Majestic BC36 Operation Manual

BR/BC Series
Woodburning Fireplace
For Models:
DO NOT DISCARD THIS MANUAL: Retain for future use.
7412944 4/07 Rev. 21
For use in U.S./Canada Underwriter's Laboratories Report No. MH6018
Homeowner's Installation and Operating Manual
2
Majestic Fireplaces® BR/BC Series
7412944
BR36 / BR42 BC36 / BC42
Listed
UL 127 / ULC-S610
Standard for Factory Built Fireplaces
Safety Information
PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING FIREPLACE.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to
follow these instructions may result in a possible fi
re hazard and will void the warranty.
Description
The BR/BC Series fireplaces are solid fuel, woodburning fireplaces. The BR36/42 (Builder Radiant) is a clean-face fireplace and the BC36/42 (Builder Circulating) unit has
fixed grilles.
Precautions
CFM Corporation fireplaces and component parts have been highly tested and will operate safely when installed in accordance with instructions provided in this manual. Carefully read and understand all instructions before beginning installation.
If you notice any damage to fireplace or component parts, immediately report damage to your Majestic Fireplaces dealer.
Only use CFM Corporation components or the warranty will be voided and a fire hazard may be created.
CFM Corporation warranty will be voided by and CFM Corporation disclaims any responsibility for the following actions:
Installation by any other than a qualified install-
er, preferably NFI or WETT (Canada) certified.
Installation of any damaged fireplace or chim-
ney component;
Modification of fireplace, chimney assembly or
any component parts thereof; (except for chase flashings as detailed in Chimney Top installation instructions).
Installation other than as instructed by CFM
Corporation; or
Installation and/or use of any component part
not manufactured or approved by CFM Corpo­ration in combination or assembly with a Majes­tic Fireplaces fireplace system, notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory.
Any such action may possibly cause a fire hazard.
Consult local building codes to ensure that you are in compliance before installing the fireplace.
Fireplaces must be vented to the out-of-doors.
Do not obstruct or modify air inlets/outlets in any manner.
Do not install combustible materials on any of the black fireplace surround.
Burn only solid wood fuel or gas logs.
Do not install a solid fuel burning insert or other products not specifi
ed for use with this fireplace.
Proposition 65 Warning: Fuels used in gas, wood-
burning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm. California Health & Safety Code Sec. 25249.6
Drafts
The fireplace should not be located in areas that create drafts (ie: frequently opened doors and central heating air inlets/outlets) that hamper the normal flow of air into the
fire.
Gas Logs
If you plan to install a gas log, the gas line should be installed before framing the fireplace. The gas line must be installed by a certified gas line installer.
Safety Information . . . . . . . . . . . . . . . . . . 2
Specifications and Framing . . . . . . . . . . 3
Parts Identification . . . . . . . . . . . . . . . . . 5
Chimney Requirements . . . . . . . . . . . . . 6
Planning Information
. . . . . . . . . . . . . . . . 7
Installation . . . . . . . . . . . . . . . . . . . . . . . 8
Replacement Parts . . . . . . . . . . . . . . . . 19
Accessories . . . . . . . . . . . . . . . . . . . . . 20
Table of Contents
3
Majestic Fireplaces® BR/BC Series
7412944
BR36 Series Woodburning Fireplace
Fig. 1 BR36 Series specifications and framing.
36"
(914mm)
"
(372mm)
"
(337mm)
40" (1016mm)
36
"
(930mm)
"
" (16mm)
45" (1162mm)
45"(1162mm)
" (13mm)
"
" (1645mm)
"
(187mm)
20"
(508mm)
"
(521mm)
" (559mm)
"
(502mm)
"
(533mm)
40"
(1035mm)
"
(
241mm)
"
(167mm)
"
(191mm)
"
(
191mm)
Outside Air
Gas Line Access
Gas Line Access
Electrical Access
Recessed Nailing Flange
11" Dia. (279mm)
Rough Opening Width 41"
Rough Opening Height
Rough Opening Depth
3" (76mm)
*
(1041mm)
8" Dia. (203mm)
" (822mm)
*If elbows are offset to the back of the unit, chase depth will be 22⁵⁄₈" (575mm).
Fig. 2 BC36 Series specifications and framing.
BC36 Series Woodburning Fireplace — Circulating Model
" (16mm)
" (13mm)
"
36"
(914mm)
34"
(880mm)
40" (1016mm)
"
"
(502mm)
"
(64mm)
" (902mm)
"
(533mm)
"
(197mm)
"
(191mm)
Recessed Nailing Flange
1
1" Dia.
(279mm)
Rough Opening Width 41"
Rough Opening Height
Rough Opening Depth
Gas Line Access
45" (1162mm)
45" (1162mm)
" (1645mm)
"
(187mm)
20"
(508mm)
"
(521mm)
" (559mm)
40
"
(1035mm)
"
(372mm)
"
(337mm)
36
"
(930mm)
3"
(76mm)
"
(241mm)
"
(191mm)
Outside Air
Gas Line Access
Electrical Access
*
(1041mm)
8" Dia. (203mm)
" (822mm)
*If elbows are offset to the back of the unit, chase depth will be 22⁵⁄₈" (575mm).
4
Majestic Fireplaces® BR/BC Series
7412944
Fig. 4 BC42 Series specifications and framing.
BC42 Series Woodburning Fireplace — Circulating Model
42"
(1067mm)
34"
(880mm)
46" (1
168mm)
"
" (16mm)
" (13mm)
"
"
(502mm)
" (64mm)
" (965mm)
"
(533mm)
"
(197mm)

