Magnum Energy RD Series User Manual

RD Series Modifi ed Sine Wave Inverter/Chargers
Owner’s Manual
Disclaimer of Liability
The use of this manual and the conditions or methods of installation, operation, use, and maintenance of the RD Series Inverter/Charger is beyond the control of Magnum Energy, Inc. Therefore, this company assumes no responsibility and expressly disclaims any liability for loss, damage, or expense whether direct, indirect, consequential, or incidental that may arise out of or be in anyway connected with such installation, operation, use, or maintenance.
Due to continuous improvements and product updates, the images shown in this manual may not exactly match the unit purchased.
Restrictions on Use
The RD Series Inverter/Charger may only be used in life-support devices or systems with the express written approval of Magnum Energy. Failure of the RD Series Inverter/Charger can reasonably be expected to cause the failure of that life-support device or system, or to affect the safety or effectiveness of that device or system. If the RD Series Inverter/Charger fails, it is reasonable to assume that the health of the user or other persons may be endangered.
Copyright Notice
Copyright © 2004, 2010 by Magnum Energy, Inc. All rights reserved. Permission to copy, distribute, and/or modify this document is prohibited without express written permission by Mag­num Energy, Inc.
Contact Information
Magnum Energy, Inc. 2211 West Casino Rd. Everett, WA 98204 Phone: 425-353-8833 Fax: 425-353-8390
Record the unit’s model and serial number in case you need to provide this information in the future. It is much easier to record this information now, instead of trying to gather it after the unit has been installed.
Model: Serial Number:
RD2212 P1
RD1824 E1
RD2824 F1
RD3924 G1
Magnum Energy® is a registered trademark of Magnum Energy, Inc.
© 2010 Magnum Energy, Inc.
Page i
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important safety instructions that must be followed during the installation
• and operation of this product.
All electrical work must be performed in accordance with local, state and federal electrical codes.
Read all instructions and safety information contained in this manual before installing or using
• this product.
This product is designed for indoor/compartment installation. It must not be exposed to rain,
• snow, moisture, or liquids of any type.
Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
• maintenance on the inverter.
Always disconnect the batteries or energy source prior to installing or performing maintenance
• on the inverter.
Live power may be present at more than one point since an inverter utilizes both batteries
• and AC.
Always verify proper wiring prior to starting the inverter.
There are no user-serviceable parts contained in this product.
This unit is provided with integral protection against overloads.
The input and output AC and DC circuits are isolated from the inverter chassis. The inverter
• system grounding is the responsibility of the installer in accordance with the NEC/CEC and local codes.
Both AC and DC overcurrent protection must be provided as part of the installation.
Use Class 1 wiring methods for fi eld-wiring connections to terminals of a Class 2 circuit.
Use only copper wires with a minimum temperature rating of 90°C.
Listed or labeled equipment shall be installed and used in accordance with any instructions
• included in the listing or labeling.
Safety Symbols
To reduce the risk of electrical shock, fi re, or other safety hazard, the following safety symbols have been placed throughout this manual to indicate dangerous and important safety instructions.
WARNING: This symbol indicates that failure to take a specifi ed action could result in
physical harm to the user.
CAUTION: This symbol indicates that failure to take a specifi ed action could result in
damage to the equipment.
Info: This symbol indicates information that emphasizes or supplements important
points of the main text.
Page ii
Remedy: This symbol provides possible solutions for related issues.
SAVE THESE INSTRUCTIONS
© 2010 Magnum Energy, Inc.
IMPORTANT BATTERY SAFETY INSTRUCTIONS
Be very careful when working around batteries, they can produce extremely high currents
• if short-circuited. Read the battery supplier’s precautions before installing the inverter and batteries.
Wear eye protection such as safety glasses when working with batteries.
Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
• maintenance on the inverter.
Never work alone. Always have someone near you when working around batteries.
Use proper lifting techniques when working with batteries.
Never use old or untested batteries. Check each battery’s label for age, type, and date code
• to ensure all batteries are identical.
Batteries are sensitive to changes in temperature. Always install batteries in a stable
• environment.
Install batteries in a well ventilated area. Batteries can produce explosive gases. For
• compartment or enclosure installations, always vent batteries to the outside.
Provide at least one inch (2.5 cm) of air space between batteries to provide optimum
• cooling.
Never smoke in the vicinity of batteries.
