Main System 28 Eco, System 24 Eco Installation Manual

© Baxi Heating UK Ltd 2011
Installation & Service Instructions
System Eco
Range
These instructions include the Benchmark Commissioning Checklist
and should be left with the user for safe keeping.
2
© Baxi Heating UK Ltd 2011
Natural Gas
Main System 24 Eco
G.C.No41 467 11
Main System 28 Eco
G.C.No41 467 12
© Baxi Heating UK Ltd 2011 All rights reserved. No part of this publication may be reproduced or transmitted in any form or by any means, or stored in any retrieval system of any nature (including in any database), in each case whether electronic, mechanical, recording or otherwise, without the prior written permission of the copyright owner, except for permitted fair dealing under Copyrights, Designs and Patents Act 1988.
Applications for the copyright owner’s permission to reproduce or make other use of any part of this publication should be made, giving details of the proposed use, to the following address:
The Company Secretary, Baxi Heating UK Limited, Brooks House, Coventry Road, Warwick. CV34 4LL
Full acknowledgement of author and source must be given.
WARNING: Any person who does any unauthorised act in relation to a copyright work may be liable to criminal prosecution and civil claims for damages.
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.
0086
ISO 9001
FM 00866
Building Regulations and the Benchmark Commissioning
Checklist
Building Regulations (England & Wales) require notification of the installation of a heating appliance to the relevant Local Authority Building Control Department. From 1 April 2005 this can be achieved via a Competent Persons Self Certification Scheme as an option to notifying the Local Authority directly. Similar arrangements will follow for Scotland and will apply in Northern Ireland from 1 January 2006.
The Health & Safety Executive operates the ‘Gas Safe Register’, a self-certification scheme for gas heating appliances.
These arrangements represent a change from the situation whereby compliance with Building Regulations was accepted as being demonstrated by completion of the Benchmark Logbook (which was then left on site with the customer).
With the introduction of Self Certification Schemes, the Benchmark Logbook is being withdrawn. However, a similar document in the form of a commissioning checklist and service interval record is incorporated at the back of these instructions.
This company is a member of the Benchmark initiative and fully supports the aims of the programme. Its aim is to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency.
Building Regulations require that installations should comply with manufacturer's instructions. It is therefore important that the commissioning checklist is completed by the installer. The relevant section of Building Regulations only relates to dwellings. Therefore the checklist only applies if the appliance is being installed in a dwelling or some related structure.
The flowchart opposite gives guidance for installers on the process necessary to ensure compliance with Building Regulations.
Supplied by HeatingSpares247.com
3
Installer Notification Guidelines
© Baxi Heating UK Ltd 2011
Choose Building
Supplied by HeatingSpares247.com
Regulations Notification
Route
Competent Person's
Self Certification Scheme
Install and Commission this appliance to manufacturer's
instructions
Complete the
Benchmark Checklist
If you notify via the ‘Gas Safe
Register’, the register will issue
the Building Regulations
certificate on members’ behalf
Building Control
Contact your relevant Local
Authority Building Control
(LABC) who will arrange
an inspection or contact a government approved
inspector
Install and Commission this appliance to manufacturer's
instructions
Scheme Members only
Call ‘Gas Safe Register’ on:
0800 408 5577
or log onto:
www.gassaferegister.co.uk
within 10 days
You must ensure that the
certificate number issued by
the ‘Gas Safe Register’ is written
onto the Benchmark Checklist
‘Gas Safe Register’ will issue a
Building Regulations Compliance
Certificate to the property owner
and inform the relevant LABC
Complete the
Benchmark Checklist
LABC will record the data
and will issue a
certificate of compliance
4
Legislation
© Baxi Heating UK Ltd 2011
Codes of Practice - refer to the most recent version
This company declare that no substances harmful to health are contained in the appliance or used during appliance manufacture.
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force, and only used in a suitably ventilated location.
In GB, the installation must be carried out by a CORGI Registered Installer. It must be carried out in accordance with the relevant requirements of the:
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building Regulations, The Building Regulations (Scotland), Building Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in Scotland.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent Person and installed in accordance with the current edition of I.S. 813 ‘Domestic Gas Installations’, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
All systems must be thoroughly flushed and treated with inhibitor (see section 6.2).
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) Regulations 1993 N
o
3083” and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:-
Type test for purpose of Regulation 5 certified by: Notified Body 0087.
Product/Production certified by: Notified Body 0086.
For GB/IE only.
IMPORTANT - Installation, Commissioning, Service & Repair
This appliance must be installed in accordance with the manufacturer’s instructions and the regulations in force. Read the instructions fully before installing or using the appliance.
In GB, this must be carried out by a competent person as stated in the Gas Safety (Installation & Use) Regulations.
Definition of competence: A person who works for a Gas Safe registered company and holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic Gas Installations”.
The addition of anything that may interfere with the normal operation of the appliance without express written permission from the manufacturer or his agent could invalidate the appliance warranty. In GB this could also infringe the Gas Safety (Installation and Use) Regulations.
Warning - Check the information on the data plate is compatible with local supply conditions.
All Gas Safe registered engineers carry an ID card with their licence number and a photograph. You can check your engineer is registered by telephoning 0800 408 5500 or online at www.gassaferegister.co.uk
In GB the following Codes of Practice apply: Standard Scope
BS 6891 Gas Installation. BS 5546 Installation of hot water supplies for domestic
purposes. BS EN 12828 Heating systems in buildings. BS EN 14336 Installation & commissioning of water based
heating systems. BS 6798 Installation of gas fired hot water boilers. BS 5440 Part 1 Flues. BS 5440 Part 2 Ventilation. BS 7074 Expansion vessels and ancillary equipment for
sealed water systems. BS 7593 Treatment of water in domestic hot water
central heating systems.
In IE the following Codes of Practice apply: Standard Scope
I.S. 813 Domestic Gas Installations. The following standards give valuable additional information; BS 5546 Installation of hot water supplies for domestic
purposes. BS EN 12828 Heating systems in buildings. BS EN 14336 Installation & commissioning of water based
heating systems. BS 7074 Expansion vessels and ancillary equipment for
sealed water systems. BS 7593 Treatment of water in domestic hot water
central heating systems.
Supplied by HeatingSpares247.com
5
Safe Manual Handling
© Baxi Heating UK Ltd 2011
General
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands. Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Do not handle or lift unless you feel physically able.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the ‘Installation’ section of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !! DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
Supplied by HeatingSpares247.com
6
© Baxi Heating UK Ltd 2011
CONTENTS
1.0 Introduction 7
2.0 General Layout 8
3.0 Appliance Operation 9
4.0 Technical Data 10
5.0 Dimensions and Fixings 11
6.0 System Details 12
7.0 Site Requirements 14
8.0 Flue Options 18
9.0 Plume Displacement 23
10.0 Installation 27
11.0 Commissioning 33
12.0 Completion 35
13.0 Servicing 36
14.0 Changing Components 38
15.0 Setting the Gas Valve 46
16.0 Electrical 47
17.0 Short Parts List 48
18.0 Fault Finding 49
Benchmark Checklist 54
Section Page
Supplied by HeatingSpares247.com
7
1.0 Introduction
© Baxi Heating UK Ltd 2011
1.1 Description
1. The Main System Eco is a fully automatic gas fired wall mounted condensing system boiler. It is room sealed and fan assisted.
2. The boiler is set to give a maximum output of :-
24 models - 25.94 kW
26.95 kW (Condensing)
28 models - 28.63 kW
30.20 kW (Condensing)
3. It is designed for use on Natural Gas (G20).
4. The boiler incorporates a circulating pump and expansion vessel. It is suitable for use only on fully pumped sealed systems.
5. The boiler data badge gives details of the model, serial number and Gas Council number and is situated on the front sloping face of the hydraulic plate. It is visible when the case front panel is removed and the control box hinged down (Fig. 1 & 1a).
6. The boiler model name and serial number are also shown on the information label on the back of the facia door. This is for user reference.
7. The boiler is intended to be installed in residential / commercial / light industrial E.M.C. environments on a governed meter supply only.
8. The boiler must be installed with one of the purpose designed flues such as the standard horizontal flue kit, part no. 5118489 .
9. All systems must be thoroughly flushed and treated with
inhibitor (see section 6.1).
1.2 Contents of Pack
1. Boiler Unit
2. Wall Plate (inc. taps)
3. Set of Pipes (inc. nuts)
4. Template & ‘Quick Fit’ Guide
5. Literature Pack
Fig. 1
Control Box
Case Front Panel
Information Label
Data Badge
Fig. 1a
Facia Door
Supplied by HeatingSpares247.com
8
2.0 General Layout
© Baxi Heating UK Ltd 2011
2.1 Layout
1. Expansion Vessel
2. Automatic Air Vent
3. Primary Return Temperature Sensor
4. Circulation Pump
5. Drain Off Point
6. Pressure Relief Valve
7. Selector Switch
8. Central Heating System Pressure Gauge
9. PCB
10. Control Box
11. Gas Valve
12. Condensate Trap
13. Heat Exchanger Air Vent
14. Electrode Assembly
15. Primary Heat Exchanger
16. Fan Assembly
17. On/Off/Reset Selector Switch
18. Central Heating Temperature Control
19. Calibration Control
20. Water Pressure Sensor
21. Gas/Air Inlet
22. Burner Mounting Panel
23. Igniter
24. Burner On Light
25. Central Heating Mode Light
26. Calibration Mode Light
27. Display
13
17
18
19
8
2
3
4
5
6
7
8
9
10
11
12
1
14
16
24
25
26
27
21
23
22
15
20
Supplied by HeatingSpares247.com
Reset
2
1
3
4
0
bar
9
3.0 Appliance Operation
© Baxi Heating UK Ltd 2011
1
2
4
5
6
7
8
19
18
9
10 12 11
14
13
15
16
17
3
Key
1 Heat Exchanger 2 Burner 3 Ignition Electrode 4 Flame Sensing Electrode 5 Gas Valve 6Pump 7 Automatic Air Vent 8 Pressure Relief Valve 9 Boiler Drain Point 10 Gas Inlet 11 Boiler Flow 12 Boiler Return 13 Pressure Gauge 14 Automatic By-Pass 15 Water Pressure Sensor 16 Safety Thermostat 17 Temperature Sensor 18 Expansion Vessel 19 Return Temperature Sensor 20 Fan
Boiler Primary Circuit
Fig. 2
20
3.1 Operating Mode (Fig. 2)
1. With a demand for heating or hot water, the pump circulates water through the primary circuit. If the pressure is at least 0.5 bar and the ignition sequence will start.
2. When the flow temperature exceeds the setting temperature, a 3 minute delay occurs before the burner relights automatically (anti-cycling). The pump continues to run during this period.
3. When the demand is satisfied the burner is extinguished and the pump continues to run for a period of 3 minutes (Pump Overrun).
IMPORTANT: When the selector switch is in the ‘0’ (Off) position the electrical supply to the boiler is isolated. The boiler will not operate.
3.2 Frost Protection Mode
1. The frost protection mode is integral to the appliance and functions when the selector switch (see Section 2.1) is in the ON position ( ). If the system temperature falls below 5° C then the boiler will fire on its minimum setting until a flow temperature of 30° C is reached. Further protection can be incorporated by using a system frost thermostat.
