use of this manual and the conditions or methods of installation, operation, use and maintenance
of the Magnum Panel is beyond the control of Magnum Energy, Inc. Therefore, this company does
not assume responsibility and expressly disclaims liability for loss, damage, or expense, whether
direct, indirect, consequential or incidental, arising out of or anyway connected with such installation,
operation, use, or maintenance.
Note as well that while every precaution has been taken to ensure the accuracy of the contents
of this manual, the specifi cations and product functionality may change without notice. Magnum
Energy, Inc. assumes no responsibility for errors or omissions.
Restrictions on Use
Magnum Energy, Inc. does not recommend the use of any o
life saving, or other medical equipment or devices designated as “critical” by the U.S. FDA where
failure or malfunction of the Magnum Energy product can be reasonably expected to cause failure
of the life support device, or to signifi cantly affect its safety or effectiveness. Using Magnum Energy
products with this particular equipment is at your own risk.
odify this document is prohibited unless express written permission from Magnum Energy, Inc.
is provided.
Contact Information
Magnum Energy, Inc.
2211 West Casino Rd.
Everett, WA 98204
Phone: 425-353-8833
F
ax: 425-353-8390
Web: www.MagnumEnergy.com
Statement of Appreciation
From all of us at Magnum Energy -
Thank you for purchasing this Magnum Panel (MP).
We
understand that you have many purchasing options in the marketplace, and are pleased that you
have decided on a Magnum Energy product. This MP enclosure was proudly designed, assembled
and tested in the United States at our Everett, Washington facility.
At Magnum, we are committed to providing you with quality products and services; we hope that
your experience with us is pleasant and professional.
Page i
Magnum Energy® is a registered trademark of Magnum Energy, Inc.
orque Values for Dual Hole Busbars ............................................................................. 37
Page iv
1.0 Safety Information
1.0 Safety Information
IMPORTANT SAFETY INSTRUCTIONS
his manual contains important safety instructions that
T
and operation of this product. Before using the Magnum Panel (MP), read all instructions
and cautionary markings on: (1) the MP enclosure, (2) the inverter/charger, and (3) the
batteries, as well as the individual manuals provided for each component of the system.
These installation instructions are for use by qualifi ed personnel only. Do not perform any
installation or servicing other than that specifi ed in this owner’s manual unless qualifi ed to do so.
Incorrect installation or servicing may result in a risk of electric shock, fi re, or other safety hazard.
must be followed during the installation
1.1 Safety Symbols
The following safety symbols have been placed throughout this manual to indicate dangerous
conditions and important safety instructions.
WARNING: This symbol
physical harm to the user.
CAUTION: This symbol indicates that failure to take a specifi ed action could result in
damage to the equipment.
Info: This symbol indicates information that emphasizes or supplements important
points of the main text.
indicates that failure to take a specifi ed action could result in
1.2 General Safety
• All electrical work must be performed in accordance with local and national electrical codes.
This product is designed for indoor/compartment installation. It must not be exposed to rain,
•
snow, moisture or liquids of any type.
• Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
• Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
maintenance on the inverter.
• Both AC and DC overcurrent protection must be provided as part of the installation.
• Use Class 1 wiring methods for fi eld wiring connections to terminals of a Class 2 circuit.
• Listed or labeled equipment shall be installed and used in accordance with any instructions
included in the listing or labeling.
• To reduce risk of electric shock, disconnect all wiring before attempting any maintenance or
cleaning. Turning off the inverter will not reduce this risk, the inverter bypass must be used or
the panel should be totally disconnected from all sources.
• All wiring must have a minimum rating of 150V, 75°C when using 120V AC inverters; or 300V,
75°C when using 120/240V AC inverters.
• AC wiring must be no less than 10 AWG (5.3 mm2) gauge copper wire.
• Battery cables should be no less than #4/0 AWG unless fused close to the battery bank for
smaller sized cables.
• Crimped and sealed copper ring terminal lugs with a 3/8” hole should be used to connect to
the DC terminals inside the MP enclosure. Soldered cable lugs are also acceptable.
• Torque all AC wiring connections and DC cable connections to the required torque values.
• Be very careful when working around batteries, they can produce extremely high currents if
short-circuited. Read
inverter and batteries.
• Wear eye protection such as safety glasses when working with batteries.
• Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
maintenance on the batteries.
• Never work alone. Always have someone near you when working around batteries.
• Use proper lifting techniques when working with batteries.
• Never use old or untested batteries. Check each battery’s label for age, type, and date code
to ensure all batteries are identical.
• Batteries are sensitive to changes in temperature. Always install batteries in a stable
environment.
• Install batteries in a well ventilated area. Batteries can produce explosive gasses. For
compartment or enclosure installations, always vent batteries to the outside.
• Provide at least one inch of air space between batteries to provide optimum cooling.
• Never smoke when in the vicinity of batteries.
• To prevent a spark at the battery and reduce the chance of explosion, always connect the
cables to the batteries fi rst. Then connect the cables to the MP enclosure/inverter system.
• Use insulated tools at all times.
• Always verify proper polarity and voltage before connecting the batteries to the MP enclosure/
inverter system.
• To reduce the chance of fi re or explosion, do not allow the battery terminals to be shortcircuited.
• In the event of accidental exposure to battery acid, wash thoroughly with soap and water. In
the event of exposure to the eyes, fl ood them for at least 15 minutes with running water and
seek immediate medical attention.
• Recycle old batteries.
• Be extra cautious to reduce the risk of dropping a metal tool onto batteries. It could short-circuit
the batteries or other electrical parts, resulting in sparks that could cause a fi re or an explosion.
the battery supplier’s precautions before installing and connecting the
• Cover the terminals to prevent accidental shorting.
The Magnum P
dardize inverter installations and allow for the ability to expand the inverter system in the future.
Specifi cally designed for multiple inverter applications, the MP enclosures ensure safety and reliability by combining all of the major components required for a renewable energy system — inverter/
battery disconnect, AC overcurrent protection, grounding connections, and a full-system bypass
switch — into an easy to install pre-wired enclosure. The modular design of the MP enclosure with
the Magnum Energy inverter allows it to be UPS shipped and easily assembled on site.
Installing an inverter system is now as simple as mounting the MP enclosure, installing the inverters, connecting the battery bank, and if needed, bringing in AC power from a generator or the
utility grid. Now all of the inverter’s required AC and DC disconnects and wire connection points
are all together, and integrated in the self-contained MP enclosure.
anels (MP) are part of a new line of enclosures from Magnum Energy that stan-
2.1 MP Series Overview
The MP enclosures are available in four basic confi gurations: the MPSL-30D, MPSH-30D, and
MPDH-30D are designed to be used with the Magnum MS-PAE inverter models when stacked in
parallel; and the MPSL-60S, which is designed for use with two MS4024 inverters when stacked
in series. These confi gurations provide different maximum power abilities to meet present and
future requirements.
2.1.1 Models
MPSL-30D (Magnum Panel,
MPSL-60S (Magnum Panel, Single Enclosure, Low Capacity, Single-pole 60A AC input breaker)
MPSH-30D (Magnum Panel, Single Enclosure, High Capacity, Double-pole 30A AC input breakers)
MPDH-30D (Magnum Panel, Dual Enclosure, High Capacity, Double-pole 30A AC input breakers)
Single Enclosure, Low Capacity, Double-pole 30A AC input breakers)
2.1.2 Standard Features
The main components and features for the MP Series enclosures are:
• Standard confi gur
• Enclosure is steel construction with a durable, white powder coat fi nish to help prevent corrosion
• Built-in, pre-wired, full system bypass switch for inverter isolation/battery maintenance
• Front-mounted AC and DC breakers for quick and easy operation
• AC, DC, and Ground busbars with set-screw type compression terminals (no lugs required)
• Full system capacity shunt (500 or 1000 DCA), allows easy connection to battery monitor
• Enclosure and components are certifi ed for indoor use to UL/CSA standards
• DC negative and ground busbars (negative can be isolated if PV-GFP device installed)
• Battery positive busbar for DC loads and PV arrays included (not available on MPSH-30D)
• Space available to add DC load/disconnect breakers (not available on MPSH-30D)
• Standalone top plate provided to allow other (non-Magnum) inverter installations
• Knockouts for inverter and battery cables, PV in/out, DC breakers
• Data cables with 300-volt rated insulation provided to allow 240V AC inverter installations
• Easy accessibility for fi eld installation/wiring of additional breakers/components
• Pre-wired AC over-current circuit breaker protection to the inverter’s input
• Space for additional AC breakers (depends on enclosure confi guration)
• Inverter DC disconnect with inverter-to-breaker battery cables included
• Plated copper busbars included for up to six additional battery positive and negative circuits
ations allow future expansion using MPX enclosures for increased power
L-30D (Magnum Panel, Single Enclosure, Low Capacity, Double 30A AC Inverter Input Breaker)
Capability for one MS-PAE Series inverter (expandable to a maximum of two MS-PAE Series
inverters stacked in parallel using an optional MPX extension box).
MPSL-30D(as shipped)
Includes:
• D
30A AC Inverter Input
Breaker (x1)
• 250A DC Disconnect
(x1)
• Inverter AC Input/
Output wires
• Data cables rated for
120/240V AC circuits
Figure 2-1a, MPSL-30D as Shipped
• D60A AC System
Bypass
• 500A/50mV DC
Shunt
• Inverter Hood (x1)
• Router Bracket
MPSL-30D
with MPXS-30D-L
Includes:
30A AC Inverter Input Breakers (x2)• D60A AC System Bypass
• D
• 250A DC Disconnects (x2)• 500A/50mV DC Shunt
• Inverter AC Input/Output wires• Inverter Hoods (x2)
• Data cables rated for 120/240V AC circuits• Router Bracket
Capability for one MS-PAE Series inverter (expandable to a maximum of three MS-PAE Series
inverters stacked in parallel using optional MPX extension boxes)
agnum Panel, Single Enclosure, High Capacity, Double 30A AC Inverter Input Breaker)
MPSH-30D(as shipped)
Includes:
• D
30A AC Inverter Input
Breaker (x1)
• 250A DC Disconnect
(x1)
• Inverter AC Input/
Output wires
• Data cables rated for
120/240V AC circuits
• D125A AC System
Bypass
• 1000A/100mV DC
Shunt
• Inverter Hood (x1)
• Router and Charge
Controller Bracket
Figure 2-3a, MPSH-30D as Shipped
MPSH-30D with MPXS-30D-L (MPX - Left Side) and MPSX-30D-R (MPX - Right Side)
Includes:
30A AC Inverter Input Breakers (x3)• D125A AC System Bypass
• D
• 250A DC Disconnects (x3)• 1000A/100mV DC Shunt
• Inverter AC Input/Output wires• Inverter Hoods (x3)
• Data cables rated for 120/240V AC circuits• Router and Controller Bracket
Field Installed Options Shown (not included):
• PAE Series parallel-stack inverters (x3) • BP-S Single Mounting Backplate
• ME-RTR R
outer • BP-D Dual Mounting Backplate
Figure 2-3b, MPSH-30D with Field Installed Options
Capability for one or two MS-PAE Series inverters (expandable to a maximum of four MS-PAE
Series inverters stacked in parallel using optional MPX extensions).
agnum Panel, Dual Enclosure, High Capacity, Double 30A AC Inverter Input Breakers)
MPDH-30D(as shipped)
Includes:
• D
30A AC Inverter Input
Breakers (x2)
• 250A DC Disconnects
(x2)
• Inverter AC Input/
Output wires
• Data cables rated for
120/240V AC circuits
• D125A AC System
Bypass
• 1000A/100mV DC
Shunt
• Inverter Hoods (x2)
• Router and Charge
Controller Bracket
Figure 2-4a, MPDH-30D as Shipped
MPDH-30D with MPXD-30D-L (MPX - Left Side) and MPXD-30D-R (MPX - Right Side)
Includes:
30A AC Inverter Input Breakers (x4)• D125A AC System Bypass
• D
• 250A DC Disconnects (x4)• 1000A/100mV DC Shunt
• Inverter AC Input/Output wires• Inverter Hoods (x4)
• Data cables rated for 120/240V AC circuits• Router and Controller Bracket
confi gured and monitored, and maintains the critical settings in nonvolatile memory.
• ME-ARC – Advanced Remote Control with LCD display; has all the features of the ME-RC remote,
but also confi gures the advanced features of the inverter (or any connected accessory).
• ME-RTR – The ME-RTR, or “router” provides parallel capability for the MS-PAE Series inverters
and includes many of the same features as the ME-ARC advanced remote control. The router
is designed with a user-friendly LCD display and rotary SELECT knob that allows all connected
MS-PAE series inverter/chargers to be programmed in sync without the need to program
each inverter separately. The router will accommodate up to four MS-PAE inverter/chargers
in parallel, plus accessories.
• ME-BMK-NS – Battery Monitor; determines battery State of Charge (DC shunt not included).
• BP-S – Single Mounting Backplate; for mounting a Magnum inverter and MP/MPX enclosures.
It can be combined with the BP-D for additional mounting surface area. UPS shippable.
• BP-D – Dual Mounting Backplate; for mounting a Magnum inverter and MP/MPX enclosures,
It can be combined with the BP-S for additional mounting surface area. UPS shippable.
