use of this manual and the conditions or methods of installation, operation, use and maintenance
of the Magnum Panel is beyond the control of Magnum Energy, Inc. Therefore, this company does
not assume responsibility and expressly disclaims liability for loss, damage, or expense, whether
direct, indirect, consequential or incidental, arising out of or anyway connected with such installation,
operation, use, or maintenance.
Note as well that while every precaution has been taken to ensure the accuracy of the contents
of this manual, the specifi cations and product functionality may change without notice. Magnum
Energy, Inc. assumes no responsibility for errors or omissions.
Restrictions on Use
Magnum Energy, Inc. does not recommend the use of any o
life saving, or other medical equipment or devices designated as “critical” by the U.S. FDA where
failure or malfunction of the Magnum Energy product can be reasonably expected to cause failure
of the life support device, or to signifi cantly affect its safety or effectiveness. Using Magnum Energy
products with this particular equipment is at your own risk.
odify this document is prohibited unless express written permission from Magnum Energy, Inc.
is provided.
Contact Information
Magnum Energy, Inc.
2211 West Casino Rd.
Everett, WA 98204
Phone: 425-353-8833
F
ax: 425-353-8390
Web: www.MagnumEnergy.com
Statement of Appreciation
From all of us at Magnum Energy -
Thank you for purchasing this Magnum Panel (MP).
We
understand that you have many purchasing options in the marketplace, and are pleased that you
have decided on a Magnum Energy product. This MP enclosure was proudly designed, assembled
and tested in the United States at our Everett, Washington facility.
At Magnum, we are committed to providing you with quality products and services; we hope that
your experience with us is pleasant and professional.
Page i
Magnum Energy® is a registered trademark of Magnum Energy, Inc.
orque Values for Dual Hole Busbars ............................................................................. 37
Page iv
1.0 Safety Information
1.0 Safety Information
IMPORTANT SAFETY INSTRUCTIONS
his manual contains important safety instructions that
T
and operation of this product. Before using the Magnum Panel (MP), read all instructions
and cautionary markings on: (1) the MP enclosure, (2) the inverter/charger, and (3) the
batteries, as well as the individual manuals provided for each component of the system.
These installation instructions are for use by qualifi ed personnel only. Do not perform any
installation or servicing other than that specifi ed in this owner’s manual unless qualifi ed to do so.
Incorrect installation or servicing may result in a risk of electric shock, fi re, or other safety hazard.
must be followed during the installation
1.1 Safety Symbols
The following safety symbols have been placed throughout this manual to indicate dangerous
conditions and important safety instructions.
WARNING: This symbol
physical harm to the user.
CAUTION: This symbol indicates that failure to take a specifi ed action could result in
damage to the equipment.
Info: This symbol indicates information that emphasizes or supplements important
points of the main text.
indicates that failure to take a specifi ed action could result in
1.2 General Safety
• All electrical work must be performed in accordance with local and national electrical codes.
This product is designed for indoor/compartment installation. It must not be exposed to rain,
•
snow, moisture or liquids of any type.
• Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
• Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
maintenance on the inverter.
• Both AC and DC overcurrent protection must be provided as part of the installation.
• Use Class 1 wiring methods for fi eld wiring connections to terminals of a Class 2 circuit.
• Listed or labeled equipment shall be installed and used in accordance with any instructions
included in the listing or labeling.
• To reduce risk of electric shock, disconnect all wiring before attempting any maintenance or
cleaning. Turning off the inverter will not reduce this risk, the inverter bypass must be used or
the panel should be totally disconnected from all sources.
• All wiring must have a minimum rating of 150V, 75°C when using 120V AC inverters; or 300V,
75°C when using 120/240V AC inverters.
• AC wiring must be no less than 10 AWG (5.3 mm2) gauge copper wire.
• Battery cables should be no less than #4/0 AWG unless fused close to the battery bank for
smaller sized cables.
• Crimped and sealed copper ring terminal lugs with a 3/8” hole should be used to connect to
the DC terminals inside the MP enclosure. Soldered cable lugs are also acceptable.
• Torque all AC wiring connections and DC cable connections to the required torque values.
• Be very careful when working around batteries, they can produce extremely high currents if
short-circuited. Read
inverter and batteries.
• Wear eye protection such as safety glasses when working with batteries.
• Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
maintenance on the batteries.
• Never work alone. Always have someone near you when working around batteries.
• Use proper lifting techniques when working with batteries.
• Never use old or untested batteries. Check each battery’s label for age, type, and date code
to ensure all batteries are identical.
• Batteries are sensitive to changes in temperature. Always install batteries in a stable
environment.