3.3 Pump Protection
1. With the selector switch (see Section 2.1) in the ON position ( ) the pump will automatically operate for 1 minute in every 24 hours to prevent sticking.
Supplied by HeatingSpares247.com
10
4.0 Technical Data
© Baxi Heating UK Ltd 2011
4.1 System 24 & 28 Eco
Flue Terminal Diameter 100mm Dimensions Projection 125mm
Outercase Dimensions
Casing Height - 780mm Overall Height Inc Flue Elbow - 965mm Casing Width - 450mm Casing Depth - 345mm
Weights
Packaged Boiler Carton 51.1 kg (24 &28) Installation Lift Weight 44.5 kg (24 & 28)
Central Heating Primary Circuit Pressures
bar Safety Discharge 3 Max Operating 2.5 Min Operating 0.5 Recommended Operating Range 1-2
Pump
Available Head See graph below
Expansion Vessel - (For Central Heating only. Integral with appliance)
bar
Min Pre-charge Pressure 0.5
(18,24) (27) Max Capacity of litre litre CH System 125 155
Primary Water Content of Boiler (unpressurised) 2.5 2.8
Connections copper tails Gas Supply - 22mm Central Heating Flow - 22mm Central Heating Return - 22mm Pressure Relief Discharge - 15mm
Temperatures
C.H. Flow Temp
(adjustable)
25°C to 80°C max (± 5°C)
NOxClass 5
Clearances Above Casing 200 mm Min
300 mm Min (80/125mm flue) Below Casing 200 mm Min Front 450 mm Min
(For Servicing)
Front 5 mm Min (In Operation) L.H. Side 5 mm Min R.H. Side 5 mm Min
(In Operation)
Heat Input CH (Net) Max Min
24 model kW 26.06 7.82
28 model kW 29.32 8.8
Heat Output CH (Non-Condensing)
Max Min
24 model kW 25.94 7.61
28 model kW 28.63 8.56
Electrical Supply 230V~ 50H
z
(Appliance must be connected to an
earthed supply)
Power Consumption
150W
Electrical Protection
IPX0D (with timer) IPX4D (without timer)
Internal Fuse Rating F2L
Appliance Category CAT I
2H
Inlet Pressure (Natural Gas - G20)
mbar 20
Injector (Natural Gas - G20)
6.0mm (24 & 28 models)
Appliance Type C
13
C
33
C
53
Heat Output CH (Condensing)
Max Min
24 model kW 26.95 8.37
28 model kW 30.20 9.42
Max Gas Rate (Natural Gas - G20)
(After 10 mins)
24 model m3/h 2.76
28 model m3/h 3.10
Condensate Drain
To accept 21.5mm (
3
/4in) plastic waste pipe
Heat Input CH (Gross) Max Min
24 model kW 28.92 8.68
28 model kW 32.54 9.77
External Fuse Rating 3A
SAP 2005 Seasonal Efficiency for 24 models
is 91.1%
SAP 2005 Seasonal Efficiency for 28 models
is 90.2%
This value is used in the UK Government’s Standard
Assessment Procedure (SAP) for energy rating of
dwellings. The test data from which it has been
calculated has been certified by 0087.
SEDBUK Declaration
Supplied by HeatingSpares247.com
5.5
5
4.5
4
3.5
3
2.5
2
Metre (wg)
1.5
1
0.5
0
0
Pump - Available Head (24,27)
200 400 600 800 1000 1200 1400
Flow Rate (l/h)
11
5.0 Dimensions and Fixings
© Baxi Heating UK Ltd 2011
Tap Rail
360° Orientation
Tube Ø 100mm
D
C
B
A
G
F
H
H
Heating
Return
(22mm)
Heating
Flow
(22mm)
Pressure Relief
Valve
(15mm)
Gas
Inlet
(22mm)
130 mm
130 mm
65 mm
Condensate
Drain
127 mm
Dimensions
A 780mm
B 345mm
C 450mm
D 116mm Ø Min.
F 145mm
G 132mm
210mm (80/125)
H 225mm
At Least 1.5
o
Supplied by HeatingSpares247.com
12
6.0 System Details
© Baxi Heating UK Ltd 2011
6.1 Central Heating Circuit
1. The appliance is suitable for fully pumped SEALED SYSTEMS
ONLY.
Treatment of Water Circulating Systems
• All recirculatory water systems will be subject to corrosion unless an appropriate water treatment is applied. This means that the efficiency of the system will deteriorate as corrosion sludge accumulates within the system, risking damage to pump and valves, boiler noise and circulation problems.
• When fitting new systems flux will be evident within the system, which can lead to damage of system components.
• All systems must be thoroughly drained and flushed out using, for example, Sentinel X300 or X400 or Fernox F3. They should be used following the flushing agent manufacturer’s instructions.
• System additives - corrosion inhibitors and flushing agents/descalers should comply to BS7593 requirements, e.g. Sentinel X100 and Fernox MB-1 which should be used following the inhibitor manufacturer’s instructions.
• Full instructions are supplied with the products, for further information contact Sentinel (0800 389 4670) or Fernox (0870 870 0362)
Failure to flush and add inhibitor to the system will invalidate the appliance warranty.
• It is important to check the inhibitor concentration after installation, system modification and at every service in accordance with the manufacturer’s instructions. (Test kits are available from inhibitor stockists.)
• For information or advice regarding any of the above contact Technical Enquiries.
6.2 Bypass
1. The boiler is fitted with an automatic integral bypass.
6.3 System Control
1. For optimum operating conditions, the heating system into which the boiler is installed should include a control system.
2. Such a system will comprise of a timer control and separate room or cylinder thermostats as appropriate.
3. The boiler should be controlled so that it operates on demand only.
4. Operation of the system under control of the boiler thermostat & TRV’s only does not produce the best results.
Supplied by HeatingSpares247.com
13
6.0 System Details
© Baxi Heating UK Ltd 2011
6.5 System Filling and Pressurising (Fig. 6)
1. A filling point connection on the central heating return pipework must be provided to facilitate initial filling and pressurising and also any subsequent water loss replacement/refilling.
2. The filling method adopted must be in accordance with all relevant water supply regulations and use approved equipment.
3. Your attention is drawn to: for GB: Guidance G24.2 and recommendation R24.2 of the Water Regulations Guide. for IE: the current edition of I.S. 813 “Domestic Gas Installations”.
4. The sealed primary circuits may be filled or replenished by means of a temporary connection between the circuit and a supply pipe, provided a ‘Listed’ double check valve or some other no less effective backflow prevention device is permanently connected at the inlet to the circuit and the temporary connection is removed after use.
6.6 Expansion Vessel (Central Heating only)
1. The appliance expansion vessel is pre-charged to 0.5 bar. Therefore, the minimum cold fill pressure is 0.5 bar. The vessel is suitable for correct operation for system capacities up to 125 litres (18, 24) 155 litres (27). For greater system capacities an additional expansion vessel must be fitted. For GB refer to BS 7074 Pt 1. For IE, the current edition of I.S. 813 “Domestic Gas Installations”.
6.7 Safety Pressure Relief Valve (Fig. 7)
1. The pressure relief valve is set at 3 bar, therefore all pipework, fittings, etc. should be suitable for pressures in excess of 3 bar and temperature in excess of 100°C.
2. The pressure relief discharge pipe should be not less than 15mm dia, run continuously downward, and discharge outside the building, preferably over a drain. It should be routed in such a manner that no hazard occurs to occupants or causes damage to wiring or electrical components. The end of the pipe should terminate facing down and towards the wall.
3. The discharge must not be above a window, entrance or other public access. Consideration must be given to the possibility that boiling water/steam could discharge from the pipe.
Fig. 6
Fig. 7
Stop Valve
Double Check Valve
DHW Mains Inlet
CH Return
Temporary Hose
Pressure Relief Valve
Discharge Pipe
Stop Valve
Supplied by HeatingSpares247.com
14
7.0 Site Requirements
© Baxi Heating UK Ltd 2011
7.1 Location
1. The boiler may be fitted to any suitable wall with the flue passing through an outside wall or roof and discharging to atmosphere in a position permitting satisfactory removal of combustion products and providing an adequate air supply. The boiler should be fitted within the building unless otherwise protected by a suitable enclosure i.e. garage or outhouse. (The boiler may be fitted inside a cupboard-see Section 7.3).
2. If the boiler is sited in an unheated enclosure then it is recommended to leave the ON/OFF Selector Switch in the domestic hot water and central heating position to give frost protection.
3. If the boiler is fitted in a room containing a bath or shower reference must be made to the relevant requirements. In GB this is the current I.E.E. Wiring Regulations and Building Regulations. In IE reference should be made to the current edition of I.S. 813 “Domestic Gas Installations” and the current ETCI rules.
4. If the boiler is to be fitted into a building of timber frame construction then reference must be made to the current edition of Institute of Gas Engineers Publication IGE/UP/7 (Gas Installations in Timber Framed Housing).
7.2 Clearances (Figs. 8 & 9)
1. A flat vertical area is required for the installation of the boiler.
2. These dimensions include the necessary clearances around the boiler for case removal, spanner access and air movement. Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler.
200mm Min
800mm
450mm
5mm Min
5mm Min
450mm Min
For Servicing
Purposes
Fig. 8
Fig. 9
In Operation
5mm Min
200mm Min
(300mm Min if
using 80/125mm
flueing system)
At Least 1.5°
Supplied by HeatingSpares247.com
15
7.0 Site Requirement
© Baxi Heating UK Ltd 2011
7.3 Ventilation of Compartments
1. Where the appliance is installed in a cupboard or compartment, no air vents are required.
2. BS 5440: Part 2 refers to room sealed appliances installed in compartments. The appliance will run sufficiently cool without ventilation.
7.4 Gas Supply
1. The gas installation should be in accordance with the relevant standards. In GB this is BS 6891. In IE this is the current edition of I.S. 813 “Domestic Gas Installations”.
2. The connection to the appliance is a 22mm copper tail located at the rear of the gas service cock (Fig. 10).
3. Ensure that the pipework from the meter to the appliance is of adequate size. Do not use pipes of a
smaller diameter than the boiler gas connection (22mm).
7.5 Electrical Supply
1. External wiring must be correctly earthed, polarised and in accordance with relevant regulations/rules. In GB this is the current I.E.E. Wiring Regulations. In IE reference should be made to the current edition of ETCI rules.
2. The mains supply is 230V ~ 50Hzfused at 3A.
NOTE: The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance.
Connection may be via a fused double-pole isolator with a contact separation of at least 3mm in all poles and servicing the boiler and system controls only.
3. When the system includes an indirect domestic hot water cylinder it is recommended that a cylinder thermostat is used in conjunction with a 3 port 2 position valve or 2 port zone valve.
7.6 Bath & Shower Rooms
1. If the boiler is fitted in a room containing a bath or shower and NOT FITTED with any optional integral timer or thermostat, it can be fitted in zone 2, (Figs. 11 & 12 show zone dimensions for a bathtub. For other examples refer to the Current I.E.E. Wiring Regulations) reference must be made to the relevant requirements. In GB this is the current I.E.E. Wiring Regulations and Building Regulations. In IE reference should be made to the current edition of I.S. 813 “Domestic Gas Installations” and the current ETCI rules.