• DC Breakers – MP enclosure has space for E-Frame/back-mounted (1” width) or Q-Frame/
DIN rail-mounted (1/2” width) DC breakers (not applicable for the MPSH-30D model).
• MPX Extensions – These enclosures allow additional Magnum inverters to be mounted and
electrically wired to the Magnum Panel to allow an integrated panel system. The top of the
MPX is designed to allow Magnum inverters to fi t seamlessly into the top. The MPX Series
enclosures come with the AC and DC breakers and wiring to install another Magnum inverter.
An inverter hood is also included with each MPX extension to allow the inverter to be mounted
vertically.
• ME-MW-W - The MagWeb Wireless allows Magnum Energy’s inverters and accessories to be
remotely monitored. Installed on the Magnum network, the MagWeb provides live Internet
monitoring of the inverter, battery monitor, and automatic generator start module. Using your
always on Internet connection, the MagWeb makes live and historical conditions available to
you through a web browser at
emote Control with LCD display; allows inverter (or connected accessory) to be
http://data.magnumenergy.com
.
2.2 Regulatory Compliance
The MP enclosure
Equipment (ISE) for use with inverters. It has been independently tested and certifi ed by Intertek
Testing Services (known as ETL) to UL 1741, 2nd Edition, and is also CSA certifi ed to C22.2 No.
107.1-01 (R2006). These certifi cations mean the MP enclosure meets the minimum requirements
of prescribed product safety standards.
Note: ETL is a Nationally Recognized Testing Laboratory (NRTL). NRTL’s are qualifi ed organizations
that meet the requirements of Occupational Safety and Health Administration (OSHA) regulations
to perform independent safety testing and product certifi cation.
carries the ETL Listed Mark and is designated as Interconnection System
Page 6
2.0 Introduction
2.3 MP External Components
The main external
the MPDH enclosure (as shown in Figure 2-6) are described below:
components of the MPSL and MPSH enclosures (as shown in Figure 2-5) and
Info:
head, T25 T
1
Inv
This plate allows a Magnum inverter to sit on top of the MP enclosure, and allow the AC
and DC wiring to be easily routed from the inverter to the MP enclosure.
The inverter plate can be replaced with the Knockout Plate, which is used as an upper
conduit/safety plate. See Section A5 for more information on the Knockout Plate.
The external components are secured to the enclosure using #10-32 x 3/8” (Pan
orx driv
erter Plate - The MP enclosure is factory shipped with the inverter plate installed.
WARNING: To
MP enclosure, the Knockout Plate must be installed if the Magnum inverter is
removed for service and the AC bypass breaker is switched ON.
2
e) thread cutting screws and #10 lock washers.
prevent accidental access to live electrical circuits inside the
access the internal components. The front cover panels are equipped with rectangular
knockouts, to allow additional AC and DC circuit breakers to be installed.
Side
MP
and communications conductors to be routed from the main MP enclosure to a MPX
extension box (when used).
DC
battery monitor) and the DC ground stud.
Conduit
enclosure are provided to allow metal and PVC conduits. For dimensions and sizes, see
Figures 3-13 and 3-14.
Access
Shunt
Access
Knockouts
- The cover(s) on the front of the MP enclosures can be removed to
Plate (x2) - These access plates (one on each side) allow the power
Plate - This plate allows access to the DC shunt (for connecting a
Multiple sized knockouts on the side and bottom of the MP
Additional
MPSL-30D (see Figure 2-7), the MPSL-60S (see Figure 2-8), the MPSH-30D (see Figure 2-9), and
the MPDH-30D (see Figures 2-10a and 2-10b) are listed alphabetically and described below:
components are located inside the MP enclosure. The components found inside the
Info:
A
compression terminals (no ring lugs required). The number of terminals available
depends on the particular busbar and the MP model.
Info:
common to each other as they are all connected to the MP chassis.
AC
GROUND
used to connect the incoming and outgoing AC circuit grounds to a common ground point.
AC LEG 1 IN Busbar - Connects incoming LEG 1 AC power from the grid or a generator to the
MP/inverter system. This busbar is used to connect the LEG 1 output of a 120/240V AC external
source (grid power or AC generator) to the MP enclosure. The AC LEG 1 IN busbar is connected to
the HOT 1 input of the inverter system (thru the inverter’s AC input breaker). The external source
is used by the inverter to charge the batteries and power downstream loads thru the inverter.
AC LEG 1 OUT Busbar - Supplies the LEG 1 power from the MP/inverter system to the AC loads.
This busbar is the connection point from the MP enclosure to the LEG 1 terminal in the electrical
panel powered by the inverter.
AC LEG 2 IN Busbar - Connects incoming LEG 2 AC power from the grid or a generator to the
MP/inverter system. This busbar is used to connect the LEG 2 output of a 120/240V AC external
source (AC generator or grid power) to the MP enclosure. The AC LEG 2 IN busbar is connected to
the HOT 2 input of the inverter system (thru the inverter’s AC input breaker). This external source
is used by the inverter to charge the batteries and power downstream loads thru the inverter.
AC LEG 2 OUT Busbar - Supplies the LEG 2 power from the MP/inverter system to the AC loads.
This busbar is the connection point from the MP enclosure to the LEG 2 terminal in the electrical
panel powered by the inverter.
AC NEUTRAL Busbars - The neutral leg for loads powered from the MP/inverter system and the
neutral leg for AC power supplied to the MP/inverter system by either a generator or grid. These
two busbars are the connection points for the AC neutrals in the system. The system neutrals
include: the neutral output from the external AC source (generator/grid), the neutral terminal in
the electrical panel that is powered by the inverter, and the input and output neutral terminals of
each inverter. Note: Both AC NEUTRAL busbars are electrically connected to each other.
All the busbars have dual hole sizes — the larger holes accept #14 to #1/0
WG
and the smaller holes accept #14 to #6 AWG — these holes have set-screw type
All AC Ground Busbars, DC Ground Busbars, and the DC Ground Stud are electrically
Busbar(s) - These busbars are connected to the MP enclosure chassis and are
• Installing MS-PAE Series inverters: Both neutral terminals are common with each other
within the MS-PAE Series, this means only one neutral from each MS-PAE inverter needs to
connect to the AC NEUTRAL busbar.
• Installing MS4024 inverters: The Neutral In and Neutral Out are not common with each
other within the MS4024; this means both input and output neutrals from each MS4024
inverter needs to connect to the AC NEUTRAL busbar.
AC NEUTRAL-GROUND Connection - A wire (green) connects the AC neutral to the system
ground. This green wire can be removed from the GROUND busbar if the primary AC neutral to
ground connection is made elsewhere in the system (see Section 3.10).
Battery Negative Connection - The bottom of the DC Shunt busbar is the connection point to
the negative terminal of the battery bank. This busbar is supplied with a 3/8-16 bolt and lock
washer to allow the battery cable to be connected.
point to the positive terminal of the battery bank. The DC disconnect provides a rear captive nut
to allow the battery cable to be front-connected using a 3/8-16 bolt and lock washer.
DC GROUND Busbar - This busbar is connected to the MP enclosure chassis and is used to tie
DC equipment grounds to a common point. This terminal is also used to connect the inverter/
MP/inverter system to the DC grounding electrode. If the DC grounding electrode conductor
is greater than #1/0 AWG, use the DC Ground Stud to connect to the DC grounding electrode
(i.e., ground rod).
DC Ground Stud - This 5/16-18 stud is connected to the MP enclosure chassis, and is provided
as a connection point to the DC grounding electrode when the conductor is larger than #1/0 AWG.
This stud also connects to the DC shunt through a busbar and serves as the DC negative to
ground connection point. If installing a PV-GFP device, this busbar must be removed (see Section 3.11). Note: For ground wires #1/0 AWG or smaller, use the DC GROUND busbar.
DC NEGATIVE Busbar - This busbar is connected to the battery bank negative through the
load side of the DC shunt. This busbar is the battery negative connection point for additional
DC circuits, such as from the DC negative output of a charge controller or when combining the
negatives of DC load circuit breakers. This busbar is rated to handle 120 amps.
DC NEGATIVE-GROUND Connection - This busbar connects the DC negative to the system
ground. It must be removed if the primary DC negative to ground connection is made elsewhere
in the system (see Section 3.11).
DC POSITIVE Busbar - This busbar is connected to the battery bank positive through the
bottom of the inverter DC disconnect. This busbar is the battery positive common point for
connecting additional DC circuits, such as from the output of a charge controller disconnect, the
DC positive feed to DC load breakers, and the positive connection to a battery status monitor.
This busbar is rated to handle 120 amps.
DC Shunt - A DC shunt installed in the DC negative side that is used to measure the amperage fl owing between the battery and the inverter (and any DC loads connected). This shunt is
pre-installed so that a battery monitor may be easily connected to display the current fl ow. See
Section A-2 for information on installing and wiring the ME-BMK-NS battery monitor inside the
MP enclosure. The MPSL-30D and MPSL-60S are supplied with a 500 amp/50mV DC shunt, and
the MPSH-30D and MPDH-30D have a 1000A/100mV DC shunt.
DC Shunt Voltage Sense Terminals - These two shunt terminals/screws serve as the sense
connections to the optional ME-BMK-NS battery monitor. When current is passed through the
shunt, the IR drop (AKA voltage drop) developed across it can be read by the battery monitor
to provide an accurate indication of the current fl owing through the shunt.
DIN Rail Track - For installing up to 1/2” (12.7mm) wide, DIN rail-mounted, Q-Frame type,
DC breakers. These breakers can be used for connecting DC loads or installing a PV-GFP device.
The track may be removed to allow 1” (25.4mm) wide, back-mounted, E-Frame type breakers
to be installed instead.
Enclosure Joining Screw/Washer - A #10-32 x 3/8” (Pan head, T25 Torx drive) thread
cutting screw and #10 lock washers are provided to join the two enclosures of the MPDH-30D
together – to have them at the same electrical potential. See Figure 3-16c for more information.
INV HOT 1 OUT Busbar - This busbar is the connection point for the HOT 1 output from each
installed inverter. The total output power combined from every inverter on this busbar is fed thru
the Inverter Bypass Breaker Assembly to the AC LEG 1 OUT Busbar.
INV HOT 2 OUT Busbar - This busbar is the connection point for the HOT 2 output from each
installed inverter. The total output power combined from every inverter on this busbar is fed thru
the Inverter Bypass Breaker Assembly to the AC LEG 2 OUT Busbar.
Positive Connection - The bottom of the inverter’s DC disconnect is the connection
circuit, a way to disconnect the AC input to the inverters, and overcurrent protection to the
inverter’s input wires when the minimum recommended AC wire sizes are used. Depending on
your MP model, the breaker provided for the inverter input will be either a double-pole 30 amp
(D30A) or a single-pole 60 amp (S60A) AC breaker.
The double-pole 30 amp AC breaker is provided on the MPSL-30D, MPSH-30D, and MPDH-30D
models to allow 120/240V AC inverters — up to 30 AC amps per leg pass-thru capability — to be
connected. The MPSL-30D and MPSH-30D come with one double-pole 30A input breaker and the
MPDH-30D comes with two double-pole 30A breakers. These three models require a double-pole
30A breaker for each additional inverter installed in a parallel-stacked confi guration.
The single 60 amp AC breaker is provided on the MPSL-60S models to allow 120V AC inverters
— up to 60 AC amps pass-thru capability — to be connected. If connecting MS4024’s in a
series-stacked confi guration, an additional single pole 60A breaker for the second MS4024 will
be required (as provided in the MPX extension kit).
Inverter Bypass Breaker Assembly - The Inverter AC Bypass Breaker Assembly is pre-wired
at the factory and consists of the inverter bypass switch and the inverter AC output disconnect
breaker. This breaker assembly provides a way to disconnect the AC output of the inverter
system, and to directly connect the AC input to the AC output by bypassing the inverter system.
The MPSL-30D and MPSL-60S are installed with a double-pole 60-amp AC bypass breaker
assembly, and the MPSL-30D and MPDH-30D are equipped with a double-pole 125-amp AC
bypass breaker assembly.
Inverter DC Disconnect Breaker - This 250 amp DC disconnect is a high interruption capacity,
magnetic-hydraulic, DC circuit breaker. These breakers were specifi cally designed and tested
to work with Magnum inverters to provide the delay time needed to minimize nuisance breaker
tripping. It provides an easy and convenient way to isolate the inverter from the battery, and
meets the NEC/CEC requirements for DC overcurrent protection when the size and length of the
battery-to-inverter cables are installed in accordance with the installation instructions in this
manual. These breakers have front-accessible connections, each provided with 3/8-16 Hex head
bolts with lock washers.
Inverter’s DC Negative Connection - Connects to Magnum inverter’s DC negative terminal.
Inverter’s DC Positive Connection - Connects to Magnum inverter’s DC positive terminal.
Mounting Dimples, BMK (x2) - These dimples allow the optional ME-BMK-NS (Battery Monitor
Kit without DC shunt) to be installed. Two #8-32 x 1/2” (T20 Torx drive) thread cutting screws
are provided to mount the battery monitor. See Section A2 for more information on mounting
the battery monitor.
Mounting Holes, Inv AC Input Breakers - Used to install additional Inverter AC Input
Breakers, which provide protection to each inverter’s AC input circuit.
Mounting Holes, Inv DC Backmount Breakers - For installing 1” (25.4mm) wide, back-
mounted, E-Frame type, DC breakers. These breakers can be used for connecting DC loads or
installing a PV-GFP device.
