Malm Fireplaces Imperial Carousel Instruction Manual

MALM FIREPLACES, INC.
368 YOLANDA AVE, SANTA ROSA, CA. 95404
707 523-7755 - 800 535-8955 - FAX: (707) 571-8036
Imperial Carousel
ASSEMBLY AND INSTALLATION INSTRUCTIONS
Listed by Lab Test
Tested to U/L Standard 737 & ULC-S627-00
SAFETY NOTICE If this fi replace is not properly installed, a house fi re may result. To reduce the risk of fi re, follow the installation instructions. Contact local building or fi re offi cials about restrictions and instal­lation inspection requirements in your area.
Please read this entire manual before you install and use your new fi replace. Failure to follow instructions may result in property damage, bodily injury, or even death.
DO NOT INSTALL THIS UNIT IN A MOBILE HOME.
1. Carefully remove all components from the shipping cartons and inspect for damage. If any damage is noted contact the shipping company or your dealer immediately. DO
NOT INSTALL THIS UNIT IF DAMAGED OR MISSING PARTS.
2. Protect the fl ooring near the intended place of installation with an old rug, blanket, or cardboard. Place the fi rebox on this material.
3. Mix and install the Malmcrete hearth refractory as follows:
a. Obtain a sturdy water-tight mixing container such as a
wheelbarrow or large wash tub, a bucket or can for trans­porting the mixture, a cement trowel, and a source for clean mixing water. It is suggested that the Malmcrete be mixed outside to avoid spillage or splatters in the dwell-
ing. b. Pour the dry Malmcrete mixture into the mixing container. c. Use 1 quart water for each bag. d. Add 1/2 to 3/4 of the water to the dry mix and mix
thourghly. Add additional water in small increments, mix-
ing throughly between additions. Do not add more water
than is necessary to get a somewhat dry mixture; to
much water in the mix may cause the refractory to crack
excessively, and will reduce the strength of the refrac-
tory. To test for proper water content, cut vertically into
the mixture with the trowel, push the trowel sideways
to open a 3 inch deep by 2 inch wide cut in the mixture,
then slide the trowel back up out of the cut. The cut
should stay open with very little "slumping" back into the
cut. Next, run the trowel over the surface of the mixture
with the blade at a slight angle to the surface of the mix-
ture, like spreading butter. The mixture should become
relatively smooth with few voids after 6 or 7 passes of the trowel using moderate pressure. Water should not fl oat to the top of the mixture.
e. Transfer the mixture to the hearth (fl oor) area inside the
fi rebox, spreading the mixture out as it is added. Use the trowel to spread the mix into the fi rebox area. Continue to add refractory until there is a minimum of 2 inches thick over the entire hearth area. To measure the depth of the mix, place a piece of tape 2 inches from the pointed end of a long nail. Insert the nail vertically through the mix every 6 inches (front to back and side to side) across the hearth; the mix should come to a uniform height up the nail, at or slightly above the tape. Trowel in the nail holes when completed.
Shape the refractory
to the contour of the Imperial hearth. If the refractory will not stay in place wait untill the refractory has set slightly. Check the refractory every few minutes to see if it has set enough to stay in place.
f. Allow the mix to cure at least 48 hours. Additional cur-
ing time is necessary in cool temperatures. The longer Malmcrete is allowed to cure before the fi rst fi re is lit, the stronger and more durable it will become.
g. Make the fi rst 3 or 4 fi res very small and of short dura-
tion to allow the refractory to adjust to the high tempera­ture of a fi re.
Refractory
2"
Glass Installation
Wear eye protection during the assembly of
this unit. Check all glass and parts for dam­age. Replace any damaged parts prior to continuing the installation. Do not assemble this unit with any damaged parts. If you should happen to break a glass panel, it must only be replaced with ceramic glass.
Your Malm Carousel is supplied with Ceramic
High temperature glass. Side pannels are
10” x 14 ½ “ polish edge ceramic glass.
The door glass is 13 1/16 x 14 9/16 ceramic glass. Replacement pannels are available through Malm dealers are directly from Malm.
1. The door panel has had the latch assembly and hinges installed at the factory. Remove the hinges leaving the glued on plate in po­sition.
