Maico ERK 100 ST, ERK 100 S, ERK 100, ERK 100 T, ERK 125 Mounting And Operating Instructions

...
Page 1
Duct fans
www.maico
VENTI LATOREN
ERK 100 ERK 100 T ERK 100 S ERK 100 ST
ERK 125 ERK 125 T
ERK 150 ERK 160 ERK 200
operating instructions
-ventilatoren.c om
Mounting and
Page 2
en Table of contents
ERK ...
Table of contents
Additional information ................................... 2
1. Scope of delivery ...................................... 3
2. General notes........................................... 3
3. Product information .................................. 4
3.1 Equipment overview, Fig. A ............... 4
3.2 Product description ........................... 4
3.3 Intended use ..................................... 5
3.4 Predictable misuse ............................ 5
4. Technical data .......................................... 5
5. Safety instructions .................................... 6
5.1 General ............................................. 6
5.2 Safe and correct practices during
operation ................................................. 6
6. Transportation, storage ............................ 7
6.1 Transport ........................................... 7
6.2 Storage ............................................. 7
7. Installation preparations ........................... 7
8. Mounting .................................................. 8
8.1 Installing fan ...................................... 8
8.2 Electrical connection ......................... 8
2
8.3 Speed control with speed controller .. 9
8.4 Operation with step transformer ...... 10
8.5 Commissioning ............................... 10
9. Maintenance .......................................... 10
10. Fault rectification .................................. 10
11. Dismantling .......................................... 12
12. Disposal ............................................... 12
13. Wiring diagrams ................................... 12
Additional information
Acknowledgements: © Maico Elektroapparate-Fabrik
GmbH. English translation from the original German operating instructions. We cannot be held responsible for mistakes or printing errors and retain the right to make technical modifications without giving prior notice brand names and protected trade marks that are referred to in this document refer to their owners or their products.
Go directly to the product with a smartphone. In the Internet under maico-ventilatoren.com.
.
The brands,
Page 3
1. Scope of delivery
ERK duct fan including mounting foot
(pre-installed)
Accessories bag containing fastening
material (4 fastening screws and 4 dowels) in the terminal box
Mounting and operating instructions
2. General notes
Read these installation and operating instructions carefully before using the fan for the first
time. Follow the instructions. Keep these instructions safe for use later on.
Page 4
3. Product information en
i
i
i
Installation staff
Installation may only be carried out by specialists who have the necessary knowledge and experience in ventilation engineering. Only qualified electricians are permitted to make the electrical connections. They are trained in electrical engineering and are aware of the risks and consequences of an electric shock.
Symbols used
Direct risk of danger. Failure to observe will result in severe
DANGER
CAUTION
NOTICE
injury or death. Possibly dangerous situation
which could result in minor to moderate injuries.
Possible situation which could cause damage to the product or its surroundings.
INFO symbol indicating important information and tips.
Bullet point for information on the corresponding subject.
Instructions. Follow the
1.
instructions given in the order stated.
3. Product information
3.1 Equipment overview, Fig. A
1 Fan housing with motor and impeller 2 Connection socket 3 Terminal box 4 Terminal box cover 5 Mounting foot 6 Clamp with screw and retaining ring P Air flow direction arrow T Rating plate
3.2 Product description
Models
ERK ..: Duct fans with guide vanes, units
with nominal sizes of DN 100, DN 125, DN 150, DN 160 or DN 200.
ERK 100 T, ERK 125 T: like ERK .., also
with follow-up relay (timer), adjustable from 3 to 15 minutes. Units with nominal size of DN 100 or DN 125.
ERK 100 S, ERK 100 ST: Duct fans with
guide vanes, powerful model. ST model with follow-up relay (timer), adjustable from 3 to 15 minutes. Units with nominal size DN
100.
Product features
Fans for air extraction or ventilation,
depending on installation position ( air flow direction arrow).
For the supply of small up to medium air
volumes.
With inlet and outlet side connection
couplings for direct installation in the ventilation ducts.
With diagonal impeller and downstream
stator. Type ERK 100 with axial impeller.
Asynchronous motor, with 1, 2 or 3 speeds
depending on unit type.