• Install batteries in a well ventilated area. Batteries can produce explosive gasses. For
compartment or enclosure installations, always vent batteries to the outside.
• Provide at least one inch of air space between batteries to provide optimum cooling.
• Never smoke when in the vicinity of batteries.
• To prevent a spark at the battery and reduce the chance of explosion, always connect the
cables to the batteries fi rst. Then connect the cables to the MP enclosure/inverter system.
• Use insulated tools at all times.
• Always verify proper polarity and voltage before connecting the batteries to the MP enclosure/
inverter system.
• To reduce the chance of fi re or explosion, do not allow the battery terminals to be shortcircuited.
• In the event of accidental exposure to battery acid, wash thoroughly with soap and water. In
the event of exposure to the eyes, fl ood them for at least 15 minutes with running water and
seek immediate medical attention.
• Recycle old batteries.
• Be extra cautious to reduce the risk of dropping a metal tool onto batteries. It could short-circuit
the batteries or other electrical parts, resulting in sparks that could cause a fi re or an explosion.
the battery supplier’s precautions before installing and connecting the
• Cover the terminals to prevent accidental shorting.
The Magnum P
dardize inverter installations and allow for the ability to expand the inverter system in the future.
Specifi cally designed for multiple inverter applications, the MP enclosures ensure safety and reliability by combining all of the major components required for a renewable energy system — inverter/
battery disconnect, AC overcurrent protection, grounding connections, and a full-system bypass
switch — into an easy to install pre-wired enclosure. The modular design of the MP enclosure with
the Magnum Energy inverter allows it to be UPS shipped and easily assembled on site.
Installing an inverter system is now as simple as mounting the MP enclosure, installing the inverters, connecting the battery bank, and if needed, bringing in AC power from a generator or the
utility grid. Now all of the inverter’s required AC and DC disconnects and wire connection points
are all together, and integrated in the self-contained MP enclosure.
anels (MP) are part of a new line of enclosures from Magnum Energy that stan-
2.1 MP Series Overview
The MP enclosures are available in four basic confi gurations: the MPSL-30D, MPSH-30D, and
MPDH-30D are designed to be used with the Magnum MS-PAE inverter models when stacked in
parallel; and the MPSL-60S, which is designed for use with two MS4024 inverters when stacked
in series. These confi gurations provide different maximum power abilities to meet present and
future requirements.
2.1.1 Models
MPSL-30D (Magnum Panel,
MPSL-60S (Magnum Panel, Single Enclosure, Low Capacity, Single-pole 60A AC input breaker)
MPSH-30D (Magnum Panel, Single Enclosure, High Capacity, Double-pole 30A AC input breakers)
MPDH-30D (Magnum Panel, Dual Enclosure, High Capacity, Double-pole 30A AC input breakers)
Single Enclosure, Low Capacity, Double-pole 30A AC input breakers)
2.1.2 Standard Features
The main components and features for the MP Series enclosures are:
• Standard confi gur
• Enclosure is steel construction with a durable, white powder coat fi nish to help prevent corrosion
• Built-in, pre-wired, full system bypass switch for inverter isolation/battery maintenance
• Front-mounted AC and DC breakers for quick and easy operation
• AC, DC, and Ground busbars with set-screw type compression terminals (no lugs required)
• Full system capacity shunt (500 or 1000 DCA), allows easy connection to battery monitor
• Enclosure and components are certifi ed for indoor use to UL/CSA standards
• DC negative and ground busbars (negative can be isolated if PV-GFP device installed)
• Battery positive busbar for DC loads and PV arrays included (not available on MPSH-30D)
• Space available to add DC load/disconnect breakers (not available on MPSH-30D)
• Standalone top plate provided to allow other (non-Magnum) inverter installations
• Knockouts for inverter and battery cables, PV in/out, DC breakers
• Data cables with 300-volt rated insulation provided to allow 240V AC inverter installations
• Easy accessibility for fi eld installation/wiring of additional breakers/components
• Pre-wired AC over-current circuit breaker protection to the inverter’s input
• Space for additional AC breakers (depends on enclosure confi guration)
• Inverter DC disconnect with inverter-to-breaker battery cables included
• Plated copper busbars included for up to six additional battery positive and negative circuits
ations allow future expansion using MPX enclosures for increased power
L-30D (Magnum Panel, Single Enclosure, Low Capacity, Double 30A AC Inverter Input Breaker)
Capability for one MS-PAE Series inverter (expandable to a maximum of two MS-PAE Series
inverters stacked in parallel using an optional MPX extension box).
