2 FEATURES ......................................................................................................................................................................... 7
3.5.1 Communication Port ...................................................................................................................................... 16
3.5.2 EPO Port .............................................................................................................................................................. 17
4 PANEL FUNCTION and OPERATION ................................................................................................................... 20
4.1 Keys Function ....................................................................................................................................................... 20
4.2 LED Function .................................................................................................................................................... 21
4.3 LCD Display Function .................................................................................................................................... 21
4.4 Single UPS Turn On/Off Operation .......................................................................................................... 23
4.4.1 Turn On Operation ...................................................................................................................................... 23
4.4.2 Turn Off Operation ..................................................................................................................................... 23
4.5 Single UPS Self-Test/Mute Test Operation ........................................................................................... 24
4.6 Single UPS Panel Function Setting ........................................................................................................... 24
4.6.3 Output Voltage Setting .............................................................................................................................. 25
4
POWERPACK SE SERIES 6-20 kVACONTENTS
4.6.4 Low Battery Voltage Shutdown Point Setting ................................................................................. 26
4.6.5 Frequency Converter Mode Setting ..................................................................................................... 27
4.6.6 Output Frequency Setting in CUCF Mode .......................................................................................... 28
4.6.6 ID Setting ........................................................................................................................................................ 28
5.2 Line Mode ............................................................................................................................................................... 31
8.1 Terms of Guarantee ............................................................................................................................................ 41
8.2 Cases Not Covered by the Guarantee .......................................................................................................... 42
9 CONTACT INFORMATION ........................................................................................................................................ 45
5
1 SAFETY INSTRUCTIONS
1.1 UPS Safety Instructions
Before applying the UPS system, Please read through all safety information and operating
instructions carefully. It’s recommended to save this manual properly for future reading.
Do not install the UPS system near the water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near the heater.
Place the UPS staying away from the wall for some distances, ensure enough space on each side
of UPS, do not block ventilation holes in the UPS housing. Install it by following the instructions
in the manual.
Please do not open the UPS case as you will, there is a high risk of electric shocks inside.
Do not connect to the equipment like hair dryer or electric heater, to ensure the safety for the
UPS.
Do not use liquid extinguisher if there is a fire, a dry powder extinguisher is recommended.
Attention:
UPS has high voltage inside, for personal safety, please do not repair by yourself. If any
questions, please contact local service center or dealer.
1.2 Battery Safety Instructions
Battery life cycle will be shortened as environment temperature rise. Replacing battery
periodically can help to keep UPS in normal state and assure backup time required.
Battery replacement should be done by authorized technician. If you want to replace the
battery cable, please purchase it from our local service center or distributors to avoid fever and
lighter which can cause fire from inadequate power capacity.
Batteries may cause electric shocks and have a high short-circuit current, for human being
safety, please follow the specifications as below when replace the batteries:
o Remove wristwatches, rings and other metal objects
o Use only tools with insulated grips and handles
o Wear insulated shoes and gloves
o Do not put the metal tools or parts on the battery
o Before disconnecting the terminals on battery, please cut off all the loads to battery first.
Do not dispose of the batteries with fire so as to avoid explosion.
Don’t open the battery, electrolyte inside will do harm to eyes and skin. Please use plenty of
clean water to wash if touching and go to see a doctor.
Do not connect the positive pole and negative pole directly, otherwise it cause electric shocks
or will be on fire.
The battery circuit is not isolated from the input voltage, high voltage may occur between the
battery terminals and ground, before touching, please verify no voltage is present.
Open the UPS package, please check the enclosed accessories including user manual, RS232 communication cable, USB cable and CD-ROM.
Check the UPS if anything damaged in transport. If find something damaged or parts missing, do not power on, please turn to the carrier and dealer.
To determine whether this UPS is the model you want to buy. Check the model name showed both on the front panel and rear panel of UPS to confirm.
Model Type
SE906S 6KVA Standard model
SE906H 6KVA Long backup model
SE9010S 10KVA Standard model
SE9010H 10KVA Long backup model
SE9015H 15KVA Long backup model
SE9020H 20KVA Long backup model
NOTE
Please save the packaging box and packaging materials for future transport use. As a heavy
product, please transit the UPS with care.
1. The UPS installation environment must be with good ventilation, away from water,
flammable gases and corrosive entities.
2. Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel air outtake hole will be unobstructed.
3. The peripheral environment temperature around the UPS should be within 0 ℃ ~ 40 ℃.
4. If dismantling the machine at low temperatures, there may be condensation droplets, users
can not install or operate it before UPS completely got dry both inside and outside,
otherwise there will be danger of electric shocks.
5. Place the UPS near the mains socket so that can cut off AC mains without any delay at any
emergent case.
6. Make sure the load connect to the UPS is off when users connect the load to UPS, and then turn on the load one by one later.
7. Please connect the UPS with the socket which is over-current protected. Do not connect the UPS with the socket which rated current is less than the Maximum input current of the UPS.
8. All the power socket should be configured with earthing device for safety.
9. UPS could be electrified or powered no matter the input power cable is tied or not, even
when the UPS is off. The only way to cut off the output is switching off the UPS and
disconnecting the mains power supply.
10. For all standard type UPS, it is advised to charge the battery over 8 hours before used. Once the AC mains power energizes the UPS, it will automatically charge the battery. Without
prior charging, UPS output remains as usual but with shorter back-up time than normal.
11. When connected to motor, display equipment, laser printer etc, UPS power selection should be based on the startup power of the load which is usually twice as rated power.
12. When wiring, please ensure input cables and output cables are connected firmly.
13. If install a leakage current protective switch, please install it on output cable.
14. For EA900II 6-20K Series UPS, before installing, prepare wires for terminal block of the UPS based on the following tables.
When connecting, please make sure to connect input cables and output cables with terminals
firmly. When the input is three-phase, if the UPS is working on Bypass mode, the total current
goes through phase R, so the line widths of phase R must be the same as output. When the input
is single-phase, before doing input connection, users have to use two short wires to connect R&S
and S&T.
3.2 Output Connection
Output connection is configured with terminal blocks. Make sure the mains wire and breakers in
the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or
fire.
NOTE
Do not use the wall receptacle as the input power source for the UPS, which rated current is less
than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
INPUT
ABCN
OUTPUT
LN
BATTERY
++
INPUT
--
ABCN
OUTPUT
LN
a. 6KVA &10KVA Long back up terminal blocks b. 6KVA &10KVA Standard type terminal blocks
Only 6-20K UPS and containing parallel ports can do parallel operation, other types is not
supported.
N+X parallel structure is the most reliable power supply structure at present, N stands for the
minimum number of UPS for the load, X stands for the number of redundant UPS,X absolutely
means how many UPS could be malfunctioning at the same time and the parallel UPS system is
still steady. The larger X is, the system is more reliable. N+X is the best method for high
reliability. Just install a little more simple accessories, at most 8 UPS could work together to form
a flexible parallel system.
This structure of power supply system increases the power safety and reliability. For example,
two single UPS make up a parallel system to load averagely, when one is malfunctioning, another
one can take all the load independently. It allows isolation repairs for malfunctioning UPS, and
according to users own different requirements, every single UPS could install manual
maintenance bypass switch.
3.3.1 Parallel System Installation
The function of parallel operation is an optional function of UPS, users can purchase parallel
function parts (including parallel card and parallel wire) and contact service personnel to install.
At most 8 UPS work together by using parallel wires to form a flexible parallel system. Each UPS
should be equipped individual battery pack.
>Parallel system installation requirement:
1. Install parallel wire, users need to purchase a specific parallel wire from our company, it’s not
recommended to use other type parallel wires. There are 2m length and 5m length to be
chosen.
2. Prepare wires for terminal block of the UPS based on the wiring spec table above in attention
items.
3. Each UPS input wiring please comply with the requirements of single UPS wiring.
4. Every UPS is recommended to connect together to one common utility power terminal block.
5. The output cables of each UPS are recommended to connect together on a common terminal
block, then output to the load.
6. Each UPS should be equipped individual battery pack.
7. Wiring installation for parallel UPS system please refer to the wiring diagrams are given
below, switches of 6KVA should withstand more than 50A/250VAC, and switches of 10KVA
should withstand more than 80A/250VAC, and switches of 15KVA should withstand more
than 100A/250VAC, and switches of 20KVA should withstand more than125A/250VAC.
