MAHLE RTI RRC750X User Manual

OPERATION
&
MAINTENANCE
MANUAL
RR750X
RTI Technologies, Inc.
York, PA 17402
800-468-2321
!!
!! TABLE OF CONTENTS !!
!!!!
RR750X
Before Using Page 2
Safety Precautions Page 3
Preparation For Use Page 4
Recycle Operation Page 4
Charging Capability Page 6
How The RR750X Works Page 9
Scheduled Maintenance Page 12
Problems & Solutions Page 14
Flow Diagram Page 15
Circuit Diagram Page 16
Wiring Diagram Page 17
BEFORE USING THE RR750X
Check for any shipping damage. If damaged, place a claim with carrier.
DO NOT USE A DAMAGED UNIT.
Verify that you have received the following:
RR750X Machine
Eight Foot Refrigerant Hose (Qty=2)
Tee Fitting
Oil Syringe
Oil Drain Cup
DOT Approved Cylinder
Refrigerant Technologies, Inc.
The RR750X should not be operated or maintained by any person who has not read all the contents of this manual. Failure to read and comply with these instructions or any one of the limitations noted herein can result in serious injury and/or property damage.
These general instructions deal with the normal operation and maintenance situations encountered with the RR750X. The instructions should not be interpreted to anticipate every possible contingency.
It is the responsibility of the owner/user to operate the RR750X in accordance with all specifications and laws which may apply.
The following pages contain rules for safe operation of the RR750X. Taking precedence over any specified rule listed herein, however, is the most important rule of all:
"USE COMMON SENSE".
A few minutes spent reading these instructions can make an operator aware of dangerous practices to avoid and precautions to take for his own safety and the safety of others.
A regular schedule of inspection of the RR750X should be established and records maintained with special attention given to hoses and replaceable filters.
May 24, 1993 Page 2
Refrigerant Technologies, Inc.
SAFETY PRECAUTIONS
! Wear safety glasses and protective gloves. Refrigerant has a very low boiling point and can cause
frostbite.
! Follow the RR750X operating procedures sequentially to avoid prematurely disconnecting hoses
or opening valves which may release refrigerant to the atmosphere.
! Do not expose the RR750X to moisture or operate in wet areas. ! Use the RR750X in locations with mechanical ventilation that provides at least four air changes
per hour or locate the unit 18 inches above the floor.
! Service hoses used with the RR750X must have shutoff devices within 12 inches of the
connection point to the system being serviced to minimize the introduction of non-condensable gases into the recovery unit and the release of refrigerant when being disconnected.
! Disconnect power before performing any maintenance or service on the RR750X. ! Avoid using an extension cord with the RR750X. If necessary, use a good condition, UL listed,
3-wire grounded, #14 AWG extension cord of the shortest possible length.
! Do not introduce refrigerant in the liquid state into the RR750X from any source having greater
than a 4.5 lb. capacity. Steady introduction of large amounts of liquid refrigerant may cause the RR750X to malfunction.
! Connect RR750X to grounded and protected 115 VAC - 60 HZ power source. ! Recover R-12 refrigerant only.
May 24, 1993 Page 3
PREPARATION FOR USE
Figure 1 Hose Connections
Refrigerant Technologies, Inc.
Place the External Cylinder on the Weight Scale Platform on the rear of the RR750X.
Connect the four hoses to the External Cylinder as shown in Figure 1.
NOTE:
Color standards for cylinder valve knobs were changed by the manufacturer during 1992.
Therefore, do not depend on color to indicate liquid or vapor valves on the External Cylinder. Look for “LIQUID” or “VAPOR” embossed on the knobs.
Tighten fittings FINGER-TIGHT only. Over tightening may cause damage to the fittings or valves and result in leaks.
It is recommended that ALL connections be checked with an electronic leak detector each time hoses are reconnected.
RECYCLE OPERATION
Set valves on the RR750X as follows in preparation for performing a Recover/Recycle operation:
! Red Valve on External Cylinder OPEN (Counter-clockwise) ! Blue Valve on External Cylinder OPEN (Counter-clockwise) ! Ball Valve on Red Hose OPEN (Handle parallel to hose) ! Ball Valve on Blue Hose OPEN (Handle parallel to hose) ! Yellow Filter Bypass Valve OFF (Handle vertical)
May 24, 1993 Page 4
Refrigerant Technologies, Inc.
Connect one end of the 8 Ft. yellow hose to the Inlet Port of the RR750X. Connect the other end to the center port of a Gauge Manifold. The hose can also be connected directly to the low side of the vehicle A/C system. The Pressure Gauge on the RR750X can then be used to monitor pressure.
If using a Gauge Manifold, connect it to the A/C system as specified by the manufacturer of the vehicle.
Open the Gauge Manifold Valves (Counter-clock-wise).
NOTE: It is recommended that the High and Low Gauge Manifold Hoses have shut-off devices
within 12 in. of the ends connected to the vehicle A/C system. This will permit the recovery of refrigerant from the hoses.
The yellow Service Hose could be connected directly to the low side of the A/C System and the RR750X Inlet Pressure Gauge used to monitor pressure.
Turn the Main Power Switch to On.
The Ready Light and Compressor-On light will illuminate. The Compressor High Pressure Light will flash momentarily. The Compressor and Condenser Fan will be heard operating as refrigerant is recovered from the vehicle.
NOTE: Several audible changes may be heard during the recovery process. The oil
re-circulation and non-condensable gas venting circuits will cycle periodically.
Refrigerant flow through check valves causes a "sizzle-type" sound.
These changing "noises are normal and nothing to be concerned
about.
The RR750X will recover refrigerant from the A/C system. The Compressor-On Light will then turn off.
!!!! DO NOT TURN THE RR750X OFF OR DISCONNECT HOSES !!!!
A small quantity of Liquid refrigerant will probably remain in the A/C system of the vehicle. This liquid will vaporize as the system components again warm to ambient temperature. This can be detected by noticing an increase in pressure readings on the Gauge Manifold.
May 24, 1993 Page 5
Loading...
+ 12 hidden pages