Mounting Holes, Inv DC Disconnect Breakers - Used to install additional Inverter DC
Disconnect Breakers, which isolate the inverter from the battery. These breakers meet the NEC/
CEC requirements for DC overcurrent protection when used in accordance with the installation
instructions in this manual.
Mounting Keyholes, MP Enclosure (x4) - Four keyholes for mounting the enclosure. See
Figures 3-5 or 3-6 for size information on these keyholes.
Input Breakers - These breakers provide protection to the inverter’s AC input
This section describes the requirements and recommendations for installing the MP enclosure.
Info:
MPSL/MPSH
inverters are required, the optional MPX enclosures are used. Refer to the MPX Extension
Owner’s Manual (PN:64-1015) for information on installing these additional inverters.
This installation section primarily explains the installation of one inverter on the
enclosure,
and two inverters on the MPDH enclosure. When additional
3.1 Pre-Installation
Before proceeding with the installation:
• Please read and familiarize yourself with the entire Installation section.
• Read and ensure you understand the “Important Product Safety Information” and the “Important
Battery Safety Instructions” at the beginning of this manual.
• Be aware of all safety and electrical codes which must be met.
• Inspect all shipping cartons for evidence of physical damage. If a shipping carton is damaged,
request that the shipping agent be present for inspection when the carton is opened.
• Unpack the MP enclosure box and remove the components. Verify that you have the components
and hardware as listed below in Section 3.1.1 (and shown in Figures 3-1 and 3-2).
• Use the information in Section 3.1.2 to help identify most of the materials and tools required
for the installation.
• Read the information provided in Section 3.1.3 to properly plan for the installation.
3.1.1 MP Parts Included
Refer to Figures 3-1 or 3-2 (and the item list below) for you particular MP model to verify the
nece
ssary parts are included. If items are missing, contact your authorized Magnum Energy dealer
or Magnum Energy.
1a
1b
2
3
4
5
6
Info: Save your proof-of-purchase as a record of your ownership; it will be needed if
the unit should require in-w
L or MPSH Models - The MPSL-30D, MPSL-60S, and MPDH-30D use a single enclosure
MPS
to provide the AC/DC breakers, busbars, and wiring for the inverter’s AC and DC circuits.
H Model - The MPDH-30D uses two enclosures, one enclosure (AC Side) provides
MPD
the AC breakers, busbars, and wiring for the inverters AC circuits; and, the other
enclosure (DC Side) provides the DC breakers, busbars, and wiring for the inverter’s
DC circuits.
Inverter Hood - The
that is mounted on a Magnum Panel to prevent items from falling into the ventilation
openings at the top of the inverter. See Section A3 for more information on this hood.
Knockout Plate -
safety plate. See Section A5 for more information on this plate.
RTR (Router) Bracket Kit - This kit consists of the router bracket and the hardware
ME-
to attach the ME-RTR (i.e., Router) to the side of the MP enclosure. This kit is not
provided with the MPSL-60S model. See Section A4 for more information on this kit.
Hardware Kit - This hardware kit consists of the Charge Controller bracket and
MP
hardware (see Section A1), the owner’s manual, communications cables (see Section
3.8), and a front cover label set (see Section 3.15).
MP AC Wiring
the inverter’s AC input and output terminals to the MP enclosure. See Section 3.6.3 for
more information on this kit.
The knockout plate is provided as an upper conduit plate, or as a
Kit - This wiring kit provides the appropriate AC wires needed to connect
arranty service.
inverter hood is required to be installed over a Magnum inverter
• Phillips screwdriver• Pencil or marker• AC/DC Voltmeter
• Drill and drill bits• 1/2” open end wrench• Level
• Torque wrenches• Ratchet drives
• Torx screwdrivers (T15, T20 and T25 drive)
Required Material and Tools
ain-reliefs, and appropriate fi
ttings• 1/4” mounting bolts and lock washers
3.1.3 Planning
Installing the MP/inverter system can be fairly straightforward if you take time to plan before
the fi
turning
common, costly mistakes.
To assist you in planning and designing your installation, review the simplifi ed system diagram
shown in Figure 3-3 for parallel-stacked inverter installations, or Figure 3-4 for series-stacked
inverter installations. These drawings are a simple overview of the MP/inverter installation. They
are not intended to provide detailed information, override or restrict any national or local electrical
codes, nor should they be the determining factor as to whether the installation is compliant – that
is the responsibility of the electrician and the onsite inspector.
rst screw. The more thorough you plan, the more time you will save, and avoid
WARNING: Installations should
or certifi ed electrician. It is the installer’s responsibility to determine which safety
codes and standards apply, and to ensure that all applicable installation requirements
are followed. Applicable installation codes vary depending on the specifi c location and
application of the installation.
Info: Detailed MP/inv
depending on you MP model.
The installation section uses the following steps to perform the MP/inverter installation:
• Find the appropriate location (Section 3.2)
• Prepare the MP enclosure and inverter (Section 3.3)
• Mounting the MP enclosure and inverter (Section 3.4)
• Beware of wiring guidelines/safety (Section 3.5)
• Wire AC circuit (Section 3.6)
• Wire DC circuits (Section 3.7)
• Wire communications cables (Section 3.8)
• Removing negative or neutral to ground connections (Sections 3.9 and 3.10)
• Determine the system ground (Section 3.11)
• Perform a fi nal installation checklist (Section 3.12)
• Perform a functional test (Section 3.13)
• Attach the front covers (Section 3.14)
• Apply external labels (Section 3.15)
erter system wiring drawings are provided in Section 4.0,
be performed by qualifi ed personnel, such as a licensed
Choosing an appropriate location for the MP/inverter system should be determined early in the
installation process; install it only in a location that meets the following requirements:
Indoors ment away from sources of high temperature and moisture. The MP enclosure uses plated copper
busbars, powder coated metal components, and plated fasteners, which means it is very tolerant to corrosive or condensing environments (one in which humidity and/or temperature change
causes water to form on components). However, inverters are complex microprocessor controlled
devices and should be treated as sophisticated electronic devices, such as computers or stereo
equipment. When selecting the location for the MP/inverter system, don’t think of it in the same
terms as the other connected equipment, e.g., batteries, generators, etc. When inverters are
exposed to a corrosive or condensing environment their life will be shorten, and damage because
of corrosion is not covered by the product warranty.
Ventilation - If a Magnum inverter is installed on the MP enclosure, the inverter will pull in air
through the intake vents. In order for the inverter to provide full output power and avoid overtemperature fault conditions, do not cover or block the MP enclosure ventilation openings or install
it in an area with limited airfl ow. At the minimum, allow 3 inches of clearance to the left and right
of the MP enclosure to provide adequate ventilation.
Close to the Battery Bank - The MP enclosure/inverter system should be located as close to the
batteries as possible. This is to ensure the battery cable length is kept short. Long DC wires tend
to lose effi ciency and reduce the overall performance of an inverter. However, the MP enclosure,
the inverter, and any other equipment that can spark (or that corrosion could damage) should not
be installed in the same compartment/room as the batteries, or mounted where it will be exposed
to gases produced by the batteries. These gases are corrosive and will damage this equipment;
also, if these gases are not ventilated and if allowed to collect, they could ignite and cause an
explosion. Consult your battery supplier for proper installation requirements.
Location
The MP/inv
erter system must be mounted indoors in a relatively clean and dry environ-
Info: Consult the inverter owner’s manual to determine the proper inverter-to-battery
ble size for the distance used. However, this cable must not be sized any smaller than
ca
0000 (4/0) AWG if the DC disconnect breaker in the MP enclosure will also be used as
the overcurrent device. If a cable smaller than 4/0 AWG is used, an appropriately sized
fuse must be installed to provide overcurrent protection to this smaller cable.
Safe - Keep any fl ammable/combustible material (e.g., paper, cloth, plastic, etc.) that may be
ignited by heat, sparks or fl ames at a minimum distance of 12 feet away from the MP/inverter
system. Do not install the MP/inverter system in any area that contains extremely fl ammable liquids like gasoline or propane, or in locations that require ignition-protected devices. Sparks from
relays, circuit breakers, etc., could ignite the fumes or spills.
Accessible - Do not block access to the front of the MP enclosure. Maintain at least a 36” (91 cm)
clear space in front to access the AC and DC wiring terminals and connections inside the MP enclosure, as they will need to be checked and tightened periodically.
RFI - Most inverters can create RFI (Radio Frequency Interference). Keep this in mind when determining the placement of the MP/inverter system. You should locate the MP/inverter system as
far away as possible from any electronic equipment susceptible to radio frequency and electromagnetic interference.
Expandability - The MP enclosure was specifi cally designed to allow multiple inverters to be connected together. Keep in mind as your power needs grow, you can connect additional inverters
(using MPX enclosures - up to your models maximum inverter capability) to increase your power
capability. Use Figures 3-5 or 3-6 (depending on your MP model) to determine if you are allowing
the appropriate vertical and horizontal room to expand your MP/inverter system.
Rodent Proof - Ensure the MP/inverter system is located in an area that prevents rodents and
insects from entering and damaging wires/components – the MP/inverter can provide a warm
habitat in a cold environment. Mesh screens or nets may need to be installed over any openings
to ensure the unit is kept rodent free and well ventilated.
allow 1-2 inverters and MPSH models allow 1-3 inverters. Installations using one inverter
do not require a MPX extension, two inverters require one MPX extension, and three inverters require two
MPX extensions.
3. To meet UL regulatory requirements, an inverter hood must be installed above each Magnum inverter that
is mounted on the Magnum Panel (vertically).
Prior to mounting any component, the installation will be easier if you prepare the MP enclosure
and the Magnum in
• Remove the MP enclosure front cover as described in Section 3.3.1.
• Remov
e the appropriate conduit knockouts as described in Section 3.3.2.
Note: It is much easier to access the enclosure sides and remove the knockouts if the enclosure
is sitting on a bench, rather than trying to remove the knockouts while the enclosure is mounted.
• Connect and separate the inverter’s AC input and output wires as described in Section 3.3.3.
When installing multiple inverters, access to the inverter’s AC terminals is limited, so take the
time to connect the wires and separate the wires prior to mounting the inverter.
3.3.1 Removing the Front Cover
To remove the front cover on each enclosure, use a T25 Torx screwdriver to unscrew the eight
upper and lower screws/w
T25 Torx drive, thread cutting screws and the washers are #10 external tooth star-washers.
The single MP enclosures (MPSL-30D, MPSL-60S, and MPSH-30D) use eight screws/washers to
hold the front cover in place, see Figure 3-8. The dual MP enclosure (MPDH-30D) also uses eight
screws/washers to hold each front cover in place (sixteen total), see Figure 3-9.
Important: On the AC side of the MPDH-30D, there is a #10-32 x3/8” Torx screw (T25 drive). It
is screwed into the right side (see Item 17, Figure 2-10a). It is used to join the two enclosures
together and must be removed prior to mounting (see Figure 3-16c).
Important: On some versions of the MP enclosure there are eight Truss head, Torx drive screws
in the middle (see Figure 3-7). DO NOT remove these middle screws to remove the front cover.
These screws are used to hold the top, middle and bottom sections of the front cover together,
and help align the knockout openings when additional breakers are installed (refer to Section A8).
verter by performing the following:
ashers as shown in Figure 3-7. The screws are #10-32 x 3/8” Pan head,
3.3.2 Planning Wire/Conduit Runs and Removing Knockouts
MP enclosure is designed to provide ample room for
The
to facilitate conduit installation for wire runs. See Figure 3-13 or 3-14 (depending on you model) to
see the size and location of these conduit knockouts. The 1/2”, 3/4”, and 1” knockouts are normally
used for the AC circuits, PV array, DC loads, and other smaller input cables. The 1 1/2” and 2”
knockouts are used to connect to the battery bank. Remove the appropriate knockout close to the
terminal where that wire connects, or whichever one works for the way your fi eld wiring comes in.
Before removing any knockout, review Figure 3-10 and think about all the wiring required and
where you are going to route the different circuits; such as:
• Wiring from the MP enclosure to the AC loads (AC sub-panel)
• Wire runs from the AC source (utility and/or a generator) to the MP enclosure
• Battery cable wiring from the battery bank to the MP enclosure
• Additional wiring from any external DC source (PV, wind, or hydro) to the MP enclosure
• Small signal wiring (remote controls, battery monitoring, auto gen starting)
As shown in Figure 3-11, remove the knockouts by tapping the edge with a straight bladed
scr
ewdriver and a hammer, then twist out with pliers. Ensure no debris remains inside the MP
enclosure after removing the knockouts.
Figure 3-11, Removing Knockouts
3.3.3 Connect and Separate Inverter AC Wires
ore mounting the inverter on the MP enclosure, we highly recommend using the wires provided
Bef
in the MP AC Wiring Kit (Item 6, Figures 3-1 and 3-2) and connecting them to the inverter’s AC
wiring terminals (see Figure 4-1 for MS4024 inverters, Figure 4-2 for MS-PAE Series inverters, or
refer to the inverters owner’s manual). It is possible to connect these wires after the inverter is
mounted, but space and access is limited - especially when installing multiple inverters side-byside on an MP enclosure system.
