(ER-AK, ER-AH, ER-AB)
13 Fan insert with rating plate
14 Hole for central screw [16]
15 Lower part of cover [2], [4], [5] or [8]
16 Central screw, self-tapping
17 Air filter
18 Upper part of cover [1] or [7]
GmbH. Translation of the original German operating
instructions. Misprints, errors and technical changes
are reserved. The brands, brand names and protected
trade marks that are referred to in this document refer
Table of contents
Scope of delivery ...................................... 4
The final mounting of the ER EC
unit, together with the ER A.. cover,
takes place after the shell phase.
Pre-requirements: The ER GH
recessed-mounted housing must be
installed according to the relevant
ER shell mounting instructions.
Please carefully read the “ER cover”
instructions before the final
mounting of the ER cover.
For filter changes and cleaning
chapter 13.1.
Follow the instructions. Pass these
instructions on to the owner for
safekeeping.
Scope of delivery
Depending on the order:
● ER-A (article no. 0084.0361):
Standard cover: Lower part of cover and
er part of cover, central screw, air filter
upp
and TimeStrip on the title page of thes
nstructions, these mounting and operati
i
i
nstructions.
● ER-AK (article no. 0084.0362):
Comfort cover: Lower part of cover
er part of cover, central screw, air filter,
upp
these mounting and operating instructions.
● ER-AH (article no. 0084.0363):
Cover with humidity control.
Lower part of cover and upper part of
cover, central screw, air filter, thes
mounting and operating instructions.
● ER-AB (article no. 0084.0364):
Cover with motion detector.
Lower part of cover and upper part of
cover, central screw, air filter, thes
ounting and operating instructions.
m
e
e
and
Specialist installer
qualifications
Mounting may only be carried out by
specialists who have the necessary
knowledge and experience in ventilation engineering. The unit must be connected in
accordance with the “General building
approval”.
Only a trained electrician is permitted to
work on the electrics. You are deemed a
trained electrician if you are familiar with the
relevant standards and guidelines, can
competently and safely create electrical
connections in line with the attached wiring
diagram and are able to recognise and avoid
risks and dangers associated with electricity
on the basis of your technical training and
experience.
Intended use
These fans are used to extract air from
interior bathrooms and toilets rooms, storage
rooms or open plan kitchens (with outside
e
windows), for example in multi-storey
residential buildings, office buildings or hotel
ng
complexes.
The fans are installed in a wall, a front wall or
a suspended ceiling and are connected to a
ventilation shaft. They can also be used as
individual units in the wall or ceiling or for
toilet seat air extraction.
These fans are only intended for domestic
use and similar purposes.
chapter 16 with more detailed
Page 5
4. Safety instructions and warnings
5
Indicates a possible situation,
Safety instructions and
warnings
Warnings: Symbols, meaning
NOTICE
The fan unit must not be used in the
following situations under any
circumstances.
gases in the vicinity of the fan. Do not
place any flammable materials, liquids or
gases near the fan, which may ignite in the
event of heat or sparks and catch fire.
fan, can soil the fan and reduce the
efficiency. Never use fan to convey these
substances.
or fire. Never use fan unit in an explosive
atmosphere (risk of explosion).
cause serious explosions or fire.
Aggressive substances may damage the fan.
Never use fan in combination with a lab
extraction unit (risk of explosion).
or aggressive gases/vapours may harm
health, especially if they are distributed
throughout the rooms by the fan. Never use
fan to distribute chemicals or aggressive
gases/vapours.
which could cause damage to
the product or its surroundings.
Risk of combustion/danger of fire
from flammable materials, liquids or
Steam-saturated or greasy air or
solid particles which may stick to the
Explosive gases and dusts may
ignite and cause serious explosions
Explosive substances in lab
extraction units may ignite and
Risk to health from chemicals or
aggressive gases/vapours. Chemicals
During the build phase, damage to
unit caused by soiling of the fan and
air channels. Fan operation is not permitted
during the build phase.
Grease and oil vapours from range
hoods may contaminate the fan and
air channels and reduce efficiency. Never
use fan to convey greasy air.
Damage to the unit when
continuously conveying steam-
saturated air. Never use fan to convey
steam-saturated air.
Damage to the unit due to imbalance
of the impeller when conveying solid
particles. Never use fan to convey solid
particles that could stick to the fan.
Damage to unit in the event of
moisture ingress. Fan with IP X5
degree of protection (jet-water protection).