Fig. 10
Gas Service Cock
Zone 2
Zone 1
Zone 0
Zone 2
Zone 2
Window Recess
Window Recess
0.6 m
Ceiling
Outside Zones
Zone 2
Zone 1
Zone 0
2.25 m
Window Recess Zone 2
0.6 m
Fig. 11
Fig. 12
In GB Only
In GB Only
Supplied by HeatingSpares247.com
16
7.0 Site Requirements
© Baxi Heating UK Ltd 2011
7.7 Condensate Drain
FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER
The condensate discharge pipe MUST NOT RISE at any point along its length. There MUST be a fall of AT LEAST 2.5° (50mm per metre) along the entire run.
1. The condensate outlet will accept 21.5mm (3/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.
2. Ensure the discharge of condensate complies with any national or local regulations in force.
BS 6798 & Part H1 of the Building Regulations give further guidance.
3. The discharge pipe should be run in a proprietary drain pipe material e.g. PVC, PVC-U, ABS, PVC-C or PP.
4. Metal pipework is NOT suitable for use in condensate discharge systems.
5. The pipe should be a minimum of 21.5mm diameter and must be supported using suitably spaced clips to prevent sagging.
6. It is advisable to keep the condensate pipe internal.
7. External runs greater than 3 metres or runs in cold areas
should use 32mm waste pipe.
8. If the boiler is fitted in an unheated location the entire condensate discharge pipe should be treated as an external run.
9. In all cases discharge pipe must be installed to aid disposal of the condensate. To reduce the risk of condensate being trapped, as few bends and fittings as possible should be used.
10. When discharging condensate into a soil stack or waste pipe the effects of existing plumbing must be considered. If soil pipes or waste pipes are subjected to internal pressure fluctuations when WC's are flushed or sinks emptied then back-pressure may force water out of the boiler trap and cause appliance lockout.
Examples are shown of the following methods of termination:­i) to an internal soil & vent pipe - Fig. 13 ii) via an internal discharge branch (e.g. sink waste) - Fig. 14 iii) to a drain or gully - Fig. 15 iv) to a purpose made soakaway - Fig. 16
Boiler
2.5° Minimum fall
Termination to an internal soil and
vent pipe
450mm min
Boiler
2.5° Minimum fall
External termination via internal discharge
branch
e.g sink waste - downstream
Sink
Pipe must terminate above water level but below surrounding surface
Boiler
Pipe must terminate above water level but below surrounding surface
2.5° Minimum fall
Termination to a drain or gully
Boiler
500mm min
2.5° Minimum fall
Termination to a purpose made soak-
away
Holes in the soak-away must face away from the building
50mm per metre of pipe run
50mm per metre of pipe run
50mm per metre of pipe run
50mm per metre of pipe run
Fig. 13
Fig. 14
Fig. 15
Fig. 16
Supplied by HeatingSpares247.com
17
7.0 Site Requirements
© Baxi Heating UK Ltd 2011
7.8 Flue (Figs. 17 & 18)
NOTE: Due to the nature of the boiler a plume of water
vapour will be discharged from the flue. This should be taken into account when siting the flue terminal.
1. The following guidelines indicate the general requirements for siting balanced flue terminals. For GB recommendations are given in BS 5440 Pt 1. For IE recommendations are given in the current edition of I.S. 813 “Domestic Gas Installations”.
2. If the terminal discharges onto a pathway or passageway, check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be provided.
*4. Reduction to the boundary is possible down to 25mm but flue deflector part no. 5111068 must be used.
IMPORTANT:
• Under car ports we recommend the use of the plume displacement kit.
• The terminal position must ensure the safe and nuisance - free dispersal of combustion products.
Fig. 18
Fig. 17
300 min
Terminal Assembly
Top View Rear Flue
Property Boundar y Line
NOTE: The distance from a fanned draught appliance terminal installed parallel to a boundary may not be less than 300mm in accordance with the diagram below
Opening Window or Door
150mm MIN.
IMPORTANT: If fitting a Plume Displacement Flue Kit, the air inlet must be a minimum of 150mm from any opening windows or doors (see Section 9.0).
Fig. 18a
Plume Displacement Kit
Air Inlet
*
Terminal Position with Minimum Distance (Fig. 18) (mm)
A
1
Directly below an opening, air brick, opening windows, etc. 300
B
1
Above an opening, air brick, opening window etc. 300
C
1
Horizontally to an opening, air brick, opening window etc. 300
D
2
Below gutters, soil pipes or drain pipes. 25
E
2
Below eaves. 25
F
2
Below balconies or car port roof. 25
G
2
From a vertical drain pipe or soil pipe. 25
H
2
From an internal or external corner. 25 I Above ground, roof or balcony level. 300 J From a surface or boundary line facing a terminal. 600 K From a terminal facing a terminal (Horizontal flue). 1200
From a terminal facing a terminal (Vertical flue). 600 L From an opening in carport (e.g. door, window)
into the dwelling. 1200 M Vertically from a terminal on the same wall. 1500 N Horizontally from a terminal on the same wall. 300 R From adjacent wall to flue (vertical only). 300 S From an adjacent opening window (vertical only). 1000 T Adjacent to windows or openings on pitched and flat roofs 600 U Below windows or openings on pitched roofs 2000
1
In addition, the terminal should be no nearer than 150 mm to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window frame.
2
Only ONE 25mm clearance is allowed per installation. If one of the dimensions D, E, F, G or H is 25mm then the remainder MUST be as B.S.5440-1.
Supplied by HeatingSpares247.com
T
J,K
U
R
N
M
I
F
I
B
L
A
G
C
I
D E
H
A
S
F
I
J,K
A
H
I
Likely flue positions requiring a flue terminal guard
18
8.0 Flue Options
© Baxi Heating UK Ltd 2011
8.1 Horizontal Flue Systems
1. The standard flue is suitable only for horizontal termination applications.
2. Maximum permissible equivalent flue lengths are:-
(60/100) (80/125)
Horizontal Concentric 10 metres 20 metres
3. Any additional “in line” bends in the flue system must be taken into consideration. Their equivalent lengths are:­Concentric Pipes: 135° bend 0.5 metres
93° bend 1.0 metres
Twin Flue Pipe 135° bend 0.25 metres
91.5° bend 0.50 metres
The elbow supplied with the standard horizontal telescopic flue kit is not included in any equivalent length calculations
NOTE: Flue length is measured from point (i) to (ii) as shown.
IMPORTANT: All flue systems must be securely supported at least once every metre. Suitable pipe supports are available as accessories.
Horizontal Flues
(ii)
(i)
Plume Displacement Kit 60 /100 Ø
1M Extensions, 45° & 93° elbows
are also available - see Section 9.0
NOTE: Horizontal flue pipes should always be installed with at least a 1.5° fall from the terminal to allow condensate to run back to the boiler.
(ii)
(i)
This bend is equivalent to 1 metre
Total equivalent length =
A+B+C+2x90°Bends
B
A
C
This bend is equivalent to 1 metre
Supplied by HeatingSpares247.com
19
8.0 Flue Options
© Baxi Heating UK Ltd 2011
Vertical Flues
Vertical Flues (Twin Pipe)
(ii)
(i)
(ii)
(i)
8.2 Twin & Vertical Flue Systems
1. Maximum permissible equivalent flue lengths are:-
(60/100) (80/125)
Vertical Concentric 10 metres 20 metres
(80/80)
Twin Pipe 20 metres
3. Any additional “in line” bends in the flue system must be taken into consideration. Their equivalent lengths are:­Concentric Pipes: 135° bend 0.5 metres
93° bend 1.0 metres
Twin Flue Pipe 135° bend 0.25 metres
91.5° bend 0.50 metres
The elbow supplied with the standard horizontal telescopic flue kit is not included in any equivalent length calculations
NOTE: Flue length is measured from point (i) to (ii) as shown.
IMPORTANT: All flue systems must be securely supported at least once every metre. Suitable pipe supports are available as accessories.
The total equivalent length for this example is
= 6.5 metres.
1m extension
135°bend
91.5°bend
1m
0.25m
0.5m
5
2
2
5.0m
0.5m
1.0m
AIR DUCT
N
o
of
fittings/pipes
Sub total
Equivalent
Length Value
Equivalent Length Air Duct = 6.5m
1m extension
135°bend
91.5°bend
1m
0.25m
0.5m
5
2
2
5.0m
0.5m
1.0m
FLUE DUCT
N
o
of
fittings/pipes
Sub total
Equivalent
Length Value
Equivalent Length Flue Duct = 6.5m
(ii)
(i)
C
Roof
Terminal
A
B
This bend is equivalent to 1 metre
Total Equivalent Length = A+B+C+1x90°Bend
All vertical and angled runs must be included, measured from the boiler adaptor point (i) to the joint with the flue terminal point (ii). One 91.5° bend or two 135° bends can be included without reduction of the flue length.
If further elbows are required the flue length must be reduced by the following amounts:-
1 metre for each 91.5° bend
0.5 metre for each 135° bend
300mm Min
Apart
1m Min
to
20m Max
Supplied by HeatingSpares247.com
20
8.0 Flue Options
© Baxi Heating UK Ltd 2011
A
B
K,K1
R
D
C
N
U,W
S
L
H
J
M
E
G
F
P
8.3 Flue Accessories
A2
Key Accessory Size Code No
FLUE GROUP A Concentric Flue System 100mm diameter
A3 Telescopic Internal Flue Kit 315-500mm 5119654 A2 Telescopic Flue (incl elbow) 5118069 A Horizontal Flue Terminal (incl elbow) 5118489 B Flue Extension 1000mm 5111074 C Flue Bend 93° 5111075 D Flue Bend (pair) 135° 5111085 U Pipe Support (painted) 100mmØ 5111080 P Wall Liner 5111067 S Flue Terminal Deflector 5111068
FLUE GROUP N Twin Flue System 80mm diameter
E Flue Extension (pair) 1000mm 5111087 F Flue Bend (pair) 90° 5111072 G Flue Bend (2 pair) 135° 5111086 J Vertical Flue Boiler Adaptor Kit 720089801 H Vertical Flue Adaptor 5111084 Y Flue Horizontal Terminal Kit 5120172 W Pipe Support (pair) 80mm 5111081
FLUE GROUP G Flue System 80/125mm diameter
A4 Horizontal Flue Kit 5118580 B Straight Extension Kit 1000mm 5118584 D Bend Kit (pair) 135° 5118597 C Bend 91.5° 5118588 R Vertical Flue Adaptor 5111070
FLUE GROUP A, N, G Vertical Flue Kits
K Vertical Flue Terminal
(use with Group G) 5111078
K1 Vertical Flue Terminal
(use with Group A) 5118576
L Pitch Roof Flashing 5122151 M Roof Cover Plate 246143 N Flat Roof Flashing 246144
A3
A4
Y
Supplied by HeatingSpares247.com
21
8.0 Flue Options
© Baxi Heating UK Ltd 2011
8.4 Twin Flue Duct Adaptor
1. The kit allows connection of a twin flue system to the boiler adaptor.
8.5 Twin Flue Connection
1. Engage the twin flue duct adaptor in the boiler adaptor, making sure that it is pushed down as far as possible.
2. Ensure that the air & flue ducts are connected correctly and that they are adequately supported (at least once every metre using the available pipe supports).