2. Place the lower hinge in the hole in the fi re­bowl, with the washer under it.
3. Insert the upper hinge into the hole at the top of the door opening. Holding the upper hinge in place, slide the glass door panel into the hinges.
7. First loosen the glass retainers. This is a metal strip secured by one screw in the mid­dle. Start with the left door panel. The gasket must be on the right side of the panel.
8. Slide the gasketed edge completely into the channel on the side of the door. The left edge of the glass should now fi t into the button at the bottom of the glass.
9. Lower the glass into the lower glass clip.
10. Repeat steps 8 and 9 with the right door panel. The gasket will be on the left side of the panel with the not polished edge at the top.
11. The remaining panels can now be installed. The edge that is not polished is placed at the top. As each panel is installed replace the glass retainer in place but do not tighten.
12. After all the glass panels are installed center the panels to reduce any gaps that may be between the glass panels.
13.Tighten the glass retainers.
4. Hold the door panel in the closed position to allow access to the hinge screws.
5. Maintaining a 1/8" clearance to the left door post, tighten the screws in the hinges snug­ly.
DO NOT OVER TIGHTEN. Re-adjust as
necessary for proper alignment.
6. Note that two panels have gasket material on one edge. These pieces go on either side of the door. Make certain that these two pieces are placed completly into the channel on either side of the door. Failure to do this will make the rest of the glass installation impossible.
Imperial Carousel - Page 2
Retainer and Screw
Glass
Lower Glass Button
Hood
Upper Glass Channel
Clearance to Combustibles
The Imperial requires a clearance to combustible walls of 24" measured from the back of the unit. For locating the center of the chimney the measurement is 45" from the backwall and 45" to the sidewall. See fi gure 1, page 2. For corner installation the center of the chimney is 45". See fi gure 2, page 2.
Clearance to Non-combustibles
The Imperial clearance to a combustible wall may be reduced with proper wall protection. Accepted methods for wall protection would allow reduction of the wall clearances. For appearance if desired a non-combustible wall covering can placed on the wall. The covering should consist of a listed wall protection board installed to the manufacturer's specifi cations. Approved protection boards at the time of this publication are Wonder­board, Dura Rock and Homosote. A non-combustible material can then be placed over the wall protection board. With most of the protection boards the clearance can be reducedby 2/3 from the original combustible wall. Be certain to check with your local building offi cials and or fi re inspector for accepted methods in your area.
Chimney System
Connector Pipe
Unit
SIDEWALL AND BACKWALL INSTALLATION Unit to Sidewall ------------------------------------------24" Unit to Backwall -----------------------------------------24" Connector to Sidewall ---------------------------------41" Center of Connector to Sidewall --------------------45" Connector to Backwall ---------------------------------41" Center of connector to Backwall --------------------45"
41"
24"
CORNER INSTALLATION Unit to Adjacent Walll ----------------------------------24" Connector to Adjacent Wall --------------------------41" Center of Connector to Adjacent Wall -------------45" Minimum Hearth Size -------------------------- 48" x 54" Or a Diameter of ----------------------------------------54"
41"
24"
Figure 2.
Figure 1.
Hearth dimensions shown are minimum requirements. It may be desired to exceede these minimum dimensions for a more decorative installation.
Imperial Carousel - Page 3
Hearth Requirements
A fl oor protector is required to protect the fl oor in front of the fi replace opening from sparks. The fl oor protector must be a minimum of 2 1/2 inch thick com­mon solid brick over 26 gauge sheet metal or equivalent.
54"
48"
16"
Door
Fire Bowl
16" From Door
8"
The fl oor protector must extend a minimum of 16 inches in front of the fi replace opening and 8 inches to either side of the fi replace and 8 inches behind the back of the unit. Refer to Figure #3.
8"
8"
Hood Assembly
Position the hood on the basic unit. Secure hood to basic unit using the 13 sheet metal screws provided.
IMPORTANT: Failure to install these screws will result in permanet damage to the unit and void the warranty.
Hood
Sheet Metal Screws 13- 14 x 1/2 Hex.