8. Output wiring length requirements: when the distance between the load and each UPS is less than 20 meters, the length difference of cables to the load should be less than 20%; when the
distance between the load and each UPS is more than 20 meters, the length difference of
cables to the load should be less than 10%.
① Install parallel wires. Two UPS to form an UPS parallel system, in order to ensure the
reliability of the parallel system, there is only one way to wire two UPS, use two parallel wires to
connect two UPS like the diagram showing below, connection looks like a circle. If three or more
than three UPS are needed, the connection is similar, you can refer to the diagram as below. How
many UPS unit, how many parallel wires you need.
INTELLIGENT SLOT
EPO
EPO
RS232
RS232
PARALLEL PORT
PARALLEL PORT
INTELLIGENT SLOT
USB
USB
BAT_NTC
BAT_NTC
EPO
EPO
PARALLEL PORT
PARALLEL PORT
RS232
RS232
INTELLIGENT SLOT
INTELLIGENT SLOT
USB
USB
BAT_NTC
BAT_NTC
INPUT BREAKER
ON
OFF
ON
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
INPUT BREAKER
ON
OFF
ON
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTI AL
BEFORE CONNECTING SUPPLY
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
Parallel system of two UPS wiring
INTELLIGENT SLOT
USB
USB
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
INTELLIGENT SLOT
BAT_NTC
BAT_NTC
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
EPO
EPO
RS232
RS232
PARALLEL PORT
PARALLEL PORT
INPUT BREAKER
ON
OFF
EPO
EPO
RS232
RS232
PARALLEL PORT
PARALLEL PORT
INPUT BREAKER
ON
OFF
USB
USB
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
INTELLIGENT SLOT
INTELLIGENT SLOT
BAT_NTC
BAT_NTC
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
INTELLIGENT SLOT
USB
USB
WARNING
HIGH LEAKAGE CURRENT
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
BEFORE CONNECTING SUPPLY
INTELLIGENT SLOT
BAT_NTC
BAT_NTC
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
EPO
EPO
RS232
RS232
PARALLEL PORT
PARALLEL PORT
INPUT BREAKER
ON
OFF
Parallel system of three UPS wiring
Caution
For three UPS parallel system or more than three unites system type, please remove the short
pin CN3 on the parallel card as following pictures, Only keep the first unit and the last unit shot
pin(CN3) connected and remove the rest ones. Open the UPS cover, find the parallel card, it’s
installed on the rear panel. Take off the short pin CN3, then screw the cover back. It’s advisable
to contact to local dealer to operate, if you have to operate by yourself, please be sure that you
have cut off all the electrical connection, be careful the electric shocks from the UPS inside.
②Connect output cables of all UPS together to a common terminal block.
③Connect input cables of all UPS together to one common utility power terminal block.
④ If the UPS is the standard type, each UPS has batteries inside already. If the UPS is the longrun type, each UPS should be equipped a individual battery pack.
⑤ After installation, check all the wiring carefully, be sure to conirm correct, then can operate
the system.
3.3.2 Parallel System Operation and Maintenance
General operation of parallel system, please refer to the operation instruction of single UPS.
Before starting the system, need to set up different ID for each UPS, specific settings please refer
to the instruction of ID setting which is given in single UPS panel function setting.
>Turn on the parallel system
Start the system with mains power: After inputting the mains power,turn on any one UPS of
system, others will start by themself at same time. All UPS will enter into Line mode.
Start the system without mains power: Make sure the battery pack is connected well and the
breaker is in “ON” position. There are two ways to start the UPS parallel system without utility
power supply:
A: Press the key on each UPS, make each LCD of each UPS light up, then turn on any one
UPS of system, others will start by themself at same time. All UPS will enter into BAT mode.
B: Turn on UPS one by one.
Hold on the OFF KEY of any one UPS of system for more than 4 seconds, it would turn off the
whole parallel system. Hold on the OFF KEY of any one UPS of system for more than 1
second(less than 4 seconds), it would turn off single UPS you choose, of course if you need to
turn on it again or turn on any other single UPS of the system, just press ON KEY of that UPS to
start it.
>Parallel system maintenance
Parallel system maintenance please follow the maintenance of single UPS.