3. Ensure that all joints and elbows are fully engaged and cannot become disconnected during operation.
Flue Duct Connection
Air Duct Connection
Supplied by HeatingSpares247.com
22
8.0 Flue Options
© Baxi Heating UK Ltd 2011
Fig. 19
100mm 685mm
8.6 For Roof Terminals
1. In the case of a pitched roof 25 - 50 degrees, position the lead tile to replace/flash over existing roof tiling. Make an aperture in the roof suitable for the lower tube of the roof terminal and ensure the integrity of the roof cover is maintained. The adjustable plastic collar can either be positioned on the lead tile or the lower tube of the roof terminal prior to the final positioning of the vertical flue through the tile. Check the collar is correctly located to suit required roof pitch (either 25° to 38° or 37° to 50°). From inside the roof adjust the flue to a vertical position and secure to the roof structure with the clamp supplied.
2. For flat roof installations the aluminium flashing must be incorporated into the roof covering and the appropriate aperture made in the roof decking. The vertical flue is lowered onto the flashing making sure the collar of the flue locates securely with the flashing. (A mastic seal may be necessary). From inside the roof, adjust the flue to a vertical position and secure to the roof structure with the clamp supplied.
IMPORTANT: If the boiler is not fitted immediately after the flue system, temporary precautions must be taken to prevent rain entry into the room of installation. Any precautionary measures must be removed prior to commissioning the boiler.
8.7 Flue Dimensions
The standard horizontal flue kit allows for lengths between 100mm and 685mm from elbow to terminal (Fig. 19).
The maximum permissible equivalent flue length is:
10 metres (60/100 system) 20 metres (80/125 system)
8.8 Flue Trim
1. The rubber flue trim supplied may be fitted to either the outside wall or on the inner wall of installation.
8.9 Terminal Guard (Fig. 20)
1. When codes of practice dictate the use of terminal guards, they can be obtained from most Plumbers’ and Builders’ Merchants.
2. There must be a clearance of at least 50mm between any part of the terminal and the guard.
3. When ordering a terminal guard, quote the appliance name and model number.
4. The flue terminal guard should be positioned centrally over the terminal and fixed as illustrated.
8.10 Flue Deflector (Fig. 21)
1. If required, push the flue deflector over the terminal end and rotate to the optimum angle for deflecting plume. Secure the deflector to the terminal with screws provided.
Fig. 20
Flue Extension
Air Duct
Flue Duct
Cut the same amount off the Air Duct & Flue Duct
Approx
1425mm
Flue Deflector
Fig. 21
Supplied by HeatingSpares247.com
23
9.0 Plume Displacement
© Baxi Heating UK Ltd 2011
9.1 Plume Displacement Kit (Fig. 23)
Kit No 5118638
Content of kit
1 0.9m 60/100 Concentric Flue 1 1m 60 Dia Exhaust Flue Pipe 1 Adaptor 2 60 Dia Support Brackets 1 93° Elbow/Plume Outlet Assembly 1 Flexible Flue Trim 3 “O” Rings 1 ‘Jubilee Clip 1 Elbow
1. This kit is recommended for installations where the condensate plume emitted from the flue may cause a nuisance or affect the surroundings.
2. The terminal must be positioned outside the building with the air inlet facing downward and outlet connection upwards.
3. The plume outlet must always be at least 45° to the wall, with the ‘peak’ uppermost to prevent rain entry (Figs. 24 &
25), and be at least 2 metres above ground level. It must be secured as shown in Fig. 18a. The plume outlet must also be at least 500mm from the air inlet in any direction (Fig. 25).
NOTE: The outlet must be positioned so that any condensate plume is directed away from adjacent surfaces. There must be a constant fall along the entire length of the flue system from the outlet back to the boiler.
4. It is possible to reduce or increase (with the addition of extensions) the length of either or both the 60/100 concentric and 60Ø exhaust.
5. Standard concentric flue extension kits may be added between the boiler elbow and the terminal assembly.
6. The minimum length of the concentric flue is 100mm when measured from the edge of the flue elbow.
IMPORTANT: The maximum equivalent length of concentric flue is:- 8 metres Additional bends may be fitted in the concentric flue, but the equivalent length must be reduced by 1 metre (93° elbow) or 0.5 metres (45° elbow).
7. 60Ø 1 metre extensions (including support bracket), and additional 93° & 45° elbows are available. Any additional 93° & 45° elbows must be accounted for when calculating flue lengths.
NOTE: Permitted positions of the plume outlet relative to doors, windows etc. are the same as for conventional concentric flues as detailed in the main Installation & Servicing Instructions and BS5440 Pt. 1. It is NOT necessary to fit a terminal guard over the air inlet or the plume outlet.
Air Inlet at Bottom
‘Peak’ Uppermost
Fig. 24
Fig. 25
500mm Min.
45°
45°
Outlet must be at least 45° from wall face
93° Elbow/Plume Outlet Assembly
60Ø Exhaust Flue Pipe
60Ø Support Bracket
60Ø Support Bracket
Flexible Flue Trim
60/100Ø Concentric Flue
Adaptor
O Ring
O Ring
O Ring
‘Jubilee’ Clip
0.9 metres
Fig. 23
Fig. 22
Elbow
Supplied by HeatingSpares247.com
24
9.0 Plume Displacement
© Baxi Heating UK Ltd 2011
Concentric 60/100 Flue
60Ø Exhaust
X
Y
Fig. 26
Fig. 27
Flue Length - Worked Example Main System 28 Eco
In Fig. 27 opposite an additional 93° elbow and pair of 45° elbows have been included in the 60Ø exhaust. Also 3 straight extension pieces have been used.
To calculate total length:­Length of 60Ø supplied in kit = 1 metre 3 x 1 metre Extensions = 3 metres 1 x 93° Elbow = 1 metre 2 x 45° Elbow = 1 metre (0.5 metres each)
Total 60Ø = 6 metres
After consulting the table in Example 3 it can be determined that the concentric flue could be up to approximately 2.3 metres long.
Concentric Flue
Support Bracket
45° Elbow
93° Elbow
1 metre Extension
1 metre supplied in kit
Additional Accessories
93° Elbow 5121639 45° Elbow (Pair) 5121370 1 metre 60Ø Extension 5121638
9.2 Determining Permissible Lengths
In the graph the solid line diagonal represents the relationship between the concentric flue assembly (and any extensions) and the 60Ø exhaust (and any extensions or additional bends).
Example 1 - Not Permissible
If, for instance, a concentric length of 5 metres was required and the 60Ø exhaust needed to be 12 metres the graph shows that this combination would NOT be permissible as the intersection point would be above the solid diagonal line.
Example 2 - Flue Lengths OK
Where both lengths have been determined they can be applied to the graph to check that the installation is permissible. For example, if it was known that 2 metres of concentric flue and 4 metres of 60Ø exhaust were required, the values could be applied to the graph as shown in Example 2. As the point of intersection of the dotted lines is below the solid diagonal line, the combination of lengths is shown to be acceptable.
Example 3 - Flue Lengths OK
In the example shown, assume that the concentric part of the flue needs to be 2.3 metres long. Find the position of ‘2.3’ on the horizontal axis of the graph and then project upwards to the solid diagonal line. This is represented by the vertical thick dotted line. Where this dotted line intersects with the solid diagonal line on the graph, project across to the vertical axis. As can be seen this corresponds with 6 metres. Therefore, the total equivalent length of the 60Ø exhaust can be up to 6 metres. Any elbow equivalencies must be accounted for i.e. 93° elbows are equal to 1 metre, each 45° elbow to 0.5 metres.
2
0
2
4
6
8
10
12
14
60 Ø Exhaust (metres) X
Concentric 60/100 Flue (metres) Y
0
16
1
34 65798
24
28
2
0
2
4
6
8
10
12
14
60 Ø Exhaust (metres) X
0
16
1
34 65798
24
28
Example 1
Flue Lengths - Not Permissible
Example 2
Flue Lengths - OK
Example 3
Flue Lengths - OK
Supplied by HeatingSpares247.com
16
14
12
10
8
6
60 Ø Exhaust (metres) X
4
2
0
0
2
34 65798
1
Concentric 60/100 Flue (metres) Y
28
24
25
9.0 Plume Displacement
© Baxi Heating UK Ltd 2011
Min. 2 metres
Fig. 28
Fig. 33
30mm
Fig. 30
Fig. 32
Fig. 31
Adaptor
Flue Trim
Position of ‘Jubilee’ Clip screw
Fig. 29
Spigot
9.3 General Fitting Notes
1. Cut a hole in the external wall which the concentric flue assembly will pass through. The hole should allow the flue to fall back to the boiler at an angle of at least 1.5°.
2. When completed the terminal must be at least 2 metres above ground level (Fig. 28).
3. Measure and cut to size the concentric assembly and any extensions that are being used.
4. Insert the concentric assembly through the hole from outside the building.
5. If required, the flexible flue trim should be fitted prior to this as it cannot be fitted after. Use the large ‘Jubilee’ clip to secure the trim to the flue (See Fig. 29, trim shown dotted), with the screw part of the clip at the bottom.
6. Connect any extensions or elbows that are being used to the concentric assembly. Engage the extension, elbow or concentric assembly in the boiler flue elbow. Fit the boiler flue elbow to the boiler adaptor.
7. Ensure that the concentric assembly and any extensions fall back to the boiler at an angle of at least 1.5° and that the external air inlet is to the bottom.
8. Use suitable brackets to support the concentric assembly and any extensions, and make good inside and outside.
9. The 60Ø exhaust can now be fitted. Slide the adaptor over the plain end of the 60Ø exhaust (Fig. 31) and engage the exhaust in the terminal. Slide the adaptor down over the spigot. Mark and drill the adaptor, using a 2mm bit, as shown in Fig. 30. Secure the adaptor to the spigot using one of the screws supplied.
10. If it is necessary to shorten the 60Ø exhaust or any of the extensions, the excess material must be cut from the plain end of the pipe.
11. Determine the position of the 60Ø exhaust and mark on the wall a suitable position for the support bracket. If extensions are being used, a support bracket is supplied in each kit.
12. Drill the wall, and fit the bracket(s) using the plug and screw provided.
13. Mark and drill the 60Ø exhaust, using a 2mm bit, as shown in Fig. 32. Complete the installation of the 60Ø exhaust, securing in the brackets.
14. Fit the 93° elbow/plume outlet and secure with the two remaining screws supplied. Ensure the plume outlet is at least 45° to the wall and that the ‘peak’ is uppermost (Fig. 33).
Supplied by HeatingSpares247.com
50mm
30mm
26
9.0 Plume Displacement
© Baxi Heating UK Ltd 2011
9.3 General Fitting Notes (cont.)
15. For aesthetic purposes it is permissible to route the 60Ø exhaust in an enclosed box, but the air inlet and plume outlet MUST remain in free air.
16. It is also possible to separate the plume outlet from the 93° elbow to allow the flue to be installed as shown in Fig. 34.
17. To do this, first slacken the two screws retaining the plume outlet to the elbow, and remove the outlet (Fig. 35). The elbow can now be used to connect the vertical to horizontal 60Ø exhaust (Fig. 34). Retighten the screws in the elbow.
18. The outlet can now be fitted into the female end of an 60Ø extension piece. It must be secured using two of the screws supplied in the bag with the ‘Jubilee’ clip.