Basic Unit
All Screws Must Be Installed
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
This stove must be connected to (1) a chimney com­plying with the requirements for Type HT chimneys in the Standard for Chimneys, Factory-Built, Residential Type and Building Heating Appliance, UL 103, or (2) a
code-approved masonry chimney with a fl ue liner.
Chimney Connector Installation
It is required to install a 8 inch all-fuel class "A" chim­ney system prior to the chimney connector installa­tion. The connector pipe included with the Imperial is 1 - 8" x 30" starter pipe, and 1 - 8" x 30" slip connec­tor. The slip connector is identifi ed by 3 holes at the top of the pipe. The slip connector has one fl air at the top with the 3 holes. The bottom is smooth. The starter pipe section has fl airings at both ends. The male end is always at the bottom.
8"
Figure 3
8"
54" Diameter Circle Hearth. 8" Minimum is measured from the fi re-box
8"
Simpson Dura-Vent Chimney System
It is required to use a Dura-Vent Universal Connector part number 8DVL-ADC or 8878 Adapter to install the chimney connector.
1. The universal connector is installed into the support box. The 8" x 30" slip pipe is then connected to the universal connector.
2. The 8" x 30" starter pipe section is then slid over the slip connector pipe. Slide the 30 inch pipe over the slip pipe only far enough as necessary to facilitate installation of the 8" x 30" starter pipe in to the unit.
3. There must be a minimum of 2 inches of overlap be­tween the 8" x 30" and 8" x 30" slip connector pipe.
Metalbestos or Security ICC EXCEL
When using Metalbestos or Security chimney systems it is required to use the Metalbestos DS-CPA Single Wall Conector pipe. Security users must use the EX adapter.
1. Installation of the Metalbestos DS-CPA or the Secu­rity EX adapter must be done fi rst.
2. Attach the 8" x 30" slip connector to the DS-CPA or EX adapter with 3 - #8 x 3/8 inch screws.
3. The 8" x 30" starter pipe section is then slid into the slip connector pipe. Slide the 30 inch pipe into the slip pipe only far enough as necessary to facilitate installation of the 8" x 30" starter pipe into the unit.
4. Slide the 8" x 30" pipe down onto the Imperial.
5. There must be a minimum of 2 inches of overlap be­tween the 8" x 30" and 8" x 30" slip connector pipe.
Other Chimney Systems
There are many other manufacturer's of chimney sys­tems. It is beyond the scope of this publication to cover installation with all of the diff erent systems available. Most systems have a method of connection to the Impe­rial's connector pipe. Confi rm installation procedures with your dealer or the manufacturer of the chimney system you have purchased.
Imperial Carousel - Page 4
Insulated Class "A" Chimney System
Insulated Pipe
Ceiling
Single Wall Chimney Adapter
Slip Connector. Sheet Metal Screw to Chim­ney Connector.
Starter Section Fits Into Hood
Hood
Support Box
Sheet Metal
Screw
Slip Connector
DuraVent 8DVL-ADC or 8878 Adapter ICC Excel Flue Extension (8EX) Selkirk Stovepipe Adaptor Or Single Wall Chimney Adapter
ADAPTER NOT INCLUDED
DuraVent 8878
ICC Excel 8EX
Malm connector pipe is designed to fi t together without requireing fastners between the connector sections.
The above illustration represents the installation procedure for dripless pipe installation. This installa­tion method of installing the connector pipe with the male end down allows for any moisture to remain on the inside of the connector pipe.
IMPORTANT: THE SINGLE WALL CONNECTOR PIPE MUST NEVER PASS THROUGH A COMBUSTIBLE CEILING OR WALL.
At fi rst glance you may become concerned that smoke will escape the pipe and enter the room. This is not how the system will work. The vacum in the chimney system will always pull air into the chim­ney. If you experience a downdraft with your installation it indicates that additional chimney height or a specialty draft cap be added to your chimney system. Contact your dealer for further information regarding downdrafts.
Do not use a damper with your Carousel. The use of damper will most likely do damage to your unit. It may cause the ceramic glass to soot up and void any warranty.
Imperial Carousel - Page 5
Loading...
+ 11 hidden pages