Never use fan outdoors.
Observe all safety
instructions.
Risks for children and
people with reduced
physical, sensory or mental
capabilities or a lack of
knowledge. Fan may only be
installed, commissioned,
cleaned and maintained by
people who can safely
recognise and avoid the risks
associated with this work.
Page 6
4. Safety instructions and warnings
6
Risk to health if filters are not
replaced or if there are no air filters.
Heavily soiled or moist air filters can
accumulate harmful substances (mould,
germs, etc.). This can also occur during a
prolonged shutdown of the fan. If the air
filter is missing, the fan and air channels
become soiled. Never operate the fan
without air filters. Only use original filters.
Regularly change air filter when a filter
change is indicated (LED or TimeStrip). If the
fan has not been used for a long time, always
replace the air filters.
Risk of injury when working at
heights. Use appropriate climbing aids
(ladders). Stability should be ensured, if
necessary have the ladders steadied by a
2nd person. Ensure that you are standing
securely and cannot lose your balance and
that there is no one under the unit.
Exercise caution when handling
packaging materials. Observe
applicable safety and accident prevention
requirements. Store packaging material out of
the reach of children (risk of suffocation).
Risks from parts which may affect
the ventilation system which are
added or modified at a later date. Parts
(range hood, air-ventilated fireplace etc.)
which are added or modified at a later date
may result in health risks and operation which
is not permitted. Parts may only be added or
modified at a later date if system compatibility
is established/ensured by a planning office. If
using an exhaust air range hood or airventilated fireplace, this must be accepted by
a regional master chimney sweep.
Danger from operating with the fan
not fully mounted. Electric
components are a potential source of
electric shock. If the unit is open, all off the
supply circuits must be switched off (mains
fuse off), secured against being accidentally
switched back on and a visible warning sign
positioned. Only operate the fan when it is
completely installed.
Risk of injury and health risk in the
event of changes or modifications or
if components which are not permitted are
used. The unit may only be operated with
original components. Changes and
modifications to the units are not permitted
and release the manufacturer from any
guarantee obligations and liability, e.g. if the
housing is drilled at a point which is not
permitted.
Danger if the relevant regulations for
electrical installations are not
observed.
● Before removing the housing cover or
removing the fan insert and before
installing the electrics, switch off all supply
circuits, switch off mains fuse, and secure
them against being accidentally switched
back on again. Attach a warning sign in a
clearly visible place.
● Be sure to observe the relevant regulations for electrical installation; e.g. DIN EN
50110-1. In Germany, particularly observe
VDE 0100, with the corresponding
sections.
● Unit may also be energized even when at
a standstill and may be switched on
automatically by sensors (time delay,
humidity etc.) or by the thermal switch in
the motor winding. Maintenance and fault
finding only permissible when carried out
by trained electricians.
● The degree of protection stated on the
rating plate is only guaranteed if
installation is undertaken correctly and if
the connecting cable is correctly guided
through the stepped grommet (The
grommet must completely enclose the
cable sheathing). The fan insert must also
be engaged and the housing cover
installed.
Page 7
5. Operating the fan
7
The factory settings meet DIN
accordance with standards.
In the event of overload (blocking),
Ensure sufficient supply air during
Certificates of approval are available
www.maico-ventilatoren.com.
For ER EC cover components
The TimeStrip for the ER-A
in chapter 16).
Operating the fan
ER EC fans run at 30 m³/h in base load
operation (factory setting).
A light switch or separate switch can be used
to switch to full load operation with 60 m³/h.
The fan control and operating unit are located
in the cover: ER-AK, ER-AH and ER-AB have
automatic functions with unit parameters that
can be set chapter 11.
● ER-A: Standard model
● ER-AK: Comfort model
● ER-AH: Model with humidity control,
barrier-free
●ER-AB: Model with motion sensor, barrier-
free
For full load operation, a start delay of
60 seconds and an overrun time of
15 minutes are specified at the factory.
18017-3. If the setting parameters in
operation with cover ER-AK, ER-AH
or ER-AB change, function in
accordance with DIN 18017-3 is not
always ensured. The planer/installer
is responsible for operation in
the fan switches off automatically.
operation.
System and product
information
6.1 Certificates of approval
on request or on our website
6.2 ER EC covers
Fig. 1.
● All covers with exhaust air filter. Troublefree filter change without tools.
● It is possible to rotate the cover by ± 5° to
compensate for housings which have been
fitted at an angle.