"
(191mm)
Recessed Nailing Flange
11" Dia. (279mm)
Rough Opening Width 47"
Rough Opening Height
Rough Opening Depth
Gas Line Access
49" (1245mm)
49" (1245mm)
" (1765mm)
"
(187mm)
20"
(508mm)
"
(521mm)
" (711mm)
40
"
(1035mm)
"
(372mm)
"
(337mm)
36
"
(930mm)
3"
(76mm)
"
(241mm)
"
(191mm)
Outside Air
Gas Line Access
Electrical Access
*
(1194mm)
8" Dia. (203mm)
" (895mm)
*If elbows are offset to the back of the unit, chase depth will be 22⁵⁄₈" (575mm).
BR42 Series Woodburning Fireplace
Fig. 3 BR42 Series specifications and framing.
42"
(1067mm)
46" (1168mm)
36"
(930mm)
"
" (16mm)
" (13mm)
"
"
(502mm)
"
(533mm)
"
(197mm)
"
(191mm)
Gas Line Access
Recessed Nailing Flange
11" Dia. (279mm)
Rough Opening Width 47"
Rough Opening Height
Rough Opening Depth
49" (1245mm)
49" (1245mm)
" (1765mm)
"
(187mm)
20"
(508mm)
"
(521mm)
" (711mm)
40
"
(1035mm)
"
(372mm)
"
(337mm)
3"
(76mm)
"
(241mm)
"
(191mm)
Outside Air
Gas Line Access
*
(1194mm)
Electrical Access
8" Dia. (203mm)
" (895mm)
*If elbows are offset to the back of the unit, chase depth will be 22⁵⁄₈" (575mm).
5
Majestic Fireplaces® BR/BC Series
7412944
Chase Installation
Insulation methods shown are optional for cold climate, not a requirement for unit operation.
FP554
Fig. 5 Fireplace and chase parts identification.
Termination Cap
Storm Collar
Pan Flashing
Draftstop
Standof
f
Surround
Damper Control
Gas Line Knockout (both sides)
Screen
Grate
Firebox
Metal Safety Strips (1,2 or 3 pieces)
Outside
Air Cover Plate
Electrical Access
Gas Line Access (both sides)
Nailing Flange
Ceiling Level
Firestop
Batt Insulation (cut our around fi
restop)
A
B
C
Front Width Back Width Depth A B C
BR/BC36 33¹⁄₄" 19⁵⁄₈" 15¹⁄₄" (845 mm) (499 mm) (387 mm)
BR/BC42 39¹⁄₄" 25⁵⁄₈" 15¹⁄₄" (997 mm) (651 mm) (387 mm)
FP1531
Fig. 4a Hearth dimensions.
6
Majestic Fireplaces® BR/BC Series
7412944
Chimney
Support
Chimney Requirements - Offset Installations
0 0 0 0 0 3" 11"
1 0 0 0 0 8¹⁄₄" 20" 0 1 0 0 0 11¹⁄₄" 25¹⁄₄" 2 0 0 0 0 13¹⁄₂" 29¹⁄₄" 1 1 0 0 0 16¹⁄₂" 34¹⁄₄" 0 0 1 0 0 20¹⁄₄" 40³⁄₄" 2 1 0 0 0 21³⁄₄" 43¹⁄₂" 0 0 0 1 0 26¹⁄₄" 51¹⁄₄" 0 1 1 0 0 28¹⁄₂" 55¹⁄₄" 1 0 0 1 0 31¹⁄₂" 60¹⁄₄” 0 1 0 1 0 34¹⁄₂" 65¹⁄₂" 0 0 2 0 0 37¹⁄₂" 70³⁄₄" 1 1 0 1 1 41¹⁄₂" 77³⁄₄" 0 0 1 1 1 45" 83³⁄₄" 0 1 2 0 1 47¹⁄₄" 87¹⁄₂" 0 0 0 2 1 51" 94" 0 1 1 1 1 53¹⁄₄" 98" 0 0 3 0 1 56¹⁄₄" 103¹⁄₄" 0 1 0 2 1 59¹⁄₄" 108¹⁄₂" 0 0 2 1 1 62¹⁄₄" 113¹⁄₂" 0 1 3 0 1 64¹⁄₂" 117¹⁄₂" 0 0 1 2 1 68¹⁄₄" 124" 0 1 2 1 1 70¹⁄₂" 128" 0 0 0 3 1 74¹⁄₄" 134¹⁄₂" 0 1 1 2 2 78" 140³⁄₄" 0 0 3 1 2 81" 146" 0 1 0 3 2 84" 151¹⁄₄" 0 0 2 2 2 87" 156¹⁄₂" 0 1 3 1 2 89¹⁄₄" 160¹⁄₄" 0 0 1 3 2 93" 166³⁄₄" 0 1 2 2 2 95¹⁄₄" 170³⁄₄" 0 0 0 4 2 99¹⁄₄" 177³⁄₄" 0 1 1 3 2 101¹⁄₄" 181³⁄₄" 0 0 3 2 2 104¹⁄₄" 186¹⁄₄" 0 1 0 4 2 107¹⁄₄" 191¹⁄₂" 0 0 2 3 2 110¹⁄₄" 196³⁄₄" 0 1 3 2 3 114" 203¹⁄₄" 0 0 1 4 3 117³⁄₄" 209³⁄₄" 0 1 2 3 3 120" 213¹⁄₂" 0 0 0 5 3 123³⁄₄" 220"
30˚ Elbow Offsets
1'
1¹⁄₂'
3' 4'
Offset
Rise
Notes: G + H cannot exceed 20 feet.
Air Space Clearances: SK8 (2-wall) = 1¹⁄₂" and "S" Series (3-wall) = 2"
Illustration Key
The following safety rules apply to offset installations (letters correspond with illustration above):
A. Height of the chimney is measured from the hearth to the chimney exit.
