Mandik FDMB, EIS 120, EIS 90 Installation Manual

FIRE damper type FDMB, is in all variants classified:
100
40
100
100
as EN 15650.
Installation in a solid wall construction
Fire damper FDMB Solid wall construction Mortar or gypsum Duct
Installation in a solid wall construction
acc. EN 13501-3 and tested acc. EN 1366-2 and acc.
Fire damper FDMB Solid wall construction Stuffing box (mineral stone wool
min. density 140 kg/m ) Fire protection mastic
min. thickness 1 mm Cement lime plate
min. thickness 15 mm Duct
Installation in a solid wall construction (Weichschott system)
Fire damper FDMB Solid wall construction Fire protection plate of mineral wool Fire protection mastic
min. thickness 1 mm Duct
Hilti CP673 PF Hilti CP673
50
40
D+60 to 800
max. 2050
D+60 to 800
max. 1650
1
Installation in a gypsum wall construction
100
40
Stuffing box (mineral stone wool min. density 140 kg/m )
Cement lime plate min. thickness 15 mm
100
Fire protection plate of mineral wool
100
Fire damper FDMB Mortar or gypsum Fire protection plate of mineral wool Gypsum wall construction Duct
Installation in a gypsum wall construction
Fire damper FDMB Gypsum wall construction Fire protection plate of miner-
al wool
50
40
Installation opening perimeter has to be reinforced by standard drywall profiles.
Installation opening perimeter has to be reinforced by standard drywall profiles.
Fire protection mastic min. thickness 1 mm
Duct
Installation in a gypsum wall construction (Weichschott system)
Fire damper FDMB Gypsum wall construction Fire resistant board
Fire protection mastic min. thickness 1 mm
Duct
Hilti CP673 PF Hilti CP673
2
D+60 to 800
max. 2050
D+60 to 800
max. 1650
Installation opening perimeter has to be reinforced by standard drywall profiles.
Installation in a solid ceiling construction
40
150*
150*
Stuffing box (mineral stone wool min. density 140 kg/m )
Cement lime plate min. thickness 15 mm
40
50
150*
* min. 110 - Concrete/ min. 125 - Aerated Concrete
Fire damper FDMB Solid ceiling construction Mortar or gypsum Duct
Installation in a solid ceiling construction
Fire damper FDMB Solid ceiling construction
* min. 110 - Concrete/ min. 125 - Aerated Concrete
Fire protection mastic min. thickness 1 mm
Duct
Installation in a solid ceiling construction (Weichschott system)
Fire damper FDMB Solid ceiling construction Fire protection plate of
mineral wool Fire protection mastic
min. thickness 1 mm Duct
Hilti CP673 PF Hilti CP673
D+60 to 800
max. 1650
3
* min. 110 - Concrete/ min. 125 - Aerated Concrete
D+60 to 800
max. 2050
Installation in a solid wall construction
100
50*
100
50*
50*
* Around the perimeter
100
Fire protection plate of mineral wool
Fire damper FDMB Solid wall construction Mortar or gypsum Duct
Installation in a solid wall construction
Fire damper FDMB Solid wall construction Stuffing box (mineral stone wool
min. density 140 kg/m ) Fire protection mastic
min. thickness 1 mm Cement lime plate
min. thickness 15 mm Duct
* Around the perimeter
Installation in a solid wall construction (Weichschott system)
Fire damper FDMB Solid wall construction
Fire protection mastic min. thickness 1 mm
Duct
Hilti CP673 PF Hilti CP673
B+60 to 800
max. 2050
A+60 to 800
max. 1650
4
Installation in a gypsum wall construction
100
50*
* Around the perimeter
100
50*
50*
Stuffing box (mineral stone wool min. density 140 kg/m )
Cement lime plate min. thickness 15 mm
* Around the perimeter
100
Fire damper FDMB Mortar or gypsum Fire protection plate of mineral wool Gypsum wall construction Duct
Installation in a gypsum wall construction
Fire damper FDMB Gypsum wall construction Fire protection plate of
mineral wool
Installation opening perimeter has to be reinforced by standard drywall profiles.
Installation opening perimeter has to be reinforced by standard drywall profiles.
Fire protection mastic min. thickness 1 mm
Duct
Installation in a gypsum wall construction (Weichschott system)
Fire damper FDMB Gypsum wall construction Fire resistant board Fire protection plate of mineral wool Fire protection mastic
min. thickness 1 mm Duct
Hilti CP673 PF Hilti CP673
5
B+60 to 800
max. 2050
A+60 to 800
max. 1650
Installation opening perimeter has to be reinforced by standard drywall profiles.