MPSL-30D(as shipped)
Includes:
• D
30A AC Inverter Input
Breaker (x1)
• 250A DC Disconnect
(x1)
• Inverter AC Input/
Output wires
• Data cables rated for
120/240V AC circuits
Figure 2-1a, MPSL-30D as Shipped
• D60A AC System
Bypass
• 500A/50mV DC
Shunt
• Inverter Hood (x1)
• Router Bracket
MPSL-30D
with MPXS-30D-L
Includes:
30A AC Inverter Input Breakers (x2)• D60A AC System Bypass
• D
• 250A DC Disconnects (x2)• 500A/50mV DC Shunt
• Inverter AC Input/Output wires• Inverter Hoods (x2)
• Data cables rated for 120/240V AC circuits• Router Bracket
Capability for one MS-PAE Series inverter (expandable to a maximum of three MS-PAE Series
inverters stacked in parallel using optional MPX extension boxes)
agnum Panel, Single Enclosure, High Capacity, Double 30A AC Inverter Input Breaker)
MPSH-30D(as shipped)
Includes:
• D
30A AC Inverter Input
Breaker (x1)
• 250A DC Disconnect
(x1)
• Inverter AC Input/
Output wires
• Data cables rated for
120/240V AC circuits
• D125A AC System
Bypass
• 1000A/100mV DC
Shunt
• Inverter Hood (x1)
• Router and Charge
Controller Bracket
Figure 2-3a, MPSH-30D as Shipped
MPSH-30D with MPXS-30D-L (MPX - Left Side) and MPSX-30D-R (MPX - Right Side)
Includes:
30A AC Inverter Input Breakers (x3)• D125A AC System Bypass
• D
• 250A DC Disconnects (x3)• 1000A/100mV DC Shunt
• Inverter AC Input/Output wires• Inverter Hoods (x3)
• Data cables rated for 120/240V AC circuits• Router and Controller Bracket
Field Installed Options Shown (not included):
• PAE Series parallel-stack inverters (x3) • BP-S Single Mounting Backplate
• ME-RTR R
outer • BP-D Dual Mounting Backplate
Figure 2-3b, MPSH-30D with Field Installed Options
Capability for one or two MS-PAE Series inverters (expandable to a maximum of four MS-PAE
Series inverters stacked in parallel using optional MPX extensions).
agnum Panel, Dual Enclosure, High Capacity, Double 30A AC Inverter Input Breakers)
MPDH-30D(as shipped)
Includes:
• D
30A AC Inverter Input
Breakers (x2)
• 250A DC Disconnects
(x2)
• Inverter AC Input/
Output wires
• Data cables rated for
120/240V AC circuits
• D125A AC System
Bypass
• 1000A/100mV DC
Shunt
• Inverter Hoods (x2)
• Router and Charge
Controller Bracket
Figure 2-4a, MPDH-30D as Shipped
MPDH-30D with MPXD-30D-L (MPX - Left Side) and MPXD-30D-R (MPX - Right Side)
Includes:
30A AC Inverter Input Breakers (x4)• D125A AC System Bypass
• D
• 250A DC Disconnects (x4)• 1000A/100mV DC Shunt
• Inverter AC Input/Output wires• Inverter Hoods (x4)
• Data cables rated for 120/240V AC circuits• Router and Controller Bracket
confi gured and monitored, and maintains the critical settings in nonvolatile memory.
• ME-ARC – Advanced Remote Control with LCD display; has all the features of the ME-RC remote,
but also confi gures the advanced features of the inverter (or any connected accessory).
• ME-RTR – The ME-RTR, or “router” provides parallel capability for the MS-PAE Series inverters
and includes many of the same features as the ME-ARC advanced remote control. The router
is designed with a user-friendly LCD display and rotary SELECT knob that allows all connected
MS-PAE series inverter/chargers to be programmed in sync without the need to program
each inverter separately. The router will accommodate up to four MS-PAE inverter/chargers
in parallel, plus accessories.
• ME-BMK-NS – Battery Monitor; determines battery State of Charge (DC shunt not included).
• BP-S – Single Mounting Backplate; for mounting a Magnum inverter and MP/MPX enclosures.
It can be combined with the BP-D for additional mounting surface area. UPS shippable.
• BP-D – Dual Mounting Backplate; for mounting a Magnum inverter and MP/MPX enclosures,
It can be combined with the BP-S for additional mounting surface area. UPS shippable.
• DC Breakers – MP enclosure has space for E-Frame/back-mounted (1” width) or Q-Frame/
DIN rail-mounted (1/2” width) DC breakers (not applicable for the MPSH-30D model).