19. Mark the female end of the extension at 30mm as shown in two positions, directly opposite each other (Fig. 36).
20. Using a suitable bit (e.g. 2mm), drill through the extension and outlet. Secure using two of the screws supplied.
21. The remaining screw must be used to secure the adaptor to the concentric terminal.
22. When the plume outlet is positioned under a balcony or other projection (Fig. 37) it must protrude at least 200mm (it is not necessary to extend it further than this).
23. When under balconies or projections it is permissible to rotate the concentric flue length up to 70°, clockwise or anti-clockwise (Fig. 38), if there is insufficient space to connect vertically.
24.This will allow the connection of the exhaust to the outlet spigot.
25. All other minimum & maximum dimensions must be adhered to, and the air inlet positioned such that it will not be subject to rain entry.
30mm
Fig. 35
Fig. 36
Fig. 34
Fig. 37
Plume Outlet
Elbow
Fig. 38
Outlet Spigot
Concentric Flue Length (shown end-on)
Supplied by HeatingSpares247.com
500mm Min.
200mm Min.
70°
27
10.0 Installation
© Baxi Heating UK Ltd 2011
10.1 Unpacking & Initial Preparation
The gas supply, gas type and pressure must be checked for suitability before connection (see Section 7.4).
1. Remove staples, open flaps and remove cardboard sheet. Remove the polystyrene side pieces and literature. Two people can then lift out the boiler (Fig. 39).
2. After considering the site requirements (see Section 7.0) position the fixing template on the wall ensuring it is level both horizontally and vertically.
3. Mark the position of the two most suitable fixing slots for the wall plate and boiler lower fixing holes. It is preferable to use the vertical fixing slots.
4. Mark the position of the centre of the flue hole (rear exit). For side flue exit, mark as shown (Fig. 40).
5. If required, mark the position of the gas and water pipes. Remove the template.
6. Cut the hole for the flue (minimum diameter 116mm).
7. Drill the wall as previously marked to accept the wall plugs supplied. Secure the wall plate using the fixing screws.
8. Using a spirit level ensure that the plate is level before finally tightening the screws.
99. Connect the gas and water pipes to the valves on the wall plate using the copper tails supplied. Ensure that the sealing washers are fitted between the connections.
10.2 Flushing
1. Connect a tube to the central heating flow or return pipe (Fig. 41).
2. Flush thoroughly (see System Details, Section 6.1).
Fig. 41
145mm
For Side Flue Exit
Central Heating Return
Flushing Tube
Wall Plate
Fig. 40
Fig. 39 Unpacking Procedure
Supplied by HeatingSpares247.com
28
10.0 Installation
© Baxi Heating UK Ltd 2011
10.3 Fitting The Boiler
1. Lift the boiler using the Lifting Points as shown by the shaded areas (Fig. 43). The boiler should be lifted by TWO PEOPLE. Engage the slots at the top rear of the boiler on the wall plate (Fig. 42) (see Safe Manual Handling page 5).
2. Ease the boiler forwards and remove the sealing caps from the boiler connections (Fig 43).
NOTE: A small amount of water may drain from the boiler once the caps are removed.
3. Insert the sealing washers between the valves and pipes
on the wall plate and the boiler connections. The rubber washers must be used on the gas connection.
4. Tighten all the connections.
10.4 Fitting the Pressure Relief Discharge Pipe
(Fig. 44)
1. Remove the discharge pipe from the kit.
2. Determine the routing of the discharge pipe in the vicinity of the boiler. Make up as much of the pipework as is practical, including the discharge pipe supplied.
3. The pipework must be at least 15mm diameter and run continuously downwards to a discharge point outside the building. See section 6.7 for further details.
4. Utilising one of the sealing washers, connect the discharge pipe to the adaptor and tighten the nut.
5. Complete the discharge pipework and route it to the outside discharge point.
IMPORTANT: Make all soldered joints before connecting to the pressure relief valve.
10.5 Condensate Drain (see Section 7.7)
1. Connect the condensate drain to the trap outlet pipe.
Ensure the discharge of condensate complies with any national or local regulations in force (see British Gas “Guidance Notes for the Installation of Domestic Gas Condensing Boilers”.
2. The connection will accept 21.5mm (
3
/4in) plastic overflow pipe which should generally discharge internally into the household drainage system. If this is not possible, discharge into an outside drain is acceptable.
Fig. 44
Pressure Relief Valve
Wall Plate
Discharge Pipe
Suggested Lifting Points
shown as shaded area
Fig. 43
Remove Sealing Caps from under the Boiler
Supplied by HeatingSpares247.com
29
10.0 Installation
© Baxi Heating UK Ltd 2011
Fig. 45
10.6 Fitting The Flue
HORIZONTAL FLUE
1. The standard flue is suitable for lengths between 100mm minimum and 685mm maximum, as measured from the edge of the flue elbow outlet to the joint between the terminal and air duct (Fig. 45).
2. Locate the flue elbow on the adaptor at the top of the boiler. Set the elbow to the required orientation (Fig. 47).
NOTE: The flue elbow is angled at 93 degrees to ensure a fall back to the boiler.
3. Measure the distance from the outside wall face to the elbow. This dimension will be known as ‘X’ (Fig. 48).
4. To dimension ‘X’ add 50mm. This dimension to be known as ‘Y’.
IMPORTANT: Check all dimensions before cutting.
5. Mark dimension ‘Y’ on the flue as shown (Fig. 49). Carefully cut the waste material from the flue, ensuring that the ducts are square and free from burrs.
Fig. 49
Wall Thickness
(X)
Wall Thickness
(X)
Flue Elbow
Fig. 47
Adaptor
Apply Lubricant for ease of assembly.
Ensure Elbow is fully engaged into Boiler Adaptor
Fig. 48
Y
Flue
Waste
100mm 685mm
Supplied by HeatingSpares247.com
30
10.0 Installation
© Baxi Heating UK Ltd 2011
Slots at bottom
Inner Flue Support Bracket
Fig. 50
Fig. 51
Fig. 52
Apply Lubricant for ease of assembly.
Ensure Flue is fully engaged into Flue Elbow
10.6 Fitting the Flue (Cont)
6. The inner flue duct support bracket may be in the waste portion of the flue. In this case retrieve the bracket before discarding the waste.
7. Take the inner flue support bracket (if not already fitted) and engage it over the flue duct. This will centralise the flue and air ducts, and ease assembly (Fig. 51).
8. Insert the flue through the hole in the wall. Fit the elbow to the boiler adaptor, ensuring that it is pushed fully in.
9. Draw the flue back through the wall and engage it in the elbow. It may be necessary to use soap solution or similar to ease assembly of the elbow adaptor and flue (Fig. 51).
10. Ensure that the terminal is positioned with the slots to the bottom (Fig. 52).
IMPORTANT: It is essential that the flue terminal is fitted as shown to ensure correct boiler operation and prevent water entering the flue.
11. Make good between the wall and air duct outside the building.
12. Fit the flue trim if required, and if necessary fit a terminal guard (see Section 8.8 & 8.9).
Supplied by HeatingSpares247.com
31
© Baxi Heating UK Ltd 2011
10.6 Fitting the Flue (Cont)
CONCENTRIC VERTICAL FLUE
15. Once the length of the vertical concentric extension has been determined mark and carefully cut off the excess material. The cut end MUST be square and free of burrs to ensure correct insertion into the boiler adaptor.
16. Measure 25mm from the end of the flue extension and apply a length of tape around the outer duct (Fig. 53).
17. Engage the extension into the adaptor up to this position (Fig. 54). Once the installation of the flue is complete and all support brackets are securely in place remove the tape.
Adaptor
Apply Lubricant for ease of assembly.
Ensure Extension is fully engaged into Boiler Adaptor
25mm
Extension
Cut End
Fig. 53
Tape
10.0 Installation
Fig. 54
Supplied by HeatingSpares247.com
32
10.0 Installation
© Baxi Heating UK Ltd 2011
10.7 Making The Electrical Connections
NOTE: Both the Live and Neutral connections are fused.
To connect an external control proceed as follows:-
1. Slacken the facia panel securing screws and lift the outercase panel so that its securing tabs are clear of the facia. Remove the panel.
2. Completely undo the screws securing the facia panel and hinge it down (Fig. 55).
3. Undo the terminal block cover securing screw and remove the cover (Fig. 55).
4. Slacken the unused cable clamp on the LH side of the boiler chassis (Fig. 56). Insert the external control wiring through the clamp and route it to the terminal block.
5. Refer to the instructions supplied with the control.
IMPORTANT: The room thermostat MUST be suitable for 230V switching.
6. Remove the link between terminals 1 & 2. The switched output from the external control must be connected to terminal 1 (Fig. 57).
7. Ensure that the external control input cable(s) have sufficient slack to allow the control box to drop down. Tighten the cable clamp on the boiler chassis.
8. Replace the terminal block cover, routing the external control input cable(s) through the second cut-out.
10.8 Preliminary Electrical Checks
1. Prior to commissioning the boiler preliminary electrical system checks should be carried out.
2. These should be performed using a suitable meter, and include checks for Earth Continuity, Resistance to Earth, Short Circuit and Polarity.
Fig. 56
Fig. 57
Fig. 55
Terminal Block
Fuses
Cable Clamp
Facia Panel
y
Terminal Block Cover
Supplied by HeatingSpares247.com
Fused supply 3A 230V ~ 50Hz
230V
Earth (green/yellow)
Neutral (blue)
Live (brown)
Always fit fast
blow 2A fuse
1
2
bk
bk
g/
b
br
33
11.0 Commissioning
© Baxi Heating UK Ltd 2011
Pump
Automatic Air
Vent
Pressure Gauge
Screw
bar
0
1
2
3
4
Fig. 59
Selector Switch
Central Heating
Temperature Control
Calibration
Control
Pump
Fig. 61
Fig. 60
Display
Heat Exchanger
Automatic Air Vent
Fig. 58
11.1 Commissioning the Boiler
1. Reference should be made to BS:EN 12828 & 14336 when commissioning the boiler.
2. At the time of commissioning, complete all relevant sections of the Benchmark Checklist at the rear of this publications.
3. Open the mains water supply to the boiler.
IMPORTANT: The heat exchanger air vent on top of the boiler (Fig. 58) MUST be opened before filling the primary system.
4. Open all hot water taps to purge the DHW system.
5. Ensure that the filling loop is connected and open, then open the heating flow and return valves on the boiler.
6. Open the screw on the automatic air vent on the pump body (Fig. 59).
7. The system must be flushed in accordance with BS 7593 (see Section 6.2) and the flushing agent manufacturers instructions.
8. Pressurise the system to 1.5 bar (Fig. 60) then close and disconnect the filling loop.
9. Turn the gas supply on and purge according to in GB BS 6891 and in IE I.S. 813 “Domestic Gas Installations”.
10. Test for gas tightness.
11. Hinge the facia panel upwards and refit the case front panel. Tighten the securing screws.
IMPORTANT: The combustion for this appliance has been checked, adjusted and preset at the factory for operation on the gas type specified on the appliance data plate. No measurement of the combustion is necessary. Do not adjust the air/gas ratio valve.
12. Having checked:
• That the boiler has been installed in accordance with these instructions.
• The integrity of the flue system and the flue seals.