To prevent a spark at the battery and reduce the chance of explosion, always connect the
• cables to the batteries fi rst. Then connect the cables to the inverter.
Use insulated tools at all times.
Always verify proper polarity and voltage before connecting the batteries to the inverter.
To reduce the chance of fi re or explosion, do not short-circuit the batteries.
In the event of accidental exposure to battery acid, wash thoroughly with soap and water. In
• the event of exposure to the eyes, fl ood them for at least 15 minutes with running water and seek immediate medical attention.
Recycle old batteries.
SAVE THESE INSTRUCTIONS
© 2010 Magnum Energy, Inc.
Page iii
Table of Contents
1.0 Introduction ..................................................................................1
1.1 Features and Benefi ts ................................................................................. 2
1.2 How an Inverter/Charger Works ................................................................... 5
1.3 What Appliances will run from a Modifi ed Sine Wave Inverter ........................... 5
1.4 Appliances and Run Time ............................................................................ 5
2.0 Installation ...................................................................................7
2.1 Pre-Installation .......................................................................................... 7
2.2 Mounting the Inverter ...............................................................................10
2.3 Wiring the Inverter - General Requirements .................................................12
2.4 DC Wiring ................................................................................................13
2.5 AC Wiring ................................................................................................19
2.6 Grounding Inverters ..................................................................................28
2.7 Inverter Notifi cation Requirements ..............................................................32
2.8 Final Inspection ........................................................................................32
2.9 Functional Test .........................................................................................32
3.0 Operation ....................................................................................34
3.1 Inverter Mode ..........................................................................................34
3.2 Standby Mode ..........................................................................................35
3.3 Battery Charging ......................................................................................35
3.4 Transfer Time ...........................................................................................37
3.5 Battery Temperature Sensor Operation ........................................................37
3.6 Protection Circuitry Operation .....................................................................38
3.7 Inverter Startup .......................................................................................39
3.8 Factory Default Values ...............................................................................40
4.0 Maintenance and Troubleshooting ...............................................41
4.1 Recommended Inverter and Battery Care .....................................................41
4.2 Troubleshooting ........................................................................................42
4.3 Resetting the Inverter ...............................................................................43
Appendix A - Specifi cations and Optional Equipment ...........................44
A-1 Inverter/Charger Specifi cations ..................................................................44
A-2 Optional Equipment and Accessories............................................................45
Appendix B - Battery Information .......................................................46
B-1 Battery Location .......................................................................................46
B-2 Battery Types ...........................................................................................46
B-3 Battery Temperature .................................................................................46
B-4 Battery Bank Sizing ..................................................................................46
B-5 Battery Bank Sizing Worksheet ...................................................................47
B-6 Battery Wiring Confi gurations .....................................................................48
Limited Warranty ................................................................................51
How to Receive Repair Service ............................................................51
Page iv
© 2010 Magnum Energy, Inc.
List of Figures
Figure 1-1, Power Switch, Status LED, and Accessory Connection Ports ................................................3
Figure 1-2, Electrical Connection Points ...........................................................................................3
Figure 1-3, Left Side Features ........................................................................................................4
Figure 2-1, Simplifi ed Installation Diagram for Permanent Installations ................................................8
Figure 2-2, Approved Mounting Positions ....................................................................................... 10
Figure 2-3, RD Series Dimensions and Side Reference ..................................................................... 11
Figure 2-4, DC and Battery Temperature Sensor Wiring ................................................................... 14
Figure 2-5, Battery Hardware Installation ......................................................................................16
Figure 2-6, Inverter DC Hardware Installation ................................................................................ 16
Figure 2-7, Battery Temperature Sensor ........................................................................................ 17
Figure 2-8, RD Series Inverter/Charger - AC Wiring ........................................................................ 20
Figure 2-9, RD Series Inverter/Charger - AC Wiring (Access Cover) .................................................. 20