BR/BC36 BR/BC42
Maximum:
90'0" 90'0"
Minimum:
Without Elbows 12' 6" 12' 6" With 2 Elbows* 14' 6" 14' 6" With 4 Elbows* 21' 0" 21' 0"
B. Do not use more than 4 elbows per chimney
.
Attach the straps of the return (top) elbow to a structural framing member
.
The offset (first) elbow of any pair does not have straps.
FP269
C. The chimney cannot be more than 30˚ (45˚ in Canada) from the vertical plane in any installation*.
D. The maximum length of the angled run of the total chimney system is 20 feet. (G plus H cannot exceed 20 feet.)
E. A chimney support (Model SKCS8) is required every 6 feet of angled run of chimney
. Chimney supports are required for every 30 feet and 60 feet (SK8 pipe) or 20 feet and 40 feet (3-wall pipe) of ver­tical chimney height above the hearth.
Determine the of
fset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling.
NOTE: This offset distance may not be your full of
fset distance. See Examples 2
and 3.
OFFSET
RISE
FP282
* In Canada, two (2) SK845 are allowed.
Fig. 6. Chimney system requirements.
D
RISE
B
G
H
B
OFFSET
C
E
6 FT
.
G
H
A
HEARTH FLOOR
CHIMNEY SECTION
CHIMNEY FLUE EXIT
ELBOW
30˚
OFFSET
ELBOW
30˚
OFFSET
ELBOW
30˚
RETURN
ELBOW
30˚
RETURN
ELBOW
SKCS8 SUPPORT
Example 1 Example 2 Example 3
7
Majestic Fireplaces® BR/BC Series
7412944
Planning Information
The Ten Foot Rule
Major U.S. building codes specify a minimum chimney height above the roof top. The “Ten Foot Rule” is a fire safety rule and not a draft rule. To ensure proper draft, it is recommended that you always meet or exceed the “Ten Foot Rule,” especially when installing a termination on a high pitch roof. (Fig. 8)
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the peak of the roof is 10' (3m) or less, the top of the chimney must be at least 2' (610mm) above the peak of the roof, but never less than 3' (914mm) in height above the highest point where it passes through the roof.
2. If a horizontal distance from the chimney to the peak of the roof is more than 10' (3m), a chimney height reference point is established on the surface of the roof a distance of 10' (3m) from the chimney in a horizontal plane. The top of the chimney must be at least 2' (610mm) above the reference point, but never less than 3' (914mm) in height above the high­est point where it passes through the roof.
Determine how the chimney will be run, length of run and chimney components required to complete the job. (Fig. 6) Never install a chimney below minimum heights.
In planning a chimney system, it is important to know:
1.
The height of a chimney is measured from the hearth to the exit point on the termination.
2. A chimney cannot be offset more than 30° from a vertical plane.
3. A chimney may run straight up or it may be neces­sary to offset it to avoid obstructions.
4. The maximum length of an angled run (total chimney system) is 20' (6 m).
5. No more than 2 offsets (4 total 30° elbows in U.S./or 2 total 45° elbows in Canada) per fireplace may be used.
6. A guy wire stabilizer is required for chimneys extend­ing more than 6' (1.8 m) above a roof line.
L
1
L
1
L
T
MODEL
SK
2 WALL CHIMNEY
TOTAL
LENGTH
(LT)
INST
ALLED
LENGTH
(L1)
SK81 SK818 SK83 SK84

