Mallory PSU Application Guide

Page 1
Type PSU Motor Start CapacitorsApplication Guide
VOLTAGE RATING
The capacitors's rated voltage must be greater than or equal to the average voltage across the capacitor' s terminals during the mo­tor starting cycle. This is not the same voltage as the motor line voltage. In addition, the cutoff voltage rating of the capaci­tor must be greater than or equal to the maximum voltage attained across the terminals of the capacitor in actual service.
dard voltage ratings are as follows:
Rated Maximum
Voltage (rms) Cut-Off Voltage (rms)
125 160 165 210 250 300 330 400
These ratings are based on the maximum capacitor temperature of 65 ºC.
CAPACITANCE RATING
The capacitance is chosen to give the necessary starting torque to the motor. The minimum capacitance value is the minimum de­signed capacitance. The maximum capacitance is 20% more than the minimum value.
Duty Cycles of Type II
Table A
Rate d
Voltag
V
(rm s
125
165
250
330
Typical life expectancy is 50,000 cycles for 125V ratings, and 40,000 total cycles for 165, 250 and 330V ratings. The number of cycles shown in the table above are for the convenient test time of 35 days
total for all ratings.
Capacitance
Rating (µF)
e
AC
From To
)
21-25 81-106 0.75 29.25 2.500 50,000 108-130 145-174 1 59 1.670 50,000 161-193 233-280 1 89 1.110 33,500 243-292 378-454 1 119 0.833 25,000 400-480 590-708 1 179 0.556 16,500 645-774 800-960 1 239 0.417 12,500
21-25 88-106 1 59 1.670 33,500 108-130 124-149 1 89 1.110 33,500 130-156 216-259 1 119 0.833 25,000 233-280 340-408 1 179 0.556 16,500 378-454 590-708 1 239 0.417 12,500
21-25 30-36 1 59 1.670 33,500
36-43 64-77 1 89 1.110 33,500
72-86 88-106 1 119 0.833 25,000 108-130 189-227 1 179 0.556 16,500 216-259 324-389 1 239 0.417 12,500
21-25 21-25 1 59 1.670 33,500
25-36 30-36 1 89 1.110 33,500
36-43 64-77 1 119 0.833 25,000
72-86 88-106 1 179 0.556 16,500 108-130 130-156 1 239 0.417 12,500
Duty Cycle
Secs.
Secs.
(On )
(Off)
Duty
Cycle
%
#
of
Starts
DUTY CYCLE
The duty cycle should be calculated for each application. It is the ratio of the time the capacitor is on voltage to the total time of one cycle. The duty cycles for the normal performance of standard Type II capacitors are listed in Table A. CDE type PSU capacitors may be
used in any intermittant application within their temperature and voltage range where the duty cycle does not exceed that listed in Table
A. This is in accordance with the standards in EIA Specification RS-463 for Type II capacitors. If a particular application exceeds the normal duty cycle, but does not exceed the values listed in Table B, an extra performance or Type I capacitor is required.
FREQUENCY
These capacitors are designed for 60 Hz application but may
be operated in the range of 47 Hz - 60 Hz without damage provided voltage limitations stated above are observed. For other variations in frequency, contact CDE.
Duty Cycles of Type I
Table B
Rate d
Voltag
V
(rm s
125 165 250 330
If an application exceeds the duty cycles of Type I, other methods of capacitor selection must be used. Contact CDE, for Engineering
assistance.
e
AC
)
Capacitance
Rating (µF)
all all all all
MOUNTING
Vertical mounting of the capacitor with the terminals up is recommended. However, horizontal mounting is
acceptable providing the vent is in the upward position. Vertical mounting with the terminals down is not recommended because the capacitor life may be reduced.
Duty Cycle %
Secs.
(On )
0.75 29.25 2.500 75,000 1 59 1.670 40,000 1 59 1.670 40,000 1 59 1.670 40,000
Secs.
(Off)
Duty
Cycle
#
of
Starts
CDE Cornell Dubilier•1605 E. Rodney French Blvd.•New Bedford, MA 02744•Ph: (508)996-8561•Fax: (508)996-3830• www.cde.com