1 level: ERK 100, ERK 100 T
2 levels: ERK 100 S, ERK 100 ST, ERK
125, ERK 125 T, ERK 150, ERK 160
3 levels: ERK 200 Alternatively speed can be controlled
using a speed controller (phase angle) or step transformer.
The high performance level should be connected when using speed controllers/transformers. The speed of timer versions ERK 100 T, ERK 100 ST and ERK 125 T cannot be controlled.
The unit is switched on or off with an
optional switch.
ERK .. T: Unit overrun time can be
adjusted. Setting range is 3…15 minutes. After being switched off with the optional switch, the fan continues to run for the set time and then switches off automatically.
4
Page 5
en 3. Product information
i
i
Thermal overload protection
The fan motor has thermal protection (temperature sensor in the motor winding). The overload protection automatically switches the fan off in the event of overheating.
The fan must remain switched off long enough for the motor and temperature limiter to cool down, before starting the fan back up. Depending on size and temperature conditions, it may take up to 10 minutes to cool down. Only then can the unit be switched back on.
3.3 Intended use
ERK are duct fans for usage similar to that
found in domestic properties.
They can be installed in any position.
The fans are used for air extraction or
ventilation, for example in productions sites, workplace applications, storage rooms, labs, workshops, rest rooms or rooms without windows.
IP X4 type protection is only satisfied
when installed in ventilation ducts, on the inlet and outlet sides with at least 1 m of duct.
They can only be operated with an
ERK fan installed directly in the duct. Folded spiral-seam ducts of a nominal size appropriate to the unit are permitted for the duct.
The ERK fan must be permanently
installed and the electrical supply cable permanently laid.
A mounting foot [5] should be used for
installation. The mounting location must demonstrate sufficient load-bearing capacity.
3.4 Predictable misuse
Maico is not liable for damages caused by use contrary to the intended purpose. Under
no circumstances should the unit be used:
for conveying steam-saturated air or
greasy air,
for conveying solid particles which may
stick to the fan.,
close to flammable materials, liquids or
gases,
for conveying chemicals, aggressive
gases or vapours,
in explosive atmospheres,
outdoors,
with a free air entry or exit, if there is no
protection against accidental contact with the impeller in accordance with EN ISO 13857.
IP X4 type protection is not satisfied when the ventilation duct on the air outlet side points straight up and there is no duct bend to prevent the supply of moisture.
4. Technical data
For technical data, refer to the rating plate.
Degree of protection IP X4 Temperature class B Weight
Temperature of air medium
Information
Dimensions and characteristic curves
Internet, catalogue.
Internet maico-ventilatoren.com or
using the QR code on page 2.
1.2 to 4.5 kg, depending on unit variant
up to 40 °C
5
Page 6
5. Safety instructions
5.1 General
Read these operating
instructions carefully before mounting and commissioning.
Assembly and electrical
connection may only be undertaken by trained specialists in accordance with Chapter 2.
The unit may only be
operated using the voltage and frequency shown on the rating plate.
The degree of protection
stated on the rating plate is only guaranteed if installation is undertaken correctly and if the cables are correctly guided into the terminal box.
Only connect unit to
permanently wired electrical installations with NYM-O or NYM-J, (3 x 1.5 mm²) cables. Additionally, a mains isolation device with contact openings of at least 3 mm at each pole must be installed.
Only operate the unit when it
is completely installed.
Ensure that foreign bodies
cannot be sucked into the unit and duct.
5. Safety instructions en
Never operate the device
without a protective grille (Maico SGR) with a free inlet/outlet. The impeller must have protection against accidental contact (EN ISO
13857).
Ensure a sufficient supply air
intake.
Modifications and alterations
to the unit are not permitted and release the manufacturer from any guarantee and liability.
5.2 Safe and correct practices during operation
Danger of injury from objects in the impeller. Do not insert any objects in the unit.
Danger of injury from rotating impeller. Do not get too close to the unit, to avoid hair, clothing or jewellery being drawn into the unit.