• MPX Extensions – These enclosures allow additional Magnum inverters to be mounted and
electrically wired to the Magnum Panel to allow an integrated panel system. The top of the
MPX is designed to allow Magnum inverters to fi t seamlessly into the top. The MPX Series
enclosures come with the AC and DC breakers and wiring to install another Magnum inverter.
An inverter hood is also included with each MPX extension to allow the inverter to be mounted
vertically.
• ME-MW-W - The MagWeb Wireless allows Magnum Energy’s inverters and accessories to be
remotely monitored. Installed on the Magnum network, the MagWeb provides live Internet
monitoring of the inverter, battery monitor, and automatic generator start module. Using your
always on Internet connection, the MagWeb makes live and historical conditions available to
you through a web browser at
emote Control with LCD display; allows inverter (or connected accessory) to be
http://data.magnumenergy.com
.
2.2 Regulatory Compliance
The MP enclosure
Equipment (ISE) for use with inverters. It has been independently tested and certifi ed by Intertek
Testing Services (known as ETL) to UL 1741, 2nd Edition, and is also CSA certifi ed to C22.2 No.
107.1-01 (R2006). These certifi cations mean the MP enclosure meets the minimum requirements
of prescribed product safety standards.
Note: ETL is a Nationally Recognized Testing Laboratory (NRTL). NRTL’s are qualifi ed organizations
that meet the requirements of Occupational Safety and Health Administration (OSHA) regulations
to perform independent safety testing and product certifi cation.
carries the ETL Listed Mark and is designated as Interconnection System
Page 6
2.0 Introduction
2.3 MP External Components
The main external
the MPDH enclosure (as shown in Figure 2-6) are described below:
components of the MPSL and MPSH enclosures (as shown in Figure 2-5) and
Info:
head, T25 T
1
Inv
This plate allows a Magnum inverter to sit on top of the MP enclosure, and allow the AC
and DC wiring to be easily routed from the inverter to the MP enclosure.
The inverter plate can be replaced with the Knockout Plate, which is used as an upper
conduit/safety plate. See Section A5 for more information on the Knockout Plate.
The external components are secured to the enclosure using #10-32 x 3/8” (Pan
orx driv
erter Plate - The MP enclosure is factory shipped with the inverter plate installed.
WARNING: To
MP enclosure, the Knockout Plate must be installed if the Magnum inverter is
removed for service and the AC bypass breaker is switched ON.
2
e) thread cutting screws and #10 lock washers.
prevent accidental access to live electrical circuits inside the
access the internal components. The front cover panels are equipped with rectangular
knockouts, to allow additional AC and DC circuit breakers to be installed.
Side
MP
and communications conductors to be routed from the main MP enclosure to a MPX
extension box (when used).
DC
battery monitor) and the DC ground stud.
Conduit
enclosure are provided to allow metal and PVC conduits. For dimensions and sizes, see
Figures 3-13 and 3-14.
Access
Shunt
Access
Knockouts
- The cover(s) on the front of the MP enclosures can be removed to
Plate (x2) - These access plates (one on each side) allow the power
Plate - This plate allows access to the DC shunt (for connecting a
Multiple sized knockouts on the side and bottom of the MP
Additional
MPSL-30D (see Figure 2-7), the MPSL-60S (see Figure 2-8), the MPSH-30D (see Figure 2-9), and
the MPDH-30D (see Figures 2-10a and 2-10b) are listed alphabetically and described below:
components are located inside the MP enclosure. The components found inside the
Info:
A
compression terminals (no ring lugs required). The number of terminals available
depends on the particular busbar and the MP model.
Info:
common to each other as they are all connected to the MP chassis.
AC
GROUND
used to connect the incoming and outgoing AC circuit grounds to a common ground point.
AC LEG 1 IN Busbar - Connects incoming LEG 1 AC power from the grid or a generator to the
MP/inverter system. This busbar is used to connect the LEG 1 output of a 120/240V AC external
source (grid power or AC generator) to the MP enclosure. The AC LEG 1 IN busbar is connected to
the HOT 1 input of the inverter system (thru the inverter’s AC input breaker). The external source
is used by the inverter to charge the batteries and power downstream loads thru the inverter.
AC LEG 1 OUT Busbar - Supplies the LEG 1 power from the MP/inverter system to the AC loads.
This busbar is the connection point from the MP enclosure to the LEG 1 terminal in the electrical
panel powered by the inverter.
AC LEG 2 IN Busbar - Connects incoming LEG 2 AC power from the grid or a generator to the
MP/inverter system. This busbar is used to connect the LEG 2 output of a 120/240V AC external
source (AC generator or grid power) to the MP enclosure. The AC LEG 2 IN busbar is connected to
the HOT 2 input of the inverter system (thru the inverter’s AC input breaker). This external source
is used by the inverter to charge the batteries and power downstream loads thru the inverter.