When connecting the inverter’s AC input and output wires, take time to separate the wires into
two bundles (AC input and AC output), and route each bundle thru different strain-reliefs on the
inverter as shown in Figure 3-12. This will help to ensure they are connected to the correct terminals in the MP enclosure after the inverter is mounted. Refer to Table 3-3 for information on each
wire in the AC wiring kit and where they are used.
Info: Once the AC wires are connected inside the inverter, ensure the AC wiring access
plate is reattached before mounting the inv
e careful to note the height at which you want to locate the MP and inverter to ensure you can
B
access any controls and wiring terminals. Use Figure 3-5 or 3-6 to determine the mounting keyhole
loctions, or use the base of the MP enclosure as a template to mark the mounting screw locations.
After marking the mounting screw locations, secure the MP enclosure to an appropriate solid noncombustible* vertical surface using appropriate mounting hardware. The mounting keyhole slots
on the MP enclosure will accept up to a maximum 1/4” screw/bolt.
The MP enclosure must be mounted on a vertical surface (on a wall) in an upright position to
meet regulatory requirements and to ensure the DC breakers operate properly. The surface and
mounting hardware must be capable of supporting at least three times the combined weight
of all the components mounted (i.e., MP enclosure, inverter, and any other accessories). When
considering the strength of the support surface, remember each MP enclosure with inverter can
weigh up to 120 lbs. (54 kg). Once the MP enclosure is fi rmly secured, set the Magnum inverter
into the top of the MP enclosure and secure it to the mounting surface.
If mounting the MPDH-30D, ensure the two enclosures (AC and DC sides) are mechanically and
electrically connected by screwing them together as shown in Figure 3-16c.
WARNING: The MP
to prevent personal injury.
CAUTION: When a Magnum inverter is installed vertically, the inverter hood (Item 2,
ures 3-1 and 3-2) must be installed over the top of the inverter to prevent objects
Fig
falling into the inverter’s vent openings.
Info: Magnum has two mounting backplates that provide a suitable non-combustible
rface and the required support for mounting MP enclosures, MPX enclosures, and
su
Magnum inverters together. The BP-S is the single backplate, and the BP-D is the dual
backplate. Harware to mount the MP enclosure is provide with either backplate.
* The Magnum
reach a temperature up
(90°C) and is required to be
mounted on a non-combustible
surface. A non-combustible surface
is one made of material that will not
ignite, burn, support combustion,
or release fl ammable vapors when
subjected to fi re or heat as per
the ASTM E136 standard. For the
most part, these are materials that
are largely comprised of inorganic
materials such as stone, steel, iron,
brick, tile, concrete, slate, and glass.
Common building materials such as
gypsum board as well as any paint,
wall coverings, and certainly wood
will not pass.
inverter base can
enclosure is heavy. Use proper lifting techniques during installation
This section describes the requirements and recommendations for wiring to/from the MP enclosure.
Read all instructions before wiring the MP enclosure.
IMPORTANT: The installation of this MP enclosure/inverter system must meet all local
codes and standards and be performed by qualifi ed personnel such as licensed electricians
or Certifi ed Renewable Energy (RE) System installers.
The NEC (National Electric Code, ANSI/NFPA 70) for the United States and the CEC (Canadian
Electrical Code, CSA 22.1) for Canada provide the standards for safely wiring residential and
commercial installations. The NEC/CEC list the requirements for wire sizes, overcurrent protection,
and installation methods and requirements.
Be aware that the MP/inverter system involves power from multiple sources (inverter, generator,
utility, batteries, solar arrays, etc.) which make the wiring more hazardous and challenging.
WARNING: The AC neutral and DC negative are bonded to ground in this enclosure.
If the AC
must remove the DC and/or AC bonding inside this enclosure. Refer to Section 3.9 and
3.10 to remove the AC and/or DC ground bond connection.
WARNING: Ensure all sources of DC power (i.e., batteries, solar, wind, or hydro) and
AC power (utilit
fuses removed) before proceeding - to prevent accidental shock.
3.5.1 General Wiring Requirements
• The AC and DC wires into and out of the MP enclosure must be protected as required by code.
This can be done by using jacketed wires or by feeding the wires through conduit.
or DC circuits are already bonded to ground elsewhere in your system, you
y power or AC generator) are de-energized (i.e., breakers opened,
Info: If using a Magnum inverter, and the AC wires are individual conductors (i.e., not
cketed), the strain reliefs on the inverter can be replaced with 3/4” grommets.
ja
• Use proper clamps or other approved methods for securing the cable/conduit to the enclosure.
• The MP enclosure is specifi cally designed for both AC and DC wiring. However, where DC wiring
must cross AC or vice-versa, try to make the wires at the crossing point 90° to one another.
• Use only copper wires with a minimum rating of 150V, 75°C if only 120V AC power is being
used; or, with a minimum rating of 300V, 75°C if 120/240V AC power is being used.
• In a system where one conductor is grounded, the wire colors on the DC side and AC side
are the same. The insulation on all grounded conductors (DC negative/AC neutral) must be
white, gray, or any color except green if marked with white at each termination (marking only
allowed on 6 AWG or larger conductors). The equipment grounding conductors must be bare
(no insulation), or have green or green with yellow-striped insulation or identifi cation. The hotungrounded conductor (DC positive/AC hot) is usually red or black.
• Terminals containing more than one conductor must be listed for multiple conductors.
• The connectors or terminals used on fl exible, fi ne stranded conductors must be specifi cally
marked or labeled for use with fi ne-stranded conductors.
• The MP enclosure includes wires (along with communication cables) with insulation rated for
at least 300 volts, which allows 120/240V AC inverters to be installed. If installing a 120/240V
AC inverter, the installer must also provide wires (both power and communication) with the
insulation rated for at least 300 volts.
3.5.2 Disconnect Switch and Overcurrent Protection
For residential and commercial electrical systems, the NEC/CEC requires a disconnect switch and
vercurrent protection
o
MP enclosure provides both AC and DC circuit breakers that are used as the disconnect switch.
These circuit breakers can also be used as the overcurrent protection device when the ampacity
of the wire and its insulating material, voltage, and temperature rating are correctly sized to the
circuit breakers in your MP enclosure. Refer to the appropriate installation section (AC Wiring or
DC Wiring) to determine the minimum recommended wire size required.
for all ungrounded conductors on the AC side as well as the DC side. The
The MP/Inverter system is intended to be installed as part of a permanently grounded electrical
s
yst
Code (CEC) CSA 22.1 in Canada, as well as all state and local code requirements. Information
and diagrams on the AC and DC ground circuits between the inverter and the MP enclosure are
provided in the AC and DC wiring sections.
Information on grounding the entire MP/inverter system to earth ground is provided in Section
3-11 and the actual system ground wiring confi guration must be determined by the installer.
3.5.5 Torque Requirements
Follow the specifi c torque recommendations in the tables below to ensure your fasteners are tightened
suffi ciently. To ensure your connections are correct, you should use an accurate, quality torque wrench.
connecting any wires, determine all wire routes to and from the MP enclosure/inverter.
•
AC input wiring from the main AC panel or from a gener
•
AC input and output from the MP enclosure to the inverter
• DC wiring from the batteries to the MP enclosure
• DC wiring from the inverter to the MP enclosure
• AC output wiring from the MP enclosure to the AC sub-panel or to dedicated circuits
• Battery Temperature Sensor cable from the inverter to the batteries
• Remote control and stacking cables to the inverter through the MP enclosure
• Ground wiring to and from the MP enclosure
em per the National Electrical Code (NEC) ANSI/NFPA 70 in the United States, Canadian Electrical
ator to the MP enclosure
CAUTION: It
torque after 5 days, and every 6 months thereafter.
CAUTION: AC and
loose and result in a fi re hazard. On the other hand, over-tightening a bolt could cause
the fastener to be snapped off.
is highly recommended to go back over all fasteners/connections and re-
DC power/wire connections that are under-torqued could become
Table 3-1, Torque Values for Dual Hole Busbars
Torque values for the dual hole busbars (i.e., AC, DC, AC NEUTRAL and GROUND busbars) -
these busbars have different torque v
Wire Size
#14 to #10 AWG
#8 AWG
#6 AWG
#4 AWG
#3 to #1/0 AWG
10-32 (Small Set-Screw)5/16-24 (Large Set-Screw)
15 in. lbs. (1.7 N-m)35 in. lbs. (4.0 N-m)
20 in. lbs. (2.3 N-m)40 in. lbs. (4.5 N-m)
25 in. lbs. (2.8 N-m)45 in. lbs. (5.1 N-m)
Table 3-2, Torque Values for
3/8-16 Bolts
1
Not Applicable45 in. lbs. (5.1 N-m)
Not Applicable50 in. lbs. (5.6 N-m)
alues for the small and large set-screws.
Busbar Set-Screw Size Torque Values
Table 3-3, Torque Values for Terminal
Screws on AC Input Breakers
10 to 12 ft. lbs.
(13.6 to 16.3 N-m)
Note 1 - The 3/8-16 bolts are used on the DC Shunt Busbars and DC Disconnect Breakers.
This section provides information on the AC wiring inside the MP enclosure. It covers all AC wiring
to/from the inverter, from the incoming external AC source, and to the outgoing external AC
distribution panel (i.e., inverter sub-panel).
AC Wiring
3.6.1 AC Wiring Guidelines
CAUTION: Before
beginning of this manual and below to ensure a safe and long-lived system:
• Read all instructions and cautionary markings located at the beginning of this manual
and in the Pre-installation section before installing the inverter and batteries.
• AC wiring must be no less than #10 AWG (5.3 mm2) gauge copper wire and be
approved for residential wiring.
• DO NOT connect the Magnum inverter’s output to an AC power source. This could
cause severe damage to the inverter and is not covered under warranty.
WARNING: To
busbars in an AC load center (circuit breaker panel) having multi-wire branch circuits
connected. Every circuit connected to a 120V AC panel must have its own neutral;
otherwise, currents on shared neutrals will add rather than subtract, overloading the
neutral conductor.
installing
reduce the risk of fi re, do not connect a 120V AC only inverter to both
an
y AC wiring, review the safety information at the
3.6.2 AC Connections
To view the AC connection points inside the MP enclosure, review Figure 3-12 for MPSL-30D and
MPSH-30D models, Figure 3-13 for MPSL-60S models, or Figure 3-13 for MPDH-30D models.
3.6.2.1 AC Input/Output Connections
The MP enclosure provides busbars that allow the AC wiring (both inverter and external) to be
easily and permanently wired. Each busbar has dual set-screw compression terminals allowing #14
to #1/0 AWG wires using the larger set-screws and #14 to #6 AWG wires using the smaller setscrews. These busbars use slotted head set-screws and should be torqued according to Table 3-1.
The lower section of the MP enclosure provides the external AC input and output busbars. The
external AC input busbars are labeled AC HOT 1 IN, AC HOT 2 IN, AC NEUTRAL, and GROUND.
These busbars are used to wire a service/distribution panel (AC main panel) which allows the
incoming utility/AC generator input to be connected to the inverter’s input breakers. The external
AC output busbars are labeled AC HOT 1 OUT, AC HOT 2 OUT, AC NEUTRAL, and GROUND. These
busbars allow a dedicated inverter panel (AC sub-panel) to be wired between the inverter’s output
and the AC loads.
The upper section of the MP enclosure provides the inverter’s AC output busbars. The inverter
busbars are labeled INV HOT 1 OUT, INV HOT 2 OUT, AC NEUTRAL, and GROUND. These busbars
combine all the inverter outputs together when stacked for increased power capability.
Info: The busbars labeled AC NEUTRAL in the MP enclosure ARE connected together.
You do
using the Magnum MS-PAE Series inverter because the input and output neutrals are
connected together. However, using any other Magnum inverter, the input and output
neutrals are not connected, so you must connect to the inverter’s input and output
neutral terminals when wiring the neutral wires.
Info: The busbars labeled GROUND in the MP enclosure ARE connected together. You do
no
CAUTION: A neutral to ground connection is provided in the MP enclosure. If a neutral
to ground connection
the MP enclosure must be disconnected. See Section 3.9 for information to disconnect
this neutral to ground connection.
not need to provide both an inverter input and output neutral connection when
t need to provide both an inverter AC input and output ground connection.
is provided elsewhere in the AC system, the connection inside
Page 38
3.0 Installation
3.6.3 Inverter AC Wires and Overcurrent Protection
d
he inverter’s AC input and output wiring must be size
T
requirements to ensure the wires’ ability to safely handle the inverter’s maximum load current. AC
wiring is required to be protected from short circuits and overloads by an overcurrent protection
device, and have a means to disconnect the AC circuits.
The wires provided in the MP AC Wire Kit (as listed in Table 3-4 for your particular MP enclosure
model) are sized to handle the inverter’s maximum load current. The MP enclosure provides AC
circuit breakers for the inverter’s AC input. These breakers are branch circuit rated and can be
used as the overcurrent protection and the AC disconnect device as long as the wires in the MP
AC Wire Kit for you particular MP enclosure (or wires with at least the same rating) are used. If
you are using other wire/circuit breaker sizes, refer to the appropriate electrical codes for proper
sizing requirements.