If one UPS of parallel system is malfunctioning, first of all, turn off the malfunctioning UPS, then
cut off the input power to the faulty UPS and disconnect the output of faulty UPS to the parallel
system, make sure that there is no electrical connection with malfunctioning UPS, after all of
those, it’s safe to do operation.
3.4 External Battery Connection Procedure for Long Back up Type
For different UPS type, users are instructed to configure different battery voltage as below sheet. More or less units are forbidden, or else something abnormal or faulty will appear.
There are two battery pack options for UPS, 16 units and 20 units. Users can choose the
different battery pack voltage in accordance with different requirements. The default units of
batteries to UPS is 16, and users can not connect 16 batteries to UPS if the UPS should be
connected 20 units. Please strictly follow the procedure of batteries connection, or will get
electric shocks.
1. Set the battery switch at ‘OFF’ position, then install batteries in series.
2. Connecting the cables to batteries firstly, or you may get electric shocks if you connect the
cables to UPS firstly. You’d better connect the red cable to battery positive pole ‘+’, black to
negative pole ‘-’, so that it would be much easier to distinguish.
3. Select proper cables to connect the batteries and UPS is very important, and there should be a
switch connected between the battery pack and UPS.
4. Finally, without any load, set on the battery switch which is connected between the UPS and
the battery pack, so that UPS can get connected to batteries, then switch in the mains power,
after doing all of those, the batteries will be charged by the UPS automatically.
Users could monitor the UPS system through the communication port such as standard RS232
port and standard USB port with computer. With a communication wire to connect UPS and
computer, could simply achieve UPS management.
EPO is short for Emergency Power Off, EPO port is on rear panel of UPS, it’s green, in some
emergent cases, users could cut off the output of UPS immediately by operating EPO port. Wiring
diagram as below:
Normally, pin1 and pin2 are connected so that the machine can be working normally. When
some emergencies happen, and when users do have to cut off the output, just need to disconnect
the connection between pin1 and pin2, or there is a anther useful simple way is pulling it out.
3.5.2 Intelligent Card (Option)
This series High frequency online UPS supply a intelligent slot on rear panel, it’s for SNMP card,
dry contact and USB card, users could insert any type intelligent card from those three into it to
monitor and manager the UPS. You don’t have to turn off the UPS when you install the intelligent
card. Procedure as following:
Fist of all, remove the intelligent slot cover;
Then insert the intelligent card(SNMP card, dry contact or USB card);
Last, screw the intelligent card back.
> SNMP card (option)
SNMP card on UPS is compatible with the most software, hardware and network operating
system, it is a network management of UPS, with this function, UPS can login on internet , which
can supply information of UPS status and input power, and even possible to control UPS via net
management system.
> Dry contact card (option)
Insert the dry contact card into the intelligent slot, it’s another type function of intelligent
monitoring.
The operation is simple, operators only need to read the manual and follow the operation
instructions listed in this manual without any special training.
4.1 Keys Function
※ ON KEY (+)
Press and hold the two keys for more than half a second to turn on the UPS.
※ OFF KEY (+)
Press and hold the two keys for more than half a second to turn off the UPS.
※ TEST/MUTE KEY (+)
Press and hold the two keys for more than 1 second in Line mode or ECO mode or CUCF mode:
UPS runs the self-test function.
Press and hold the two keys for more than 1 second in battery mode: UPS runs the mute
function.
※ INQUIRING KEY (,)
Non-function setting mode:
Press and hold or for more than half a second (less than 2 seconds): display the items
orderly.
Press and hold for more than 2 seconds: Circularly and orderly display the items every 2
seconds, when press and hold the key for some time again, it will turn to output status.
Function setting mode:
Press and hold the key or for more than half a second (less than 2 seconds): Select the
set option.
A. The top diagram is for load and battery capacity indication, each grid of which represents
25%. When UPS is over load, the load light will blink the same as the battery light blink when
the capacity of battery get low or battery disconnected.
B. The fan icon is for fan working indication; when fan normally runs, the icon will display rotation; if the fan is not connected or faulty, the icon blinks;
C. Press the mute button under the battery mode, buzzer icon will blink; it will disappear in other cases.
D. Fault icon will be on when UPS is in fault mode, otherwise it will not.
※ Digital display area:
A. Under none setting mode, it will display UPS output information when UPS normally runs in
AC mode; other information like input, battery, load and temperature will be showed after
pressing the inquiring key; Fault code will be told in fault mode.