AC LEG 2 OUT Busbar - Supplies the LEG 2 power from the MP/inverter system to the AC loads.
This busbar is the connection point from the MP enclosure to the LEG 2 terminal in the electrical
panel powered by the inverter.
AC NEUTRAL Busbars - The neutral leg for loads powered from the MP/inverter system and the
neutral leg for AC power supplied to the MP/inverter system by either a generator or grid. These
two busbars are the connection points for the AC neutrals in the system. The system neutrals
include: the neutral output from the external AC source (generator/grid), the neutral terminal in
the electrical panel that is powered by the inverter, and the input and output neutral terminals of
each inverter. Note: Both AC NEUTRAL busbars are electrically connected to each other.
All the busbars have dual hole sizes — the larger holes accept #14 to #1/0
WG
and the smaller holes accept #14 to #6 AWG — these holes have set-screw type
All AC Ground Busbars, DC Ground Busbars, and the DC Ground Stud are electrically
Busbar(s) - These busbars are connected to the MP enclosure chassis and are
• Installing MS-PAE Series inverters: Both neutral terminals are common with each other
within the MS-PAE Series, this means only one neutral from each MS-PAE inverter needs to
connect to the AC NEUTRAL busbar.
• Installing MS4024 inverters: The Neutral In and Neutral Out are not common with each
other within the MS4024; this means both input and output neutrals from each MS4024
inverter needs to connect to the AC NEUTRAL busbar.
AC NEUTRAL-GROUND Connection - A wire (green) connects the AC neutral to the system
ground. This green wire can be removed from the GROUND busbar if the primary AC neutral to
ground connection is made elsewhere in the system (see Section 3.10).
Battery Negative Connection - The bottom of the DC Shunt busbar is the connection point to
the negative terminal of the battery bank. This busbar is supplied with a 3/8-16 bolt and lock
washer to allow the battery cable to be connected.
point to the positive terminal of the battery bank. The DC disconnect provides a rear captive nut
to allow the battery cable to be front-connected using a 3/8-16 bolt and lock washer.
DC GROUND Busbar - This busbar is connected to the MP enclosure chassis and is used to tie
DC equipment grounds to a common point. This terminal is also used to connect the inverter/
MP/inverter system to the DC grounding electrode. If the DC grounding electrode conductor
is greater than #1/0 AWG, use the DC Ground Stud to connect to the DC grounding electrode
(i.e., ground rod).
DC Ground Stud - This 5/16-18 stud is connected to the MP enclosure chassis, and is provided
as a connection point to the DC grounding electrode when the conductor is larger than #1/0 AWG.
This stud also connects to the DC shunt through a busbar and serves as the DC negative to
ground connection point. If installing a PV-GFP device, this busbar must be removed (see Section 3.11). Note: For ground wires #1/0 AWG or smaller, use the DC GROUND busbar.
DC NEGATIVE Busbar - This busbar is connected to the battery bank negative through the
load side of the DC shunt. This busbar is the battery negative connection point for additional
DC circuits, such as from the DC negative output of a charge controller or when combining the
negatives of DC load circuit breakers. This busbar is rated to handle 120 amps.
DC NEGATIVE-GROUND Connection - This busbar connects the DC negative to the system
ground. It must be removed if the primary DC negative to ground connection is made elsewhere
in the system (see Section 3.11).
DC POSITIVE Busbar - This busbar is connected to the battery bank positive through the
bottom of the inverter DC disconnect. This busbar is the battery positive common point for
connecting additional DC circuits, such as from the output of a charge controller disconnect, the
DC positive feed to DC load breakers, and the positive connection to a battery status monitor.
This busbar is rated to handle 120 amps.
DC Shunt - A DC shunt installed in the DC negative side that is used to measure the amperage fl owing between the battery and the inverter (and any DC loads connected). This shunt is
pre-installed so that a battery monitor may be easily connected to display the current fl ow. See
Section A-2 for information on installing and wiring the ME-BMK-NS battery monitor inside the
MP enclosure. The MPSL-30D and MPSL-60S are supplied with a 500 amp/50mV DC shunt, and
the MPSH-30D and MPDH-30D have a 1000A/100mV DC shunt.
DC Shunt Voltage Sense Terminals - These two shunt terminals/screws serve as the sense
connections to the optional ME-BMK-NS battery monitor. When current is passed through the
shunt, the IR drop (AKA voltage drop) developed across it can be read by the battery monitor
to provide an accurate indication of the current fl owing through the shunt.
