The 2095 Series syrup “Sold-Out” Switch automatically
FOR ELECTRICAL DISPENSING VALVES
shuts off an electric dispensing valve when syrup is sold
out and turns on “Sold-Out” light. This prevents the
operator from selling a drink of carbonated water only,
with no syrup. The switch automatically resets when the
empty Bag-In-Box is replaced and syrup line pressure is
restored.
Note: This switch is designed for use with Bag-In-Box
systems only, NOT transfer tanks.
PLUMBING
Refer to Diagram A
1) Shut off gas supply to syrup pump.
2) Open dispensing valve to relieve all syrup line
pressure.
3) Install barbed switch into syrup line near dispensing
valve and securely clamp both sides.
4) Switch may be mounted in any position in syrup line.
ELECTRICAL
Refer to Diagram B
1) Disconnect power.
2) Select location for LED “Sold-Out” light f a c i n g
operator. (Light intensity is very limited when viewed
from
side.) Preferred location is on front surface of valve
cover as shown. (Diagram B).
3) Drill 1/4” (6.3 mm) hole. slide LED lens into hole from
front of valve. Next feed LED light through hole from
inside or back, slip LED light into lens making sure
fingers of lens snap into place.
4) Place sold out label next to light.
5) REFER TO DIAGRAM C - Locate the 24 VAC leads
running up the tower to the dispensing valve switch
and solenoid. Cut one wire (the black wire if they are
colored white and black). On the end going up the
tower connect the gray wire from the “Sold Out”
switch. Then on the end going down connect the
black wire from switch. Connect these using the 2
butt connectors. Cut and strip the other wire (white if
they are color coded) and connect the white wire from
the switch to both ends of this wire using the closed
end connector.
START-UP
1) Reconnect power to dispensing valve. Light should
go on.
2) Turn on gas supply to Bag-In-Box pump. Pump
should start and pressurize syrup line. Light should go
off.
3) Open dispensing valve to insure system is dispensing
p ro p e r l y. NOTE: It is recommended to re - b r i x
dispensing valve after installation has been
completed.
Fountain Syrup Sold-Out Switch
Models 2095-501 (6.3mm) 1/4” ID Tu b e
2095-540 (9.6mm) 3/8” ID Tu b e
FOR MECHANICAL DISPENSING VALVES
The 2095 Series Syrup “Sold-Out” Switch automatically
turns on a automatically turns off the light when the
empty Bag-In-Box is “Sold-Out” light to alert operator
when the Bag-In-Box is empty or replaced and syrup
pressure is restored. if syrup pressure drops below
minimum required. The switch
Note: This switch is designed for use with Bag-In-Box
systems only, NOT transfer tanks.
PLUMBING
Refer to Diagram A
1 ) Shut off gas supply to syrup pump.
2) Open dispensing valve to relieve all syrup line
pressure.
3) Install barbed switch into syrup line near dispensing
valve and securely clamp both sides.
4) Switch may be mounted in any position in syrup line.
ELECTRICAL
Refer to Diagram B
The 2095 Series switch and LED light are designed to
operate on 24 Volt AC. An existing power source may be
used or if not available a suitable 24 Volt transformer
must be added.
1 ) Disconnect power.
2) Select location for LED “Sold-Out” light facing
operator. (Light intensity is very limited when viewed
from side). Preferred location is on front surface of
valve cover as shown. (Diagram B).
3) Drill 1/4” (6.3 mm) hole, slide LED lens into hole from
front of valve. Next feed LED light through hole from
inside or back, slip LED light into lens making sure
fingers of lens snap into place.
4) Place sold out label next to light.
5) REFER TO DIAGRAM C -Connect the black wire from
the sold out switch to one wire from 24 VAC supply
(black wire if they are color coded) and then connect
the white from the sold out switch control to the other
wire from the 24 VAC supply. Insulate the end of the
gray wire using the closed end connector. (Note:
Gray wire is not connected to any other wire.)
START-UP
1) Connect 24 Volt power to dispensing valve. Light
should go on.
2) Turn on gas supply to Bag-In-Box pump. Pump
should start and pressurize syrup line. Light should
go off.
3) Open dispensing valve to insure system is dispensing
p ro p e r l y. NOTE: It is recommended to re - b r i x
dispensing valve after installation has been
completed.
4) The 2095 Series switch is set to close when syrup
pressure is over 20 (±3) PSI (1.4 BAR) & to open when
pressure is under 13 (±3) PSI (.9 BAR)
PARTS INCLUDED IN KITS
DIAGRAM D
U.S.A.
Flojet
20 Icon
Foothill Ranch, CA 92610-3000
Tel: (949) 859-4945
Fax: (949) 859-1153
© Copyright 2001, ITT Industries Printed in U.S.A. All Rights Reserved Form: 81000-040 11/01
UNITED KINGDOM
Flojet, Unit 1, Avant Business Centre
Denbigh West Industrial Estate
Milton Keynes, Bucks, England MK1 1DL
Tel: 44 1908 370088
Fax: 44 1908 373731