B. Under setting mode, users could adjust different output voltage, activate ECO mode, activate
CUCF mode, select an ID number and so on by operating function setting key and inquiring
keys.
※ Mode display area:
A. This area will display the power capacity of the machine after starting the UPS within 20
seconds.
B. After over 20 seconds, this area will display the working mode of the machine. Such as
STDBY(standby Mode), BYPASS(Bypass Mode), LINE(AC Mode), BAT(Battery Mode),
BATT(Battery Self Test Mode ), ECO(Economic mode), SHUTDN(Shutdown mode),
CUCF(Constant Voltage and Constant Frequency Mode).
1. Once mains power is plugged in, the UPS will charge the battery, at the moment, LCD
shows that the output voltage is 0, which means UPS has no output as default condition. If it is
expected to have output of bypass, you can set the BPS “ON” by LCD setting menu.
2. Press and hold the ON key for more than half a second to start the UPS, then it will start
the inverter.
3. Once started, the UPS will perform a self-test function, and LED will light and go off
circularly and orderly. When self-test finishes, it will come to online mode, the corresponding
LED lights, UPS is working in line mode.
Turn on the UPS by DC without mains power
1. When main power is disconnected, press and hold the ON key for more than half a second to
start UPS.
2. The operation of UPS in the process of start is almost the same as that when mains power is on. After the self-test finishes, the corresponding LED lights and UPS are working in battery
mode.
4.4.2 Turn Off Operation
> Turn off the UPS in line mode
1. Press and hold the OFF key for more than half a second to turn off the UPS and inverter.
2. After UPS shutting down, LED goes out and there is no output. If output is needed, you can set
BPS “ON” on LCD setting menu.
> Turn off the UPS in DC mode without mains power
1. Press and hold the OFF key for more than half a second to turn off the UPS.
2. When turning off the UPS, it will do self-test first. LED lights go out circularly and orderly
until there is no display on the panel.
1. When UPS is in LINE Mode, press and hold the self-test/mute key for more than 1 second,
LED light will go off circularly and orderly. UPS comes to self-test mode and tests its status. It
will exit automatically after finishing test.
2. When UPS is in BAT Mode, press and hold the self-test/mute key for more than 1 second, the
buzzer stops beeping. If you press and hold the self-test/mute key for one more second, it will
restart to beep again.
4.6 Single UPS Panel Function Setting
UPS has setting function. It can run the setting in any mode. After setting, it will become effective
at once when meets some standards. The set information can be saved only when the battery
connected and normally turning off the UPS.
4.6.1 ECO Mode Setting
1. Enter the setting interface. Press and hold the function setting keyfor more than 2
seconds, then come to setting interface, press and hold the inquiring key (,) for
more than half a second(less than 2 seconds), select the function setting, choose output
voltage setting interface, at the moment, the letters “ECO” will flash.
2. Enter the ECO setting interface. Press and hold the function setting keyfor more than
half a second(less than 2 seconds), then come to setting interface of ECO, at this time, the
letters “ECO” will not flash any more. The “ON” (or OFF) will flash. Press and hold the
inquiring key (,) for more than half a second (less than 2 seconds) to determine
whether the ECO function is used or not. If used, the corresponding word is “ON”, if not, the
word is “OFF”. It can be determined by yourself.
3. Confirm the ECO selecting interface. After selecting ON or OFF, press and hold the function
setting key for more than half a second (less than 2 seconds). Now, the ECO setting
function is completed and the “ON” or “OFF” will light without flash.
4. Exit from the setting interface. Press and hold function setting keyfor more than 2 seconds, exit from the setting interface and return to main interface.
1. Enter the setting interface. Press and hold the function setting keyfor more than 2
seconds, then come to setting interface, press and hold the inquiring key (,) for
more than half a second(less than 2 seconds), select the function setting, choose output
voltage setting interface, at the moment, the letters “IPP” will flash.
2. Enter the IPP setting interface. Press and hold the function setting keyfor more than half a second(less than 2 seconds), then come to setting interface of IPP, at this time, the letters
“IPP” will not flash any more, the numerical value next to the IPP will flash. Press and hold the
inquiring key (,) for more than half a second (less than 2 seconds) to select the
numerical value. There are two Input methods, the value ‘1’ means single phase input, the
value ‘3’ means three phase input. The default input method is single phase.