DIN Rail Track - For installing up to 1/2” (12.7mm) wide, DIN rail-mounted, Q-Frame type,
DC breakers. These breakers can be used for connecting DC loads or installing a PV-GFP device.
The track may be removed to allow 1” (25.4mm) wide, back-mounted, E-Frame type breakers
to be installed instead.
Enclosure Joining Screw/Washer - A #10-32 x 3/8” (Pan head, T25 Torx drive) thread
cutting screw and #10 lock washers are provided to join the two enclosures of the MPDH-30D
together – to have them at the same electrical potential. See Figure 3-16c for more information.
INV HOT 1 OUT Busbar - This busbar is the connection point for the HOT 1 output from each
installed inverter. The total output power combined from every inverter on this busbar is fed thru
the Inverter Bypass Breaker Assembly to the AC LEG 1 OUT Busbar.
INV HOT 2 OUT Busbar - This busbar is the connection point for the HOT 2 output from each
installed inverter. The total output power combined from every inverter on this busbar is fed thru
the Inverter Bypass Breaker Assembly to the AC LEG 2 OUT Busbar.
Positive Connection - The bottom of the inverter’s DC disconnect is the connection
circuit, a way to disconnect the AC input to the inverters, and overcurrent protection to the
inverter’s input wires when the minimum recommended AC wire sizes are used. Depending on
your MP model, the breaker provided for the inverter input will be either a double-pole 30 amp
(D30A) or a single-pole 60 amp (S60A) AC breaker.
The double-pole 30 amp AC breaker is provided on the MPSL-30D, MPSH-30D, and MPDH-30D
models to allow 120/240V AC inverters — up to 30 AC amps per leg pass-thru capability — to be
connected. The MPSL-30D and MPSH-30D come with one double-pole 30A input breaker and the
MPDH-30D comes with two double-pole 30A breakers. These three models require a double-pole
30A breaker for each additional inverter installed in a parallel-stacked confi guration.
The single 60 amp AC breaker is provided on the MPSL-60S models to allow 120V AC inverters
— up to 60 AC amps pass-thru capability — to be connected. If connecting MS4024’s in a
series-stacked confi guration, an additional single pole 60A breaker for the second MS4024 will
be required (as provided in the MPX extension kit).
Inverter Bypass Breaker Assembly - The Inverter AC Bypass Breaker Assembly is pre-wired
at the factory and consists of the inverter bypass switch and the inverter AC output disconnect
breaker. This breaker assembly provides a way to disconnect the AC output of the inverter
system, and to directly connect the AC input to the AC output by bypassing the inverter system.
The MPSL-30D and MPSL-60S are installed with a double-pole 60-amp AC bypass breaker
assembly, and the MPSL-30D and MPDH-30D are equipped with a double-pole 125-amp AC
bypass breaker assembly.
Inverter DC Disconnect Breaker - This 250 amp DC disconnect is a high interruption capacity,
magnetic-hydraulic, DC circuit breaker. These breakers were specifi cally designed and tested
to work with Magnum inverters to provide the delay time needed to minimize nuisance breaker
tripping. It provides an easy and convenient way to isolate the inverter from the battery, and
meets the NEC/CEC requirements for DC overcurrent protection when the size and length of the
battery-to-inverter cables are installed in accordance with the installation instructions in this
manual. These breakers have front-accessible connections, each provided with 3/8-16 Hex head
bolts with lock washers.
Inverter’s DC Negative Connection - Connects to Magnum inverter’s DC negative terminal.
Inverter’s DC Positive Connection - Connects to Magnum inverter’s DC positive terminal.
Mounting Dimples, BMK (x2) - These dimples allow the optional ME-BMK-NS (Battery Monitor
Kit without DC shunt) to be installed. Two #8-32 x 1/2” (T20 Torx drive) thread cutting screws
are provided to mount the battery monitor. See Section A2 for more information on mounting
the battery monitor.
Mounting Holes, Inv AC Input Breakers - Used to install additional Inverter AC Input
Breakers, which provide protection to each inverter’s AC input circuit.
Mounting Holes, Inv DC Backmount Breakers - For installing 1” (25.4mm) wide, back-
mounted, E-Frame type, DC breakers. These breakers can be used for connecting DC loads or
installing a PV-GFP device.
Mounting Holes, Inv DC Disconnect Breakers - Used to install additional Inverter DC
Disconnect Breakers, which isolate the inverter from the battery. These breakers meet the NEC/
CEC requirements for DC overcurrent protection when used in accordance with the installation
instructions in this manual.
Mounting Keyholes, MP Enclosure (x4) - Four keyholes for mounting the enclosure. See
Figures 3-5 or 3-6 for size information on these keyholes.