● ER AH and ER-AB are barrier-free
products. In automatic mode, they switch
the fan automatically on and off.
ER-A cover
● Standard model
● Air volume 30 m³/h, 60 m³/h
● Filter change display via TimeStrip
( title page).
standard cover is visibly attached to
a location of your choice (e.g. next to
the fan) after the filter change interval has elapsed, it can be disposed
of in the domestic waste. Do not
affix the TimeStrip under the
cover. New TimeStrips are included
in the scope of delivery of the
exchange air filter ( accessories
Page 8
6. System and product information
8
ER-AK cover
● Comfort version with time module.
● With operating parameters that can be set.
Setting via touch operating elements.
● Air volume 30 m³/h, 60 m³/h according to
factory setting. Further volumetric flows
that can be set: Base load 20, 30 or
40 m³/h, full load 60 or 100 m³/h.
● Start delay, overrun time and interval
mode can be set.
● LED filter change display.
ER-AH cover
● Model with humidity control and time
module (like ER AK).
● Barrier-free product. In automatic mode,
the fans switch on when the humidity
value limit is exceeded and switches off
again after the humidity has been reduced.
● LED filter change display.
ER-AB cover
● Model with motion detector and time
module (like ER AK).
● Barrier-free product. In automatic mode,
the fans switch on automatically, if motion
is detected, without a start delay. If no
further motion is detected, the fans switch
off after 2 minutes plus the overrun time.
● LED filter change display.
Page 9
6. System and product information
9
ER-A
ER-AK
ER-AH
ER-AB
Filter
Filter change display (6 months) with LED
Controller with time module
Control with fully automatic humidity control: Extraction
takes place automatically if the specified switch
humidity is exceeded
Control with motion detector. Full load level
after motion is detected (range of motion of the motion
sensor is
Barrier
and off automatically
Not speed
Electrical plug connection for quick connection
of the ER EC with ER GH housing and ER
or ER
Air volume
Air volume of the base load and full load levels can be set
Additional air volumes that can be set in base load: 20 m³/h,
40 m³/h and full load 100 m³/h
Full load level on/off via light switch or separate switch.
During manual operation (e.g.
delay and overrun time apply.
Full load operation (60
and overrun time of 15
Full load operation (60 m³/h), start delay can be set with
0, 30,
Overrun time of the full load level can be set for 0, 3, 6,
,
24 or 30 minutes
Adjustable interval control for ventilating rooms that are not
regularly used. Time interval can be set for
12 hours, 10 min. operating time per interval
Interval control can be switched off.
Switching option: The base
by an additional switch.
6.3 ER EC functions
change display (6 months) with TimeStrip ●
●●●
●●●
-on
●
.
5 m)
-free product, as the fan switches itself on
-controllable ●●●●
-AK, ER-AH
-AB with the ER EC fan insert.
– base load 30 m³/h for continuous operation ●●●●
using light switch), the start
m³/h) with start delay of 60 seconds
minutes, non-adjustable
60*, 90 or 120 seconds
15*
●
●●
●●●
●●●
●●●
● ● ● ●
●
●●●**
●●●
0*, 1, 2, 4, 6 or
●●●
load can be switched on or off
* Factory setting: Tolerance of time details max. ± 5 %
** For the ER-B, the start delay only affects the light switch operation
● ● ●
● ● ● ●
Page 10
7. Environmental conditions and operating limits
10
Rated voltage
230 V
Power frequency
50 Hz
ER-AK, ER-AH and ER-AB
2/2,5/3/5/17W *
Degree of protection
IP X5
52 dB(A)
ER-A, ER-AK, ER-AH, ER-AB
ER-A.. cover
0.6 kg
Environmental conditions and
operating limits
Permitted maximum air temperature + 40 °C.
The domestic air supply must be set up so
that virtually no air can flow into the living
areas from the kitchen, bathroom or WC.
A room from which the air has to be extracted
must be fitted with a non-closable, free supply
air cross section of at least 150 cm²,e.g.
with Maico door ventilation grille MLK.
ER EC units have resistance to interference
in line with EN 55014-2 (depending on pulse
shape and an energy factor of 1000 to 4000
V). These values can be exceeded when
operating with fluorescent tubes. In this case,
additional interference suppression measures
(L, C components or RC module, protection
diodes, varistors) are required.
7.1 Regulations for operation with
fireplaces
For operation with air-ventilated fireplaces,
sufficient supply air intake must be
ensured. The maximum permitted pressure
difference per residential unit is 4 Pa.