Figure 2-10, AC Terminal Block ..................................................................................................... 21
Figure 2-11, AC Wiring for Single In - Single Out (30 A) Confi gurations ............................................. 24
Figure 2-12, AC Wiring for Single In - Single Out (60 A) Confi gurations ............................................. 25
Figure 2-13, AC Wiring for Dual In - Single Out Confi gurations ......................................................... 26
Figure 2-14, AC Wiring for Dual In - Dual Out Confi gurations ............................................................ 27
Figure 2-15, Grounding System for RD Series ................................................................................. 28
Figure 2-16, Multiple Connections to DC Ground Rod (Method 1) ....................................................... 29
Figure 2-17, Multiple Connections to DC Ground Rod (Method 2) ....................................................... 30
Figure 2-18, Single Connection to DC Ground Rod (Method 3) .......................................................... 30
Figure 2-19, Warning Label .......................................................................................................... 32
Figure 2-20, AC Voltage Checks .................................................................................................... 33
Figure 3-1, Power Flow - Inverter Mode .........................................................................................34
Figure 3-2, Power Flow - Standby Mode ......................................................................................... 35
Figure 3-3, Automatic 4-Stage Charging Graph ............................................................................... 36
Figure 3-4, BTS Temperature to Charge Voltage Change .................................................................. 37
Figure 3-5, Power Switch and Status Indicator ................................................................................ 39
Figure 4-1, Performing an Inverter Reset .......................................................................................43
Figure B-1, Series Battery Wiring .................................................................................................. 48
Figure B-2, Parallel Battery Wiring ................................................................................................ 48
Figure B-3, Series-Parallel Battery Wiring....................................................................................... 48
Figure B-4, Battery Bank Wiring Examples (12-volt) ........................................................................ 49
Figure B-5, Battery Bank Wiring Examples (24-volt) ........................................................................ 50
List of Tables
Table 1-1, Typical Appliance Power Consumption ............................................................................... 6
Table 2-1, Recommended DC Wire/Overcurrent Device for Rated Use ................................................ 15
Table 2-2, DC Wire Size For Increased Distance .............................................................................. 16
Table 2-3, AC Input/Output Wiring Confi gurations ........................................................................... 23
Table 2-4, AC Grounding Electrode Conductor Sizing ....................................................................... 29
Table 2-5, Equipment Grounding Conductor Sizing .......................................................................... 31
Table 3-1, Inverter Battery Turn On/Off Levels ................................................................................ 38
Table 3-2, Inverter/Charger Default Values .................................................................................... 40
Table 4-1, Basic Troubleshooting ................................................................................................... 42
© 2010 Magnum Energy, Inc.
Page v
Introduction
1.0 Introduction
Congratulations on your purchase of the RD Series inverter/charger from Magnum Energy. The RD Series is a modifi ed sine wave inverter designed especially for renewable energy use. Powerful, yet simple to operate, this inverter/charger will provide you with the years of trouble-free performance you have come to expect from Magnum Energy, all backed by our limited 2 year warranty.
Installation is easy. Simply connect the inverter’s output to your distribution circuits or electrical panel, connect your utility power cable (AC) to the inverter’s easy-to-reach terminal block, connect the batteries, and then switch it on for power.
Use the optional accessories listed below to control and monitor many other Magnum devices.
The RD Series inverter/charger includes the following:
1800, 2200, 2800, or 3900 watt models in a small footprint – less weight and area needed
for installation (shelf, bulkhead, or upside-down mounting)
Modifi ed Sine Wave output
Automatic Power Factor Corrected (PFC) multi-stage battery charging
RS485 standard communication protocol
Remote and Network ports (easy connection for optional accessories)
ON/OFF inverter-mounted switch with LED indicator
30 Amp per leg/input (can connect two inputs together to allow 60 Amp pass-thru)
2
Large AC access and terminal block [wire size: 10 to 6 AWG (5.3 to 13.3 mm
DC terminal covers with 360 degree connection
Field-serviceable for qualifi ed personnel – tested repair kits available
ETL listed to UL STD 1741, 1st edition for safety
Automatic battery temperature compensation (using battery temperature sensor) – for
• optimum charging even during extreme temperature changes
Overcurrent, over-temperature, and high/low battery voltage protection
) CU]
The following accessories are also available for use with the RD Series inverter/charger:
ME-RC50 (Basic Remote Control) - easy to read LCD display panel that enables standard
inverter and accessories set up, control, and troubleshooting.
ME-ARC50 (Advanced Remote Control) - easy to read LCD display panel that enables advance
inverter and accessories set up, control, and troubleshooting.
ME-AGS-N (Automatic Generator Start Module - Network version) - automatically starts/stops
your generator.
ME-BMK (Battery Monitor Kit - with Shunt) - provides precise DC voltage/current measurements
and provides information on your battery’s State of Charge (SOC) condition.
ME-CB (Conduit Box) - provides 1/2” - 2” knockouts for connecting AC and DC conduit runs
to the inverter.
