As you work on a J-Series Ice Machine, be sure to
pay close attention to the safety notices in this
manual. Disregarding the notices may lead to serious
injury and/or damage to the ice machine.
Procedural Notices
As you work on a J-Series Ice Machine, be sure to
read the procedural notices in this manual. These
notices supply helpful information which may assist
you as you work.
Throughout this manual, you will see the following
types of safety notices:
WARNING
Text in a Warning box alerts you to a potential
personal injury situation. Be sure to read the
Warning statement before proceeding, and work
carefully.
CAUTION
Text in a Caution box alerts you to a situation in
which you could damage the ice machine. Be sure
to read the Caution statement before proceeding,
and work carefully.
Throughout this manual, you will see the following
types of procedural notices:
Important
Text in an Important box provides you with
information that may help you perform a procedure
more efficiently. Disregarding this information will
not cause damage or injury, but it may slow you
down as you work.
NOTE: Text set off as a Note provides you with
simple, but useful, extra information about the
procedure you are performing.
We reserve the right to make product improvements at any time.
Specifications and design are subject to change without notice.
Location of Ice Machine ....................................................................................................................................2-5
Heat of Rejection................................................................................................................................................2-5
Water Connections and Drains.......................................................................................................................2-10
Routing Line Sets.........................................................................................................................................2-13
Line Set Routing and Sizing.........................................................................................................................2-16
Head Pressure Control Valve.......................................................................................................................2-16
Fan Motor.....................................................................................................................................................2-16
Water Level Check.........................................................................................................................................3-2
Air-Cooled Condenser (Self-Contained and Remote Models).......................................................................3-3
Water-Cooled Condenser and Water Regulating Valve.................................................................................3-4
Interior Cleaning and Sanitizing
General ...........................................................................................................................................................3-5
Removal of Parts for Cleaning/Sanitizing......................................................................................................3-8
Water Treatment/Filtration............................................................................................................................3-14
Removal from Service/Winterization
General .........................................................................................................................................................3-15
Bin Switch....................................................................................................................................................6-36
Discharge Line Thermistor...........................................................................................................................6-43
Control Board Relays...................................................................................................................................6-45
Electronic Control Board (Old Style)...........................................................................................................6-46
Electronic Control Board (New Style).........................................................................................................6-47
Ice Thickness Probe (Harvest Initiation)
General .........................................................................................................................................................6-50
How the Probe Works..................................................................................................................................6-50
Freeze Time Lock-In Feature.......................................................................................................................6-50
Maximum Freeze Time................................................................................................................................6-50
Installation of New Probe on Old Style Control Board................................................................................6-50
Diagnosing Probe Control Circuitry
Ice Machine Cycles Into Harvest Before Water Contact with Probe.....................................................6-51
Ice Machine Does Not Cycle Into Harvest When Water Contacts Probe ..............................................6-52
Diagnosing Ice Machine That Will Not Run..................................................................................................6-53
iv
Table of Contents (cont.)
Section 7 - Refrigeration System
Sequence of Operation
Self-Contained Air- or Water-Cooled Models...............................................................................................7-1
General ...........................................................................................................................................................7-8
Before Beginning Service...............................................................................................................................7-9
Ice Production Check.....................................................................................................................................7-9
Water System Checklist...............................................................................................................................7-10
How to Use the Refrigeration System Operational Analysis Tables............................................................7-22
Refrigeration System Operational Analysis Tables
Single TXV ............................................................................................................................................7-24
Headmaster Control Valve.....................................................................................................................7-28
v
Table of Contents (cont.)
Section 7 - Refrigeration System (cont.)
Pressure Control Specifications and Diagnostics
Fan Cycle Control ........................................................................................................................................7-30
High Pressure Cutout (HPCO) Control........................................................................................................7-30
HFC Refrigerant Questions and Answers....................................................................................................7-57
vi
Section 1Warranty
Section 1
Warranty
Coverage
GENERAL
The following Warranty outline is provided for your
convenience. For a detailed explanation, read the
warranty bond shipped with each product.
