Manitowoc KY0350A, KD0250A, KY0250A, KD0350A, KD0350W Installation, Operation And Maintenance Manual

...
Ice Machines
K Series
Installation, Operation and Maintenance Manual
Part Number 000012545 Rev 02 11/16
Safety Notices
Safety Notices
Read these precautions to prevent personal injury:
Routine adjustments and maintenance procedures outlined in this manual are not covered by the warranty.
Proper installation, care and maintenance are essential for maximum performance and trouble-free operation of your equipment. Visit our website www.kool-aire.com for manual updates, translations, or contact information for service agents in your area.
This equipment contains high voltage electricity and refrigerant charge. Installation and repairs are to be performed by properly trained technicians aware of the dangers of dealing with high voltage electricity and refrigerant under pressure. The technician must also be certified in proper refrigerant handling and servicing procedures. All lockout and tag out procedures must be followed when working on this equipment.
This equipment is intended for indoor use only. Do not install or operate this equipment in outdoor areas.
Warning
n
Follow these electrical requirements during installation of this equipment.
All field wiring must conform to all applicable codes of the authority having jurisdiction. It is the responsibility of the end user to provide the disconnect means to satisfy local codes. Refer to rating plate for proper voltage.
This appliance must be grounded.
This equipment must be positioned so that the plug is accessible unless other means for disconnection from the power supply (e.g., circuit breaker or disconnect switch) is provided.
Check all wiring connections, including factory terminals, before operation. Connections can become loose during shipment and installation.
Warning
n
Follow these precautions to prevent personal injury during installation of this equipment:
Installation must comply with all applicable equipment fire and health codes with the authority having jurisdiction.
To avoid instability the installation area must be capable of supporting the combined weight of the equipment and product. Additionally the equipment must be level side to side and front to back.
Ice machines require a deflector when installed on an ice storage bin. Prior to using a non-OEM ice storage system with this ice machine, contact the bin manufacturer to assure their ice deflector is compatible.
Remove all removable panels before lifting and installing and use appropriate safety equipment during installation and servicing. Two or more people are required to lift or move this appliance to prevent tipping and/or injury.
Do not damage the refrigeration circuit when installing, maintaining or servicing the unit.
Connect to a potable water supply only.
This equipment contains refrigerant charge. Installation of the line sets must be performed by a properly trained and EPA certified refrigeration technician aware of the dangers of dealing with refrigerant charged equipment.
Legs or casters must be installed and the legs/casters must be screwed in completely. When casters are installed the mass of this unit will allow it to move uncontrolled on an inclined surface. These units must be tethered/secured to comply with all applicable codes. Swivel casters must be mounted on the front and rigid casters must be mounted on the rear. Lock the front casters after installation is complete.
Some 50 Hz models may contain up to 150 grams of R290 (propane) refrigerant. R290 (propane) is flammable in concentrations of air between approximately 2.1% and 9.5% by volume (LEL lower explosion limit and UEL upper explosion limit). An ignition source at a temperature higher than 470°C is needed for a combustion to occur. Refer to nameplate to identify the type of refrigerant in your equipment. Only trained and qualified personnel aware of the dangers are allowed to work on the equipment.
Warning
n
Follow these precautions to prevent personal injury while operating or maintaining this equipment:
Crush/Pinch Hazard. Keep hands clear of moving components. Components can move without warning unless power is disconnected and all potential energy is removed.
Moisture collecting on the floor will create a slippery surface. Clean up any water on the floor immediately to prevent a slip hazard.
Objects placed or dropped in the bin can affect human health and safety. Locate and remove any objects immediately.
Never use sharp objects or tools to remove ice or frost. Do not use mechanical devices or other means to accelerate the defrosting process.
When using cleaning fluids or chemicals, rubber gloves and eye protection (and/or face shield) must be worn.
DANGER
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision concerning use of the appliance by a person responsible for their safety. Do not allow children to play with, clean or maintain this appliance without proper supervision.
Warning
n
This product is hermetically sealed and contains fluorinated greenhouse gas R410A.
DANGER
Follow these precautions to prevent personal injury during use and maintenance of this equipment:
It is the responsibility of the equipment owner to perform a Personal Protective Equipment Hazard Assessment to ensure adequate protection during maintenance procedures.