ME-SBC (Smart Battery Combiner) - monitors and keeps a second battery charged using a
portion of the current that is charging a main battery.
MMP (Mini Magnum Panel) - combines all of the major components required for a renewable
energy system into a single, easy to install pre-wired enclosure.
© 2010 Magnum Energy, IncPage 1
Introduction
1.1 Features and Benefi ts
The RD Series inverter/charger is designed to allow easy access to wiring, circuit breakers, and controls. Its die cast baseplate with one-piece aluminum cover ensures maximum durability with minimum weight, as well as cooler more effi cient operation.
The front of the RD Series is equipped with the following features (see Figures 1-1 and 1-2):
Power ON/OFF Switch - a momentary pushbutton switch that alternately turns the inverter
1
On or Off.
Status LED Indicator - this green LED illuminates to provide information on the inverter
2
or charger operation.
Stack/Accessories Connection Port (red label) - a RJ11 port that accepts the optional
3
Remote Switch Adapters (RSAs) which enable remote on/off switch operation.
Info: The stacking feature is NOT available with the RD Series.
Network Connection Port (green label) - a RJ11 port that accepts optional network
4
capable accessories (e.g., Auto Gen Start or Battery Monitor).
Remote Connection Port (blue label) - a RJ11 port that allows the optional remote
5
controls (ME-RC50 or ME-ARC50) to be connected.
BTS Connection Port (yellow label) - RJ11 port that accepts the remote Battery
6
Temperature Sensor (BTS) accessory.
DC Equipment Ground Terminal - this connection is used to tie the exposed chassis of
7
the inverter to the DC grounding system. This terminal accepts CU/AL conductors from #14 to #2 AWG (2.1 to 33.6 mm2).
AC Input/Output Connections - two 3/4” knockouts provided with cable-clamp strain
8
reliefs to allow and hold the AC input and output fi eld wiring.
Intake Air Vents - ventilation openings to pull in air to help keep the inverter cool for
9
peak performance.
Positive DC Terminal - provides 360 degree connection point for the positive (+) cable
10
from the battery bank; provided with a Kep or Flange nut on a 5/16-18 bolt (5/8” usable length) to hold the battery cable to the DC terminal.
Negative DC Terminal - provides 360 degree connection point for the negative (-) cable
11
from the battery bank; provided with a Kep or Flange nut on a 5/16-18 bolt (5/8” usable length) to hold the battery cable to the DC terminal.
12 Mounting Flange - used to secure the inverter to a shelf or wall.
© 2010 Magnum Energy, Inc.
Page 2
Introduction
POWER ON/OFF SWITCH
1
STATUS (CHARGING/INVERTING)
2
LED
STACK/ACCESSORIES PORT
3
(RED LABEL - RJ11 CONNECTION)
NETWORK PORT
4
(GREEN LABEL - RJ11 CONNECTION)
REMOTE PORT
5
(BLUE LABEL - RJ11 CONNECTION)
BATTERY TEMPERATURE SENSOR PORT
6
(YELLOW LABEL - RJ11 CONNECTION)
Figure 1-1, Power Switch, Status LED, and Accessory Connection Ports
INTAKE AIR VENTS
(AND ON RIGHT SIDE)
8
9
AC INPUT/
UTPUT
O
CONNECTIONS
7
DC
QUIPMENT
E
GROUND
TERMINAL
10
POSITIVE (+)
TERMINAL
DC
(UNDER COVER)
11
NEGATIVE (-)
TERMINAL
DC
(UNDER COVER)
12
MOUNTING
FLANGE
Figure 1-2, Electrical Connection Points
© 2010 Magnum Energy, IncPage 3
Introduction
The left side of the RD Series is equipped with the following features (see Figure 1-3):
Exhaust Air Vent - ventilation openings that allow heated air to be removed by the
13
internal cooling fan.
Model/Serial Number Label - includes model/serial number information, date of
14
manufacture, and inverter and charger specifi cations. See the RD Speci cations in
Appendix A for more information and the different models that are available.
AC Access Cover - provides access to the internal AC wiring terminal block. This terminal
15
block is used to hardwire all inverter AC input and output wiring connections. Remove the two screws to access the AC wiring terminal block.
Input Circuit Breaker - this circuit breaker protects the unit’s internal charger wiring
16
and pass-thru relay while in Standby Mode. This circuit breaker will pop out when it opens. Press in to reset. This input circuit breaker is not branch-circuit rated, therefore, branch-circuit rated breakers must be installed in the inverter’s input wiring.