6
Page 7
en 5. Safety instructions
i
i
This fan unit can be used by
children aged 8 and above, and by people with reduced physical, sensory or mental capabilities or by persons with insufficient experience or knowledge provided they are supervised by a person responsible for their safety, or they have been instructed about the safe operation of the unit and can understand the resulting risks thereof. Children must not play with the unit. Cleaning and maintenance must not be carried out by children without supervision.
6. Transportation, storage
6.1 Transport
Information
Use appropriate means of transport for
transport purposes.
Maico accepts no indemnification or
warranty claims in the event of improper transport.
6.2 Storage
Only store fan horizontally in a suitable,
dry room: ambient temperature
- 10 to + 60 °C.
Before installing, check that the motor
bearing is working properly.
Maico accepts no liability for corrosion
damage caused by improper storage, e.g. storage in a damp room.
7. Installation preparations
Information
For installation, we recommend flexible
fixing cuffs (type ELR). These prevent the transmission of vibrations to the duct system.
If duct system is already in place,
cut through folded spiral-seam duct at installation location. Take account of spacing for fixing cuffs.
Dispose of packaging material in
accordance with Chapter 12.
Lay a permanent power cable to the
installation location.
With free inlet, fit a SGR type protective
grille appropriate for the unit.
Always note the relevant specifications for
electrical installations and when fitting equipment. In Germany, observe DIN VDE 0100 and the corresponding parts in particular.
7
Page 8
8. Installation Electrical connection en
i
i
i
8. Mounting
8.1 Installing fan
Danger from incorrect installation location or incorrect
CAUTION
1. Remove pre-installed mounting foot [5] by opening both clamps and taking out fan housing [1] and connection sockets [2].
2. Fit mounting foot [5] at installation location using appropriate fastening material.
3. Slide folded spiral-seam ducts suitable for the diameter of the connection sockets onto the two connection sockets on the inlet and outlet sides. If necessary, first attach flexible fixing cuffs onto connection sockets.
4. Insert fan housing and two connection sockets in grooves of the two clamps. Close the clamps and screw down.
5. Fit suitable insulation, sound-deadening and installation material.
attachment.
1. Only fit in places with sufficient load-bearing capacity.
2. If necessary, the customer should provide fastening material suitable for the installation location.
Make sure that there is free access to terminal box [3].
Ensure that the components do not twist and are inserted correctly in the clamp grooves in order to prevent leakages.
8.2 Electrical connection
Danger to life from electric shock.
DANGER
NOTICE
ERK fans are not approved for
operation with frequency converters.
Speed can be controlled using a speed
controller (phase angle) or step transformer. For speed controller accessories online or valid Maico catalogue.
Units with ERK 100 T, ERK 100 ST and
ERK 125 T timers have an extra PCB with potentiometer in the terminal box. This can be used to set the follow-up relay (timer) from 3 to 15 minutes. The speed of timer units cannot be controlled.
The high performance level should be
connected when using speed controllers/transformers.
1. Switch off mains fuse and prevent from being started up again. Attach warning sign.
2. Remove terminal box cover [4] and accessories bag.
Prior to accessing the connection terminals, switch off all supply circuits. Switch off mains fuse, secure against being accidentally switched back on and position a visible warning sign.
Risk of damage to unit in the event of short-circuits.
Insulate any unnecessary cable cores.
Information
8
Page 9
en 8. Installation Electrical connection
i
NOTICE
Danger of short-circuits and damage to the unit. Water/dampness may penetrate the terminal box if the power cable is introduced incorrectly (leaking) or if the cable grommet is not fitted correctly.
Pierce cable grommet such that it can fully surround the power cable and makes close contact in the terminal box.
3. Pierce cable grommet [8] in terminal box with a nozzle pin.
4. Guide the power cable into the terminal box such that the cable grommet fits around the cable sheathing completely. If necessary, seal the cable grommet on­site.
5. Wire fan to the terminal block according to the wiring diagram ( chapter 13). Note the screws' tightening torque of 0.7 Nm.
6. Secure power cable with tension relief [7] to ensure that the power cable is seated firmly.
7. On ERK .. T units, set the unit overrun time with potentiometer [9] (setting range 3 to 15 minutes).
8. Fit optional on/off switch.
9. Connect other optional accessory components ( chapters 8.3 and 8.4).
NOTICE
Unit damage due to moisture in the event of improperly attached terminal box cover.