The fan may only be installed in residential
units with air-ventilated fireplaces if:
● the evaluation criteria drawn up by the
responsible, regional master chimney
sweep are met;
● a parallel operation of air-ventilated
fireplaces for liquid or gaseous fuels and
the air-extracting equipment can be
prevented, or
● the extraction of exhaust gas from the airventilated fireplaces is monitored by
special safety equipment. The ventilation
system or the fireplaces must be switched
off if the equipment is triggered.
Technical data
For technical data, the rating plate [T].
For characteristic curves Internet.
Power consumption:
ER EC and ER-A
Sound power level L
Mains cable to ER EC,
depending on switching
variant for
Weight
ER GH housing
ER EC fan insert
19 to
WA7
3/5W*
3 x 1.5 mm²
or
5 x 1.5 mm²
0.6 kg
0.72 kg
* Specification according to DIN 18017-3 with
an equivalent absorption area of A
= 10 m2
L
Storage
Only store ER EC covers in a suitable, dry
room. Ambient temperature - 10 °C to + 60 °C.
Maico accepts no liability for corrosion
damage caused by improper storage,
e.g. storage in damp surroundings.
Page 11
10. Fan insert
11
NOTICE
2
Fan insert
10 Accommodation mounts
11 Stud with locking hook
12 Sealing plugs
13 Fan insert
X Locking hook
Y Fixing holes for alternative
screw fixings
The fan insert is delivered separately. The
installation takes place in the completion
stage. Operation of the ER EC unit during
the shell phase is not permissible.
10.1 Installation of fan insert
1. Before accessing the connection
terminals, shut down all supply circuits
(switch off mains fuse), secure against
being accidentally switched back on and
position a visible warning sign.
2. Remove plaster protective cover and clean
ER GH housing from construction soiling if
necessary.
3. Check wiring diagram sticker for
correctness of the ticked fan type.
4. Check ease of movement of shutter. When
installed, it must close automatically.
5. Check that connection data matches the
technical data on the unit ( rating plate).
6. Plug the fan insert directly into the 3 studs
[11] with locking hooks [X]. Make sure that
the fan insert audibly clicks into all 3 snapfit fasteners.
7. Check for firm seating of the fan insert.
To do this, gently pull and press on the fan
insert. It must not move.
Function will be impaired if fan insert
element is not inserted correctly. Ensure
proper insertion in the locking hooks. If the
fan insert is not firmly seated, screw it to
the housing at the 3 [Y] positions shown in
the figure above. Suitable mounting material is to be supplied by the customer.
Page 12
10. Fan insert
12
The degree of protection, according
It is possible to rotate the cover by
For ER-A, no setting function.
changed.
3
10.2 Commissioning
1. Switch on mains fuse and remove warning
sign.
2. Run function test.
3. Check that the fan is running smoothly.
4. During the shell phase, switch off mains
fuse, secure against being accidentally
switched back on and position a visible
warning sign.
10.3 Removing fan insert
1. Before removing the fan insert, switch off
all supply circuits (switch off mains fuse),
secure against being accidentally switched
back on and position a visible warning
sign.
2. Remove the ER-A.. cover. To do so,
swivel the upper part of the cover
upwards, remove air filter [17], unscrew
the central screw [16] and carefully
remove the entire upper part.
3. Press the 3 locking hooks [X] of the stud
[11] and evenly pull the fan insert out of
the housing in parallel.
to the rating plate, is only ensured in
case of proper installation (fan insert
correctly engaged).
Installing the cover
ER-A, ER-AK, ER-AH, ER-AB
± 5° to compensate for housings
which have been fitted at an angle.
1. ER-AK, ER-AH, ER-AB: Pull off the
sealing plugs [12] from the motor board
interface ( Fig. 2). Plug flat channel with
plug of the ER cover in the interface
connector. Ensure correct connection.
2. ER-A, ER-AK, ER-AH, ER-AB:
Screw cover to the fan insert with the
central screw [16]. If installing on a wall,
ensure that the Maico name is on the
bottom right.
3. Insert the air filter [17] and fold down the
upper part of the cover (upper part must
audibly engage).
4. Run function test: Test all unit functions
(overrun time, interval, humidity control
etc.).