3. Confirm the IPP selecting interface. After selecting input method, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the IPP setting
function is completed and the value next to IPP will light without flash.
4. Exit from the setting interface. Press and hold function setting keyfor more than 2 seconds, exit from the setting interface and return to main interface.
4.6.3 Output Voltage Setting
1. Enter the setting interface. Press and hold the function setting keyfor more than 2
seconds, then come to setting interface, press and hold the inquiring key (,) for
more than half a second(less than 2 seconds), select the function setting, choose output
voltage setting interface, at the moment, the letters “OPU” will flash.
2. Enter the output voltage setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of output voltage
OPU, at this time, the letters “OPU” will not flash any more. The numerical value next to the
OPU will flash. Press and hold the inquiring key (,) for more than half a second (less
than 2 seconds), select the numerical value in accordance with “OPU” function. The provided
voltages are 208V, 220V, 230V, 240V, you can choose anyone by yourself (The default value is
220V).
3. Confirm the output voltage setting interface. After selecting numerical value, press and hold the function settingfor more than half a second (less than 2 seconds). Now, the OPU
setting function is completed and the numerical value will light without flash.
4. Exit from the setting interface. Press and hold function setting keyfor more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
4.6.4 Low Battery Voltage Shutdown Point Setting
1. Enter the setting interface. Press and hold the function setting keyfor more than 2
seconds, then come to setting interface, Press and hold the inquiring key (,) for
more than half a second(less than 2 seconds), select the function setting, choose battery
voltage setting interface, at the moment, the letters “bat” will flash.
2. Enter the battery voltage selecting interface. Press and hold the function setting keyfor more than half a second(less than 2 seconds), then come to setting interface of battery
voltage, this time, the numerical value will flash. Press and hold the inquiring key (,)
for more than half a second (less than 2 seconds), select the numerical value in accordance
with “battery” function. The provided voltages are 10V, 10.2V, 10.5V, numbers stand for the
voltage of each battery, you can choose anyone by yourself (The default is 10V), anyone has
been chosen, under BAT mode, UPS will shutdown when its battery voltage achieve the
voltage you chose.
3. Confirm the battery voltage selecting interface. After selecting numerical value, press and hold the function setting, for more than half a second (less than 2 seconds). Now, the
battery setting function is completed and the numerical value will light without flash.
4. Exit from the setting interface. Press and hold function setting keyfor more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
1. CUCF mode only can be set in STDBY mode. In STDBY mode, enter the setting interface. Press
and hold the function setting keyfor more than 2 seconds, then come to setting interface,
Press and hold the inquiring key (,) for more than half a second(less than 2 seconds),
select the function setting, choose battery voltage setting interface, at the moment, the letters
“CF” will flash.
2. Enter the CF setting interface. Press and hold the function setting keyfor more than half
a second(less than 2 seconds), then come to setting interface of CF, at this time, the letters “CF”
will not flash any more. The “ON” (or OFF) will flash. Press and hold the inquiring key (,
) for more than half a second (less than 2 seconds) to determine whether the CF function is
used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can be
determined by yourself.
3. Confirm the CF selecting interface. After selecting ON or OFF, press and hold the function
setting key for more than half a second (less than 2 seconds). Now, the CF setting
function is completed and the “ON” or “OFF” will light without flash.
4. Exit from the setting interface. Press and hold function setting keyfor more than 2
seconds, exit from the setting interface and return to main interface.
5. After setting CF at “ON”, UPS would be back in STDBY Mode. The default value of CF is OFF.
1. Output frequency only can be set when CUCF mode is ON.
2. In STDBY mode, enter the setting interface. Press and hold the function setting keyfor
more than 2 seconds, then come to setting interface, Press and hold the inquiring key (,
) for more than half a second(less than 2 seconds), select the function setting, choose
battery voltage setting interface, at the moment, the letters “OPF” will flash.