Do Not Store Or Use Gasoline Or Other Flammable Vapors Or Liquids In The Vicinity Of This Or Any Other Appliance. Never use flammable oil soaked cloths or combustible cleaning solutions for cleaning.
All covers and access panels must be in place and properly secured when operating this equipment.
Risk of fire/shock. All minimum clearances must be maintained. Do not obstruct vents or openings.
Failure to disconnect power at the main power supply disconnect could result in serious injury or death. The power switch DOES NOT disconnect all incoming power.
All utility connections and fixtures must be maintained in accordance with the authority having jurisdiction.
Turn off and lockout all utilities (gas, electric, water) according to approved practices during maintenance or servicing.
Units with two power cords must be plugged into individual branch circuits. During movement, cleaning or repair it is necessary to unplug both power cords.
Never use a high-pressure water jet for cleaning on the interior or exterior of this unit. Do not use power cleaning equipment, steel wool, scrapers or wire brushes on stainless steel or painted surfaces.
Two or more people are required to move this equipment to prevent tipping.
Locking the front casters after moving is the owner’s and operator’s responsibility. When casters are installed, the mass of this unit will allow it to move uncontrolled on an inclined surface. These units must be tethered/secured to comply with all applicable codes.
The on-site supervisor is responsible for ensuring that operators are made aware of the inherent dangers of operating this equipment.
Do not operate any appliance with a damaged cord or plug. All repairs must be performed by a qualified service company.
Safety Notices
Section 1 General Information
Section 2 Installation
Table of Contents
Safety Notices ..................................................................................................................... 3
Model Numbers .................................................................................................................. 7
Ice Deflector ........................................................................................................................7
Bin Installation .........................................................................................................................................7
Air Baffle .............................................................................................................................7
Warranty Information ........................................................................................................ 7
Model Nomenclature ............................................................................................................................8
Location of Ice Machine ..................................................................................................... 9
Clearance Requirements ....................................................................................................9
Ice Machine Heat of Rejection .........................................................................................10
Removing Drain Plug and Leveling the Ice Storage Bin ................................................10
Air Baffle ...........................................................................................................................10
Electrical Service ..............................................................................................................11
Minimum Circuit Ampacity .............................................................................................................. 11
Electrical Requirements .................................................................................................................... 11
Ground Fault Circuit Interrupter .................................................................................................... 11
Minimum Power Cord Specifications ........................................................................................... 11
For United Kingdom Only ................................................................................................................ 11
Maximum Breaker Size & Minimum Circuit Amperage Chart .......................................12
Water Supply and Drain Requirements .......................................................................... 13
Water Supply ......................................................................................................................................... 13
Water Inlet Lines .................................................................................................................................. 13
Drain Connections .............................................................................................................................. 13
Water Supply and Drain Line Sizing/Connections ......................................................... 14
Water-Cooled Condenser Water Pressure ..................................................................................14
Cooling Tower Applications (Water-Cooled Models) ............................................................. 14
Remote Condenser/Line Set Installation ........................................................................15
Remote Ice Machine Refrigerant Charge ....................................................................................15
General ....................................................................................................................................................16
Wiring ...................................................................................................................................................... 16
Guidelines for Routing Line Sets ....................................................................................................16
Calculating Remote Condenser Installation Distances ..........................................................17
Route the Line Set ............................................................................................................................... 18
Connect the Line Set .......................................................................................................................... 18
Pressure Test and Evacuate Line Set and Condenser ............................................................. 18
Open Line Set Valves .......................................................................................................................... 18
Installation Check List ......................................................................................................19
Additional Checks for Remote Models ...........................................................................19