Input Breakers - These breakers provide protection to the inverter’s AC input
This section describes the requirements and recommendations for installing the MP enclosure.
Info:
MPSL/MPSH
inverters are required, the optional MPX enclosures are used. Refer to the MPX Extension
Owner’s Manual (PN:64-1015) for information on installing these additional inverters.
This installation section primarily explains the installation of one inverter on the
enclosure,
and two inverters on the MPDH enclosure. When additional
3.1 Pre-Installation
Before proceeding with the installation:
• Please read and familiarize yourself with the entire Installation section.
• Read and ensure you understand the “Important Product Safety Information” and the “Important
Battery Safety Instructions” at the beginning of this manual.
• Be aware of all safety and electrical codes which must be met.
• Inspect all shipping cartons for evidence of physical damage. If a shipping carton is damaged,
request that the shipping agent be present for inspection when the carton is opened.
• Unpack the MP enclosure box and remove the components. Verify that you have the components
and hardware as listed below in Section 3.1.1 (and shown in Figures 3-1 and 3-2).
• Use the information in Section 3.1.2 to help identify most of the materials and tools required
for the installation.
• Read the information provided in Section 3.1.3 to properly plan for the installation.
3.1.1 MP Parts Included
Refer to Figures 3-1 or 3-2 (and the item list below) for you particular MP model to verify the
nece
ssary parts are included. If items are missing, contact your authorized Magnum Energy dealer
or Magnum Energy.
1a
1b
2
3
4
5
6
Info: Save your proof-of-purchase as a record of your ownership; it will be needed if
the unit should require in-w
L or MPSH Models - The MPSL-30D, MPSL-60S, and MPDH-30D use a single enclosure
MPS
to provide the AC/DC breakers, busbars, and wiring for the inverter’s AC and DC circuits.
H Model - The MPDH-30D uses two enclosures, one enclosure (AC Side) provides
MPD
the AC breakers, busbars, and wiring for the inverters AC circuits; and, the other
enclosure (DC Side) provides the DC breakers, busbars, and wiring for the inverter’s
DC circuits.
Inverter Hood - The
that is mounted on a Magnum Panel to prevent items from falling into the ventilation
openings at the top of the inverter. See Section A3 for more information on this hood.
Knockout Plate -
safety plate. See Section A5 for more information on this plate.
RTR (Router) Bracket Kit - This kit consists of the router bracket and the hardware
ME-
to attach the ME-RTR (i.e., Router) to the side of the MP enclosure. This kit is not
provided with the MPSL-60S model. See Section A4 for more information on this kit.
Hardware Kit - This hardware kit consists of the Charge Controller bracket and
MP
hardware (see Section A1), the owner’s manual, communications cables (see Section
3.8), and a front cover label set (see Section 3.15).
MP AC Wiring
the inverter’s AC input and output terminals to the MP enclosure. See Section 3.6.3 for
more information on this kit.
The knockout plate is provided as an upper conduit plate, or as a
Kit - This wiring kit provides the appropriate AC wires needed to connect
arranty service.
inverter hood is required to be installed over a Magnum inverter
• Phillips screwdriver• Pencil or marker• AC/DC Voltmeter
• Drill and drill bits• 1/2” open end wrench• Level
• Torque wrenches• Ratchet drives
• Torx screwdrivers (T15, T20 and T25 drive)
Required Material and Tools
ain-reliefs, and appropriate fi
ttings• 1/4” mounting bolts and lock washers
3.1.3 Planning
Installing the MP/inverter system can be fairly straightforward if you take time to plan before
the fi
turning
common, costly mistakes.
To assist you in planning and designing your installation, review the simplifi ed system diagram
shown in Figure 3-3 for parallel-stacked inverter installations, or Figure 3-4 for series-stacked
inverter installations. These drawings are a simple overview of the MP/inverter installation. They
are not intended to provide detailed information, override or restrict any national or local electrical
codes, nor should they be the determining factor as to whether the installation is compliant – that
is the responsibility of the electrician and the onsite inspector.
rst screw. The more thorough you plan, the more time you will save, and avoid
WARNING: Installations should
or certifi ed electrician. It is the installer’s responsibility to determine which safety
codes and standards apply, and to ensure that all applicable installation requirements
are followed. Applicable installation codes vary depending on the specifi c location and
application of the installation.
Info: Detailed MP/inv
depending on you MP model.