"

"

"

"

"

"

"

"
Fig. 7 Installed lengths of chimney sections.
FP288
AC246
Fig. 8 Ten Foot Rule illustration.
2' Min.
2' Min.
3'
Min.
0 To 10'
3'
Min.
0 To 10'
Reference Point
Preplanning an installation is very important to ensure safety and to save time and money. An installer must predetermine where a fireplace will be set and how the chimney system will be run.
Mounting the Fireplace
A fireplace may only be mounted on the following sur­faces:
1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed beneath
each of the four (4) corners of the fireplace.
The fireplace must be spaced 1/2" (13mm) from a com­bustible back wall and 1/2" (13mm) from a combustible side wall or support. (Page 14, Fig. 20)
Planning the Chimney Run
8
Majestic Fireplaces® BR/BC Series
7412944
Insulating Fireplace Enclosure
for Cold Climates
Installation
Chimney Supports
The chimney system is supported by the fireplace for vertical chimney heights less than 30' (9m) above the hearth. Chimney supports are required if the vertical height exceeds 30' (9m) with SK8 chimneys or 20' (6m) with 3-wall chimneys. Locate chimney supports at ceil­ing holes or other structural framing at 30' (9m) (SK8) or 20' (6m) (3-wall) heights. Spacing between chimney supports must not exceed 30' (9m) (SK8) or 20' (6m) (3-wall). Use Chimney Support Model SKCS8. (NOTE:
The SKCS8 can not be mounted directly to the fireplace.) Support provided by elbow straps fulfills the
support requirement only if they are spaced as previ­ously described. (A chimney support is 2¹⁄₂" (64mm) long when installed.)
Angled chimney runs require a support every 6' (1.8m) in addition to the elbow straps. Chimney supports are used for this function. (Fig. 9)
Chase Installation
A chase is a vertical box-like structure which encloses the fireplace and/or chimney. Chases are typically built on the outside of the house with fireplace opening cut into the outer wall of a room. (Page 5, Fig. 5)
If you need help in determining fireplace location or how the chimney system should be run, contact your Majes­tic Fireplaces dealer for assistance.
If you live in a cold climate, it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible.
Insulate base of fireplace with a noncombustible insulation rated for a minimum of 300°F
. Insulating
is very important for outside wall installations over a concrete slab. If fireplace is installed on a platform, insulation should be placed on top of the platform before fireplace is set. (Fig. 10)
When a fireplace is installed in a chase or on a outside wall, enclosure should be treated like any outside wall in a home. Insulation should be installed on the inside wall as well as the outside wall(s). In a chase, it is also a good idea to install a firestop at the first ceiling level above the fireplace and enclose the chase with sheeting material. Insulation may then be installed above sheeting material to assure the space around the fireplace is totally protected. (Fig. 5)
When installing the chimney, DO NOT caulk between outer pipe and firestop. It is vital that some air be al­lowed to flow through this very thin gap.
CAUTION: WHEN INSTALLING A FIREPLACE IN AN INSULATED ENCLOSURE, BE SURE ALL REQUIRED AIR SPACES ARE MAINTAINED. (Page 14, Figure 20)
FP284
Fig. 9 Chimney support installation
Chimney Sup­port Strap
SKCS8