Contact your local Manitowoc representative or
Manitowoc Ice, Inc. if you need further warranty
information.
PARTS
1. Manitowoc warrants the ice machine against
defects in materials and workmanship, under
normal use and service for three (3) years from
the date of original installation.
2. The evaporator and compressor are covered by an
additional two (2) year (five years total) warranty
beginning on the date of the original installation.
LABOR
1. Labor required to repair or replace defective
components is covered for three (3) years from
the date of original installation.
2. The evaporator is covered by an additional two
(2) year (five years total) labor warranty
beginning on the date of the original installation.
EXCLUSIONS
The following items are not included in the ice
machine’s warranty coverage:
1. Normal maintenance, adjustments and cleaning as
outlined in the Owner/Operator Use and Care
Guide.
2. Repairs due to unauthorized modifications to the
ice machine or the use of non-standard parts
without prior written approval Manitowoc Ice,
Inc.
3. Damage caused by improper installation of the ice
machine, electrical supply, water supply or
drainage, or damage caused by floods, storms, or
other acts of God.
4. Premium labor rates due to holidays, overtime,
etc.; travel time; flat rate service call charges;
mileage and miscellaneous tools and material
charges not listed on the payment schedule.
Additional labor charges resulting from the
inaccessibility of the ice machine are also
excluded.
5. Parts or assemblies subjected to misuse, abuse,
neglect or accidents.
6. Damage or problems caused by installation,
cleaning and/or maintenance procedures
inconsistent with the technical instructions
provided in the Installation Manual and the
Owner/Operator Use and Care Guide.
AUTHORIZED WARRANTY SERVICE
To comply with the provisions of the warranty, a
refrigeration service company, qualified and
authorized by a Manitowoc distributor, or a
Contracted Service Representative must perform the
warranty repair.
1-1
WarrantySection 1
THIS PAGE INTENTIONALLY LEFT BLANK
1-2
Section 2Installation References
Section 2
Installation References
Refer to Installation Manual for complete installation guidelines
system with an ice deflector. The J1300 and J1800
require a Manitowoc Ice Deflector Kit (K00092)
when installing with a non-Manitowoc ice storage
NOTE: All measurements are in inches.
Bin ModelDimension ADimension B
C32034.0032.00
C42034.0044.00
system.
For other Manitowoc Ice Machines, do not use a
non-Manitowoc ice storage system before
confirming with the manufacturer that their ice
2-3
deflector is compatible with Manitowoc ice
machines.
Section 2Installation References
2-4
Section 2Installation References
REMOTE CONDENSERS
JC0495/JC0895/JC1095/JC1395 Condensers
OPTIONAL
29.16
38.00
34.00
6.00
29.50
3.50
4.00
6.50
14.62
27.94
1.50
OPTIONAL
20.00
16.00
SV1297
Dual Circuit Condenser - DC0862
OPTIONAL
47.25
43.25
39.25
35.25
31.25
3.91
8.56
29.16
6.34
8.50
14.69
29.30
22.40
3.38
24.00
6.34
8.50
SV1578
OPTIONAL
19.69
15.69
JC1895 Remote Condenser
OPTIONAL
29.16
47.25
43.25
39.25
35.25
31.25
8.56
3.91
29.50
6.34
8.50
14.69
27.94
SV1301
NOTE: All measurements are in inches.
1.60
OPTIONAL
19.69
15.69
11.69
7.69
3.69
2-5
Location of Ice Machine
A Manitowoc ice machine operates most efficiently
when it is:
1. Located Away From Heat Sources
Do not install the ice machine near heatgenerating equipment or in an area of direct
sunlight.
Air Temperature Around Ice Machine
MinimumMaximum
35°F (1.7°C)110°F (43.3°C)
CAUTION
The ice machine must be protected if it will be
subjected to temperatures below 32°F (0°C).
Failure caused by exposure to freezing
temperatures is not covered by the warranty. See
“Winterization” in the Owner/Operator Use and
Care Guide.