When parallel stacking, a Magnum MS4024PAE or MS4448PAE inverter will be used. The full AC
continuous pass-thru capacity of these inverters is 30 amps for each AC leg (AC HOT 1 or AC HOT 2),
and requires a maximum 30 amp breaker on each AC input to protect the inverter’s internal passthru relay. This correlates with the MPSL-30D, MPSH-30D, or MPDH-30D models, which include a
double-pole 30 amp input inverter breaker and requires a minimum wire size of #10 AWG1 in conduit.
When series stacking, the Magnum MS4024 inverter will be used. The AC HOT 1 and AC HOT 2 in
this inverter may be combined to obtain a 60 amps pass-thru capability. When tying the AC HOT
1 and HOT 2 together for a 60 amp continuous pass-thru capability, the AC input to the inverter
requires a 60 amp breaker. This correlates with the MPSL-60S models, which include a single 60
amp breaker for each inverter and requires a minimum wire size of #6 AWG1 in conduit.
per the local electrical safety code
Info: Additional space is provided in the MP enclosure to allow an AC breaker to be
installed for
MPX Extension Kit along with the required hardware and wires for installation.
AC Wire
Reference
INV HOT 1
IN
INV HOT 2
IN
INV NEUTRAL
IN
INV AC
GROUND
INV HOT 1
OUT
INV HOT 2
OUT
INV NEUTRAL
OUT
each additional inverter installed. These breakers are included with the
Table 3-4, MP AC Wire Kits
Separate
Wires
into:
AC
INPUT
Side
(3 wire
bundle)
AC
OUTPUT
Side
(2-3 wire
bundle)
A80-MPAC-30D-SH
(for MPSL-30D,
MPSH-30D and
MPDH-30D/AC Side)
#10 AWG Black
2
(24")
#10 AWG Red
2
(24")
NA (MS-PAE neutrals
in common)
#10 AWG Green
(24")
#10 AWG Black
w/Stripe (24”)
2
#10 AWG Red
w/Stripe (24”)
2
#10 AWG White
(24”)
A80-MPAC-60S-SH
(for MPSL
-60S)
#6 AWG Black
2
(24")
NA (provided with
MPX wire kit)
#6 AWG White
(24")
#10 AWG Green
(24")
#6 AWG Black
w/Stripe (24”)
NA (provided with
MPX wire kit)
#6 AWG White
w/Stripe (24”)
A80-MPAC-30D-LG
(for MPDH-30D/DC
Side)
#10 AWG Black
(33")
#10 AWG Red
(33")
NA (MS-PAE neutrals
in common)
#10 AWG Green
(33")
#10 AWG Black
2
w/Stripe (33”)
#10 AWG Red
w/Stripe (33”)
#10 AWG White
(33”)
2
2
2
Note 1 - This wire must be copper with a minimum rating of 300V, 75°C at an ambient temperature of 30°C.
Note 2 of the inverter AC input breakers.
This wire is longer than required to allow at least 7” to be cut and used for connecting to the bottom
3.6.4 External AC Wires and Overcurrent Protection
The MP enclosure also provides a full system AC branchbypass switch. This AC breaker can be used as the overcurrent protection and disconnect for the
total current that the MP enclosure system provides to the inverter’s AC electrical sub-panel. This
is true as long as the wires routed from the MP enclosure to the inverter’s AC electrical sub-panel
are no smaller than those listed in Table 3-5 for your particular MP enclosure model. If you are
using other circuit breakers or wire sizes, refer to the appropriate electrical codes for proper sizing
requirements.
Table 3-5, Minimum AC Wire Size for AC Output Breaker
Note - The recommended minimum wire sizes listed above are based on using copper wire with a minimum
rating of 300V and at an ambient temperature of 30°C (86°F). If more than three cables are used together,
a cable fi ll factor de-rating may be needed. The insulation of the wire must be rated for the environmental
condition in which it will be used (i.e., for residential use, THHN is commonly used).
Note - Refer to Section 3.11 to asssit in determining the appropiate ground conductors for the AC system
based on the conductors used to/from the MP enclosure.
3.6.5
The following steps are basic guidelines for installing and connecting the AC wiring to and from the
inverter (refer
4.0 for the specifi c wiring diagrams for you particular MP enclosure.
Wiring External AC Source and AC Load Panel
. Route appropriate wires/cables from a dedicated breaker in the AC electrical main panel through
1
one of the MP enclosure’s knockouts to the AC input busbars (INPUT FROM GEN/GRID).
2. Route appropriate wires/cables (determined from Table 3-4) from the AC input busbars (OUTPUT
TO INVERTER LOADS) through another MP enclosure knockout to the AC electrical sub-panel.
AC Conductor Wiring
WARNING: To prevent electrical shock, make sure all AC power (inverter, generator,
or utility) is off before making any AC connections inside the MP enclosure.
AC Output Breaker
(part of Bypass
Assembly)
to Figures 3-17 thru 3-19 depending on your particular model). Also see Section
Conductor Temperature Rating
75°C (167°F)
WG (65 amps)#6 AWG (75 amps)
90°C (194°F)
CAUTION: When connecting external AC wires to the MP enclosure, the proper phasing
sequence (i.e.,
throughout the installation process. Refer to the system installation drawings in Section
4.0 showing the proper phasing convention. In the event the power conductors from
the external AC source (i.e., generator or grid) or the wiring into or out of the inverters
are not phased correctly, damage may occur.
Wiring Inverter AC Input/Output
1. Route the inverter’s AC input wires (previously connected in Section 3.3.3) to the top of the
inverter AC input breaker(s) inside the MP enclosure (INPUT TO INVERTER).
2. Route the inverter’s AC output wires (previously connected in Section 3.3.3) to the inverter
AC output busbars inside the MP enclosure (OUTPUT FROM INVERTER).
AC Wiring Inspection
After verifying all AC connections are correct, and all AC terminal screws are torqued correctly
(refer to Tables 3-1 to 3-3), replace the covers on the main electrical panel/sub-panel.
This section describes the DC wiring from inside the MP enclosure to the inverter, and from the
MP enclosure to the battery bank.
If installing optional DC breakers, see Section A6 in Appendix A.
Info:
3.7.1
• When the inverter is installed in a Photovoltaic System, the NEC requires that the DC circuit
conductors and overcurrent devices to the inverter be sized to carry not less than 125% of
the inverter’s maximum current rating.
• The DC positive and negative cables from the battery bank should be tied together with wire
ties or electrical tape approximately every six inches. This helps improve the surge capability
and reduces the effects of inductance, which improves the inverter waveform and reduces the
wear of the inverter’s fi lter capacitors.
• Crimped and sealed copper compression lugs with a 3/8” hole should be used to connect the
battery cables to the DC Disconnect Breaker and the DC Shunt busbar inside the MP enclosure.
• The battery bank voltage MUST match the DC voltage required by the inverter (i.e., 24-volt
battery bank for a 24-volt inverter), or the inverter may be damaged.
• The DC cables must be of a type listed for use in conduit (i.e., THHN, RHW or THW).
• To ensure the maximum performance from the inverter, all connections from the battery
bank to the inverter through the MP enclosure should be minimized, the exception is the DC
circuit breaker in the positive line and the DC shunt in the negative line. Any other additional
connection will contribute to additional voltage drops and may loosen during use.
• All wiring to the inverter and battery terminals should be checked periodically (once a month)
for proper tightness. Refer to the torque requirements in Tables 3-1 to 3-3.
• After making the battery connections and ensuring they are properly tightened, cover the
outside of the connection
jelly/anti-corrosion grease between the terminal and the battery cable.
• Ensure the color code for the DC cables/wires are correct: RED for positive (+); WHITE for
negative (-); and GREEN, GREEN with YELLOW stripe, or bare for DC equipment grounds.
DC Wiring Guidelines
WARNING:
inside the MP enclosure may be energized - DO NOT TOUCH. Disconnect all power
sources before removing the cover.
WARNING:Even
signifi cant hazards are present because of the high current available, particularly if the
battery system has a short circuit.
CAUTION: Before wiring the
of this manual and the following information to ensure a safe and long-lived system.
CAUTION: If you are using fi ne-stranded DC cables, the crimp or compression lug
used must be
Failure to use the proper terminal may cause the connection to heat-up, and it may
eventually fail or become a fi re hazard.
CAUTION: DO NOT connect the battery cables to the inverter until all wiring is
complete, and the correct DC voltage and polarity ha
During
normal
though the DC voltage/battery bank is considered “low voltage”,
specifi cally marked or labeled for use with fi ne-stranded conductors.
with petroleum jelly or an antioxidant grease/spray. Do not put
operation the terminals, busbars, and electrical components
DC cables, review the safety information at the beginning
3.7.2 Inverter DC Overcurrent Protection and DC Disconnect
a battery-based inverter system, the NEC/CEC assumes that each ungrounded conductor is
In
connected
and could potentially damage that conductor under fault conditions. Because of this, the NEC/
CEC requires that all ungrounded conductors in the inverter’s DC system be protected by an
overcurrent device, this can be either a circuit breaker or fuse. These breakers or fuses are not
intended to protect equipment from damage, but protect the conductor/wire from overheating
which may potentiality cause a fi re. This means the overcurrent device is required to open before
the conductor reaches its maximum current carrying capability, thereby preventing a fi re.
The NEC also requires the inverter system to have a DC disconnect switch to allow service providers
to isolate the inverter from the battery. The disconnect must be either a DC rated circuit breaker
or switch.
The MP enclosure is provided with a 250 amp UL listed, high interruption capacity, magnetichydraulic, DC rated circuit breaker. These breakers are designed to interrupt the tremendous
amount of current a battery can deliver when short-circuited. They are also specifi cally designed
to have a long enough time delay to prevent the breaker from tripping, as the inverter requires
high current levels when powering heavy loads.
If the battery cables to the inverter are no longer than fi ve feet and the wire size is a minimum
#4/0 AWG1 , the circuit breakers in the MP enclosure can provide the inverter system with both
the DC overcurrent protection device and a safety disconnect switch.
If your battery to inverter cable length is greater than fi ve feet, the DC wire size will need to be
increased. Longer distances cause an increase in resistance, which affects the performance of the
inverter.
If your battery to inverter cable size is smaller than the recommended minimum DC wire size (#4/0
AWG1), you must install a fuse/circuit breaker close to the battery bank that is compatible with this
smaller cable to protect against a potential fi re.
to
some
source
that supplies currents in excess of the ampacity rating of the conductor
CAUTION: In a
DC wire to achieve maximum effi ciency and to reduce fi re hazards associated with
overheating. Always keep your wire runs as short as practical to help prevent low
voltage shutdowns.
Info: Circuit breakers or fuses that are used on the DC side must be UL listed and DC
rated for the application.
3.8.2.1
When installing multiple inverters, the MP enclosure provides the space to add a 250 amp breaker,
for each additional inverter. These breakers — along with all the wires and hardware — are provided
with the MPX Series Extension Kit.
All MP enclosures (except for the MPSH-30D) provide space to fi eld install additional DC breakers
for use as DC input/output breakers for PV, charge controllers, or DC loads. See Section A6 for
more information.
1
Note 1 - Wire must be copper with a minimum rating of 300V, 75°C at an ambient temperature of 30°C.
Optional DC Breakers/Disconnects
low voltage/high amperage system, it is important to use the correct
Do not put anything between the DC cable lug and the DC terminals (i.e., on the Inverter DC
Disconnect, DC shunt busbars,
these connections is stacked correctly. Incorrectly installed hardware causes a high resistance
connection which could lead to poor inverter performance, and may melt the cable and terminal
connections. Follow Figure 3-20 to connect the DC cables and stack the hardware correctly.
batteries, or inverter terminals). Ensure the hardware used to hold
Info:A
fter making the battery connections a
n
d ensuring they are properly torqued,
cover the outside of the connection with petroleum jelly or an antioxidant grease/spray.
Do not put jelly/anti-corrosion grease between the terminal and the battery cable.
Inverter Hardware Stack-up:
Inverter DC Terminals
INVERTER DC NEGA
POSITIVE CONNECTIONS
MAGNUM INVERTER
TIVE
AND
BATTERY POSITIVE CONNECTIONTO
1
Inverter Cable Lugs
[(-) to Shunt Busbar,
2
(+) to Inverter DC Breaker]
5/16-18 Nut (Flange or Kep)
3
DO NOT Place anything between
the inverter DC terminals and the
Depending
batteries
interconnecting DC cables should be the same size and rating as those used between the battery
bank and the inverter.
Place the batteries as close as practical to the MP enclosure/inverter system, preferably in an
insulated and ventilated enclosure. Allow adequate space above the batteries to access the terminals
and vent caps (as applicable). Also allow at least 1” of space between the batteries to provide good
air fl ow. DO NOT mount the batteries directly under the MP enclosure/inverter system.
upon the voltage of the batteries used in the installation (2V, 6V, or 12V DC), the
must
be
wired
in series, parallel, or series-parallel to provide the correct voltage. The
Info: To ensure the best performance from the MP enclosure/inverter system, batteries
should
3.7.4.1 Wiring the MP enclosure to the Battery Bank/Inverter
WARNING: Ensure that
or disconnecting the battery cables, and that all sources of power (both AC and DC)
are disconnected from the inverter.
WARNING: Lethal currents
to the battery bank touch each other. During the installation and wiring process, ensure
the cable ends are insulated or covered to prevent touching/shorting the cables.
CAUTION: DO NO
accessory wiring are completed, 2) the correct DC and AC overcurrent protection have
been installed and, 3) the correct DC voltage and polarity have been verifi ed.
