The use of this manual and the conditions or methods of installation,
operation, use, and maintenance of the MMS Series inverter/
charger are beyond the control of Magnum Energy, Inc. Therefore,
this company assumes no responsibility and expressly disclaims
any liability for loss, damage, or expense whether direct, indirect,
consequential, or incidental that may arise out of or be in any way
connected with such installation, operation, use, or maintenance.
Due to continuous improvements and product updates, the images
shown in this manual may not exactly match the unit purchased.
Restrictions on Use
The MMS Series inverter/charger may only be used in life support
devices or systems with the express written approval of Magnum
Energy. Failure of this inverter can reasonably be expected to cause
the failure of that life support device or system, or to affect the safety
or effectiveness of that device or system. If the MMS Series inverter
fails, it is reasonable to assume that the health of the user or other
persons may be endangered.
Shorepower or External AC power – refers to alternating current
(AC) provided by the utility electric power grid or from a generator.
Mobile application – refers to inverters used in a recreational vehicle
(RV), boat, or a truck installation.
Safety Symbols
To reduce the risk of electrical shock, fi re, or other safety hazard, the
following safety symbols have been placed throughout this manual
to indicate dangerous and important safety instructions.
WARNING: This symbol indicates that failure to take a
specifi ed action could result in physical harm to the user.
CAUTION: This symbol indicates that failure to take a
specifi ed action could result in damage to the equipment.
Info: This symbol indicates information that emphasizes
or supplements important points of the main text.
IMPORTANT PRODUCT SAFETY INSTRUCTIONS
This manual contains important safety instructions that must be followed during the installation and operation of this product. Read all
instructions and safety information contained in this manual before
installing or using this product.
• All electrical work must be performed in accordance with local,
state, and federal electrical codes.
• This product is designed for indoor/compartment installation.
DO NOT expose to rain, snow, moisture, or liquids of any type.
• Use insulated tools to reduce the chance of electrical shock or
accidental short circuits.
• Remove all jewelry (such as rings, watches, bracelets, etc.,) when
installing or performing maintenance on the inverter.
• Always disconnect the batteries or energy source prior to installing or performing maintenance on the inverter. Live power may
be present at more than one point since an inverter utilizes both
batteries and AC. Turning off the inverter may not reduce this
risk. As long as AC power is connected, it will pass through the
inverter regardless of the ON/OFF power switch setting.
• Always verify proper wiring prior to starting the inverter.
• Do not operate the inverter if it has been damaged.
• Do not dismantle the inverter; there are no user-serviceable parts
contained in this product. Attempting to service the unit yourself
could cause electrical shock. Internal capacitors remain charged
after all power is disconnected.
• No AC or DC disconnects are provided as an integral part of this
inverter. Both AC and DC disconnects must be provided as part
of the system installation.
• No overcurrent protection for the battery supply is provided as
an integral part of this inverter. Overcurrent protection of the
battery cables must be provided as part of the installation.
• No overcurrent protection for the AC output wiring is provided
as an integral part of this inverter. Overcurrent protection of the
AC output wiring must be provided as part of the installation.
IMPORTANT BATTERY SAFETY INSTRUCTIONS
• Wear eye protection (safety glasses) when working with batteries.
• Remove all jewelry such as rings, watches, bracelets, etc., when
installing or performing maintenance on the batteries.
• Never work alone. Always have someone near you when working
around batteries.
• Use proper lifting techniques when working with batteries.
• Never use old or untested batteries. Check each battery’s label
for age, type, and date code to ensure all batteries are identical.
• Batteries are sensitive to changes in temperature. Always install
batteries in a stable environment.
• Install batteries in a well ventilated area. Batteries can produce
explosive gasses. For compartment or enclosure installations,
always vent batteries to the outside.
• Provide at least one inch (2.5 cm) of air space between batteries
to provide optimum cooling.
• Never smoke when in the vicinity of batteries.
• To prevent a spark at the battery and to reduce the chance of
explosion, always connect the cables to the batteries fi rst. Then
connect the cables to the inverter.
• Use insulated tools at all times.
• Always verify proper polarity and voltage before connecting the
batteries to the inverter.
• To reduce the chance of fi re or explosion, do not short-circuit
the batteries.
• In the event of accidental exposure to battery acid, wash thoroughly with soap and water. In the event of exposure to the eyes,
fl ood them for at least 15 minutes with running water and seek
immediate medical attention.