2. Located in a Contaminant-Free Area
Airborne contaminants can damage ice machines.
Air-cooled models are particularly vulnerable.
3. Provided with Sufficient Air Clearance
Adequate airflow through and around the ice
machine is essential for maximum ice production
and long component life.
Air Clearance Around Ice Machine
ModelAreaClearance
Self-ContainedTop8” (20 cm)
Air-CooledSides8” (20 cm)
Back5” (12 cm)
Water-CooledTop
or RemoteSides5” (12 cm)
Back
1
This clearance is not required, but it is recommended
for efficient operation and servicing.
1
Section 2Installation References
Heat of Rejection
Ice machines, like other refrigeration equipment,
reject heat through the condenser.
It is helpful to know the amount of heat rejected by
the ice machine when you are sizing air conditioning
equipment for the ice machine installation area.
This information is also necessary when evaluating
the benefits of using water-cooled or remote
condensers to reduce air conditioning loads. The
amount of heat added to an air conditioned
environment by an ice machine with a water-cooled
or remote condenser is negligible.
Knowing the amount of heat rejected is also
important when sizing a cooling tower for a watercooled condensing unit. The peak figure is used for
sizing the cooling tower.
Because the heat of rejection varies during the ice
making cycle, the figure shown is an average.
2
1
Peak
Important
Two stacked ice machines may share a single ice
storage bin. A stacking kit is required for stacking
two ice machines. Follow the instructions supplied
with the stacking kit.
2-6
Section 2Installation References
Electrical Fuse Size/Circuit Ampacity
MINIMUM CIRCUIT AMPACITY
WARNING
All electrical work, including wire routing and
grounding, must conform to local, state and
national electrical codes.
VOLTAGE
The maximum allowable voltage variation is +/- 10%
of the rated voltage, at start-up (when the electrical
load is the highest).
FUSE/CIRCUIT BREAKER
A separate fuse/circuit breaker must be provided for
each ice machine. Circuit breakers must be H.A.C.R.
rated. (H.A.C.R. rating does not apply in Canada.)
The minimum circuit ampacity is used to help select
the wire size of the electrical supply. (It is NOT the
ice machine’s running amp load.)
The wire size, or gauge, is also dependent upon the
location, materials used, length of run, etc., and
therefore must be determined by a qualified
electrician.
J250 Ice Machines with Power Cord (Cord is 6’ long, with NEMA 5-15P plug configuration.)
These diagrams are not intended to show proper
wire routing, wire sizing, disconnects, etc., only
the correct wire connections.
All electrical work, including wire routing and
grounding, must conform to local, state and
national electrical codes.
Self Contained Ice Machine
115/1/60 or 208-230/1/60
L
1
GROUND
ICE MACHINE
N = 115V
OR
L2 = 208-230
TO SEPARATE
GROUND
L
1
Self Contained Ice Machine
L
208-230/3/60
1
L
2
L
3
GROUND
ICE MACHINE
Self Contained Ice Machine
208-240/1/50
L
1
TO SEPARATE
GROUND
SV1190
L
1
L
2
L
3
L
1
SV1258
GROUND
N
ICE MACHINE
N
GROUND
TO SEPARATE
FUSE/BREAKER.
SV1191
2-8
Section 2Installation References
V
Remote Ice Machine
REMOTE ELECTRICAL CONNECTIONS
WARNING
These diagrams are not intended to show proper
wire routing, wire sizing, disconnects, etc., only
the correct wire connections.
All electrical work, including wire routing and
grounding, must conform to local, state and
national electrical codes.
NOTE: The single circuit condenser should be wired
directly to the ice machine’s electrical panel. The
condenser fan runs only when the ice machine is
operating.