CAUTION: The inverter’s internal AC transfer relay is rated for 30 amps per leg. The
pass-thru current must be no greater than 30 amps per leg or damage to the relays may occur.
13
EXHAUST
AIR VENTS
(BACK SIDE)
MODEL/SERIAL NUMBER
ABEL
L
14
AC ACCESS COVER
INPUT CIRCUIT BREAKER
16
15
© 2010 Magnum Energy, Inc.
Figure 1-3, Left Side Features
Page 4
Introduction
1.2 How an Inverter/Charger Works
An inverter takes direct current (DC) from your batteries and turns it into alternating current (AC). It also takes alternating current (when connected to a generator or to utility power) and transforms it into direct current to charge your batteries. These two modes of operation associated with this inverter/charger are referred to in this document as:
Inverter Mode:
When the inverter is properly connected to batteries and turned on, the direct current (DC) from the batteries is transformed into a modifi ed sine wave alternating current (AC). This AC is similar to the voltage provided by a utility for your home, and is used to power the AC electrical appliances (i.e., AC loads) connected to the inverter’s output.
Standby Mode:
When an external source of AC power (e.g., utility power or generator) is connected and qualifi ed on the inverter’s AC input, it operates in the Standby Mode. In the Standby Mode, the unit operates as a Battery Charger to convert the incoming AC power into DC power to recharge the batteries; and at the same time, automatically closes an internal AC Transfer Relay to pass the incoming AC power directly to the inverter’s output to continue powering the connected electrical appliances.
1.3 What Appliances will run from a Modifi ed Sine Wave Inverter
Today’s inverters come in two basic output waveforms: modifi ed sine wave (which is actually a modifi ed square wave) and pure sine wave. Modifi ed sine wave inverters approximate a pure sine waveform and will run most appliances and electronics without any problems. These inverters are less expensive, and therefore, offer a viable alternative to more expensive pure sine inverters.
The output of a modifi ed sine wave inverter will run most electronic and household items, including but not limited to: TV, VCR, satellite dish receiver, computers, and printers. Some devices such as rechargeable power supplies for phones, drills, and other like items may not run, and could even be at risk for damage from modifi ed sine wave inverters.
1.4 Appliances and Run Time
The RD Series inverter/charger can power a wide range of household appliances including small motors, hair dryers, clocks, and other electrical devices. As with any appliance using batteries for power, there is a certain length of time that it can run – this is called “run time.” Actual run time depends on several variables, including: the size and type of appliance, the type of batteries installed in your application, as well as the battery’s capacity and age. Other factors such as the battery’s state of charge and temperature can also affect the length of time your appliances can run.
Appliances such as TVs, VCRs, stereos, computers, and lights can all be successfully powered by your inverter. Depending on your inverter capacity, electrical appliances that use larger loads such as coffee pots and hair dryers can be used for short durations. However, loads that are used for longer periods (stoves, water heaters, etc.) can quickly drain your batteries and are not recommended for inverter applications.
© 2010 Magnum Energy, IncPage 5
Introduction
All electrical appliances are rated by the amount of power they consume (see Table 1-1). The rating is printed on the product’s nameplate label, usually located on its chassis near the AC power cord. Even though it is diffi cult to calculate exactly how long an inverter will run a particular appliance, the best advice is trial and error. Your RD Series inverter has a built-in safeguard that automatically protects your batteries from over-discharge.
Info: For optimum performance, a minimum battery bank of 200 AH is recommended
for moderate loads (<1000W) and greater than 400 AH for heavy loads (1000W).
Table 1-1, Typical Appliance Power Consumption
Device Load Device Load
Blender 400W Coffee Maker 1200W
Computer 300W Color TV 150W
VCR 40W Hair Dryer 1000W
Hot Plate 1800W Iron 1000W
Light (Flo) 10W Light (Inc) 100W
Microwave 1000W Refrigerator 500W
© 2010 Magnum Energy, Inc.
Page 6
Installation
2.0 Installation
WARNING: Installations should be performed by quali ed personnel, such as a licensed
or certifi ed electrician. It is the installer’s responsibility to determine which safety codes apply and to ensure that all applicable installation requirements are followed. Applicable installation codes vary depending on the specifi c location and application of the installation.
CAUTION: Review the “Important Product Safety Information” on page ii, and the
“Important Battery Safety Instructions” on page iii before any installation.