Before Starting the Ice Machine ......................................................................................19
Part Number 000012545 Rev 02 11/16 5
Section 3 Operation
Section 4 Maintenance
Section 5 Troubleshooting
Table of Contents (continued)
Ice Making Sequence of Operation .................................................................................21
Control Board Timers ......................................................................................................................... 21
Safety Limits .......................................................................................................................................... 21
Operational Checks ..........................................................................................................22
General ....................................................................................................................................................22
Minimum/Maximum Slab Weights ............................................................................................... 22
Ice Thickness Check ............................................................................................................................ 22
Cleaning and Sanitizing ................................................................................................... 23
General ....................................................................................................................................................23
Cleaning/Sanitizing Procedure.......................................................................................................23
Preventative Maintenance Cleaning Procedure .......................................................................23
Exterior Cleaning ................................................................................................................................. 23
Cleaning/Sanitizing Procedure .......................................................................................24
Sanitizing Procedure .......................................................................................................................... 25
Parts Removal for Cleaning/Sanitizing ..........................................................................26
Preventative Maintenance Cleaning Procedure ............................................................27
Door Removal ...................................................................................................................27
Cleaning the Condenser Filter .........................................................................................27
Cleaning the Condenser ..................................................................................................27
Removal from Service/Winterization .............................................................................28
Water-Cooled Ice Machines ............................................................................................................. 28
Checklist ............................................................................................................................ 29
Safety Limit Feature .........................................................................................................30
6 Part Number 000012545 Rev 02 11/16
Section 1
General Information
Model Numbers
This manual covers the following models:
Self-Contained
Air-Cooled
KD0250A KY0250A KD0350A KY0350A KD0420A KY0420A KD0500A KY0500A KD0600A KY0600A KD1000A KY1000A KD1350A KY1350A KD1800A KY1800A
Self-Contained
Water-Cooled
----
---­KD0350W KY0350W KD0420W KY0420W KD0500W KY0500W KD0600W KY0600W KD1000W KY1000W KD1350W KY1350W
Remote
----
----
----
----
----
----
----
----
----
---­KY1000N KD1000N KY1350N KD1350N KY1800N KD1800N
Ice Deflector
An ice deflector is required when the ice machine is installed on a bin. An ice deflector is not required when the ice machine is installed on a dispenser.
BIN INSTALLATION
All ice machines installed on a bin require an ice deflector.
Koolaire bins have a deflector installed and require no modifications when used with a forward facing evaporator.
Align sides and back of ice machine with sides and back of bin, when placing ice machine on bin.
Air Baffle
Self-Contained Air-Cooled Only
The air-cooled baffle prevents condenser air from recirculating.
Warranty Information
Visit www.kool-aire.com for:
Warranty Verification
Warranty Registration
View and download a copy of your warranty
Part Number 000012545 Rev 02 11/16 7
General Information Section 1
MODEL NOMENCLATURE
CONDENSER TYPE A -Self-Contained Air-Cooled W -Self-Contained Water-Cooled N -Remote Air-Cooled
3 -Three Phase NO INDICATOR -1 Phase
ICE CUBE SIZE D -Dice
Y -Half-Dice
ICE MACHINE MODEL
Ice Machine Series
# HERTZ 5 -50HZ 6 -60HZ
KD 1350 A3 – 263
VOLTAGE 161 -115/60/1 261 -208-230 /60/1 251 -230/50/1 263 -208-230 /60/3
8 Part Number 000012545 Rev 02 11/16
Section 2
Installation
Location of Ice Machine
The location selected for the ice machine must meet the following criteria. If any of these criteria are not met, select another location.
The location must be free of airborne and other contaminants.
The air temperature must be at least 35°F (1.6°C), but must not exceed 110°F (43.4°C).
NOTE: K1350 Minimum air temperature is 40°F (4.4°C).
Remote air-cooled - The air temperature must be at least
-20°F (-29°C), but must not exceed 120°F (49°C).
The location must not be near heat-generating (ovens, dishwashers, etc.) equipment or in direct sunlight and must be protected from weather.
The location must not obstruct airflow through or around the ice machine. Refer to the clearance requirements chart.
These ice machines are intended for use in applications such as:
Staff kitchen areas in shops, offices and other work environments
Clients in hotels, motels, farmhouses, bed and breakfast and other residential type environments
Catering and similar non-retail applications
Clearance Requirements
Warning
n
Do not obstruct ice machine vents or openings.
K0250 Self-Contained
Air-Cooled
Top/Sides 12" (30.5 cm) N/A
Back 5" (12.7 cm) N/A
K0350/K0420 K0500/K0600/ K1000/K1350/
K1800
Top/Sides 8" (20.3 cm) 8" (20.3 cm)
Back 5" (12.7 cm) 5" (12.7 cm)
K0420
Tropical Rating
50 Hz Only
Top 24" (61.0 cm) 8" (20.3 cm)
Sides 12" (30.5 cm) 8" (20.3 cm)
Back 5" (12.7 cm) 5" (12.7 cm)
K1000
Tropical Rating
50 Hz Only
Top 12" (30.5 cm) 8" (20.3 cm)
Sides 8" (20.3 cm) 8" (20.3 cm)
Back 5" (12.7 cm) 5" (12.7 cm)
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Air-Cooled
Self-Contained
Water-Cooled
Water-Cooled
and Remote*
Water-Cooled
Water-Cooled
and Remote
Warning
n
Two or more people or a lifting device are required to lift this appliance.