With Single Circuit Model Condenser
208-230/3/60 or 380-415/3/50
L
1
SINGLE
CIRCUIT
REMOTE
CONDENSER
ICE
F
F
L
L
L
2
1
1
2
2
GROUND
NOTE:
FAN MOTOR
IS 208-230
L
1
L
2
Remote Ice Machine
With Single Circuit Model Condenser
115/1/60 or 208-230/1/60
L
F
F
L
L
1
L
2
2
1
1
2
GROUND
GROUND
NOTE:
CONDENSER FAN
MOTOR VOLTAGE
MATCHES ICE MACHINE
N = 115V OR L2 = 208-230V
TO SEPARATE
SINGLE
CIRCUIT
REMOTE
CONDENSER
ICE
L
L
GROUND
SV1255
L
3
GROUND
TO SEPARATE
L
GROUND
3
SV1199
Remote Ice Machine
With Single Circuit Model Condenser
230/1/50
L
1
SINGLE
CIRCUIT
REMOTE
1
2
CONDENSER
ICE
L
2
GROUND
F
2
F
1
L
1
NOTE:
FAN MOTOR IS
220-240 VOLT
L
1
N
GROUND
TO SEPARATE
FUSE/BREAKER (220-240).
N
GROUND
SV1256
2-9
Water Connections and Drains
V
V
V
CAUTION
Plumbing must conform to local and state
codes.
Section 2Installation References
Location
Ice making
water inlet
Ice making
water drain
Condenser
water inlet
Condenser
Water Drain
Water
Temperature
33°F (0.6°C) min.
90°F (32.2°C) max
--1/2” F.P.T.1/2”
33°F (0.6°C) min.
90°F (32.2°C) max
--1/2” F.P.T.1/2”
Water
Pressure
20 psi min.
80 psi max
20 psi min.
150 psi max
Female Pipe Fitting
(F.P.T.)
1
Size
3/8” F.P.T.3/8”
J1300/J1800 - 1/2” F.P.T.
All Others - 3/8” F.P.T.
Bin Drain--3/4” F.P.T.3/4”
1
F.P.T. - Female Pipe Thread
CONDENSER WATER
INLET FITTING
1/2” F.P.T.
CONDENSER WATER
DRAIN FITTING
1/2” F.P.T.
ICE MAKING WATER
INLET TUBING
3/8” MIN. I.D.
CONDENSER WATER
DRAIN TUBING
1/2” MIN. I.D.
CONDENSER WATER
Tube Size Up to Ice
Machine Fitting
INLET TUBING
1/2” MIN. I.D.
BIN DRAIN
FITTING
3/4” F.P.T.
ICE MAKING WATER
INLET FITTING
3/8” F.P.T.
3/4” MIN. I.D.
BIN DRAIN
TUBING
18”
ENT
ICE MAKING WATER
DRAIN FITTING
1/2” F.P.T.
VENT
SLOPE
WATER
SHUT OFF
ALVE
ICE MAKING WATER
DRAIN TUBING
1/2” MIN. I.D.
OPEN, TRAPPED OR
ENTED DRAIN
SV1304
2-10
Section 2Installation References
Cooling Tower Applications(Water-Cooled Models)
A water cooling tower installation does not require
modification of the ice machine. The water regulator
valve for the condenser continues to control the
refrigeration discharge pressure.
It is necessary to know the amount of heat rejection,
and the pressure drop through the condenser and
water valves (inlet and outlet) when using a cooling
tower on an ice machine.
• Water entering the condenser must not exceed
90°F (32.2°C).
• Water flow through the condenser must not
exceed 5 gallons per minute.
• Allow for a pressure drop of 7 psi between the
condenser water inlet and the outlet of the ice
machine.
Each remote ice machines ships from the factory with
a refrigerant charge appropriate for installation with
line sets of up to 50’ (15.25 m). The serial tag on the
ice machine indicates the refrigerant charge.
Additional refrigerant may be required for
installations using line sets between 50’ and 100’
(15.25-30.5 m) long. If additional refrigerant is
required, an additional label located next to the serial
tag states the amount of refrigerant to be added.
Typical Additional Refrigerant Label
IMPORTANT
EPA CERTIFIED TECHNICIANS
If remote line set length i s between 50’ and 100’
(15.25-30.5 m), add 1.5 lb (24 oz) (0.68 kg) of
refrigerant to the nameplate charge.
