Malm Fireplaces Zircon 30, Zircon 38, Lancer 76 Instruction Manual

Malm Fireplaces, Inc.Malm Fireplaces, Inc.
Malm Fireplaces, Inc.
Malm Fireplaces, Inc.Malm Fireplaces, Inc.
368 Yolanda Avenue
Santa Rosa, Ca 95404
(707) 523-7755 - Fax: (707) 571-8036
Zircon 30
Tested to U/L Standard 737 & 1482
Assembly And Installation Instructions
LEAVE THESE INSTRUCTIONS WITH THE OWNER.
SAFETY NOTICE If this fireplace is not properly installed, a house fire may result. To reduce the risk of fire, follow the installation instructions. Contact local building or fire officials about restrictions and installation inspection requirements in your area.
This stove must be connected to (1) a chimney complying with the require­ments for Type HT chimneys in the Standard for Chimneys, Factory-Built, Residential Type and Building Heating Appliance, UL 103, or (2) a code­approved masonry chimney with a flue liner.
Please read this entire manual before you install and use your new fireplace. Failure to follow instructions may result in property damage, bodily injury, or even death.
DO NOT INSTALL THIS UNIT IN A MOBILE HOME.
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1. Carefully remove all components from the shipping cartons and inspect for damage. If any damage is noted contact the shipping company or your dealer immediately. DO NOT INSTALL THIS UNIT IF DAMAGED OR MISSING PARTS.
2. Protect the flooring near the intended place of installation with an old rug, blanket, or cardboard. Place the firebox on this material.
3. Mix and install the Malmcrete hearth refractory as follows: a. Obtain a sturdy water-tight mixing container such as a wheelbarrow or large wash tub, a bucket or can for
transporting the mixture, a cement trowel, and a source for clean mixing water. It is suggested that the
Malmcrete be mixed outside to avoid spillage or splatters in the dwelling. b. Pour the dry Malmcrete mixture into the mixing container. c. Use 1 quart water for each bag. d. Add 1/2 to 3/4 of the water to the dry mix and mix thourghly. Add additional water in small increments, mixing
throughly between additions. Do not add more water than is necessary to get a somewhat dry mixture; to much
water in the mix may cause the refractory to crack excessively, and will reduce the strength of the refractory.
To test for proper water content, cut vertically into the mixture with the trowel, push the trowel sideways to open
a 3 inch deep by 2 inch wide cut in the mixture, then slide the trowel back up out of the cut. The cut should
stay open with very little "slumping" back into the cut. Next, run the trowel over the surface of the mixture with
the blade at a slight angle to the surface of the mixture, like spreading butter. The mixture should become
relatively smooth with few voids after 6 or 7 passes of the trowel using moderate pressure. Water should not
float to the top of the mixture. e. Transfer the mixture to the hearth (floor) area inside the firebox, spreading the mixture out as it is added. Use
the trowel to spread the mix into the firebox area. Continue to add refractory until there is a minimum of 2 inches
thick over the entire hearth area. To measure the depth of the mix, place a piece of tape 2 inches from the pointed
end of a long nail. Insert the nail vertically through the mix every 6 inches (front to back and side to side) across
the hearth; the mix should come to a uniform height up the nail, at or slightly above the tape. Trowel in the nail
holes when completed.
f. Allow the mix to cure at least 48 hours. Additional curing time is necessary in cool temperatures. The longer
Malmcrete is allowed to cure before the first fire is lit, the stronger and more durable it will become.
g. Make the first 3 or 4 fires very small and of short duration to allow the refractory to adjust to the high temperature
of a fire.
Hearth Requirements
A floor protector is required to protect the floor in front of the fireplace opening from sparks. The floor protector must be a minimum of 3/8 inch thick non-combustible material such as brick, concrete, slate, ceramic tile, or a listed floor protection board such as Wonderboard or Homosote.
The floor protector must extend a minimum of 16 inches in front of the fireplace opening and 8 inches to either side of the fireplace. The Zircon has been designed to provide floor protection allowing for flexible design of the hearth setting.
Clearance to Combustibles
The Zircon requires a clearance to combustible walls of 16" measured from the back of the unit. For locating the center of the chimney the measurement is 22 1/2" from the backwall and 47" to the sidewall. See figure 1, page 3. For corner installation the center of the chimney is 27". See figure 2, page 3.
Clearance to Non-combustibles
The Zircon clearance to a combustible wall may be reduced with proper wall protection. Accepted methods for wall protection would allow reduction of the wall clearances. For appearance if desired a non-combustible wall covering can placed on the wall. The covering should consist of a listed wall protection board installed to the manufacturer's specifications. Approved protection boards at the time of this publication are Wonderboard, Dura Rock and Homosote. A non-combustible material can then be placed over the wall protection board. With most of the protection boards the clearance can be reduced to 8 inches from the original combustible wall. Be certain to check with your local building officials and or fire inspector for accepted methods in your area. Refer to NFPA 211.
Page - 2
CLEARANCES
SIDEWALL AND BACKWALL INSTALLATION
Unit to Sidewall ----------------------------------- 32" Unit to Backwall----------------------------------- 16" Connector to Sidewall ---------------------- 43 1/2" Center of Connector to Sidewall -------------- 47" Connector to Backwall -------------------------- 18" Center of connector to Backwall --------- 21 1/2"
!
#
46"
$
16"
"
CORNER INSTALLATION
Unit to Adjacent Wall ------------------------------ 16" Connector to Adjacent Wall ----------------- 23 1/2" Center of Connector to Adjacent Wall --------- 27"
Minimum Hearth Size -----------------46" x 30 1/2"
Hearth is not required to extend under the Zircon's base.
#
#
#
$
32"
#
8"
$
43 1/2"
$
!
16"
"
!
18"
"
#
Figure 1
Hearth dimensions shown are minimum requirements. It may be desired to exceede these minimum dimensions for a more decorative installation. The hearth material must be 3/8" or thicker noncombustible material. It is not required for the hearth material to extend under the base of the fireplace.
$
16"
30 1/2"
$
!
23 1/2"
"
Figure 2
!
16"
"
Page - 3