CAUTION: The Magnum inverter is NOT reverse polarity protected. Before making
the fi
the correct battery voltage and polarity. If the positive (+) terminal of the battery is
mistakenly connected to the negative (–) terminal of the inverter and vice versa, the
inverter will be damaged and will not be covered under warranty. Color code the cables
to avoid polarity confusion.
The following steps are basic guidelines for installing and connecting the DC wiring into and out of
the MP enclosure (refer to Figures 3-21 thru 3-23 depending on your particular model). Also see
Section 4.0 for the specifi c wiring diagrams for your particular MP enclosure.
1. Route the DC cables from inside the MP enclosure and connect them to the inverter’s DC
terminals; the negative cable (-) from the top side of the DC shunt busbar to the inverter’s DC
negative terminal, and
DC positive terminal. Be careful to observe proper polarity.
2. Route the DC cables from the battery bank — with the cables not connected to the battery —
and connect them to the MP enclosure; negative (-) to the bottom side of the DC shunt busbar,
positive (+) to the bottom side of the DC breaker. Be careful to observe proper polarity.
3. Ensure the DC wire connections (on the batteries, inverter, DC circuit breaker, and DC shunt
busbars) are fl ush on the surface of the DC terminals and the hardware used to hold these
connections are stacked correctly (see Figure 3-20); and then securely tighten these DC connections
(refer to the torque requirements in Table 3-2).
be
the same size, type, rating, and age. Do not use old or untested batteries.
of
all AC and DC breakers are switched OFF before connecting
will be present if the positive and negative cables attached
T connect the DC wires to the battery bank until: 1) all DC, AC, and
nal DC connection from the batteries to the inverter, use a voltmeter to verify
the positive cable (+) from the top side of the DC breaker to the inverter’s
CAUTION: Only after
should the DC circuit breaker be closed to provide power to the inverter.
4. Route an appropriately sized DC grounding wire (green or bare wire) from the inverter’s DC
equipment ground terminal and from the battery bank enclosure to the DC GROUND busbar in the
MP enclosure. Refer to Section 3.11 for grounding information and sizing the DC ground wires.
the entire installation is complete and all connections are verifi ed
Figures 3-21 thru 3-23 show the connection points for the DC wiring inside the MP enclosures.
DC NEGA
ONNECTION
C
ADDITIONAL INVERTER
DC NEGA
NEGATIVE
ADDITIONAL BATTERY BANK
NEGATIVE
DC EQUIPMENT
GROUNDING
CONNECTION
TIVE CABLE
TO INVERTER
TIVE
ABLE CONNECTION
C
BATTERY BANK
CABLE CONNECTION
CABLE CONNECTION
DC POSITIVE
ONNECTIONTO INVERTER
C
C
ABLE
BATTERY BANK
POSITIVE C
DC GROUNDING
ELECTRODE
CONNECTIONS
DC CONNECTIONS
UNDER
(
DISCONNECT)
ABLE CONNECTION
THE
DC
DC1
DC2
DC3
DC4
DC5
DC6
DC7
DC8
Figure 3-21, DC Wiring Connection Points for MPSL Models
Inverter’s DC Negative Cable Connection - Cable connection to Magnum inverter’s
DC negative terminal. Electrically connected to the top of the DC shunt.
Inverter’s DC Positive Cable Connection - Cable connection to Magnum inverter’s
DC positive terminal. Electrically connected to the top of the inverter’s DC disconnect.
Additional Inverter DC Negative Cable Connection - Provided so that as more inverter’s
are added, cables can be added and connected to the inverter’s DC negative terminals.
Battery Bank Negative Cable Connection - DC Negative Busbar connection (bottom
connection of DC shunt); connects cables to the battery bank’s negative terminal.
Additional Battery Bank Negative Cable Connection - Provided to connect
additional cables to the battery bank’s negative terminal when additional Magnum
inverters are installed.
Battery Bank Positive Cable Connection - Bottom of the inverter’s DC disconnect
breaker; connects the battery cable to the battery bank’s positive terminal.
DC Equipment Grounding Connection - This busbar is used as the common DC
equipment ground point for all DC equipment connected in the MP/inverter system.
DC Grounding Electrode Connections - These are the connection points for the MP/
inverter system to the DC grounding electrode. Use DC8A for #6 to #1/0 AWG wires,
and DC8B for greater than #1/0 AWG wires.
Figure 3-22, DC Wiring Connection Points for MPSH-30D
Inverter’s DC Negative Cable Connection - Cable connection to Magnum inverter’s
DC negative terminal. Electrically connected to the top of the DC shunt.
Inverter’s DC Positive Cable Connection - Cable connection to Magnum inverter’s
DC positive terminal. Electrically connected to the top of the inverter’s DC disconnect.
Additional Inverter DC Negative Cable Connections - Provided so that as more inverter’s are added, cables can be added and connected to the inverter’s DC negative terminals.
Battery Bank Negative Cable Connection - DC Negative Busbar connection (bottom
connection of DC shunt); connects cables to the battery bank’s negative terminal.
Additional Battery Bank Negative Cable Connections - Provided to connect
additional cables to the battery bank’s negative terminal when additional Magnum
inverters are installed.
Battery Bank Positive Cable Connection - Bottom of the inverter’s DC disconnect
breaker; connects the battery cable to the battery bank’s positive terminal.
DC Equipment Grounding Connection - This busbar is used as the common DC
equipment ground point for all DC equipment connected in the MP/inverter system.
DC Grounding Electrode Connections - These are the connection points for the MP/
inverter system to the DC grounding electrode. Use DC8A for #6 to #1/0 AWG wires,
and DC8B for greater than #1/0 AWG wires.
Figure 3-23, DC Wiring Connection Points for MPDH-30D (DC Side)
DC1
DC2
DC3
DC4
DC5
DC6
DC7
DC8
Inverter’s DC Negative Cable Connections - Cable connections to Magnum inverter’s
DC negative terminal. Electrically connected to the top of the DC shunt.
Inverter’s DC Positive Cable Connections - Cable connections to Magnum inverter’s
DC positive terminal. Electrically connected to the top of the inverter’s DC disconnect.
Additional Inverter DC Negative Cable Connections - Provided so that as more inverter’s are added, cables can be added and connected to the inverter’s DC negative terminals.
Battery Bank Negative Cable Connections - DC negative busbar connections (bottom
connection of DC shunt); connect cables to the battery bank’s negative terminal.
Additional Battery Bank Negative Cable Connections - Provided to connect
additional cables to the battery bank’s negative terminal when additional Magnum
inverters are installed.
Battery Bank Positive Cable Connections - Bottom of the inverter’s DC disconnect
breaker; connect battery cables to the battery bank’s positive terminal.
DC Equipment Grounding Connections - These busbars are used as the common
DC equipment ground point for all DC equipment connected in the MP/inverter system.
DC Grounding Electrode Connections - These are the connection points for the MP/
inverter system to the DC grounding electrode. Use DC8A for #6 to #1/0 AWG wires,
and DC8B for greater than #1/0 AWG wires.
NEC/CEC requires the insulation of all conductors inside the MP enclosure to be rated for the
The
highest voltage present. The MP enclosure is designed to work with inverters that provide 120/240V
AC (i.e., MS-PAE Series), therefore, the voltage rating of the communications cables inside the MP
enclosure must be rated for 300 volts or higher to be code compliant.
With the purchase of the MP enclosure, Magnum has included three six-foot, yellow communication
cables with 300-volt rated insulation. These communications cables — shown below — are provided
to make the connections between Magnum inverters and any accessories easier and code compliant.
Figure 3-27 shows a basic drawing for connecting accessories into and out of the MP enclosure.
Refer to Section 4.0 for specifi c communications wiring diagrams for your particular MP enclosure.
Info: These cables carry less than 30 volts and are thus considered a “limited energy
circuit”, which is normally not required to be installed in conduit.
F
igure 3-24 shows the ‘REMOTE’ cable. It allows
a remote control — such as the ME-RC (Remote
Control), ME-ARC (Advance Remote Control), or
ME-RTR (Router) — to be connected to the inverter
through the MP enclosure. This cable is a 6’ (1.83 m),
4-conductor, telephone-type cable with a RJ14 (m)
connector and a blue REMOTE label on each end. One
end of this cable is connected to the remote, and the
other end is routed inside the MP enclosure and then
connected to the inverter’s REMOTE port.
Figure 3-24, REMOTE Communication Cable (300V Rated)
Figure 3-25 shows
Magnum accessories — like the ME-AGS-N (Auto
Generator Start - Network) or ME-BMK-NS (Battery
Monitor - No Shunt) — to be connected to the inverter
through the MP enclosure. This cable is a 6’ (1.83
m), 4-conductor, telephone-type with a RJ14 (m)
connector and a green NETWORK label on each end.
One end of this cable is connected to the accessory,
and the other end is routed inside the MP enclosure
and then connected to the inverter’s NETWORK port.
the ‘NETWORK’ cable. It allows
Figure 3-25, NETWORK Communication Cable (300V Rated)
Figure 3-26 shows
the Magnum Battery Temperature Sensor (BTS) to be
connected to the inverter through the MP enclosure.
This is a 6’ (1.83 m), 4-conductor, telephone-type
cable with a RJ14 (m) connector on one end and
a RJ14 (f) plug on the opposite end. The female
plug connects to the ME-BTS (Battery Temperature
Sensor). After connecting to the ME-BTS, this
extension cable is routed inside the MP enclosure and
connects to the inverter’s BTS port.
The MP enclosure
of ground for the AC system. The neutral to ground connection is done by connecting a green wire
(Item 19, in Figures 2-7 and 2-8, Item 23 in Figure 2-9, or Item 13 in Figure 2-10a, depending on
your MP model) between the AC NEUTRAL busbar and the GROUND busbar inside the MP enclosure.
In installations where the MP enclosure is powered from utility power or large permanently installed
generator systems, the AC neutral to ground connection is normally provided inside the main AC
electrical distribution panel. In these installations, the factory-installed NEUTRAL-GROUND wire in
the MP enclosure must be removed to prevent multiple neutral to ground connections.
To remove the NEUTRAL-GROUND wire:
1. See Figure 3-28 below to help you locate the green wire with the NEUTRAL-GROUND CONNECTION label inside your MP enclosure.
2. Remove this green wire by loosening the screws on the AC NEUTRAL busbar and the GROUND
busbar.
3. After this wire is removed, tighten the loose screws back into the busbars to prevent them
from being lost.
is shipped with the AC neutral connected to ground to provide the single point
The MP enclosure
of ground for the DC system. This negative to ground connection is done by connecting the DC
Shunt (battery negative connection point) to the DC Ground Stud using the NEGATIVE-GROUND
busbar. If a negative to ground connection is made elsewhere in the DC system — either at the
battery terminal, inside a charge controller, or if you are installing a PV-Ground Fault Protection (PVGFP) device — this busbar must be removed to prevent multiple negative to ground connections.
Step 1, Remove Plate and Locate NEG-GND Busbar
is shipped with the DC Negative connected to Ground to provide the single point
Follow the steps below to remove the
NEG
ATIVE-GROUND busbar (refer to
NEGATIVE-
GROUND
busbar
the diagram to the left to help locate the
components discussed):
1. Remove the Shunt Access Plate on
the right side of the MP enclosure.
DC
Ground
Stud
Locate the NEGATIVE-GROUND busbar (Item 27, in Figure 2-9; or Item
29, in Figures 2-7, 2-8 or 2-10b - depending on your MP model) attached
to the DC Shunt.
DC
Shunt
2. Remove the 5/16” fl ange nut (1/2”
wrench) holding the busbar to the
DC Ground Stud and then remove
the 3/8” brass bolt and washer (9/16”
wrench) from the top terminal of the
DC Shunt.
3. Remove the NEGATIVE-GROUND
busbar.
4. Reattach the fl ange nut on the DC
Shunt
Access Plate
Ground Stud and the brass bolt/
washer back onto the DC Shunt.
Ensure the hardware on the top ter-
MP Enclosure
minal of the DC Shunt is stacked/
reattached and torqued correctly.
Note: The DC Shunt hardware is
shown correctly stacked in the Step
4 diagram below.
MP/inverter system uses both AC and DC electrical systems, therefore each electrical system
The
is required to be properly connected to a permanent, common “ground” or “earth” reference. A
MP/inverter system that is properly grounded limits the risk of electrical shock, reduces radio
frequency noise, and minimizes excessive surge voltages induced by lightning. To understand
how the conductors in the electrical circuit will be connected to the system ground, the following
terms should be understood (also refer to Figure 3-30):
• Grounded Conductor (GC): The wire/cable in the electrical system that normally carries current
(usually the AC neutral and/or the DC negative), and is intentionally connected or “bonded” to
the ground system. This wire, or the ends of this wire, must be colored white or gray.
• Equipment Grounding Conductor (EGC): A wire/cable that does not normally carry current
and is used to connect the exposed metal parts of equipment — that might be accidentally
energized — to the grounding electrode system or to the grounded conductor. This wire, or the
ends of this wire, must be green or green with a yellow stripe; or, this wire can be bare copper.
• Grounding Electrode Conductor (GEC): The wire/cable that does not normally carry current,
and connects the grounded conductor and/or the equipment grounding conductor at the service
equipment (i.e., equipment delivering the electrical energy) to the grounding electrode.