CAUTION: The inverter is heavy. Use proper lifting techniques during installation to
prevent personal injury.
The simplifi ed system diagram shown in Figure 2-1 should be reviewed to assist you in planning and designing your installation. This drawing is not intended to override or restrict any national or local electrical codes. This drawing should not be the determining factor as to whether the installation is compliant, that is the responsibility of the electrician and the onsite inspector.
2.1 Pre-Installation
Before installing the inverter, read the entire installation section to determine how you are going to install your RD inverter/charger. The more thorough you plan in the beginning, the better your inverter needs will be met.
2.1.1 Unpacking and Inspection
Carefully remove the RD Series inverter/charger from its shipping container and inspect all contents. Verify the following items are included:
The RD Inverter/Charger
Red and black DC terminal covers with Phillips screws
AC access cover with two Phillips screws
Two 5/16” Kep or Flange nuts (installed on the DC terminals)
Battery Temperature Sensor
Warning label
RD Series Owner’s Manual
If items appear to be missing or damaged, contact your authorized Magnum Energy dealer or Magnum Energy. If at all possible, keep your shipping box. It will help protect your inverter from damage if it ever needs to be returned for service. Save your proof-of-purchase as a record of your ownership; it will also be needed if the unit should require in-warranty service.
Record the unit’s model and serial number in the front of this manual in case you need to provide this information in the future. It is much easier to record this information now, instead of trying to gather it after the unit has been installed.
2.1.2 Required Tools and Materials Hardware/Materials
Conduit, strain-reliefs, and appropriate fi ttings 1/4” mounting bolts and lock washers
Electrical tape Wire ties
Tools
Miscellaneous screwdrivers Pliers Wire strippers
Drill and drill bits Pencil or marker Multimeter
Level 1/2” wrench
© 2010 Magnum Energy, IncPage 7
Installation
Utilit y Power
120/240 VAC Ou tput
Main Panel
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
120/240VAC
power to
in v e rt e r
AC
Transfer
Switch
Gen erator Po wer
120/240 VAC Ou tput
or
t
ra
ne
e
G
r
ito
c
pa
a
C
x
lu
F
ME-RC50
PWR
FAU LT
CHG
INV
ON/OFF
CHARGE R
ON/OFF
Remote Controls (Magnum A ccessories )
120 VAC Inverter power
(or 120/240 VAC p ass-thru
powe r) t o Sub-panel
SELECT
TECHAGS METER SETUPSHOREINVERTER
RD Series
Inverter/
Charger
ME-ARC50
Sub-panel
OFF
OFF
OFF
OFF
ME-AGS-N
Auto Gen Start
Controller
(M agnum
A ccessory)
30A
OFF
ON
30 A
OFF
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
DC
Shunt
DC
Overcurrent
protection
120
VAC
240
VAC
(Breaker or
ME-BMK
Fuse /sw itch )
B attery M o nito r
with shunt
(Magnum
BTS
A ccessory)
Battery Bank
ME-SBC
S ma rt B attery
Combiner
(M agnum
A ccessory)
Figure 2-1, Simplifi ed Installation Diagram for Permanent Installations
120
VAC
© 2010 Magnum Energy, Inc.
Page 8
Installation
2.1.3 Locating the Inverter
Only install the inverter in a location that meets the following requirements:
Clean and Dry - The inverter should not be installed in an area that allows dust, fumes, insects, or
rodents to enter or block the inverter’s ventilation openings. This area also must be free from any risk of condensation, water, or any other liquid that can enter or fall on the inverter. The inverter uses stainless steel fasteners, plated copper busbars, and a power-coated aluminum base. The internal circuit boards are conformal coated. All of this is done to help fi ght the harmful effects of corrosive environments. However, the inverter’s life is uncertain if used in the above types of environments, and inverter failure under these conditions is not covered under warranty.
Info: If the inverter is installed in an area where moisture may occur, we
recommend putting silicone dielectric grease compound into the electrical ports (see Figure 1-1, Items 3-6). Before installing the cables, or if leaving any ports open, squirt a liberal amount into each port. Silicone dielectric makes an effective moisture
and corrosive barrier to help protect and prevent corrosion to the RJ11 connections.
Cool - The inverter should be protected from direct sun exposure or equipment that produces
extreme heat. The ambient temperature around the inverter must not exceed 77°F (25°C) to meet power specifi cations.