The ice machine must be protected if it will be subjected to temperatures below 32°F (0°C). Failure caused by
Caution
,
exposure to freezing temperatures is not covered by the warranty.
Part Number 000012545 Rev 02 11/16 9
Installation Section 2
Ice Machine Heat of Rejection
Series
Ice Machine
K0250 4600 5450 K0350 3800 6000 K0420 5400 6300 K0500 5300 6100 K0600 9000 13900 K1000 17000 20700 K1350 23900 29000 K1800 29800 34700
1 B.T.U./Hour 2 Because the heat of rejection varies during the ice making cycle, the
figure shown is an average.
Air Conditioning
Heat of Rejection
2
Ice machines, like other refrigeration equipment, reject heat through the condenser. It is helpful to know the amount of heat rejected by the ice machine when sizing air conditioning equipment where self-contained air-cooled ice machines are installed.
This information is also necessary when evaluating the benefits of using water-cooled or remote condensers to reduce air conditioning loads. The amount of heat added to an air conditioned environment by an ice machine using a water-cooled or remote condenser is negligible.
Knowing the amount of heat rejected is also important when sizing a cooling tower for a water-cooled condenser. Use the peak figure for sizing the cooling tower.
1
Peak
Removing Drain Plug and Leveling the Ice Storage Bin
Warning
n
To avoid instability, the bin/dispenser must be installed in an area capable of supporting the weight of the bin/ dispenser, ice machine and a full bin of ice (48" models 1000 lbs [454 kg], 30" models 750 lbs [340 kg]). The bin/ dispenser must be level side-to-side and front-to-back before installing the ice machine.
1. Remove threaded plug from drain fitting.
2. Screw the leveling legs onto the bottom of the bin.
3. Screw the foot of each leg in as far as possible.
Caution
,
The legs must be screwed in tightly to prevent them from bending.
4. Move the bin into its final position.
5. Level the bin to assure that the bin door closes and seals and the ice machine operates properly. Use a level on top of the bin. Turn the base of each foot as necessary to level the bin.
6. Inspect bin gasket prior to ice machine installation. (Our bins come with a closed cell foam gasket installed along the top surface of the bin.)
7. Remove all panels from ice machine before lifting and installing on bin. Remove front panel, top cover, left and right side panels.
Air Baffle
Self-Contained Air-Cooled Only
To install:
1. Loosen the back panel screws next to the condenser.
2. Align the keyhole slots in the air baffle with the screw holes and slide the baffle down to lock in place.
Air Baffle
10 Part Number 000012545 Rev 02 11/16
Section 2 Installation
Electrical Service
Warning
n
All electrical work, including wire routing and grounding must conform to all applicable national and local electrical codes.
MINIMUM CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select the wire size of the electrical supply. (Minimum circuit ampacity is not the ice machine’s running amp load.)
ELECTRICAL REQUIREMENTS
Refer to Ice Machine Model/Serial Plate for voltage/ amperage specifications.
A separate fuse/circuit breaker must be provided for each ice machine.
The wire size (or gauge) is dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician.
The ice machine must be grounded. Check all green ground screws in the control box and verify they are tight before starting the ice machine.
The maximum allowable voltage variation is ±10% of the rated voltage at ice machine start-up (when the electrical load is highest).
Caution
,
Observe correct polarity of incoming line voltage. Incorrect polarity can lead to erratic ice machine operation. Operate equipment only on the type of electricity indicated on the specification plate.
GROUND FAULT CIRCUIT INTERRUPTER
Ground Fault Circuit Interrupter (GFCI/GFI) protection is a system that shuts down the electric circuit (opens it) when it senses an unexpected loss of power, presumably to ground. GFCI/GFI circuit protection is not recommended with our equipment. If code requires the use of a GFCI/GFI, then you must follow the local code. The circuit must be dedicated, sized properly and there must be a panel GFCI/ GFI breaker. We do not recommend GFCI/GFI outlets as they are known for more intermittent nuisance trips than panel breakers.
