Manitowoc Ice 2095-540 User Manual

The 2095 Series syrup “Sold-Out” Switch automatically
FOR ELECTRICAL DISPENSING VALVES
shuts off an electric dispensing valve when syrup is sold out and turns on “Sold-Out” light. This prevents the operator from selling a drink of carbonated water only, with no syrup. The switch automatically resets when the empty Bag-In-Box is replaced and syrup line pressure is restored.
Note: This switch is designed for use with Bag-In-Box systems only, NOT transfer tanks.
PLUMBING
Refer to Diagram A
1) Shut off gas supply to syrup pump.
2) Open dispensing valve to relieve all syrup line pressure.
3) Install barbed switch into syrup line near dispensing valve and securely clamp both sides.
4) Switch may be mounted in any position in syrup line.
ELECTRICAL
Refer to Diagram B
1) Disconnect power.
2) Select location for LED “Sold-Out” light f a c i n g operator. (Light intensity is very limited when viewed from
side.) Preferred location is on front surface of valve cover as shown. (Diagram B).
3) Drill 1/4” (6.3 mm) hole. slide LED lens into hole from front of valve. Next feed LED light through hole from inside or back, slip LED light into lens making sure fingers of lens snap into place.
4) Place sold out label next to light.
5) REFER TO DIAGRAM C - Locate the 24 VAC leads running up the tower to the dispensing valve switch and solenoid. Cut one wire (the black wire if they are colored white and black). On the end going up the tower connect the gray wire from the “Sold Out” switch. Then on the end going down connect the black wire from switch. Connect these using the 2 butt connectors. Cut and strip the other wire (white if they are color coded) and connect the white wire from the switch to both ends of this wire using the closed end connector.
START-UP
1) Reconnect power to dispensing valve. Light should go on.
2) Turn on gas supply to Bag-In-Box pump. Pump should start and pressurize syrup line. Light should go off.
3) Open dispensing valve to insure system is dispensing p ro p e r l y. NOTE: It is recommended to re - b r i x dispensing valve after installation has been completed.
Fountain Syrup Sold-Out Switch
Models 2095-501 (6.3mm) 1/4” ID Tu b e
2095-540 (9.6mm) 3/8” ID Tu b e
FOR MECHANICAL DISPENSING VALVES
The 2095 Series Syrup “Sold-Out” Switch automatically turns on a automatically turns off the light when the empty Bag-In-Box is “Sold-Out” light to alert operator when the Bag-In-Box is empty or replaced and syrup pressure is restored. if syrup pressure drops below minimum required. The switch
Note: This switch is designed for use with Bag-In-Box systems only, NOT transfer tanks.
PLUMBING
Refer to Diagram A
1 ) Shut off gas supply to syrup pump.
2) Open dispensing valve to relieve all syrup line pressure.
3) Install barbed switch into syrup line near dispensing valve and securely clamp both sides.
4) Switch may be mounted in any position in syrup line.
ELECTRICAL
Refer to Diagram B
The 2095 Series switch and LED light are designed to operate on 24 Volt AC. An existing power source may be used or if not available a suitable 24 Volt transformer must be added.
1 ) Disconnect power.
2) Select location for LED “Sold-Out” light facing operator. (Light intensity is very limited when viewed from side). Preferred location is on front surface of valve cover as shown. (Diagram B).
3) Drill 1/4” (6.3 mm) hole, slide LED lens into hole from front of valve. Next feed LED light through hole from inside or back, slip LED light into lens making sure fingers of lens snap into place.
4) Place sold out label next to light.
5) REFER TO DIAGRAM C -Connect the black wire from the sold out switch to one wire from 24 VAC supply (black wire if they are color coded) and then connect the white from the sold out switch control to the other wire from the 24 VAC supply. Insulate the end of the gray wire using the closed end connector. (Note: Gray wire is not connected to any other wire.)
START-UP
1) Connect 24 Volt power to dispensing valve. Light should go on.
2) Turn on gas supply to Bag-In-Box pump. Pump should start and pressurize syrup line. Light should go off.
3) Open dispensing valve to insure system is dispensing p ro p e r l y. NOTE: It is recommended to re - b r i x dispensing valve after installation has been completed.
4) The 2095 Series switch is set to close when syrup pressure is over 20 (±3) PSI (1.4 BAR) & to open when pressure is under 13 (±3) PSI (.9 BAR)
PARTS INCLUDED IN KITS DIAGRAM D
U.S.A. Flojet 20 Icon Foothill Ranch, CA 92610-3000 Tel: (949) 859-4945 Fax: (949) 859-1153
© Copyright 2001, ITT Industries Printed in U.S.A. All Rights Reserved Form: 81000-040 11/01
UNITED KINGDOM Flojet, Unit 1, Avant Business Centre Denbigh West Industrial Estate Milton Keynes, Bucks, England MK1 1DL Tel: 44 1908 370088 Fax: 44 1908 373731
Loading...