Ventilation - In order for the inverter to provide full output power and avoid over-temperature
fault conditions; do not cover or block the inverter’s ventilation openings, or install this inverter in an area with limited airfl ow. The inverter uses two fans to provide forced-air cooling. These fans pull in air through the intake vents (see Figure 1-2, Item 9) and blow out air through the exhaust vents (see Figure 1-3, Item 13). Allow at the minimum an airspace clearance of 6” (15.2 cm) at the intake and exhaust vents, and 3” (7.6 cm) everywhere else to provide adequate ventilation.
If installed in an enclosure, a fresh-air intake opening must be provided directly to the front side (intake vents) of the inverter, and an exhaust opening on the back side (exhaust vents) of the inverter. This allows cool air from the outside to fl ow into the inverter, and heated air to exit the inverter and the enclosure. When mounted in an enclosed compartment, airfl ow must be 100 cfm in order to maintain no more than a 68°F (20°C) rise in compartment temperature.
CAUTION: Do not mount this inverter in a zero clearance compartment, nor cover or
obstruct the ventilation openings – overheating may result.
Safe - Keep any fl ammable/combustible material (e.g., paper, cloth, plastic, etc.) that may be
ignited by heat, sparks, or fl ames at a minimum distance of 2 feet (61 cm) away from the inverter. Do not install this inverter in any area that contains extremely fl ammable liquids like gasoline or propane, or in locations that require ignition-protected devices.
Close to the battery bank - As with any inverter, it should be located as close to the batteries as
possible. Long DC wires tend to loose effi ciency and reduce the overall performance of an inverter. However, the unit should NOT be installed in the same compartment as the batteries, or mounted where it will be exposed to gases produced by the batteries. These gases are corrosive and will damage the inverter; also, if these gases are not ventilated and allowed to collect, they could ignite and cause an explosion.
Info: The battery bank should be installed in a clean, dry, ventilated environment where
they are protected from high and low temperatures. The batteries must be mounted upright (if using liquid batteries) and securely fastened. The location must be fully accessible and protected from exposure to heat producing devices, and away from any fuel tanks.
© 2010 Magnum Energy, IncPage 9
Installation
Accessible - Do not block access to the inverter’s remote control and accessory ports, as well
as the inverter’s controls and status indicator. Also allow enough room to access the AC and DC wiring terminals and connections, as they will need to be checked and tightened periodically. See Figure 2-3 for the RD Series’ inverter/charger dimensions.
Away from sensitive electronic equipment - High-powered inverters can generate levels of RFI
(Radio Frequency Interference). Locate any electronic equipment susceptible to radio frequency and electromagnetic interference as far away from the inverter as possible.
2.2 Mounting the Inverter
The inverter base can reach a temperature up to 90°C (194°F) and it is recommended that it should be mounted on a non-combustible surface*. This surface and the mounting hardware must also be capable of supporting at least twice the weight of the inverter. To meet regulatory requirements, the RD Series must be mounted in one of the following positions, as shown in Figure 2-2:
above or under a horizontal surface (shelf or table)
• or, on a vertical surface (wall) with the DC terminals to the right
• or, on a vertical surface (wall) with DC terminals toward the bottom, MP-HOOD (inverter hood)
• installed on the top, and either the ME-CB (Conduit Box) or MMP Series (single inverter) enclosure installed on the inverter’s bottom.
Info: The ME-CB and the MMP Series enclosure prevent material from falling out the
bottom in the event of an internal fi re, and also allow suffi cient ventilation to prevent the inverter from overheating under normal operating conditions. The MP-HOOD inverter hood helps prevent items from falling inside, causing damage to the inverter.
Info: Magnum provides a backplate with a suitable surface for mounting the
inverter. These backplates also provide the ability to mount the MMP Series enclosure (PN: BP-MMP).
After determining the mounting position, refer to the physical dimensions as shown in Figure 2-3, or use the base of the inverter as a template to mark your mounting screw locations.
* Non-combustible surface - A surface made of material that will not ignite, burn, support combustion, or release fl ammable vapors when subjected to fi re or heat as per the ASTM E136 standard. For the most part, these are materials that are largely comprised of inorganic matter such as stone, steel, iron, brick, tile, concrete, slate, and glass. Avoid common building materials such as gypsum board, painted surfaces, wall coverings, and any type of wood.