The installation section uses the following steps to perform the MP/inverter installation:
• Find the appropriate location (Section 3.2)
• Prepare the MP enclosure and inverter (Section 3.3)
• Mounting the MP enclosure and inverter (Section 3.4)
• Beware of wiring guidelines/safety (Section 3.5)
• Wire AC circuit (Section 3.6)
• Wire DC circuits (Section 3.7)
• Wire communications cables (Section 3.8)
• Removing negative or neutral to ground connections (Sections 3.9 and 3.10)
• Determine the system ground (Section 3.11)
• Perform a fi nal installation checklist (Section 3.12)
• Perform a functional test (Section 3.13)
• Attach the front covers (Section 3.14)
• Apply external labels (Section 3.15)
erter system wiring drawings are provided in Section 4.0,
be performed by qualifi ed personnel, such as a licensed
Choosing an appropriate location for the MP/inverter system should be determined early in the
installation process; install it only in a location that meets the following requirements:
Indoors ment away from sources of high temperature and moisture. The MP enclosure uses plated copper
busbars, powder coated metal components, and plated fasteners, which means it is very tolerant to corrosive or condensing environments (one in which humidity and/or temperature change
causes water to form on components). However, inverters are complex microprocessor controlled
devices and should be treated as sophisticated electronic devices, such as computers or stereo
equipment. When selecting the location for the MP/inverter system, don’t think of it in the same
terms as the other connected equipment, e.g., batteries, generators, etc. When inverters are
exposed to a corrosive or condensing environment their life will be shorten, and damage because
of corrosion is not covered by the product warranty.
Ventilation - If a Magnum inverter is installed on the MP enclosure, the inverter will pull in air
through the intake vents. In order for the inverter to provide full output power and avoid overtemperature fault conditions, do not cover or block the MP enclosure ventilation openings or install
it in an area with limited airfl ow. At the minimum, allow 3 inches of clearance to the left and right
of the MP enclosure to provide adequate ventilation.
Close to the Battery Bank - The MP enclosure/inverter system should be located as close to the
batteries as possible. This is to ensure the battery cable length is kept short. Long DC wires tend
to lose effi ciency and reduce the overall performance of an inverter. However, the MP enclosure,
the inverter, and any other equipment that can spark (or that corrosion could damage) should not
be installed in the same compartment/room as the batteries, or mounted where it will be exposed
to gases produced by the batteries. These gases are corrosive and will damage this equipment;
also, if these gases are not ventilated and if allowed to collect, they could ignite and cause an
explosion. Consult your battery supplier for proper installation requirements.
Location
The MP/inv
erter system must be mounted indoors in a relatively clean and dry environ-
Info: Consult the inverter owner’s manual to determine the proper inverter-to-battery
ble size for the distance used. However, this cable must not be sized any smaller than
ca
0000 (4/0) AWG if the DC disconnect breaker in the MP enclosure will also be used as
the overcurrent device. If a cable smaller than 4/0 AWG is used, an appropriately sized
fuse must be installed to provide overcurrent protection to this smaller cable.
Safe - Keep any fl ammable/combustible material (e.g., paper, cloth, plastic, etc.) that may be
ignited by heat, sparks or fl ames at a minimum distance of 12 feet away from the MP/inverter
system. Do not install the MP/inverter system in any area that contains extremely fl ammable liquids like gasoline or propane, or in locations that require ignition-protected devices. Sparks from
relays, circuit breakers, etc., could ignite the fumes or spills.
Accessible - Do not block access to the front of the MP enclosure. Maintain at least a 36” (91 cm)
clear space in front to access the AC and DC wiring terminals and connections inside the MP enclosure, as they will need to be checked and tightened periodically.
RFI - Most inverters can create RFI (Radio Frequency Interference). Keep this in mind when determining the placement of the MP/inverter system. You should locate the MP/inverter system as
far away as possible from any electronic equipment susceptible to radio frequency and electromagnetic interference.
Expandability - The MP enclosure was specifi cally designed to allow multiple inverters to be connected together. Keep in mind as your power needs grow, you can connect additional inverters
(using MPX enclosures - up to your models maximum inverter capability) to increase your power
capability. Use Figures 3-5 or 3-6 (depending on your MP model) to determine if you are allowing
the appropriate vertical and horizontal room to expand your MP/inverter system.
Rodent Proof - Ensure the MP/inverter system is located in an area that prevents rodents and
insects from entering and damaging wires/components – the MP/inverter can provide a warm
habitat in a cold environment. Mesh screens or nets may need to be installed over any openings
to ensure the unit is kept rodent free and well ventilated.
allow 1-2 inverters and MPSH models allow 1-3 inverters. Installations using one inverter
do not require a MPX extension, two inverters require one MPX extension, and three inverters require two
MPX extensions.
3. To meet UL regulatory requirements, an inverter hood must be installed above each Magnum inverter that
is mounted on the Magnum Panel (vertically).