MINIMUM POWER CORD SPECIFICATIONS
Maximum Breaker
Size 15 amp 14 gauge 6 feet (1.83 m) 20 amp 12 gauge 6 feet (1.83 m) 30 amp 10 gauge 6 feet (1.83 m) 40 amp 8 gauge 6 feet (1.83 m)
Minimum Wire
Size
Maximum Length
of Power Cord
If a power cord is used, the wire size to the receptacle is dependent upon location, materials used, length of run, etc., so it must be determined by a qualified electrician. Local, state or national requirements will supersede our minimum requirements.
FOR UNITED KINGDOM ONLY
As the colors of the wires in the mains lead of the appliance may not correspond with the colored markings identifying the terminals in your plug, proceed as follows:
The wire which is colored green and yellow must be connected to the terminal in the plug which is marked with the letter E or by the earth ground symbol or colored green or green and yellow.
The wire colored blue must be connected to the terminal which is marked with the letter N or colored black.
The wire colored brown must be connected to the terminal which is marked with the letter L or colored red.
Part Number 000012545 Rev 02 11/16 11
Installation Section 2
Maximum Breaker Size & Minimum Circuit Amperage Chart
Important
Due to continuous improvements, this information is for reference only. Please refer to the ice machine serial number tag to verify electrical data. Serial tag information overrides information listed on this page.
Air-Cooled Water-Cooled Remote
Ice Machine
K0250
K0350
K0420
K0500
K0600
K1000
K1350
K1800
Voltage/
Phase/Cycle
115/1/60 15 9.44 N/A N/A N/A N/A 230/1/50 15 4.5 N/A N/A N/A N/A 230/1/60 15 4.7 N/A N/A N/A N/A 115/1/60 15 12.1 15 11.4 N/A N/A 230/1/50 15 6.3 15 5.9 N/A N/A 230/1/60 15 6.2 15 5.8 N/A N/A 115/1/60 15 11.3 15 10.6 N/A N/A 230/1/50 15 6.2 15 5.8 N/A N/A 230/1/60 15 6.2 15 5.8 N/A N/A 115/1/60 20 12.7 20 12.0 N/A N/A 230/1/50 15 6.3 15 5.9 N/A N/A
208-230/1/60 20 9.2 20 8.8 N/A N/A
230/1/50 20 8.6 20 8.2 N/A N/A
208-230/1/60 20 13.9 20 13.2 20 12.8
230/1/50 20 13.8 20 13.1 20 14.1 208-230/1/60 30 18.2 30 16.8 30 17.8 208-230/3/60 20 13.6 20 12.2 20 13.2
230/1/50 30 18.2 30 16.8 30 17.8 208-230/1/60 30 19.6 N/A N/A 30 19.6 208-230/3/60 20 13.3 N/A N/A 20 12.9
230/1/50 30 19.6 N/A N/A 30 19.6
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
Maximum
Fuse/Circuit
Breaker
Minimum
Circuit Amps
12 Part Number 000012545 Rev 02 11/16
Section 2 Installation
Water Supply and Drain Requirements
WATER SUPPLY
Local water conditions may require treatment of the water to inhibit scale formation, filter sediment, and remove chlorine odor and taste.
Warning
n
Connect to a potable water supply only. Plumbing must conform to state, local and national codes.
WATER INLET LINES
Follow these guidelines to install water inlet lines:
If you are installing a water filter system, refer to the installation instructions supplied with the filter system for ice making water inlet connections.
Do not connect the ice machine to a hot water supply. Be sure all hot water restrictors installed for other equipment are working. (Check valves on sink faucets, dishwashers, etc.)
If water pressure exceeds the maximum recommended pressure of 80 psi (552 kPa), obtain a water pressure regulator from your local distributor.
Install a water shut-off valve for both the ice making and condenser water lines.
Insulate water inlet lines to prevent condensation.
DRAIN CONNECTIONS
Follow these guidelines when installing drain lines to prevent drain water from flowing back into the ice machine and storage bin:
Drain lines must have a 1.5 inch drop per 5 feet of run (2.5 cm per meter), and must not create traps.
The floor drain must be large enough to accommodate drainage from all drains.