• The integrity of the boiler combustion circuit and the relevant seals.
Proceed to put the boiler into operation as follows:
Supplied by HeatingSpares247.com
Reset
2
1
3
4
0
bar
34
11.0 Commissioning
© Baxi Heating UK Ltd 2011
Selector Switch
Display
Central Heating
Temperature Control
Calibration Control
Fig. 63
Fig. 64
Fig. 65
Fig. 66
Fig. 67
Central Heating
Temperature Control
Calibration Control
Fig. 62
x 2
11.2 Check the Operational (Working) Gas Inlet
Pressure
1. Ensure that all controls are calling for heat, and the selector switch is in the central heating and hot water position ( ). The current boiler temperature is shown on the display.
2. To check the gas rate it is necessary to set the boiler to ‘Calibration Mode’.
3. Turn both temperature control knobs fully anticlockwise, then quickly turn the DHW temperature knob
1
/4clockwise
twice and back fully anticlockwise (Fig. 62).
4. The display will now alternate between ‘SF’ and the current boiler temperature and both green LEDs will flash (Figs. 63 &
64).
5. Turn CH temperature control knob fully clockwise. As the knob is turned the display will change from ‘0’ to ‘00’ (Fig. 65) indicating maximum rate, then revert to ‘P’ alternating with the current boiler temperature (Figs 66 & 67).
6. With the boiler operating in the maximum rate condition check that the operational (working) gas pressure at the inlet gas pressure test point (Fig. 62a) is in accordance with B.S. 6798 & B.S. 6891.
7. Ensure that this inlet pressure can be obtained with all other gas appliances in the property working.
Measure the Gas Rate
8. With any other appliances & pilot lights turned OFF the gas rate can be measured. It should be between:-
24 model 2.76 m
3
/h
28 model 3.10 m
3
/h
9. The ‘Calibration Function’ is active for 20 minutes unless the maximum CH temperature is exceeded.
10. The function can be disabled at any time by turning the DHW temperature knob.
11. Carefully read and complete all sections of the Benchmark Commissioning Checklist at the rear of this publication that are relevant to the boiler and installation. These details will be required in the event of any warranty work. The publication must be handed to the user for safe keeping and each subsequent regular service visit recorded.
12. For IE, it is necessary to complete a “Declaration of Conformity” to indicate compliance with I.S. 813. An example of this is given in I.S. 813 “Domestic Gas Installations”. This is in addition to the Benchmark Commissioning Checklist.
Gas Valve
Gas Pressure
Test Point
Fig. 62a
Supplied by HeatingSpares247.com
Reset
2
1
4
0
bar
3
35
12.0 Completion
© Baxi Heating UK Ltd 2011
12.1 Completion
1. Instruct the user in the operation of the boiler and system including the integral timer, explaining the operational sequence.
2. Set the central heating and hot water temperature control knobs to the requirements of the user.
3. Carefully read and complete all sections of the Benchmark Commissioning Checklist at the rear of this publication that are relevant to the appliance and installation. These details will be required in the event of any warranty work. The publication must be handed to the user for safe keeping and each subsequent regular service visit recorded.
4. For IE, it is necessary to complete a “Declaration of Conformity” to indicate compliance with I.S. 813. An example of this is given in I.S. 813 “Domestic Gas Installations”. This is in addition to the Benchmark Commissioning Checklist.
5. Hand over the Users Operating, Installation and Servicing Instructions giving advice on the necessity of regular servicing.
Fig. 68
Facia Panel
Case Front Panel
Supplied by HeatingSpares247.com
36
13.0 Servicing
© Baxi Heating UK Ltd 2011
Case Front Panel
Fig. 69
Facia Panel Securing
Screws
Fig. 70
Inner Door
Panel
Fig. 71
Condensate
Trap
Sump
13 .1 Annual Servicing
1. For reasons of safety and economy, it is recommended that the boiler is serviced annually. Servicing must be performed by a competent person in accordance with B.S. 7967-4.
2. After servicing, complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication.
IMPORTANT: During routine servicing, and after any maintenance or change of part of the combustion circuit, the following must be checked:-
• The integrity of the complete flue system and the flue seals.
• The integrity of the boiler combustion circuit and relevant seals as described in Section 13.2.
• The operational gas inlet pressure as described in Section
11.2.1 to 11.2.7 and the gas rate as described in 11.2.8.
• The combustion performance as described in ‘Check the
Combustion Performance’ (13.1.4 to 13.1.6 below).
3. Competence to carry out Checking Combustion
Performance
B.S. 6798 ‘Specification for Installation & Maintenance of Gas Fired Boilers not exceeding 70kW’ advises that:-
• The person carrying out a combustion measurement should have been assessed as competent in the use of a flue gas analyser and the interpretation of the results.
• The flue gas analyser used should be one meeting the requirements of BS7927 or BS-EN50379-3 and be calibrated in accordance with the analyser manufacturers’ requirements.
• Competence can be demonstrated by satisfactory completion of the CPA1 ACS assessment, which covers the use of electronic portable combustion gas analysers in accordance with BS 7967, Parts 1 to 4.
Check the Combustion Performance (CO/CO
2
ratio)
4. Set the boiler to operate at maximum rate as described in Section 15.1.1 to 15.1.6.
5. Remove the plug from the flue sampling point, insert the analyser probe and obtain the CO/CO
2
ratio. This must be
less than 0.004.
6. If the combustion reading (CO/CO
2
ratio) is greater than this, and the integrity of the complete flue system and combustion circuit seals has been verified, and the inlet gas pressure and gas rate are satisfactory either:
• Perform the ‘Annual Servicing - Inspection’ (Section 13.2) &
re-check
• Adjust the gas valve (Section 15.0) & re-check
• Replace the gas valve (Section 14.23) & re-check
13.2 Annual Servicing - Inspection
1. Ensure that the boiler is cool.
2. Ensure that both the gas and electrical supplies to the
boiler are isolated.
3. Slacken the screws securing the facia panel. Lift the outercase panel so that its securing tabs are clear of the facia. Remove the panel, allowing the facia to hinge down (Fig. 69).
4. Remove the screws securing the inner door panel. Lift the panel slightly to disengage it from the studs on top of the case (Fig. 70).
5. Unscrew the sump from the bottom of the condensate trap assembly (Fig. 71) and remove any deposits from the sump and trap. Clean as necessary and replace the sump.
Supplied by HeatingSpares247.com
37
13.0 Servicing
© Baxi Heating UK Ltd 2011
13.2 Annual Servicing - Inspection (Cont)
6. Undo the nut on the gas pipe at the gas/air inlet (Fig. 72) and the gas valve. Remove the pipe, taking care not to lose the sealing washers. Also remove the injector.
7. Disconnect the electrode lead caps, remove the strain relief clip from the sensing lead and disconnect the lead. Remove the fan electrical plugs and pull the sensing pipe off the fan.
8. Undo the screw securing the fan air inlet pipe to the bracket on the boiler top panel. Remove the pipe (Fig. 73).
9. Undo the five retaining nuts and washers and remove the fan, gas/air inlet and burner assembly (Figs. 74).
10. Carefully clean any debris from the heat exchanger.
11. Inspect the burner, electrode position, insulation, and gasket, cleaning or replacing if necessary. Clean any dirt or dust from the air box.
12. Reassemble in reverse order.
13. Complete the relevant Service Interval Record section of the Benchmark Commissioning Checklist at the rear of this publication and then hand it back to the user.
Gas Pipe
Injector
Fan Air Inlet Pipe
Gas/Air Inlet
Fan, Gas/Air Inlet &
Burner Assembly
Fig. 72
Fig. 73
Fig. 74
Supplied by HeatingSpares247.com
38
14.0 Changing Components
© Baxi Heating UK Ltd 2011
IMPORTANT: When changing components ensure that
both the gas and electrical supplies to the boiler are isolated before any work is started. When the component has been changed turn the selector switch fully anticlockwise against the spring pressure to the reset position and hold for 5 seconds to reset the boiler before recommissioning.
See Section 13.1 “Annual Servicing” for removal of case panel, door etc.
14.1 Igniter (Fig. 75)
1. Disconnect the igniter feed plug and the electrode leads, noting their positions.
2. Undo the nuts and screws securing the igniter to the boiler top panel. Remove the igniter.
3. Fit the new igniter and reassemble in reverse order.
14.2 Electrode Assembly (Fig. 76)
1. Disconnect the electrode lead caps, remove the strain relief clip from the sensing lead and disconnect the lead.
2. Undo the extended nuts securing the electrode assembly to the combustion box panel and remove the assembly.
3. Check the condition of the sealing gasket and replace if necessary. Reassemble in reverse order.
Fig. 75
Igniter
Igniter Feed
Plug
Electrode
Leads
Fig. 76
Spark
Electrode
Electrode
Leads
Sealing
Gasket
Supplied by HeatingSpares247.com
39
14.0 Changing Components
© Baxi Heating UK Ltd 2011
14.3 Fan
1. Undo the nut on the gas pipe at the gas/air inlet (Fig. 77) and the gas valve. Remove the pipe, taking care not to lose the sealing washers. Also remove the injector.
2. Disconnect the electrode lead caps, remove the strain relief clip from the sensing lead and disconnect the lead. Remove the fan electrical plugs and pull the sensing pipe off the fan.
3. Undo the screw securing the fan air inlet pipe to the bracket on the boiler top panel. Remove the pipe (Fig. 78).
4. Undo the five retaining nuts and washers and remove the fan, gas/air inlet and burner assembly (Fig. 79).
5. Remove the air box and gasket from the fan and transfer to the new fan. Examine and replace the gasket if necessary.
6. Remove the four nuts and separate the fan from the gas/air inlet. Note the position of the orifice plate and examine the gasket, replacing if necessary (Fig. 79).
7. Fit the new fan, ensuring that the orifice plate is correctly fitted, and that the gasket is in position.
8. Examine the insulation around the burner and the heat exchanger gasket and replace if necessary.
9. Reassemble in reverse order, ensuring that the injector is in place and the sensing pipe is connected to the fan.
14.4 Injector (Fig. 77)
1. Undo the nut on the gas pipe at the gas/air inlet and the gas valve. Remove the pipe.
2. Extract and replace the injector and reassemble in reverse order. Check the condition of the sealing washers, replacing if necessary.
Air Box
Fan
Gasket
Orifice Plate
Fig. 79
Fig. 77
Gas Pipe
Injector
Fan Air Inlet Pipe
Gas/Air Inlet
Gasket
Gasket
Gas/Air Inlet
Fig. 78
Supplied by HeatingSpares247.com
40
14.0 Changing Components
© Baxi Heating UK Ltd 2011
14.5 Burner (Fig. 80)
1. Undo the nut on the gas pipe at the gas/air inlet and the gas valve. Remove the pipe, taking care not to lose the sealing washers. Also remove the injector.
2. Disconnect the electrode lead caps, remove the strain relief clip from the sensing lead and disconnect the lead. Remove the fan electrical plugs and pull the sensing pipe off the fan.