• Grounding Electrode (GE): A ground rod or conducting element that establishes an electrical
connection to the earth or common ground reference.
• System Bonding Jumper (SBJ): The connection between the grounded circuit conductor in
the electrical system and the equipment grounding conductor at a separately derived system.
There are two types of grounding — equipment grounding and system grounding.
The exposed metal parts of the equipment in the system usually don’t carry electricity. However, if
the exposed metal becomes electrifi ed by a live wire, a person touching this live part could complete
the electrical circuit and receive a shock. Equipment grounding prevents shock by connecting all
the exposed metal parts of equipment (via Equipment Grounding Conductors - EGC) together
at a common ground point (Ground BusBar - GBB). This common ground point — installed in
the service disconnect panel for each electrical system (AC and DC) — is then connected (via
Grounding Electrode Conductor - GEC) to the common ground reference, such as a ground rod
(Grounding Electrode - GE). This connection to earth is made at only one point in each electrical
system; otherwise, parallel paths will exist for the currents to fl ow. These parallel current paths
would represent a safety hazard and are not allowed in installations wired per the NEC/CEC.
System grounding takes one of the current-carrying conductors (Grounded Conductor - GC) and
attaches it to the common ground point (Ground BusBar - GBB), usually by a System Bonding
Jumper (SBJ) in each electrical service disconnect panel. On the AC side, that is the neutral
conductor (GC-AC); on the DC side, it’s the negative conductor (GC-DC). The closer the grounding
connection is to the source, the better the protection from high voltage surges due to lightning.
Figure 3-30, Grounding System for Inverter with MP Enclosure
the largest ungrounded conductor feeding the AC load center. One #8 AWG (8.4 mm2) copper
conductor will serve as an AC grounding electrode conductor for AC power conductors smaller than
and including #2 AWG (33.6 mm2) copper. SeeTable 3-6 for additional values.
- The size of the AC Grounding Electrode Conductor (GEC–AC) depends on the size of
Table 3-6, AC Grounding Electrode Conductor Sizing
Size of Largest Ungrounded
Conductor
#2 A
WG or smaller
#1 to #1/0 A
#2/0 or #3/0 AWG
Over #3/0 AWG
through 350 kcmil
WG
Minimum Size of Grounding
Electrode Conductor
WG (8.4 mm
#8 A
#6 AWG (13.3 mm
#4 AWG (21.1 mm
#2 AWG (33.6 mm
2
)
2
)
2
)
2
)
DC Side - To size the DC grounding electrode conductor, fi rst determine which one of the following
three methods will be used to connect the DC and AC grounding points in the inverter’s two
electrical systems (AC and DC) to the common “earth” ground.
Info: There are many variables to consider when choosing the size of the DC grounding
electrode conductor
. The MP enclosure provides the means to ground both the AC and
DC to a single ground, and when feasible, the Single Connection to Ground (Method 1)
is recommended. With this method the NEC allows a #6 AWG wire, which makes the
overall installation simpler and less costly.
1. Single Connection to Ground (Method 1): The AC Grounding Electrode Conductor
(GEC–AC) is bonded to the DC ground point and the DC Grounding Electrode Conductor (GEC–DC)
is the only connection to the grounding electrode, which must be a rod, pipe, or plate electrode
(see Figure 3-31).
Normally the size of the DC grounding electrode conductor must be no less than the size of the
battery bank’s negative cable. However, in this method, since there is only one connection to the
ground rod the NEC allows an exception. The DC grounding electrode conductor is not required
to be larger than #6 AWG (13 mm2) copper. The reasoning for allowing this smaller grounding
electrode conductor is that it is only required to stabilize the system voltage with respect to earth,
and the other properly-sized conductors in each electrical system will safely carry any fault currents
if they occur.
Figure 3-31, Single Connection to DC Ground Rod (Method 1)
Page 56
3.0 Installation
DC
SOURCE
MAIN AC PANEL
.HOT 1
.NEUT
.GND
.HOT 2
.DC SIDE
.AC SIDE
MP ENCLOSURE
AC
SOURCE
AC and DC sides shared
DC Electrical
System
AC Electrical
System
Grounding System
.GND
.POS
.NEG
GBB
GE
GEC-AC
GBB
MAGNUM
I
NVERTER
GEC-DC
SBJ
SBJ
GC-DC
GC-AC
HOT 1
HOT 2
NEUT
BAT
BAT
EGC
EGC
DC
SOURCE
MAIN AC PANEL
.HOT 1
.NEUT
.GND
.HOT 2
.DC SIDE
.AC SIDE
MP ENCLOSURE
AC
SOURCE
DC side dedicated
AC side dedicated
DC Electrical
System
AC Electrical
System
Grounding System
.GND
.POS
.NEG
GBB
GE
GEC-AC
GE
GBB
MAGNUM
I
NVERTER
GEC-DC
BC
SBJ
SBJ
GC-DC
GC-AC
BAT
BAT
HOT 1
HOT 2
NEUT
EGC
EGC
2. Multiple Connections to Ground - Single Electrode (Method 2): When the
AC and
DC service panels are near each other, then the AC Grounding Electrode Conductor (GEC–AC) and
DC Grounding Electrode Conductor (GEC–DC) can be connected to a single grounding electrode
(see Figure 3-32). In this method — since there are multiple connections to the DC grounding
electrode — the size of the DC grounding electrode conductor cannot be smaller than the largest
conductor in the DC system (usually the battery-to-inverter cable).
Figure 3-32, Multiple Connections to DC Ground Rod (Method 2)
3. Multiple Connections to Ground - Multiple Electrodes (Method 3): This method
a separate grounding electrode for the DC system and the AC system (see Figure 3-33). In this
method — since there are multiple connections to the DC Grounding Electrode (GEC–DC) — the
size of the DC grounding electrode conductor cannot be smaller than the largest conductor in the
DC system (usually the battery-to-inverter cable).
The DC Grounding Electrode (GE–DC) must be bonded to the AC Grounding Electrode (GE–AC)
to make a grounding electrode system; this Bonding Conductor (BC) cannot be smaller than the
largest grounding electrode conductor, either AC or DC.
Figure3-33, Multiple Connections to DC Ground Rod (Method 3)
The MP enclosure and all other non-current carrying exposed metal surfaces in the entire electrical
yst
em that may be accidentally energized must be grounded. The equipment-grounding conductor
s
must be sized to safely carry the maximum ground-fault current likely to be imposed on it from
where a ground-fault may occur.
AC Side - When the inverter’s AC input circuit breaker provided in the MP enclosure is being
used as the inverter’s AC overcurrent protection device, the AC Equipment Grounding Conductor
(EGC–AC) for the inverter is based on the AC breaker size provided (#10 AWG for all MP models).
Connect the AC equipment-grounding conductor from the inverter’s AC ground connection to the
AC Ground Busbar (GBB) in the MP enclosure (Item 25 in Figure 2-7 or 2-8, Item 22 in Figure
2-9, or Item 16 in Figure 2-10a - depending on your MP model).
DC Side - When the DC circuit breaker provided in the MP enclosure is being used as the inverter’s
DC overcurrent protection device, the DC Equipment Grounding Conductor (EGC–DC) for the
inverter should be #4 AWG, which is based on the 250 amp DC breaker size provided. Connect the
DC equipment-grounding conductor from the inverter’s DC ground connection to the DC Ground
Busbar (GBB) in the MP enclosure (Item 27 in Figures 2-7 or 2-8, Item 25 in Figure 2-9, or Item
26 in Figure 2-10b - depending on your MP model).
If you are using AC or DC overcurrent protection that is different than that provided in the MP
enclosure or installing optional DC breakers inside the MP enclosure, in accordance with the NEC/
CEC you must determine your equipment-grounding conductors based on the ampere rating of
the overcurrent device protecting the circuit conductors. Use Table 3-7 to help determine the
equipment-grounding conductor. If the circuit conductors are oversized to compensate for voltage
drop, the equipment-grounding conductor must also be oversized proportionally.
Table 3-7, Equipment Grounding Conductor Sizing
Rating of Overcurrent DeviceMinimum Size of Copper Ground Wire
15 amp#14 AWG
20 amp#12 AWG
30 - 60 amp#10 A
100 amp#8 AWG
200 amp#6 AWG
300 amp#4 AWG
400 amp#3 AWG
WG
3.11.3 System Bonding Jumper
The MP enclosure provides the single point of ground [System Bonding Jumper (SBJ)] for the AC
DC system. If
and
in an off-grid system) and there is no other connection to ground from neutral (in the AC system)
or negative (in the DC system), then leave the ground bond connections in place. Remove any
other neutral to ground connection in the AC system, such as in other electrical sub-panels; or,
any negative to ground connection in the DC system.
For utility connected systems where the neutral and ground are already bonded in the main utility
circuit breaker box (AC distribution panel), the NEUTRAL-GROUND wire MUST BE REMOVED from
the MP enclosure. See Section 3.9 to remove this neutral to ground connection.
Info: Inverters and portable generators that have electrical outlets usually have the
neutral
to be connected to the MP/inverter system as they would fi rst need to be modifi ed to
separate the neutral and ground bonding internally.
For systems or devices that connect the DC negative to ground independently (i.e., separate DC
main electrical distribution panel or PV-GFP device), the NEGATIVE-GROUND busbar (Item 27 in
Figure 2-9, or Item 29 in Figures 2-7, 2-8 and 2-10b - depending on your MP model) MUST BE
REMOVED inside the MP enclosure. See Section 3.10 to remove this negative to ground connection.
the MP enclosure is the central connection point for all ground wiring (usually
and ground bonded internally. These types of devices are not recommended
Use this checklist
have been completed before proceeding with the functional test.
Mounting
❐ The MP enclosure/inverter system is securely mounted in a clean, dry, and ventilated area.
❐ The MP enclosure/inverter system is not mounted in the same enclosure as maintenance-free
or vented type batteries.
❐ The MP enclosure is mounted in a ‘vertical only’ position.
❐ There is adequate clearance to access the front and to view/adjust the remote (if installed).
DC Wiring
Inverter Side:
❐ The inverter is correctly placed on the MP enclosure with the inverter’s DC terminals attached
to the inverter DC negative and positiv
Battery Bank Side:
❐ An appropriately sized DC cable is routed from the positive (+) battery terminal and attached
to the bottom terminal of the inverter DC disconnect breaker inside the MP enclosure.
❐ An appropriately sized DC cable is routed from the negative (-) battery terminal and attached
to the busbar which is connected to the bottom terminal of the DC shunt inside the MP enclosure.
❐ The DC hardware is stacked correctly (refer to Figure 3-20).
❐ The DC cable connections are torqued correctly (refer to Tables 3-1 to 3-3).
AC Wiring
❐ To Inverter: The AC wires are appropriately sized and routed from the inverter AC Input breaker(s)
inside MP enclosure to the inverter’s AC input terminals.
❐ From Inverter: The AC wires are appropriately sized and routed from the inverter’s AC output
terminals to the AC output busbars (INV HOT 1 OUT, INV HOT 2 OUT, AC NEUTRAL and GROUND)
inside MP enclosure.
❐ To Main AC Electrical Panel: The AC wires are appropriately sized and are routed from the AC
input busbars (AC LEG 1 IN, AC LEG 2 IN, AC NEUTRAL and GROUND) inside MP enclosure to the
circuit breaker in the main AC electrical panel (i.e., main panel) powered by the generator or grid.
Use Table 3-4 to determine the AC wire size to/from the MP enclosure.
❐ To Inverter AC Load Panel: The AC wires are appropriately sized and routed from the AC output
busbars (AC LEG 1 OUT, AC LEG 2 OUT, AC NEUTRAL and GROUND) inside MP enclosure to the
main circuit breaker in the electrical panel powered by the inverter (i.e., sub-panel). Use Table
3-4 to determine the AC wire size to/from the MP enclosure.
❐ AC wires connected to the busbars/circuit breakers are torqued correctly (see Tables 3-1 to 3-3).
Grounding
❐ There is only one bonding connection to ground for the DC electrical system (negative to ground)
and one bonding connection to ground for the AC electrical system (neutral to ground). These
bonding connections may be connected to the same grounding electrode system (ground rod). If
separate electrodes are used, they must be bonded together.
❐ The exposed metal parts of equipment are properly grounded.
❐ Equipment grounding conductors are properly sized.
Electrical Connections
❐ Connectors are listed for the intended use and environment (inside, outside, wet, etc.).
❐ Pressure/screw terminals tightened to the recommended torque specifi cation.
❐ Terminals containing more than one conductor are listed for multiple conductors.
❐ Connectors using fl exible, fi ne-stranded conductors are listed for use with such conductors.
❐ All electrical terminal connections in the inverter are re-torqued to tighten any connections that
may have loosened since the initial installation.
as a fi nal review to ensure all essential steps of the MP enclosures installation
❐ Conductors are rated for the application and the environment.
❐ Standard building-
Note: Welding, marine, locomotive (DLO), and auto battery cables don’t meet NEC/CEC
requirements. Flexible RHW or THW cables are available, but these cables require very limited,
specially listed terminals. When the battery conductors leave the battery enclosure, the conductors
must be of a type listed for use in conduit (RHW or THW).
❐ The DC and AC color codes for the ground conductors are the same – grounded conductors are
white and equipment-grounding conductors are green, green/yellow, or bare (no insulation).