Run separate bin and ice machine drain lines. Insulate them to prevent condensation.
Vent the bin and ice machine drain to the atmosphere. Do not vent the condenser drain on water-cooled models.
A separate auxiliary drain is located in the ice machine base to remove moisture in high humidity areas. The drain fitting is a female socket for 1/2" CPVC pipe. The drain is sealed and the seal must be removed before attaching the drain fitting/tubing. Tap the seal out with a wooden dowel or similar tool. Seal the CPVC pipe to the ice machine socket with silicone sealant to allow future removal.
Caution
,
Do not apply heat to water valve inlet fitting. This will damage plastic water inlet connection.
Part Number 000012545 Rev 02 11/16 13
Installation Section 2
Water Supply and Drain Line Sizing/Connections
Location Water Temperature Water Pressure Ice Machine Fitting
Ice Making Water
Inlet
Ice Making Water
Drain
Condenser Water
Inlet
Condenser Water
Drain
Bin Drain
Large Capacity
Bin Drain
WATERCOOLED CONDENSER WATER PRESSURE
Water pressure at the condenser cannot exceed 150 psig (1034 kPa) with the standard water-regulating valve. Contact your distributor if your water pressure is greater than 150 psig (1034 kPa). A special order condenser/water­regulating valve is available that allows water pressure up to 350 psig (2413 kPa).
The Commonwealth of Massachusetts requires that all water-cooled models must be connected only to a closed loop, cooling tower system.
35°F (2°C) Min.
90°F (32°C) Max.
1/2" (1.27 cm) Female Pipe Thread 1/2" (1.27 cm) min. inside
90°F (32°C) Max. Standard
1/2" (1.27 cm) Female Pipe Thread 1/2" (1.27 cm) min. inside
3/4" (1.91 cm) Female Pipe Thread 3/4" (1.91 cm) min. inside
1" (2.54 cm) Male Pipe Thread 1" (2.54 cm) min. inside diameter
20 psi (140 kPa) Min. 80 psi (552 kPa) Max.
20 psi (140 kPa) Min.
150 psi (1034 kPa) Max.
High Pressure Option
20 psi (140 kPa) Min.
350 psi (2410 kPa) Max.
3/8" (.95 cm) Female Pipe Thread 3/8" (.95 cm) min. inside
COOLING TOWER APPLICATIONS WATERCOOLED MODELS
A water cooling tower installation does not require modification of the ice machine. The water regulator valve for the condenser continues to control the refrigeration discharge pressure.
It is necessary to know the amount of heat rejection and
Important
the pressure drop through the condenser and water valves (inlet and outlet) when using a cooling tower on an ice machine.
Water entering the condenser must not exceed 90°F (32°C).
Water flow through the condenser must not exceed 5 gallons (19 liters) per minute.
Allow for a pressure drop of 7 psi (50 kPa) between the condenser water inlet and the outlet of the ice machine.
Water exiting the condenser must not exceed 110°F (43°C).
Tubing Size Up to Ice Machine
Fitting
diameter
diameter
3/8" Female Pipe Thread
diameter
diameter
14 Part Number 000012545 Rev 02 11/16
Section 2 Installation
Remote Condenser/Line Set Installation
Ice Machine
K1000 KC1000
K1350 KC1350
K1800 KC1350
*Line Set Discharge Line Liquid Line
RTK 1/2" (1.27 cm) 5/16" (.79 cm) RLK 1/2" (1.27 cm) 3/8" (.95 cm)
Air Temperature Around the Condenser
Minimum Maximum
-20°F (-29°C) 120°F (49°C)
Remote systems are only approved and warranted as a complete new package. Warranty on the refrigeration system will be void if a new ice machine head section is connected to pre-existing (used) tubing or remote condensers.
Remote Single
Circuit Condenser
Important
Line Set*
RTK-20-R410A RTK-35-R410A RTK-50-R410A RLK-20-R410A RLK-35-R410A RLK-50-R410A RLK-20-R410A RLK-35-R410A RLK-50-R410A
REMOTE ICE MACHINE REFRIGERANT CHARGE
Each remote ice machine ships from the factory with a refrigerant charge appropriate for installation with line sets of up to 50' (15 m). The serial tag on the ice machine indicates the refrigerant charge.