SHELF OR TABLE MOUNTED
(UP SIDE DOWN)
30
30
SHELF OR TABLE
M
(RIGHT SIDE UP)
WALL MOUNTED
(DC TERMINALS TO THE RIGHT)
Figure 2-2, Approved Mounting Positions
© 2010 Magnum Energy, Inc.
OUNTED
WALL MOUNTED (DC TERMINALS
THE BOTTOM*)
ON
*WHEN THE INVERTER
IS MOUNTED IN THIS POSITION, THE MP-
HOOD (
HOOD ON TOP), AND THE
ME-CB (
ON BOTTOM) OR MMP
SERIES
INVERTER
CONDUIT BOX
ENCLOSURE
MUST BE USED
Page 10
Installation
TOP S
IDE
LEFT
S
IDE
LEFT
S
IDE
FRONT
S
IDE
BOTTOM
S
IDE
BACK
S
IDE
TOP S
IDE
RIGHT
S
IDE
6 5/8"
(16.8 cm)
RIGHT
S
IDE
8"
(20.3 cm)
4 7/8"
(12.4 cm)
Keyhole s lots
(x4) and
mounting holes
(x4) accept up to 9/32"
(7 mm)
screw/bolt
Figure 2-3, RD Series Dimensions and Side Reference
12" (30.5 cm)
12 5/8" (32.1 cm)
(5.1 cm)
© 2010 Magnum Energy, IncPage 11
2"
4 7/8"
(12.4 cm)
13 3/4"
(34.9 cm)
Installation
2.3 Wiring the Inverter - General Requirements
This section describes the requirements and recommendations for wiring the RD Series inverter/ charger. Before wiring the inverter/charger, read all instructions.
All wiring should meet all local codes and industry standards, and be performed by qualifi ed personnel such as a licensed electrician.
The NEC (National Electric Code, ANSI/NFPA 70) for the United States and the CEC (Canadian Electrical Code) for Canada provide safe wiring standards. The NEC/CEC list requirements for wire sizes, overcurrent protection, and installation methods/standards.
Inverter/charger systems involve power from multiple sources (e.g., inverter, generator, utility power, batteries, etc.) which makes the wiring more hazardous and challenging.
The input and output AC and DC circuits are isolated from the inverter chassis. The inverter system grounding is the responsibility of the installer in accordance with the NEC/CEC and local codes.
WARNING: Ensure the sources of DC power (i.e., batteries) and AC power (utility
power or AC generator) are de-energized (i.e., breakers opened, fuses removed) before proceeding – to prevent accidental shock.
2.3.1 Protecting Wire - Conduit Box
The AC and DC wires into and out of the inverter must be protected as required by code. This can be done by using jacketed wires or by feeding wires through a conduit. Magnum offers for purchase a DC conduit box (ME-CB), or a single inverter enclosure (MMP Series) that includes the AC and DC inverter breakers that allow both the AC and DC conduits to be connected to the inverter.
Info: If using the ME-CB conduit box or the MMP enclosure, and the AC wires are
individual conductors (i.e., not jacketed), the strain reliefs can be removed and replaced with 3/4” grommets.
2.3.2 Wiring Requirements
All conductors that are at risk for physical damage must be protected by tape, or placed
• in a raceway.
Always check for existing electrical, plumbing, or other areas of potential damage prior to
• making cuts in structural surfaces or walls.
Do not mix AC and DC wiring in the same panel unless specifi cally approved/designed for
• both AC and DC wiring. Where DC wiring must cross AC or vice-versa, try to make the wires 90° to one another at the crossing point.
Both AC and DC overcurrent protection must be provided as part of the installation.
The inverter requires a reliable negative and ground return path directly to the battery.
Use only copper wires with a minimum temperature rating of 90°C.
2.3.3 Wire Routing
Before connecting any wires, determine all wire routes to and from the inverter. Conductors passing through walls or other structural members must be protected to minimize insulation damage, such as chafi ng. During installation, always avoid placing conductors near sources of chafi ng caused by vibration or constant rubbing. Typical routing scenarios include:
AC input wiring from utility power source to the inverter
AC input wiring from a generator (optional) to the inverter
DC input wiring from the batteries to the inverter
AC output wiring from the inverter to the AC main panel or to dedicated circuits
Battery Temperature Sensor cable from the inverter to the batteries
Remote control cable (optional) to the inverter
Ground wiring to and from the inverter
© 2010 Magnum Energy, Inc.
Page 12
Loading...
+ 40 hidden pages