1. The terminal box cover sealing must be flush all the way round the terminal box.
2. Tighten screws to a tightening torque of 1.0 Nm.
10. Fit terminal box cover.
8.3 Speed control with speed controller
ERK units (other than ERK .. T units) can be controlled in an infinitely variable manner using a speed controller appropriate to the unit type ( online, catalogue).
The technology used in the phase angle controller may cause humming noises.
NOTICE
The fan will stop and suffer functional problems if the output voltage on the speed controller is too low.
1. Observe information in the speed controller operating instructions.
2. Always set the minimum speed on the speed controller such that the fan motor starts up again after power failure.
9
Page 10
8. Installation Electrical connection en
8.4 Operation with step transformer
The speed of ERK units (other than ERK .. T) can be set gradually with a 5-step transformer (type TR or TRE) appropriate to the unit type ( online, catalogue).
ERK unit:
1 level: ERK 100, ERK 100 T
2 levels: ERK 100 S, ERK 100 ST, ERK
125, ERK 125 T, ERK 150, ERK 160
3 levels: ERK 200
8.5 Commissioning
1. Check that all screw connections are tight.
2. Check air channel for dirt and clean if necessary.
3. Check that connection data matches technical data on the unit (rating plate unit instructions envelope).
4. Remove protection against switching back on and switch on mains fuse.
5. Run function test. Check that the impeller runs quietly and ensure this if necessary. It is also important that the air can flow unhindered.
6. Switch off unit.
9. Maintenance
The unit is maintenance-free.
10. Fault rectification
Call on the services of a trained electrician
any time there is a fault.
Repairs should only be carried out by a
trained electrician.
Danger to life from electric shock.
DANGER
Prior to accessing the connection terminals, switch off all supply circuits. Switch off the mains fuse, secure against being accidentally switched back on and position a visible warning sign.
Fault Cause, measure Fan does
not switch on.
Motor's thermal overload protection switches the fan off.
Fan does not switch on.
Deposits on the impeller and in the housing caused by dust in the air.
Impeller not turning.
No mains voltage. Check whether the mains
fuse has failed. Switch on if necessary.
Motor too hot. Leave the unit switched off
until the motor and the temperature limiter cool down. Cool-down time can be up to 10 minutes. Only then, switch the unit back on.
Impeller blocked.
Repairs may only be carried out by a trained specialist:
and clean if necessary.
Call on the services of a trained electrician. Install air filter in the duct system. Under no circumstances should the inside of the unit be cleaned with water or a high-pressure cleaner.
Switch off unit. Ensure that the impeller is not blocked by foreign bodies.
Check impeller
10
Page 11
If the fault still continues or occurs
i
again, disconnect the fan from the power supply at all poles.
Let a certified electrician determine the cause of the fault and eliminate it.
Page 12
en 11. Dismantling
i
i
11. Dismantling
Dismantling may only be undertaken by a trained electrician ( chapter
2).
Danger to life from electric shock.
DANGER
1. Switch off mains fuse, secure and fit warning sign.
2. Remove folded spiral-seam ducts from fan.
3. Remove the terminal box cover.
4. Remove all cables.
5. Remove fan.
Prior to accessing the connection terminals, switch off all supply circuits. Switch off the mains fuse, secure against being accidentally switched back on and position a visible warning sign.
12. Disposal
Do not dispose of in domestic waste. The unit contains in part
materials that can be recycled and in part substances that should not end up in the domestic waste.
Dispose of the unit once it has reached the end of its service life according to the regulations valid where you are.
13. Wiring diagrams
ERK 100
ERK 100 S, ERK 125, ERK 150, ERK 160
12
Page 13
13. Wiring diagrams en
ERK 100 T
ERK 100 ST, ERK 125 T
ERK 200
13
Page 14
de gb
Maico Elektroapparate-Fabrik GmbH • Steinbeisstr. 20 • 78056 Villingen-Schwenningen • Germany • Service +49 (0) 7720 694 447 • technik@maico.de