Specifications
Please consult the manufacturer’s
installation manual for all details and
requirements before making a final
design layout decision.
MODEL FRONT WIDTH BACK WIDTH HEIGHT DEPTH GLASS SIZE
MODEL HEIGHT FRONT WIDTH BACK WIDTH DEPTH VIEWING AREA
ECHEL72
58,000 BTU (NG)
45,000 BTU (LP)
ACTUAL FRAMING ACTUAL FRAMING ACTUAL FRAMING ACTUAL FRAMING
Actual Framing Actual Framing Actual Framing Actual Framing
82" 84-1/4" 82" 84-1/4" 47-3/4" 48" 17-1/8" 18-1/4"
ECHELON II 72
Direct Vent Gas Fireplace
71-1/2" x 12-1/2"
ECHEL72
30-1/2"
[775]
23-3/4"
[603]
2-3/4" [70]
8-9/16"
[217]
47-3/4"
[1213]
2-3/8" [60]
18-5/8"
[473]
24-1/2"
[622]
8-7/8"
[225]
17-1/8"
[435]
7-1/4"
[184]
GAS ACCESS
82" [2083]
J
TOP
86" [2184]
75-1/8" [1908]
1" [25]
8-9/16"
[217]
o
8" [203]
CENTERED ON APPLIANCE
ELECTRICAL ACCESS
15-5/8"
[397]
48-1/2"
[1232]
4" [102]
8-9/16"
[217]
75"
[1905]
5/8" [16]
25"
[635]
24"
[610]
Additional information can be found online at www.majesticproducts.com
FRONTLEFT RIGHT
75 [1905]
13-1/8"
[333]
16-3/4"
[425]
73-3/16" [1859]
76-5/16" [1938]
CFT FRONT

Specifications
MEASUREMENT FROM
TOP EDGE OPENING
24
27
30
31
TO CEILING
9
6
3
Measurement from top edge
opening to bottom of appliance
=24-1/2"
MAX.
Note:
All measurements in inches.
31" [787]
0" [0]
0" [0]
55-1/2" [1410]
48" [1219]
1" [25]
1" [25]
Header depth
not to exceed
3-1/2" [89]
Adjust framing dimensions
for interior sheathing (such
as Sheetrock).
If appliance is installed o of oor,
maintain required clearances to
combustibles. Construct platform in
accordance with local building codes.
10" [254]
48"
[1219]
18-1/4"
[464]
84-1/4"
[2140]
31" [787]
0" [0]
0" [0]
55-1/2" [1410]
48" [1219]
1" [25]
1" [25]
ECHEL72
APPLIANCE LOCATION
1"
[895]
[25]
1"
88"
[25]
[2235]
84-1/4
[2140]**
1124-3/8"
[3159]
Refer to Section 10 of install manual for hearth,
mantel and wall projection information.
If a Heat-Zone
refer to
Section 5.E of install manual for information.
2 HEAT-ZONES = Add 4" to ** dimension
1 HEAT-ZONE = Add 2" to ** dimension
84-1/4 [2140]**
WALL PENETRATION
Do not pack with insulation or
other material.
10"
75"*
[1905]
12"
84-1/4 [2140]**
®
or Heat-Duct will be installed,
18-1/4"
[464]
74"
[1880]
* Shows center of vent framing
hole for top venting. Center of hole
is 1" [25] above center of horizontal
vent pipe.
See clearances
in install manual
84-1/4
[2140]**
FRAMING DIMENSION
CLEARANCES TO COMBUSTIBLES
MANTEL PROJECTIONS - COMBUSTIBLE
MANTEL PROJECTIONS - NON-COMBUSTIBLE
Note: All measurements in inches.
MAX.
13-16
6
5
4
3
2
9
8
1
7
6
MEASUREMENTS FROM TOP ED GE
OF THE APPLIANCE OPENING
Measurement from top edg e of opening
to bottom of appliance = 2 4-1/2"
OVERLAP FIT
TO CEILING
31
MIN.
18
11
10
Note: All measurements in inches.
MAX.
INSIDE FIT
TO CEILING
14-16
31 MIN.
7
18
6
5
11
10
9
4
MEASUREMENTS FROM TOP E DGE
OF THE APPLIANCE OPENI NG
Measurement from top edge of opening
to bottom of applianc e = 24-1/2"
Majestic — A Brand of Hearth & Home Technologies
7571 215th Street West | Lakeville, MN 55044
877-486-9123 | majesticproducts.com
MANTEL LEG/WALL PROJECTIONS
COMBUSTIBLE OR NON-COMBUSTIBLE
Note: Clearance from
opening to
perpendicualar wall
Top View
4-1/2"
minimum
3' maximum
FIREPLACE OPENING
See appliance dimension diagram
in install manual - Dimension B
Acceptable on both sides of opening
PRODUCT LISTING CODES
US ANSI Z21.88-2014
CAN CSA 2.33-2014
UL307B
Top View
FIREPLACE OPENING
See appliance dimension diagram
in install manual - Dimension B
Product information provided is not
complete and is subject to change
without notice. Product installation
must adhere strictly to instructions
accompanying product to avoid risk
of fire and potential injury.
7"
minimum
Note: Clearance from
opening to
perpendicualar wall
UNLIMITED