Additional refrigerant may be required for installations using line sets between 50' and 100' (15-30 m) long. If additional refrigerant is required, refer to the chart below for the correct amount to be added.
Ice Machine
K1000 2 lbs (907g) K1350 2 lbs (907g) K1800 2 lbs (907g)
Refrigerant to be added for
50'-100' Line Sets
Important
EPA CERTIFIED TECHNICIANS
If remote line set length is between 50' and 100' (15 and 30 m), add additional refrigerant to the nameplate charge. Refer to the table below for the model being worked on.
Tubing length: _________________________________
Refrigerant added to nameplate: __________________
New total refrigerant charge: _____________________
Warning
n
Potential Personal Injury Situation
The ice machine contains refrigerant charge. Installation of the line sets must be performed by a properly trained and EPA certified refrigeration technician aware of the dangers of dealing with refrigerant charged equipment.
Part Number 000012545 Rev 02 11/16 15
Installation Section 2
GENERAL
Condensers must be mounted horizontally with the fan motor on top with nothing obstructing it. There must be at least a 16" (41 cm) clearance from the bottom for air intake. The front coupling panel and one other panel (back or side) must also be unobstructed.
Remote condenser installations consist of vertical and horizontal line sets between the ice machine and the condenser. When combined, they must fit within approved specifications. The following guidelines, drawings and calculation methods must be followed to verify a proper remote condenser installation.
Caution
,
The compressor warranty (including the labor replacement warranty) will not apply if the remote ice machine is not installed according to specifications.
The warranty also will not apply if the refrigeration system is modified with a condenser, heat reclaim device, or other parts or assemblies not manufactured by us unless we specifically approved the component in writing.
3
2
1
DOWNWARD
DOWNWARD
HORIZONTAL
HORIZONTAL
SPIRAL
SPIRAL
1
2
3
WIRING
Interconnecting line voltage wiring is used to energize and de-energize the condenser fan motor.
The remote condenser voltage matches the ice machine head section voltage.
Interconnecting Wire Connections
Ice Machine Head Section Remote Condenser
F1 L1 F2 L2
GUIDELINES FOR ROUTING LINE SETS
First, cut a 2.5" (6.35 cm) circular hole in the wall or roof for tubing routing. The line set end with the 90° bend will connect to the ice machine. The straight end will connect to the remote condenser.
Follow these guidelines when routing the refrigerant lines. This will help ensure proper performance and service accessibility.
1. Optional - Make the service loop in the line sets (as shown in Routing Line Sets graphic). This permits easy access to the ice machine for cleaning and service. Do not use hard rigid copper at this location.
2. Required - Do not form traps in the refrigeration lines (except the service loop). Refrigerant oil must be free to drain toward the ice machine or the condenser. Route excess tubing in a supported downward horizontal spiral (as shown below). Do not coil tubing vertically.
3. Required - Keep outdoor refrigerant line runs as short as possible.
Routing Line Sets
16 Part Number 000012545 Rev 02 11/16
Section 2 Installation
H
H
H
CALCULATING REMOTE CONDENSER INSTALLATION DISTANCES
Line Set Length
The maximum length is 100' (30 m). The ice machine compressor must have the proper oil
return. The receiver is designed to hold a charge sufficient to operate the ice machine in ambient temperatures between -20°F (-29°C) and 120°F (49°C), with line set lengths of up to 100' (30 m).
Line Set Rise/Drop
The maximum rise is 35' (10.7 m). The maximum drop is 15' (4.5 m).
Caution
,
If a line set has a rise followed by a drop, another rise cannot be made. Likewise, if a line set has a drop followed by a rise, another drop cannot be made.
Calculated Line Set Distance
The maximum calculated distance is 150' (45 m). Line set rises, drops, horizontal runs (or combinations
of these) in excess of the stated maximums will exceed compressor start-up and design limits. This will cause poor oil return to the compressor.
Make the following calculations to make sure the line set layout is within specifications.
1. Insert the measured rise into the formula below. Multiply by 1.7 to get the calculated rise. (Example: A condenser located 10 feet above the ice machine has a calculated rise of 17 feet.)
2. Insert the measured drop into the formula below. Multiply by 6.6 to get the calculated drop. (Example. A condenser located 10 feet below the ice machine has a calculated drop of 66 feet.)