For ER-AK, ER-AH, ER-AB, all
operating parameters can be
Page 13
12. Settings with touch operating unit
13
LEDs
1
flash
V1
(60)**
(100)**
Te
Ta
Ti
4
Settings with touch operating
unit: ER-AK, ER-AH, ER-AB
RESET Resetting filter change interval
LED Filter change display
Sensor Humidity sensor (ER-AH) or
motion sensor (ER-AB).
V1,V2… Main menu with menu level V1, V2,
Te, Ta or Ti
MENU Select/save operating parameters
(set values – menu level)
Ti Interval time [in hours], then
air extraction duration 10 minutes.
12.1 Filter change function
The air filter must be changed every 6 months,
regardless of the operating time.
After filter change time has expired, the
filter change LED blinks (red) every 5 sec.
To reset the filter change interval, push the
<RESET> button for 2 seconds. As a
confirmation, the filter change LED flashes 1x
briefly. A new RESET is not possible for the
next 6 months.
12.2 Changing setting parameters
V2
* Additional setting values for ER-AK, ER-AB
** Setting values for ER-AH
● Main menu: Menu levels V1, V2, Te, Ta
and Ti
●Submenus (Parameter menus): LED 1
to 5 show the selected setting values.
● Bold = factory setting
● To select and save the setting value
(parameter value), push the MENU button.
Operating concept
1. Press <MENU> button for 2 seconds:
Main menu V1 is selected, the 1st LED is
lit up red.
2. With the button <+> or <–>, select the
menu level V1, V2, Te, Ta or Ti, display
with LEDs (ascending/descending). The
figure shows menu level Ta.
1 2 3 4 5
20 30 40 60*100*
20
0 30 6090 120
0 3 6 1524 30
0 1 2 4 6 12
30
40 60 100
Page 14
12. Settings with touch operating unit
14
The controller continuously checks
the relative humidity.
The start delay is deactivated with
turned on.
3. Press the button <MENU> to change
parameter level (LED flashes briefly 2x).
The last set value is shown (the corres-
ponding LED is lit up constantly*). Here,
the parameters of the respective level
are available to you. Example Ta: 0, 3,
6, 15, 24 or 30 minutes ( Table).
* To switch off the Te start delay, push
the Ta overrun time or Ti interval
time <–> until the V1 LED flashes.
4. Press <MENU> button for 2 seconds:
The setting is saved. All 5 LEDs switch
off.
Adjustment hints
●Ti interval operation: Thefan is switched
off during the interval time. Then, the fan
runs for 10 minutes with nominal ventilation (full load level) V2 or in the set level
60 or 100m³/h.
● Settings menu is automatically exited after
60 seconds without pushing buttons.
12.3 Automatic humidity function
ER-AH
the humidity in permanent base load
operation. If the unit is operated
without permanent base load operation, the fan starts every 2 minutes
for 30 seconds with reduced speed
(base load 20 m³/h) and measures
the automatic humidity function
Once the ER EC unit is installed, it adjusts to
the currently prevailing room humidity
(relative humidity). This humidity value is
saved as the first reference value. The
reference value does not have to be specified
manually.
If the relative humidity falls below the
reference value during operation, the newly
established reference value is saved. The
lowest possible reference value is 45 %
relative humidity.
If the room humidity rises quickly, the ER
EC unit (depending on the humidity) turns up
continuously to match the humidity. The
maximum flow rate at 100 % r. h. is 60 m³/h
or 100 m³/h, depending on the setting of V2.
If the humidity falls below the reference
value, overrun operation mode starts with the
set overrun time. Then, the current reference
value is saved.
If the humidity does not fall below the
reference value within 60 minutes, the
ER EC unit switches to the set overrun mode
and then switches off.
In case of “Light on” the ER EC unit starts
up. If the light is switched off, the ER EC unit
continues to run until the remaining overrun
time has passed. The automatic humidity
function is then assigned maximum priority
again and controls the unit as described
above.
Notes
● ER EC units can also be operated using
a light switch during operation with
automatic humidity function.
● The interval operation is deactivated
during the humidity operating mode.
● Overrun time:
● A set overrun time of 0 minutes is only
valid for manual function with a light
switch.
● For operation with automatic humidity
function, the minimum overrun time is
3 minutes.
● For settings > 0 minutes, the overrun
time is the same for manual (light switch)
and humidity operating modes.
● Volumetric flows that can be set
V1: 20, 30, 40 m³/h
V2: 60, 100 m³/h
See chapter 12.2.
Page 15
12. Settings with touch operating unit
15
NOTICE
5
12.4 Motion detector function
ER AB
If a movement is detected/recognised, the
ER EC unit switches to full load level
automatically without a start delay.
