Manitowoc Ice 2840-000 Installation Manual

PRODUCT DATA
Pump Design ..............................................Quad Diaphragm
Motor ................Permanent Magnet ............................TENV
Check Valve Material ........................EPDM
Housing Material ..................Polypropylene
Accumulator Tank
..Diaphragm Material ............................Butyl
Liner Material ........................Polypropylene
Ports ..............................3/4” HB Inlet & 1/2” HB/Qest Outlet
Net Weight ................................................8.8 Pounds (4 kgs)
PERFORMANCE SPECIFICATIONS
PUMP
Motor ................Max Amp Draw ....................1.5 @ 115 VAC
0.75 @ 230 VAC
Cycle ........................................50/60 Hertz
Liquid Temperature
..Min. ..............................................45°F (7°C)
Max. ........................................140°F (60°C)
Priming ..............Dry ............................................5 ft. (1.5 M)
Wet ..........................................15 ft. (4.6 M)
Flow Rate ..........Max ..............3.5/4.5 GPM @ 0 PSI (0.0 bar)
Pressure Switch
Off ......................................45 PSI (3.1 bar)
On ......................................30 PSI (2.1 bar)
TANK
Total Volume ....................................................1.1 gal. (4.1 It.
Operating Pressure ..............................................Gal (0.8 It.)
Air Pressure Setting........................................25 PSI (1.7 bar)
STANDARD MODEL NUMBERING SYSTEM
2840 Series
Booster Pump System
DIMENSIONAL DRAWING
Inches (millimeters)
The standard model numbering system is used for models up to -500. Numbers -500 and over are used for variations from standard assemblies such as special pump or tank specifications. Consult the factory for special models to meet specific requirements.
INSTALLATION & SERVICE INFORMATION FOR MODELS 2840-000 & 2840-010 115 VOLTS AC AND MODEL 2840-210 230 VOLTS AC
a:
Model 2840-010 Model 2840-210
b:
Model 2840-000
2840 Series Booster Pump System
28 X X - X X X
Pump Service Voltage Switch Options
20 = Duplex 0 = 115V AC 0 = 40 PSI 0 = Std (2130) 1 = 12V DC 1 = 45 PSI 1 = Timer 40 = Quad 2 = 230V AC 4 = 70 PSI 2 = Inlet Sw. (4300) 3 = 24V DC 6 = 95 PSI
Pentaflex
50 =
50
(3.4)
40
(2.8)
30
(2.1)
20
(1.4)
10
(0.7)
Pressure in PSI (bar)
0
4 = 36V DC
b
a
3.0
4.0
1.0
2.0
(7.6)
(11.4)
(3.8)
Flow in GPM (l/min)
(15.1)
5.0
(18.9)
7 1/2 (191)
7 13/16
(198)
(13)
11 1/4
(286)
10 1/4
(260)
7 13/16
(198)
7 1/2 (191)
4 3/16
(106)
1/2
10 1/4
(260)
10 1/4
(260)
12 7/8
(327)
GENERAL SAFETY INFORMATION
Protect yourself and others by observing all safety information. Shut off power and drain pressure from system prior to service.
DESCRIPTION
The FLOJET 2840 series Booster Pump Systems are designed to provide a constant water pressure of 25 to 45 psi (1.7 - 3.1 bar) and maximum flow of 3.5 or 4.5 GPM at 10 psi (0. 7 bar). The pump is fully automatic with a built-in switch and check valve to maintain system pressure and will supply smooth water flow from a trickle to full flow Typical uses are; Commercial Ice Machines, Pure Water Dispensing, Water Purifiers, Small Domestic and Commercial Appliances where the water supply pressure is very low or fluctuates widely.
OPERATION
IMPORTANT - For correct operation, the tank must be properly pressurized on the air side before the pump is started. Follow instructions on the tank label and check air pressure after filling and before starting the pump. The air valve is a standard tire valve. Compressed air hose or hand pump may be used to pressurize. Pressure can be reduced by pressing the center pin in the valve.
Make sure pump inlet connection is securely connected to the water supply and no inlet valves are open. Open all valves or taps on outlet side to purge air from the system. Turn power on to the pump, pump will start up. Allow system to pump for a minute or until all the air has been purged from the system. Close all valves in the system, the pump will pressurize the tank, shut off and operate automatically to maintain pressure In the system.
To completely fill the pressure tank for maximum volume, shut off power to pump and open faucet (or valve) closest to tank. Trapped air will be expelled. Turn on power to pump. and close faucet when water is free of air.
WINTERIZING TIP
When units are exposed to freezing conditions.
1. Open discharge valve (Faucet nearest to the Booster System).
2. Open inlet side to pump (Remove inlet hose to the Booster System).
3. Run Pump for approximately 2 minutes, (Dry) or until system is out of fluid.
4. Leave discharge. value open and inlet hose removed until next usage.
DO NOT USE PUMP IN A FLAMMABLE
ENVIRONMENT. DO NOT USE TO PUMP
FLAMMABLE OR EXPLOSIVE FLUIDS
SUCH AS GASOLINE, FUEL OIL,
KEROSENE, ETC.
MOUNTING
The FLOJET 2840 Series Water Pressure System should be mounted in a dry and adequately ventilated area.
Select a location where the plumbing is as direct as possible and the inlet strainer is visible and accessible for cleaning.
The unit can be floor or wall mounted. If wall mounted, the Pump head should be down or lower than the motor.
Fasten base securely with the four rubber mounting feet assembled to base as shown below.
PLUMBING
Fasten strainer in a visible and accessible location for future cleaning. Use 3/4” ID hose between pump inlet & strainer. Connect strainer inlet to water supply line and clamp all hose connections securely to avoid air leaks. IMPORTANT - if water supply line has pressure fluctuations that may exceed 30 psi (2.1 bar) - use a pressure regulator to limit inlet pressure to 30 psi (2.1 bar) maximum.
Regulator may be installed at any convenient location between water supply and inlet strainer.
ELECTRICAL
RISK OF AN ELECTRICAL SHOCK!
When wiring an electrically driven pump, follow all electrical and safety codes, as well as the most recent National Electrical Code (NEC) and the Occupational Safety and Health Act (OSHA).
RISK OF PRODUCT DAMAGE!
Make certain the power source conforms to the pump voltage. Be sure all power is disconnected before installation or removal.
Use the maximum recommended fuse for pump protection. Recommended fuse amp rating is located on pump label. Failure to provide correct overload device may result in motor failure.
For 115V AC plug AC cord into a conventional 115V AC outlet.
WARNING
WARNING
Vertical Horizontal
1/2” NPT Pressure
Out
Water
Supply
Optional
Regulator
If Required
Inlet
Strainer
Loading...
+ 2 hidden pages