3. Undo the screw securing the fan air inlet pipe to the bracket on the boiler top panel. Remove the pipe.
4. Undo the five retaining nuts and washers and remove the fan, gas/air inlet and burner assembly.
5. Remove the electrode assembly and draw the insulation piece away. Undo the burner securing screws.
6. Fit the new burner and gasket, examine the insulation and heat exchanger gasket, replacing if necessary.
7. Reassemble in reverse order.
14.6 Insulation (Fig. 80)
1. Undo the nut on the gas pipe at the gas/air inlet and the gas valve. Remove the pipe, taking care not to lose the sealing washers. Also remove the injector.
2. Disconnect the electrode lead caps, remove the strain relief clip from the sensing lead and disconnect the lead. Remove the fan electrical plugs and pull the sensing pipe off the fan.
3. Undo the screw securing the fan air inlet pipe to the bracket on the boiler top panel. Remove the pipe.
4. Undo the five retaining nuts and washers and remove the fan, gas/air inlet and burner assembly.
5. Remove the electrode assembly and draw the insulation piece away. Replace the insulation and reassemble in reverse order. Examine the heat exchanger gasket and replace as necessary.
Fig. 80
Electrode Assembly
Burner
Insulation
Supplied by HeatingSpares247.com
41
14.0 Changing Components
© Baxi Heating UK Ltd 2011
14.7 Safety Thermostat (Fig. 81)
1. Pull the plug off the thermostat.
2. Remove the screws securing the thermostat to the mounting plate on the flow pipe.
3. Reassemble in reverse order, ensuring that the plug is pushed fully on.
14.8 Central Heating Temperature Sensor (NTC)
(Fig. 82)
1. Drain the boiler primary circuit. Pull the plug off the safety thermostat and disconnect the in-line plug in the sensor wire.
2. Unscrew the sensor from the heat exchanger. Reassemble the new sensor in reverse order, using a new sealing washer.
14.9 Water Pressure Sensor (Fig. 83)
1. Drain the boiler primary circuit.
2. Disconnect the two wires from the sensor.
3. Unscrew the sensor from the hydraulic outlet assembly, examine the sealing washer and replace if necessary.
4. Reassemble in reverse order. The component is not polarised - either wire will fit each terminal.
14.10 DHW Temperature Sensor (NTC) (Fig. 83)
1. Turn off the mains cold water supply tap and draw off the residual domestic hot water.
2. Ease the retaining tab on the sensor away and disconnect the electrical plug.
3. Unscrew the sensor from the hydraulic outlet assembly. Examine the sealing washer,replacing if necessary.
4. Reassemble in reverse order. The plug will only fit one way.
Central Heating
Temperature Sensor
Safety Thermostat
Fig. 81
Fig. 82
Fig. 83
Water Pressure Sensor
Domestic Hot Water Temperature Sensor
Supplied by HeatingSpares247.com
42
14.0 Changing Components
© Baxi Heating UK Ltd 2011
14.11 Heat Exchanger Automatic Air Vent (Fig. 84)
1. Drain the boiler primary circuit and unscrew the automatic air vent from the pump body.
2. Examine the ‘O’ ring seal, replacing if necessary, and fit it to the new automatic air vent.
3. Reassemble in reverse order, transferring the grommet to the new vent.
4. Ensure that the grommet is is sealed correctly to the boiler top panel.
14.12 Pump - Head Only (Fig. 85)
1. Drain the boiler primary circuit and remove the socket head screws securing the pump head to the body and draw the head away.
2. Undo the screw on the pump wiring cover and remove the cover. Using a suitable flat bladed screw driver press the cable securing levers downwards to release each wire after noting their position.
3. A standard replacement Grundfos 15-60 head can now be fitted. Connect the pump wiring to the new head. The pump speed must be set to 3 (Fig. 86).
4. Reassemble in reverse order.
14.13 Pump - Complete (Fig. 87)
1. Drain the boiler primary circuit.
2. Undo the two screws securing the body to the pipe and manifold and draw the pump forwards.
3. Undo the screw on the pump wiring cover and remove the cover. Using a suitable flat bladed screw driver press the cable securing levers downwards to release each wire after noting their position.
4. Unscrew the automatic air vent from the pump body.
5. Connect the wiring to the new pump. Examine the ‘O’ ring seals on the return pipe and manifold, replacing if necessary.
6. Fit the air vent to the pump body and reassemble in reverse order.
14.14 Automatic Air Vent (Fig. 87)
1. Drain the boiler primary circuit and unscrew the automatic air vent from the pump body.
2. Examine the ‘O’ ring seal, replacing if necessary, and fit it to the new automatic air vent.
3. Reassemble in reverse order.
Pump Setting
Socket Headed
Screw
Pump Head
Pump Body
Automatic Air
Vent
Fig. 85
Fig. 87
Fig. 86
Pump Wiring
Cover
Pump Wiring
Cover
Heat Exchanger
Air Vent
Grommet
Fig. 84
Supplied by HeatingSpares247.com
43
14.0 Changing Components
© Baxi Heating UK Ltd 2011
14.15 Pressure Gauge (Figs. 88 & 89)
1. Drain the boiler primary circuit and undo the nut on the pressure gauge capillary.
2. Undo the screws securing the gauge retaining bracket.
3. Remove the bracket and gauge assembly. Depress the barbs on the side of the gauge and remove the retaining bracket.
4. Examine the sealing washer, replace if necessary.
5. Reassemble in reverse order.
14.17 Pressure Relief Valve (Fig. 90)
1. Drain the boiler primary circuit.
2. Disconnect the discharge pipe from the valve. Using a suitable hexagon key undo the grub screw sufficiently to release the valve.
3. Note the orientation of the valve, rotate it and withdraw it from the manifold.
4. Fit the new valve and ‘O’ ring seal and set to the previously noted orientation. Reassemble in reverse order.
Pressure Gauge
Pressure Gauge
Capillary
Gauge Retaining
Bracket
Fig. 89
Fig. 88
‘O’ Ring Seal
Discharge
Pipe
Grub Screw
Pressure
Relief Valve
Fig. 90
Supplied by HeatingSpares247.com
44
14.0 Changing Components
© Baxi Heating UK Ltd 2011
14.18 P.C.B. (Figs. 91 & 92)
1. Note the settings of the temperature control knobs, rotate them fully anticlockwise and carefully pull them off the drive pins.
2. Completely undo the screws securing the control box cover and release the cover retaining barbs from their slots. Disengage the rear of the cover from the control box hinge pin.
3. Note the position of all plugs and wires on the P.C.B. and disconnect them.
4. Undo the securing screws and remove the P.C.B. Transfer the control knob drive pins to the new P.C.B. and turn them fully anticlockwise.
5. Reassemble in reverse order, ensuring that the temperature controllers are reset to their previous positions.
14.19 Selector Switch (Figs. 91 & 92)
1. Note the setting of the selector switch knob and carefully pull it off the facia.
2. Completely undo the screws securing the control box cover and release the cover retaining barbs from their slots. Disengage the rear of the cover from the control box hinge pin.
3. Note the position of the electrical connections and the orientation of the switch. Remove the electrical connections.
4. Remove the screws securing the switch to the facia panel.
5. Fit the new switch, ensuring that it is correctly positioned and reassemble in reverse order.
Control Box Cover
P.C.B.
Selector
Switch
Facia
Selector Switch Knob
Temperature Control Knobs
Fig. 91
Fig. 92
Drive Pins
Supplied by HeatingSpares247.com
45
14.0 Changing Components
© Baxi Heating UK Ltd 2011
14.20 Gas Valve (Fig. 93)
IMPORTANT: After replacing the valve the CO2must be checked and adjusted as detailed in Section 15.0 Setting the Gas Valve. Only change the valve if a suitable calibrated combustion analyser is available, operated by a competent person - see section 13.1.
1. Turn the gas cock off and undo the nut on the gas feed elbow under the boiler.
2. Remove the screws securing the gas valve to the boiler bottom panel.
3. Pull off the power lead, earth lead and sensing pipe.
4. Undo the nut on the gas pipe at the gas/air inlet and the gas valve. Remove the pipe, taking care not to lose the sealing washers. Remove the valve.
5. Remove the outlet adaptor and inlet pipe and transfer them to the new valve. Examine the ‘O’ ring seals, replace if necessary.
6. Reassemble in reverse order., ensuring that all seals are in place and the injector is fitted.
NOTE: To assist the boiler to light prior to final setting, use a suitable hexagon key to wind out the Throttle adjustment screw until it is flush with the valve body, then turn the screw 4 full turns clockwise (Fig. 93a). If the boiler will not light, or the correct CO
2
cannot be achieved
contact the ‘heateam’ technical helpline.
14.21 Expansion Vessel (Fig. 94)
1. Drain the boiler primary circuit and undo the nut on the vessel connection pipe.
2. Remove the screw retaining the air inlet pipe, and swing the pipe to one side.
3. Undo and remove the locknut and spring washer securing the vessel spigot to the boiler lower panel.
4. Remove the bracket and vessel from the boiler.
5. Locate the retaining bracket on the upper flange of the new vessel and fit to the boiler.
6. Examine the sealing washer, replacing if necessary, and reassemble in reverse order.
Gas Valve
Gas Feed
Elbow
Fig. 93
Earth Lead
Expansion Vessel
Boiler Chassis
Lock Nut
Spring
Washer
Fig. 94
Retaining Bracket
Sensing Pipe
Venturi Inlet
Pipe
Power Lead
Fig. 93a
Throttle
Adjustment Screw
Supplied by HeatingSpares247.com
46
© Baxi Heating UK Ltd 2011
Selector Switch
Display
Central Heating
Temperature Control
Domestic Hot Water Temperature Control
Fig. 96
Fig. 97
Fig. 98
Fig. 99 Fig. 100
Central Heating
Temperature Control
Calibration Control
Fig. 95
x 2
Fig. 101
Flue Adaptor Test
Point
Plug
Analyser Probe
Throttle
Adjustment Screw
(cover removed)
Offset
Adjustment Screw
(cap fitted)
Gas Valve
Fig. 102
If the CO2is reset at minimum rate it must be rechecked at maximum rate again and adjusted if required. If the CO2is reset at maximum rate it must be rechecked at minimum rate and adjusted if required.
Do not turn the adjustment screws more than 1/8 of a turn at a time. Allow the analyser reading to settle before any further adjustment
Reduce CO
2
at min. rate
Increase CO
2
at min. rate
Reduce CO
2
at max. rate
Increase CO
2
at max. rate
15.0 Setting the Gas Valve
15.1 Setting the Gas Valve (CO
2
check)
IMPORTANT: The CO
2
must be only be checked and adjusted to set the valve if a suitable calibrated combustion analyser is available, operated by a competent person - see Section 13.1
1. The combustion (CO
2
) may be checked after running the boiler for several minutes. To do this it is necessary to set the boiler to ‘Calibration Mode’.
2. Ensure that all external controls are calling for heat. The actual current boiler temperature is shown on the display.
3. Turn both control knobs fully anticlockwise, then quickly turn the right hand knob
1
/4clockwise twice and back fully
anticlockwise (Fig. 95).
4. The display will now alternate between ‘SF’ and the current boiler temperature and both green LEDs will flash (Figs. 96 & 97).
5. Turn the left hand knob fully clockwise. As the knob is turned the display will change, indicating the fan speed.
6. The display will show ‘00’, indicating maximum rate, then revert to ‘P ‘ alternating with the current boiler temperature (Figs. 98, 99 & 100).
7. Remove the plug from the flue sampling test point. Insert the analyser probe and allow sufficient time for the reading to settle (Fig. 101).