3. Insert the measured horizontal distance into the formula below. No calculation is necessary.
4. Add together the calculated rise, calculated drop, and horizontal distance to get the total calculated distance. If this total exceeds 150' (45 m), move the condenser to a new location and perform the calculations again.
Maximum Line Set Distance Formula
Step 1. Measured Rise (35' [10.7 m] Maximum) ______ x 1.7 = _______ Calculated Rise Step 2. Measured Drop (15' [4.5 m] Maximum) ______ x 6.6 = _______ Calculated Drop Step 3. Measured Horizontal Distance (100' [30 m] Maximum) _______ Horizontal Distance Step 4. Total Calculated Distance 150' (45 m) _______ Total Calculated Distance
D
R
SV1196 SV1195 SV1194
Combination of a Rise and a
HorizontalRun
D
Combination of a Drop and a
HorizontalRun
R
Combination of a Rise, a Drop and a
Horizontal Run
Part Number 000012545 Rev 02 11/16 17
Installation Section 2
ROUTE THE LINE SET
Route the line set to avoid traps and kinks.
Minimize the amount of line set exposed on the roof.
CONNECT THE LINE SET
Cut the line set to the correct length.
Purge line set with dry nitrogen while brazing.
Line set shutoff valves on the ice machine must remain closed and be protected from heat during brazing.
PRESSURE TEST AND EVACUATE LINE SET AND CONDENSER
Lineset shutoff valves must remain closed until pressure testing and evacuation are complete.
Pressure test @ 150 psi (1000 kPa) for a minimum of 15 minutes.
Minimum evacuation level is 500 microns.
Pressure test the line set and condenser with 150 psig of dry nitrogen. Add nitrogen at the line set shutoff valves located at the back of the ice machine head section. Complete the pressure test, verify no leaks are present and remove the nitrogen from the system before connecting the vacuum pump.
OPEN LINE SET VALVES
You will not hear refrigerant flow when the valves are opened. Refrigerant will not flow until the ice machine is started and the solenoid valve opens.
All valve caps must be reinstalled, tightened and leak­checked to assure no refrigerant leakage exists.
Counterclockwise opens all valves.
18 Part Number 000012545 Rev 02 11/16
Section 2 Installation
Installation Check List
Is the Ice Machine level?
Have all of the electrical and water connections
beenmade?
Has the supply voltage been tested and checked
against the rating on the nameplate?
Is there proper clearance around the ice machine forair
circulation?
Is the ice machine grounded and polarity correct?
Has the ice machine been installed where ambient
temperatures will remain in the range of 35° - 110°F (1.6° - 43.3°C)?
Has the ice machine been installed where the incoming
water temperature will remain in the rangeof 35° - 90°F (1.6° - 32.2°C)?
Is there a separate drain for the potable water,
binandwater-cooled condenser?
Additional Checks for Remote Models
Does the remote condenser fan operate properly
afterstart-up?
Has the remote condenser been located where
ambient temperatures will remain in the range of -20°­120°F (-29 - 49°C).
Is the line set routed properly?
Are both refrigeration lines to remote condenser run so
they do not lay in water and are properly insulated?
Before Starting the Ice Machine
All ice machines are factory-operated and adjusted before shipment. Normally, new installations do not require any adjustment.
To ensure proper operation, follow the Operational Checks in Section 3 of this manual. Starting the ice machine and completing the Operational Checks are the responsibilities of the owner/operator.
Adjustments and maintenance procedures outlined in this manual are not covered by the warranty.
Are the ice machine and bin drains vented?
Are all refrigerant lines free from contact with
othercomponents?
Are all electrical leads free from contact with
refrigeration lines and moving equipment?
Has the owner/operator been instructed
regardingmaintenance and the use of our Cleanerand Sanitizer?
Has the owner/operator completed the
warrantyregistration card?
Has the ice machine and bin been sanitized?
Is the ice thickness set correctly? (Refer to
OperationalChecks to check/set the correct ice bridgethickness).
Warning
n
Potential Personal Injury Situation
Do not operate equipment that has been misused, abused, neglected, damaged, or altered/modified from that of original manufactured specifications.
Part Number 000012545 Rev 02 11/16 19
Installation Section 2
THIS PAGE INTENTIONALLY LEFT BLANK
20 Part Number 000012545 Rev 02 11/16
Loading...
+ 44 hidden pages