 1, 940 4.8 1.8 1.44 .72 1.6 0.8
AMC56-208 20 ,800 31,200 2, 850 6.0 2.3 1.80 .90 2.0 1.0
AMC66-232 23 ,200 34,800 2, 970 7.2 2.8 2.16 1.1 2.4 1.2
SP* = Shaded Pole motor(s) PSC* = Permanent Split Capacitor(s) EC* = Electronically Commutated Motor(s)
Standard voltage for AMC models is 115/1/60
BTUH @ +25ºF S.T.
10ºT.D. 15ºT.D. 115/1 208-230/1 115/1 208-230/1 115/1 208-230/1
CFM
SP* MOTOR AMPS PSC* MOTOR AMPS EC* MOTOR AMPS
Electric Defrost Models
Model Number
ELC36-53 5,300 6,360 1440 1.4 N/A 0.6 2070 9.0 4.5
ELC36-62 6,200 7,440 1290 1.4 N/A 0.6 2070 9.0 4.5
ELC36-69 6,900 8,200 1245 1.4 N/A 0.6 2070 90 4.5
ELC46-77 7,700 9,240 2075 1.8 N/A 0.8 2990 13.0 6.5
ELC46-90 9,000 10,800 1860 1.8 N/A 0.8 2990 130 6.5
6 FPI
ELC46-100 10,0 00 12,000 17 40 1 .8 N/A 0 .8 2990 13.0 6.5
ELC56-125 12,5 00 15,000 21 60 2 .3 N/A 1 .0 3910 17.0 8.5
ELC46-140 14,0 00 16,800 18 20 1 .8 N/A 0 .8 3910 17.0 8.5
ELC56-160 16,0 00 19,200 25 50 2 .3 N/A 1 .0 3910 17.0 8.5
ELC66-218 21,8 00 23,200 30 00 2 .8 N/A 1 .2 3910 17.0 8.5
ELC34-48 4,800 5,760 1500 1.4 N/A 0 .6 2070 90 4.5
ELC34-58 5,800 6,960 1395 1.4 N/A 0 .6 2070 9.0 4 .5
ELC34-65 6,500 7,800 1350 1.4 N/A 0 .6 2070 9.0 4 .5
ELC44-72 7,200 8,640 2120 1.8 N/A 0 .8 2990 13.0 6.5
ELC44-84 8,400 10,080 1980 1.8 N/A 0.8 2990 13.0 6.5
4 FPI
ELC44-95 9,500 11,400 1900 1.8 N/A 0.8 2990 13.0 6.5
ELC54-115 11,5 00 13,800 22 80 2 .3 N/A 1 .0 3910 17.0 8.5
ELC44-128 12,8 00 15,360 19 40 1 .8 N/A 0 .8 3910 17.0 8.5
ELC54-145 14,5 00 17,400 26 50 2 .3 N/A 1 .0 3910 17.0 8.5
ELC64-173 17,3 00 20,760 30 80 2 .8 N/A 1 .2 3940 17.0 8.5
SP* = Shaded Pole motor(s) PSC* = Permanent Split Capacitor(s) EC* = Electronically Commutated Motor(s)
230V/1 motors are suitable for 208V operation. Standard voltage for ELC models is 208-230/1/60
BTUH @ 10ºT.D.
-20ºS.T. +20ºS.T. 208-230/1 208-230/1 208-230/1 208-230/1 460/1
SP* MOTOR AMPS PSC* MOTOR AMPS EC* MOTOR AMPS
CFM
DEFROST
WATTS
DEFROST AMPS