❐ All wiring insulation have a minimum rating of 150V, 75°C when using only 120V AC power/
inverter; or, with a minimum rating of 300V, 75°C when using 120/240V AC power/inverter.
❐ Strain reliefs/cable clamps or conduit are used on all cables and cords.
❐ Conductors between the inverter and battery bank are installed in conduit.
❐ No multi-wire branch circuits when single, 120V AC inverters are connected to 120/240V AC
load centers.
Note: A multi-wire branch circuit is a three-wire circuit with a shared neutral for two, 120V AC
branch circuits.
Overcurrent Protection
❐ Properly sized and rated disconnects and overcurrent devices are used in the ungrounded
conductors in each circuit (AC and DC).
❐ Overcurrent devices in the DC circuits are listed for DC operation.
❐ DC overcurrent protection is provided at the batteries when they are located in a separate room,
or more than fi ve feet away from the MP enclosure.
❐ The DC overcurrent protection device and battery cables to the inverter are sized for the inverter’s
DC input current.
Note: Inverter’s DC input current is calculated using rated AC output in watts, divided by lowest
battery voltage, divided by inverter effi ciency at that power level.
❐ When the inverter DC disconnect breaker inside the MP enclosure is not used as the DC overcurrent
device, high interrupt, listed, DC-rated fuses or circuit breakers must be used in the battery cable
circuits.
wire conductors and appropriate wiring methods are used.
Batteries
❐ Battery terminals and other live parts are guarded, and adequate working space around the
battery bank is provided.
❐ Batteries are installed in well-vented areas (garages, outbuildings), and not in living areas.
❐ Adhere to the “IMPORTANT BATTERY SAFETY INSTRUCTIONS” at the beginning of this manual.
Marking
❐ Battery bank is labeled with maximum operating voltage, equalization voltage, and polarity.
❐ Utility Back-up Systems: Exterior visible sign indicating the building contains an inverter back-
up system and identifi es the locations of the disconnects.
❐ An electrical system supplied by a 120V AC only inverter includes a label warning against
connecting multi-wire branch circuits.
❐ All required “Warning” and “Caution” signs/labels are installed in the proper locations, as required
in the NEC/CEC.
Inspection
❐ Electrical inspection complete and a Certifi cate of Electrical Inspection has been issued by the
local Authority Having Jurisdiction (AHJ). The local AHJ or inspector has the fi nal say on what is
or is not acceptable. Local codes may modify the requirements of the NEC/CEC.
Part of this checklist is obtained from the Photovoltaic Electrical Power Systems Inspector/Installer Checklist
created by John Wiles, Southwest Technology Development Institute, New Mexico State University, June 2006.
After all electrical
the electrical panel have been completed, follow the steps below to test the installation of the MP
enclosure and to verify proper operation of the AC breakers.
connections from the MP enclosure to the inverter, batteries, AC source, and
WARNING:Du
ring this functional test, the front cover is removed and exposes
personnel to potential dangerous voltages and shock hazards inside the MP enclosure
that may cause damage, injury, or death. If you do not have experience working with
AC and DC voltage circuits, do not attempt this test – use an experienced electrical
installer.
CAUTION: During this functional test, if any step cannot be verifi ed or is incorrect,
stop and recheck/correct the connections before proceeding to the next step
1
Turn OFF all breakers (i.e., DC Disconnect, INV BYP, AC OUT, and INV IN) in the MP enclosure.
.
.
2. Perform DC voltage/polarity checks (refer to Figure 3-34 for single enclosures or Figure 3-35
for dual enclosures):
a. Use a DC voltmeter or multimeter (set to DC Volts) and place the negative (-) meter probe
(usually black) on the negative battery busbar (bottom of the DC shunt). Then place the positive
(+) meter probe (usually red) at the bottom of each DC breaker. Verify the battery voltage is
correct for your particular inverter model (i.e., 24-volt battery bank for a 24-volt inverter).
b. Ensure the voltmeter reading is a positive number. When the probes are connected correctly
(positive probe on DC circuit breaker and negative probe on battery negative busbar) and the
number is positive, the polarity of the battery voltage is correct.
If the battery voltage and polarity are correct, apply battery power to the inverter by turning the
inverter DC disconnect breaker(s) to the ON (up) position.
3. AC break
Note: For the following steps, refer to Figure 3-36 for MPSL-30D and MPSH-30D models, Figure
3-37 for the MPSL-60S models, and Figure 3-38 for MPDH-30D models.
a. Now that the appropriate battery voltage is connected to the inverter, turn OFF all inverter
loads in the inverter load panel (i.e., sub-panel) and turn the inverter ON.
b. Connect an AC voltmeter (or multimeter set to AC Volts) to the Inverter AC Output
Terminals and verify the correct AC voltage from the inverter. Refer to Figure 3-36, 3-37, or
3-38 (depending on your MP model) to determine the correct inverter AC output voltage.
ers connections/operation:
CAUTION: Ensure you have read your inverter’s owner’s manual and are familar with
the power
Info: If the inverter does not turn on, refer to the Troubleshooting section for your
particular inverter
Info: If the inverter has a Search mode feature, the inverter’s AC full output voltage will
not be
to bring the inverter out of Search mode.
If using a Magnum inverter, use a light bulb that requires more than 5 watts (5 watts
is the default setting) to bring the inverter out of Search mode; or, turn the Search
mode off (inverter full output will always be on) with a remote control (i.e., ME-RC,
ME-ARC, or ME-RTR).
-up test for y
present/on until Search is turned OFF, or a large enough light bulb is connected
our particualr in
.
verter and remote control.
CAUTION: To prevent damage to valuable equipment, DO NOT connect anything to the
put of the MP but a light bulb until all wiring and voltages are confi rmed to be correct.
out
c. Turn ON the AC OUT1 breaker in the MP enclosure and confi rm that the inverter AC output
voltage is passing thru the AC OUT breaker by verifying that the inverter AC output voltage
is present on the AC Output Terminals.
d. Turn ON the INV BYP1 breaker in the MP enclosure (BYPASS Operation) and verify that
the inverter AC output voltage is no longer present on the AC Output Terminals (all voltage
readings should be 0 volts AC).
e. Turn the inverter OFF.
f. Apply power from an external AC source (utility grid or AC generator) to the AC Input
Terminals and verify the correct AC voltage from the external AC source. Refer to Figure 3-36,
3-37, or 3-38 (depending on your MP model) to determine the correct AC input voltage.
g. Connect the voltmeter to the AC Output Terminals and check that the external AC source
voltage is passing thru the INV BYP breaker by verifying the AC source voltage is now present
on the AC Output Terminals.
h. Turn ON the AC OUT1 and INV IN breakers in the MP enclosure (NORMAL Operation) and
wait for the inverter to connect to the external AC source (approximately 30 seconds). Verify
that the external AC source is present on the AC Output Terminals.
Info: Even though the inverter is turned off, with the external AC source connected
and the INV IN
— after a brief period of time (normally within 30 seconds) — and pass-thru the AC OUT breaker to the AC Output Terminals.
This concludes the MP functional test. If all steps pass, the MP enclosure is ready for use. Disconnect
all power to the MP enclosure and proceed to Section 3.14 to install the front cover.
If any of the steps fail, recheck your wiring connections within the Installation section and/or refer
to the Troubleshooting section for your inverter.
Note 1 - The INV BYP and AC OUT breakers are interlocked together. Physically turning ON one will turn
OFF the other, and vice versa.
breaker turned ON, the external AC source will connect to the inverter
Use the screws and washers that were removed in Step 3.3.1 to attach the front cover to the MP
enclosure. See Figure 3-39 for MPSL and MPSH models, or Figure 3-40 for MPDH models.
Attaching Front Covers
Info: The MP enclosure uses #10-32 x 3/8” Pan head, T25 Torx drive screws, and
#10-32
and MPSH models) use a total of 8 of these screws/washers, the dual enclosure (MPDH
model) uses a total of 16 of these screws/washers.
lock
ashers to hold each front cover in place. The single enclosures (MPSL
w
Figure 3-39, Attaching Front
Cover - MPSL/MPSH Models
er the front cover’s are attached, open and close all circuit breakers, checking for correct
Aft
alignment and free operation with the cover now in-place.
The hardware installation procedures for the MP enclosure are complete, if multiple inverters are
installed, ensure the inverters are labeled to identify their relationship to one another (see Section
3.15). Otherwise, proceed to Section 5.0 to familiarize yourself with the operation of the MP/inverter
system. Also, refer to the Appendix section to learn about the different options available for use
with your MP/inverter system.
elp reduce operator and maintenance errors resulting from incorrect identifi cation of the inverters
T
and circuit breakers, a Master/Slave Identifi cation Label Set is provided. After the MP enclosure/
Inverter system is wired and tested for proper operation, refer to Figure 3-41 to apply the labels
to the front cover of each inverter and to each circuit breaker in the MP enclosure. These labels
allow the operator to clearly identify the AC and DC breakers wired to each inverter; and to know
the relationship of each inverter to one another when connected in a parallel-stacked confi guration.
Diagrams of the AC, DC, and communications wiring for the different MP Series enclosures are
provided in this section to assist the system installer. Use Table 4-1 to quickly fi nd the wiring
diagram for your MP model.
Wiring Diagrams
Info: Due to the variety of applications and differences in local and national electrical
codes,
intended to override or restrict any national or local electrical codes; and, these diagrams
should not be the determining factor as to whether the installation is compliant, that
is the responsibility of the electrician and the onsite inspector.
these
wiring
diagrams should be used as a general guideline only. They are not
Table 4-1, MP Wiring Diagrams
MP Enclosure Models
Wiring Diagrams
Inverter AC Input/Output
Wiring
Inverter AC WiringFigure 4-3aFigure 4-4aFigure 4-5aFigure 4-6a
External AC WiringFigure 4-3bFigure 4-4bFigure 4-5bFigure 4-6b
Full System WiringFigure 4-3eFigure 4-4eFigure 4-5eFigure 4-6f
Figure 4-3cFigure 4-4cFigure 4-5c
Figure 4-6c
and
Figure 4-6d
Description of Wiring Diagrams:
• Inverter AC Input/Output Wiring - These diagr
AC input and output wires, separating them into two bundles (AC Input and AC Output), and
routing each bundle thru different strain-reliefs on the inverter.
• Inverter AC Wiring - These diagrams show the AC wiring inside the MP enclosure from the
inverter’s AC input and output wires.
• External AC Wiring - These diagrams show the AC wiring inside the MP enclosure to the
external AC source (i.e., generator or grid) and the external AC loads (main panel or sub-panel).
• DC Wiring (Inverter and External) - These diagrams show the DC wiring inside the MP
enclosure to the inverter’s DC terminals and the DC wiring to the external DC source (i.e.,
battery bank).
• Communications Wiring - These diagrams show the communications cables wired inside the
MP enclosure. These communications cables are for connecting the BTS and remote control
into and out of the MP enclosure.
• Full System Wiring - These diagrams show all the wiring (inverter AC/DC, external AC/
DC, and communications) as a fully complete system with the maximum amount of inverters
allowed for each specifi c model.
Figure 4-1, Inverter AC Input and Output Wiring Diagram - MS4024
Info: When wiring the MS4024 (or any other MS Series inverter), both the inverter input
and output
enclosure. This is because — depending on the inverter’s operating mode — the inverter’s
input and output neutral terminals may not be connected together (i.e., inverter’s
neutrals are not connected when “inverting”, and are combined when “charging”).
Note: Because a neutral to ground connection is also made in the MP enclosure, the neutral to
ground connection inside the MS4024 must be disconnected. Refer to the MS4024 owner’s manual
for information on how this is done.
neutral wires must be connected to a AC NEUTRAL busbar inside the MP
Figure 4-2, Inverter AC Input and Output Wiring Diagram - MS-PAE Series
Info: When wiring the MS-PAE Series inverter, only a single neutral wire (either an
inverter
busbar inside the MP enclosure. This is because the input and output neutral terminals
are connected together inside the MS-PAE Series inverter.
Info: The busbars labeled AC NEUTRAL in the MP enclosure ARE connected together,
so all neutr
The MP enclosure
your inverter/battery system. These breakers are used as the main power disconnecting means
and/or overcurrent
operation of the breakers within the MP enclosure.
Info:
refer to the relev
Info: F
If
short-circuit condition occurs, or if a load is placed on the circuit breaker that is more than its
a
rated capacity, the breaker will trip OFF (down). On the AC breakers, a red indicator will display
through the clear window on the circuit breaker to show a tripped condition. On the other circuit
breakers, the handle will trip all the way to the OFF position.
Before resetting the breaker, fi rst determine the cause of the overcurrent fault. Then, reset the
circuit breaker by turning it all the way OFF, and then all the way back ON. For proper maintenance
and longer life, the circuit breakers should be turned off and on several times at least once a year.
This will help to prevent the contacts inside from sticking together.
To shut the MP/inverter system OFF completely, all of the circuit breakers in the MP
enclosure must be switched to the OFF position.
provides you with circuit breakers/disconnects to easily operate and maintain
protection. Refer to Figure 5-1 to view a simple diagram of the functional
Figure 5-1 is for descriptive purposes only, for specifi c wiring directions please
ant wiring diagr
or information on operating the inverter, refer to its owner’s manual.