Tubing length: ____________________________
Refrigerant added to nameplate: ______________
New total refrigerant charge: _________________
If there is no additional label, the nameplate charge is
sufficient for line sets up to 100’ (30.5 m). (See the
chart below.)
Condensers must be mounted horizontally with the
fan motor on top.
Remote condenser installations consist of vertical and
horizontal line set distances between the machine and
the condenser. When combined, they must fit within
approved specifications. The following guidelines,
drawings and calculation methods must be followed
to verify a proper remote condenser installation.
CAUTION
The 60 month compressor warranty (including the
36 month labor replacement warranty) will not
apply if the remote ice machine is not installed
according to specifications.
This warranty also will not apply if the
refrigeration system is modified with a condenser,
heat reclaim device, or other parts or assemblies
not manufactured by Manitowoc Ice Inc, unless
specifically approved in writing by Manitowoc Ice
Inc.
Guidelines for Routing Line Sets
First, cut a 2.5” (63.5 mm) circular hole in the wall or
roof for tubing routing. Connect the line set end with
the 90° bend to the ice machine. Connect the straight
end to the remote condenser.
Then, follow these guidelines when routing the
refrigerant lines. This will help insure proper
performance and service accessibility.
1. Make the service loop in the line sets as shown
below. This permits easy access to the ice
machine for cleaning and service. Do not use hard
rigid copper at this location.
2. Do not form traps in the refrigeration lines
(except the service loop). Refrigerant oil must be
free to drain toward the ice machine or the
condenser. Route excess tubing in a supported
downward horizontal spiral as shown below. Do
not coil tubing vertically.
The ice machine compressor must have the proper oil
return. The receiver is designed to hold a charge
sufficient to operate the ice machine in ambient
temperatures between -20°F (-28.9°C) and 130°F
(54.4°C), with line set lengths of up to 100’ (30.5 m).
Section 2Installation References
Make the following calculations to make sure the line
set layout is within specifications.
1. Insert the measured rise into the formula below.
Multiply by 1.7 to get the calculated rise.
(Example: A condenser located 10 feet above the
ice machine has a calculated rise of 17 feet.)
2. Insert the measured drop into the formula below.
Multiply by 6.6 to get the calculated drop.
(Example. A condenser located 10 feet below the
ice machine has a calculated drop of 66 feet.)
Line Set Rise/Drop
The maximum rise is 35’ (10.7 m).
The maximum drop is 15’ (4.5 m).
CAUTION
If a line set has a rise followed by a drop, another
rise cannot be made. Likewise, if a line set has a
drop followed by a rise, another drop cannot be
made.
3. Insert the measured horizontal distance into the
formula below. No calculation is necessary.
4. Add together the calculated rise, calculated
drop, and horizontal distance to get the total
calculated distance. If this total exceeds 150’
(45.7 m), move the condenser to a new location
and perform the calculations again.
Calculated Line Set Distance
The maximum distance is 150’ (45.7 m).
Line set rises, drops, horizontal runs (or combinations
of these) in excess of the stated maximums will
exceed compressor start-up and design limits. This
will cause poor oil return to the compressor.
Maximum Line Set Distance Formula
Step 1.Measured Rise (35’ [10.7 m] Maximum)______ x 1.7=_______ Calculated Rise
Step 2.Measured Drop (15’ [4.5 m] Maximum)______ x 6.6=_______ Calculated Drop
Step 3.Measured Horizontal Distance (100’ [30.5 m] Maximum)=_______ Horizontal Distance
Step 4.Total Calculated Distance 150’ (45.7 m)=_______ Total Calculated Distance
H
H
H
2-14
R
Combination of a Rise
and a Horizontal Run
D
SV1195SV1196
Combination of a Drop
and a Horizontal Run
R
D
SV1194
Combination of a Rise, a Drop
and a Horizontal Run
Section 2Installation References
SINGLE CIRCUIT
REMOTE
CONDENSER
ELECTRICAL
DISCONNECT
DISCHARGE
LINE
LIQUID
LINE
NOTE:
BORE A 2.5” DIAMETER HOLE IN
THE ROOF OR WALL FOR
TUBING.