The CO
2
should be 9.0% + 0.0 - 0.4
8. It is possible to alter the CO
2
by adjustment of the gas valve. Remove the plastic cover from the Throttle Adjustment Screw. At maximum rate the Throttle Adjustment Screw should be turned, using a suitable hexagon key, until the correct reading is obtained (Fig. 102). Turning clockwise will reduce the CO
2
. Anticlockwise will
increase th e CO
2
.
9. The CO
2
must then be checked at minimum rate. Turn the left hand knob fully anti-clockwise. As the knob is turned the display will change, indicating the fan speed. When the display reads ‘ 0’ the boiler runs at minimum rate.
The CO
2
should be 8.4% + 0.0 - 0.4
10. With the boiler on minimum, the Offset Adjustment Screw must be altered, using a suitable hexagon key, after removing the cap (Fig. 102). Turning anti-clockwise will reduce the CO
2
. Clockwise will increase th e CO2.
11. The ‘Calibration Function’ is maintained for 20 minutes unless the maximum CH temperature is exceeded. The function can be disabled at any time by turning the right hand knob.
12. Check the Combustion Performance (CO/CO
2
ratio).
This must be less than 0.004.
Supplied by HeatingSpares247.com
Reset
2
1
3
4
0
bar
47
16.0 Electrical
© Baxi Heating UK Ltd 2011
Water Pressure
16.1 Illustrated Wiring Diagram
Supplied by HeatingSpares247.com
Switch
Return Heating Temp Sensor
b
b
Central Heating NTC Sensor
gr
gr
Overheat Stat
b
b
r
54321
r
bk
X401
54321
910 8 7 6
br
g
g
X400
9876
1
4
2
b
bk
br
5
g
b
3
1
2
g/y
Fan
Link
Control PCB
X501
r
bk
b
br
Ignition Electrode
X9
Pump
br
b
Gas Valve
b
b
a
br
556789
b
br
Spark Generator
12
X1
br
bk
g/y
b
br
b
b
X2 X3
b
br
b
br
br
bk
1212 3344
br
L
N
br
E
N
L
Mains Input
br bk b w
bk
r
- brown
- black
- blue
- white
- green
g
- green / yellow
g/y
- red
r
- greygr
48
17.0 Short Parts List
© Baxi Heating UK Ltd 2011
Short Parts List
Key G.C. Description Manufacturers No. No. Part No.
A Fan 5121447
B Electrode Assembly 5130293
C Gas Valve 5122149
D Burner 5130292
E Water Pressure Switch 5114748
F Pump 248042
G NTC Sensor 5114725
H Overheat Thermostat 5114729
J NTC Sensor 5130291
K Pressure Gauge 248090
L PCB 24 5131262
PCB 28 5131263
D
A
C
E
F
L
K
B
J
G
H
Supplied by HeatingSpares247.com
49
18.0 Fault Finding
© Baxi Heating UK Ltd 2011
NOTE: When instructed to turn the
selector to the reset position turn the selector switch fully anticlockwise against the spring pressure to the reset position and hold for 5 seconds to reset the boiler.
18.1 Initial Fault Finding Checks
1. Check that gas, water and electrical supplies are available at the boiler.
2. Electrical supply = 230V ~ 50 Hz.
3. CH water system pressurised to 0.5 bar minimum when the boiler is cold.
4. The preferred minimum gas pressure is 20 mbar.
5. Carry out electrical system checks, i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable meter.
NOTE: These checks must be repeated after any servicing or fault finding.
6. Ensure all external controls are calling for heat and check all external and internal fuses. Before any servicing or replacement of parts, ensure the gas and electrical supplies are isolated.
18.2 Error Codes
1. If a fault occurs on the boiler an error code may be shown by the facia display.
2. The codes are either two or three digit, preceded by the letter 'E'. For example, code E133 will be displayed by 'E1' alternating with '33'. E50 is shown as 'E' then '50'
E20, E28 & E50 indicate faulty or incorrect components.
E110 shows overheat of the primary water.
E119 is displayed when the primary water pressure is less than 0.5 bar.
E133 indicates that the gas supply has been interrupted, ignition has failed or the flame has not been detected.
E125 is displayed in either of two situations:­i) If within 15 seconds of the burner lighting the boiler temperature has not changed by 1°. ii) If within 10 minutes of the burner lighting the boiler temperature twice exceeds the selected temperature by 30°. In these instances poor primary circulation is indicated.
3. By turning the selector switch to the 'Reset' position for a minimum of 5 seconds when E110 & E133 are displayed it is possible to relight the boiler.
4. If this does not have any effect, or the codes are displayed regularly further investigation is required.
Central Heating NTC Fault Incorrect PCB Fitted Hot Water NTC Fault Safety Thermostat Operated Water Pressure Switch Not Operated Circulation Fault (Primary Circuit) Interruption Of Power Supply while in fault mode Interruption Of Gas Supply or Flame Failure Fan or Fan Wiring Fault
E20 E28 E50 E110 E119 E125 E131 E133 E160
Table Of Error Codes
Supplied by HeatingSpares247.com
50
18.0 Fault Finding
© Baxi Heating UK Ltd 2011
Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components Central Heating - Follow operational sequence
Turn selector switch to
The display illuminates
Error 20, 28 or 50 flashing
Error 119 flashing
Burner lights
Error 110 flashing Error 133 flashing
Turn Central Heating
thermostat to Maximum.
Pump runs
Fan runs
Spark at ignition electrodes for
up to 5 seconds and for 3
attempts
3-way valve is open to Central
Heating circuit
Go to section ‘A’
Go to section ‘E’
Ensure all controls (and
integral clock if fitted) are
calling for heat
Go to section ‘J’
Go to section ‘B’
Error 160 flashing
Go to section ‘D’
Error 133 flashing
Burner does not stay alights
after 5 seconds
Error 133 flashing Go to section ‘H’
Operation sequence
successful
If the error 110 is still flashing.
Go to section ‘I’
Fan runs at correct speed
YES
YES
NO
NO
NO
YES
YES
YES
YES
YES
YES YES
YES
NO
YES YES
YES
YES
NO
NO
NO
NO
NO
Burner output modulates to
maintain the temperature set
Burner goes out
Go to section ‘C’
Ensure controls are set to
demand and verify the
contacts are closed
Error 160 flashing
Go to section ‘K’
YES
Go to section ‘G’
Turn the selector switch to
reset
Go to section ‘F’
YES
Check the Central Heating
NTC sensor
Go to section ‘E’
Fan stops after 10 seconds
Pump continues to run for 3
minutes
(room thermostat open)
NO
NO
YES
NO
YES
YES
Turn the selector switch to
reset position for 5 seconds
NO
Error 125 flashing
Ensure that primary
circulation is OK & that
there is no blockage
YES
Supplied by HeatingSpares247.com
51
18.0 Fault Finding
© Baxi Heating UK Ltd 2011
Fault Finding Solutions Sections
Is there 230V at:
Is there 230V at:
Main terminals L and N Check electrical supply
1.
NO
Main terminal fuse Replace fuse
Replace PCB
Display illuminated
2.
NO
PCB - X1 connector terminals 1,2
Check wiring
3.
NO
NO
A
Pump Replace pump
1.
YES
PCB - X3 connector terminals 3 & 4 Replace PCB
2.
NO
Change pump supply cable
YES
B
CH system pressure less than 0.5 bar Re-pressurise system
1.
YES
Check the tap of the automatic air vent is opened
Open the automatic air vent
2.
NO
C
NO
YES
Fan connections correct at fan. PCB ­X2 connector, is 230V AC across terminals 5 & 7
Fan jammed or faulty winding
Replace PCB
Replace fan
YES
D
If pump jammed, release
NO
NO
Replace water pressure switch
Check connection water pressure switch terminal COM - NO and PCB connector X400 terminals 3,4
YES
E20 or E50 - Temperature sensors faulty. Cold resistance approximately 10kΩ @ 25° C (Temperature sensors) 20kΩ @ 25° C (Flue sensor) (resistance reduces with increase in temp.)
E28 - Incorrect PCB fitted
NO
E
Replace sensor or PCB (E28)
Supplied by HeatingSpares247.com
52
18.0 Fault Finding
© Baxi Heating UK Ltd 2011
Gas at burner
Ensure gas is on and purged
Replace PCB
Replace gas valve
PCB - X3 connector is 230V AC across
terminals 1 & 2
YES
NO
NO
F
Replace PCB
G
Check and correct if necessary
1. Ignition electrode and lead
2. Electrode connection
3. Spark gap and position
voltage at PCB - X2 connector is 110V AC across terminals 2 & 5 (Note: from multimeter connect ‘common’ to 2 & ‘volts’ to 5) Check wiring
YES
NO
Replace igniter
YES
Check and correct the connection of the
tube between the venturi and gas valve
1.
2.
Check and correct if necessary
1. The mechanical set of the gas valve (CO2 values - see instruction)
2. Flame sensing electrode and lead connections
3. Flame sensing electrode position
Flame current should be more than 0.5 μ A
Replace PCB
Replace PCB
YES
YES
Replace flame sensing electrode
NO
Check the gas supply pressure:
For Natural Gas MINIMUM 17 mbar
I
Replace safety thermostat
YES
NO
Overheat thermostat operated or
faulty, i.e. continuity across
thermostat terminals
Allow to cool. Continuity
across thermostat terminals
more than 1.5 ohm
2.
1.
H
Supplied by HeatingSpares247.com
53
© Baxi Heating UK Ltd 2011
18.0 Fault Finding
K
J
L
Is there 230V at: PCB - X3 connector terminals 5 & 6 central heating mode
Replace PCB
NO
Change pump supply cable
YES
Fan connections correct at fan. PCB - X401 connector terminals 5,6,7 & 8
YES
Replace fan
Temperature sensors faulty. Cold resistance approximately 10kΩ @ 25° C (CH sensor) (resistance reduces with increase in temp.)
NO
Replace sensor
YES If pump is running the heat exchanger could be obstructed
Replace heat exchanger
1.
2.
Supplied by HeatingSpares247.com
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This does not affect the customer’s statutory rights.
If yes, and if required by the manufacturer, has a water scale reducer been fitted?
CONDENSING BOILERS ONLY
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798 Yes
If the condensate pipe terminates externally has the pipe diameter been increased and weatherproof insulation fitted? Yes
54
Supplied by HeatingSpares247.com
Service Record
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Always use the manufacturer’s specified spare part when replacing controls.
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Service 1 Service 2
Service 3 Service 4
Service 5 Service 6
Service 7 Service 8
Service 9 Service 10
55
Supplied by HeatingSpares247.com
© Baxi Heating UK Ltd 2011
Comp No5119528 - Iss 5 - 6 /11
All descriptions and illustrations provided in this leaflet have been
carefully prepared but we reserve the right to make changes and
improvements in our products which may affect the accuracy of the
information contained in this leaflet. All goods are sold subject to our
standard Conditions of Sale which are available on request.
MAIN
A Trading Division of Baxi Heating UK Ltd (3879156)
Brooks House, Coventry Road, Warwick. CV34 4LL After Sales Service 0844 871 1570 Technical Enquiries 0844 871 1555 Website www.mainheating.co.uk e&oe
Supplied by HeatingSpares247.com
Loading...