If no movement is registered, the overrun
delay starts. Then, the ER EC unit switches
off.
Cleaning/maintenance
The unit is practically maintenance-free. Only
the air filter needs replacing every 6 months
at the latest, depending on the degree of
soiling.
The unit will be damaged if incorrect
cleaning agent is used. Do not use
aggressive cleaning agents.
1. Clean ER-A.. cover only with a dry cloth.
2. If the cover is very dirty, remove it and
clean with water.
13.1 Filter change
Change the air filter when:
● ER-A: bar [B] is completely filled (red).
● ER-AK, ER-AH, ER-AB: LED on the lower
side of the housing blinks red.
ER-A
1. Change air filter [17].
2. Remove used TimeStrip.
3. Stick on a new TimeStrip.
4. Press activation button [A].
The red dye in the interior of the bar [B] is
released. The bar indicator first fills
slightly. Within the next 6 months, the bar
indicator [B] will rise to the upper edge
(indicator value 6).
ER-A, ER-AH, ER-AB
1. Change air filter [17].
2. Press <RESET> button for 2 seconds.
The filter change interval is reset.
The LED flashes briefly 1x.
Page 16
13. Cleaning/maintenance
16
Filter change interval every
Filter mats ZRF:
Fan output
● Dirty filter.
supply air cross section.
No fan overrun
Connect the fan as per the
wiring diagram.
Fan doesn’t
start up
Check whether the fan
Fan is
● Dirty filter.
correctly.
The main duct
is undersized
Re-calculate pressure losses.
Additional
Damage to the unit if
wiring diagrams in chap. 12.
If the fault persists or reoccurs:
6
13.2 Filter change, second room
19 Protective grille
20 Filter mat
21 Adapter
6 months, depending on the
degree of soiling.
1. Pull the protective grille [19] forwards.
2. Take out filter mat [20] and replace it.
3. Insert new filter mat into protective grille,
then press protective grille into correct
position on adapter [21] until it audibly
engages.
Pack of 5, filter class G2 in
accordance with EN 779,
Art. no. 0093.0923
Fault finding and repairs only permissible
when carried out by trained specialists.
Fault Cause, measure
inadequate
Replace filter.
● Locking hook not
engaged. Engage fan insert
correctly.
● Incorrect duct diameter.
Check duct diameter of the
main duct.
● Supply air cross section
is too small. Increase the
insert is correctly inserted.
too loud
consumers
connected to
terminal 4
Replace filter.
● Fan insert incorrectly
installed. Fit fan insert
connected incorrectly.
Do not connect additional
consumers
to terminal 4.
The unit may only be
connected according to the
Disconnect the fan completely from
the mains power supply. Have error
established and rectified by a trained
electrician. In case of questions
regarding fault rectification:
Service: +49 7720 6940.
Large pack of replacement air filters
ZF EC+ for ER-A, article no. 0093.0611
● 100x ZF EC+ replacement air filter
(filter class G2) and
x filter change display (TimeStrip)
● 100
ZF EC replacement air filter
for ER-AK, ER-AH and ER-AB,
article no. 0093.0758
● 5x ZF EC replacement air filter
(filter class G2)
Large pack of ZF EC replacement air
filters for ER-AK, ER-AH and ER-AB,
article no. 0093.0759
● 100x ZF EC replacement air filter
(filter class G2)
ZRF replacement air filter for ER-ZR
second room connection set,
article no. 0093.0923
● 5x replacement air filters for internal
grille or ER-ZR second room extracti
(
filter class G2)
Dismantling
by a trained electrician ( chapter 2).
on
Accessories
Air filter
Replacement air filters can be
ordered at:
www.shop.maico-ventilatoren.com
Replacement air filter ZF EC+
for ER-A, article no. 0093.0610
● 5x ZF EC+ replacement air filter
(filter class G2)
● 5x f
ilter change display (TimeStrip)
and
Environmentally responsible
disposal
The ventilation unit and the packaging
contain parts that can be recycled, and
should not end up in the domestic waste.
Dispose of the packaging material in an
environmentally-friendly way, in compliance
with the regulations valid in the country where
you are.
Dispose of the air filter in an environmenttally-friendly way, in compliance with the
regulations valid in the country where you
are.
At the end of its service life, dispose of the
unit in an environmentally-friendly way, in
compliance with the regulations valid in the
country where you are.