3. Enter the OPF setting interface. Press and hold the function setting keyfor more than half a second(less than 2 seconds), then come to setting interface of OPF, at this time, the
letters “OPF” will not flash any more. The “OFF” (or 50HZ, 60HZ) will flash. Press and hold the
inquiring key (,) for more than half a second (less than 2 seconds) to determine
whether the CF function is used or not. If used, select 50HZ or 60HZ according to you. It is
determined by yourself, the default value is 50HZ.
4. Confirm the OPF selecting interface. After selecting 50HZ or 60HZ, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the OPF
setting function is completed and the “50HZ” or “60HZ” will light without flash.
5. Exit from the setting interface. Press and hold function setting keyfor more than 2 seconds, exit from the setting interface and return to main interface.
4.6.6 ID Setting
1. Enter the setting interface. Press and hold the function setting keyfor more than 2
seconds, then come to setting interface, press and hold the inquiring key (,) for
more than half a second(less than 2 seconds), select the function setting, choose output
voltage setting interface, at the moment, the letters “Id” will flash.
2. Enter the output voltage setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of ID, at this
time, the letters “Id” will not flash any more. The numerical value next to the “Id” will flash.
Press and hold the inquiring key (,) for more than half a second (less than 2
Press and hold the inquiring keyfor more than 2 seconds, LCD begins to display the items
circularly and orderly which transfer to another every 2 seconds. Press and hold the key for
some time again within 30s, it will return to output status.
5 WORKING MODE INTRODUCTION
5.1 Bypass Mode
LED indications on front panel in bypass mode are as following:
Bypass yellow LED is on, the buzzer beeps once every 2 minutes. The warning red LED is on
when beeping, what LCD displays depending on the exact load and battery capacity.
Turn to bypass mode under the following two conditions:
1. Turn off the UPS line mode while start the bypass output.
2. Overload in line mode.
NOTE
When UPS is working in bypass mode, it has no back up function.
5.2 Line Mode
LED indications on front panel in line mode or CUCF mode are as following: The inverter green
LED is on.
When input AC mains correspond to the working conditions, UPS will work in line mode.
5.3 Battery Mode
LED indications on front panel in battery mode are as following: both the inverter green LED and
battery yellow LED is on, the buzzer beeps once every 4 seconds. The warning red LED will be
on while beeping.
Attention:
When the output is short-circuited, the action of the protection of the UPS will show up. Before
turning off the UPS, please make sure to disconnect the entire load and cut off the AC mains
power supply, otherwise will make the AC input short-circuit.
Appendix 1: EMC Level
The series product is designed to meet the below standard.
EMS
IEC61000-4-2(ESD)
Level 4
IEC61000-4-3(RS) Level 3
IEC61000-4-4(EFT)
IEC61000-4-5(Surge)
Level 4
Level 4
EMI
GB9254-1998/IEC 62040-2
Class B
Appendix 2: Symbol instructions:
Symbols and significations
Symbol Significations Symbol Significations
Our products are under a two-year guarantee starting from the date of delivery against
malfunctions resulting from production, material and workmanship faults. Malfunctions
due to such type of faults will be removed without claiming any price of workmanship or
spare parts to be replaced.
Whether aforementioned malfunctions originate from usage faults or not are determined
with a report to be issued by service stations, if there exists no service stations, by one of
seller, dealer, agency, representative, importer or manufacturer or producer of those
products respectively.
Repair time of defective products is twenty business days at most. This period starts
from the date when products are delivered to one of seller, dealer, agency,
representative, importer or one of manufacturer or producer. Provided that products
break down within the period of guarantee, the time passing during the repair process is
added to the guarantee time. Provided that faults of products cannot be removed within
ten business days, manufacturer-producer or importer is obliged to assign another
product having similar features for the use of consumers until the faulty product has
been repaired.
Even though consumers exercise their repair rights, they can claim free replacement of
products, refund or price discount at the rate of faultin the events;
That, besides, the product,as of the date when the product is delivered to
the consumer, breaks down four times a year or six times within the
guarantee period to be determined by the manufacturer-producer and/or
importer at least, on the condition of being in guarantee period, such
malfunctions perpetuate passing over;
That maximum time required for the repair of products is exceeded;
That repair of the malfunction is determined as impossible through a
report to be issued by service station, if there exists no service station,
one of seller, dealer, agency, representative, importer or manufacturer or
producer of the company respectively.
The consumer is, on demand, obliged to submit guarantee certificate in terms of repairs