SEAL WITH TAR OR PITCH.
SLOPE TO PREVENT ENTRANCE
ELECTRICAL
DISCONNECT
ELECTRICAL
SUPPLY
BIN
ICE
MACHINE
DISCHARGE
REFRIGERANT
LINE
36.00”
DROP
LIQUID
REFRIGERANT
LINE
Typical Single Circuit Remote Condenser Installation
SV1184
2-15
Usage With Non-Manitow oc Multi-Circuit Condensers
Section 2Installation References
WARRANTY
1. The sixty (60) month compressor warranty,
including the thirty-six (36) month labor
replacement warranty, shall not apply when the
remote ice machine is not installed within the
remote specifications outlined in the Installation
Manual.
2. The foregoing warranty shall not apply to any ice
machine installed and/or maintained inconsistent
with the technical instructions provided by
Manitowoc Ice, Inc..
3. Performance may vary from sales specification.
4. J Model ARI certified standard ratings only apply
when used with a Manitowoc remote condenser.
5. Manitowoc ice machines are UL listed with
Manitowoc condensers only.
6. If the design of the condenser meets the
specifications laid out, Manitowoc will only
approve warranty coverage on the Manitowocmanufactured portion of the system.
7. Since Manitowoc does not test the condenser in
conjunction with the ice machine, Manitowoc
will not endorse, recommend, or approve of the
condenser, and will not be responsible for its
performance or reliability.
LINE SET ROUTING AND SIZING
Remote condenser installations consist of vertical and
horizontal line set distances to the condenser that,
when combined, must fit within approved guidelines.
The line set sizing guidelines, drawings, and length
calculation methods must be followed to verify a
proper remote condenser installation. Refer to the
Installation Instructions for specifications for remote
line sets and maximum remote condenser location.
HEAD PRESSURE CONTROL VALVE
Any remote condenser connected to a Manitowoc
J-model ice machine must have a head pressure
control valve (P/N 836809-3), available from
Manitowoc distributors, installed on the condenser
package. Manitowoc will not accept substitute offthe-shelf head pressure control valves.
CAUTION
Do not use a fan cycle control to maintain discharge
pressure. Compressor failure will result.
FAN MOTOR
The condenser fan must be on during the complete
ice machine freeze cycle. Do not cycle with a fan
cycle control.
2-16
The ice machine has a condenser fan motor circuit
designed for use with a Manitowoc condenser. It is
recommended that this circuit be used to control the
condenser fan(s) on the multi-circuit condenser. This
will assure it is on at the proper time.
Do not exceed the rated amps for the fan motor
circuit listed on the ice machine serial tag.
Section 2Installation References
INTERNAL CONDENSER VOLUME
The multi-circuit condenser internal volume must not
be less, nor greater, than that used by Manitowoc.
CAUTION
Do not exceed internal volume and try to add
charge to compensate. Compressor failure will
result.
CONDENSER
∆∆∆∆
T
∆T is the difference in temperature between the
condensing refrigerant and the entering air. The ∆T
should be 15-20°F at the beginning of the freeze
cycle (peak load conditions) and drop to 12-17°F
during the last 75% of the freeze cycle (average load
conditions).
REFRIGERANT CHARGE
Remote ice machines have the serial plate refrigerant
charge (total system charge) located in the ice maker
section. Remote condensers and line sets are supplied
with only a vapor charge.
CAUTION
Never add more than nameplate charge to ice
machine for any reason.
QUICK-CONNECT FITTINGS
The ice machine and the line sets come with quickconnect fittings. It is recommended that matching
quick-connects (available from Manitowoc
distributors) be installed in the multi-circuit
condenser, and a vapor “holding” charge (5 oz.) of
refrigerant be added.