Congratulations on your purchase of an MMS Series inverter/charger
from Magnum Energy, Inc. This product is designed especially for
your mobile application. Powerful, yet simple to use, this product will
provide you with years of trouble-free use.
1.1 MMS Series Models
MMS1012 – a 1000 watt inverter/charger with 20-amp AC transfer
capability and a 50-amp, 4-stage Power Factor Correction (PFC)
charger. The AC input and output are provided with pigtail wires to
allow hardwiring to a main AC distribution panel and to an inverter
sub-panel. Features isolated input/output neutrals for mobile
applications. Includes a 15-foot battery temperature sensor.
Figure 1, MMS1012 Model Inverter/Charger
MMS1012-G – a 1000 watt inverter/charger with 20-amp AC transfer
capability and a 50-amp, 4-stage PFC charger. The AC input is
provided by a standard 3-foot plug-in power cord, and the AC output
is provided by a standard GFCI two plug outlet. Features isolated
input/output neutrals for mobile applications. Includes a 15-foot
battery temperature sensor.
An inverter takes direct current (DC) from your batteries and turns
it into alternating current (AC), like you use at home. With MMS
Series models, it also takes alternating current (when connected to
a generator or to shorepower) and transforms it into direct current
to recharge your batteries.
The two modes of operation associated with this inverter/charger
are referred to in this document as:
Inverter Mode: DC from the batteries is transformed into pure sine
wave AC for powering your mobile applications.
Standby Mode: The unit operates as a battery charger to convert
incoming AC power into DC power to recharge the batteries while
continuing to pass the incoming AC power directly to the inverter’s
output, to power any AC loads.
1.2.1 Inverter Applications for Mobile Installations
Inverters can be used to provide power in mobile situations—RV,
truck, or boat. In these applications, the inverter provides power to
the AC loads using the energy stored in the batteries and recharges
the batteries when shorepower or an onboard generator is available.
1.3 Advantages of a Pure Sine Wave vs Modifi ed Sine
Wave Inverter
Today’s inverters come in two basic output waveforms: modifi ed sine
wave (which is actually a modifi ed square wave) and pure sine wave.
Modifi ed sine wave inverters approximate a pure sine waveform and
will run most appliances and electronics without any problems. These
inverters are less expensive and, therefore, offer a viable alternative
to more expensive pure sine wave inverters.
The output of a pure sine wave inverter is equal to, or in many
cases, better than the shorepower used in your home. Virtually any
electronic device will operate from a pure sine wave inverter. Motors run cooler, microwaves usually cook faster, and clocks keep
better time just to name a few examples. Without compromising
quality or performance, the MagnaSine provides you with all of the
advantages of a pure sine wave inverter at a much lower cost than
many on the market.
1.4 Appliances and Run Time
The MMS Series inverter/charger can power a wide range of household
appliances. As with any appliance using batteries for power, there
is a certain length of time that it can run—this is called “run time”.
Actual run time depends on several variables including the size and
the type of appliance, the type of batteries installed in your application, as well as the battery’s capacity and age. Other factors such
as the battery’s state of charge and temperature can also affect the
length of time your appliances can run.
Depending on your inverter capacity, larger electrical appliances such
as coffee pots and hair dryers can be used for short durations. However, loads that are used for longer periods such as stoves or water
heaters can quickly drain your batteries and are not recommended
for inverter applications.
All electrical appliances are rated by the amount of power they
consume. The rating is printed on the product’s nameplate label,
usually located on its chassis near the AC power cord. Even though
it is diffi cult to calculate exactly how long an inverter will run a par-
ticular appliance, the best advice is trial and error. Your MMS Series
inverter/charger has a built-in safeguard that automatically protects
your batteries from being over-discharged.
1.5 Standard Features and Benefi ts
The MMS Series inverter/charger converts 12 volts of direct cur-
rent (VDC) power from your battery to 120 volts alternating current
(VAC) power.
power using Power Factor Correction (PFC) technology to keep the
inverter’s battery bank fully charged. This inverter is designed to allow
easy installation and use, and with its die-cast aluminum baseplate
it ensures maximum durability and cooler, more effi cient operation.
The multi-stage battery charger optimizes incoming AC
The inverter/charger provides the following:
• 1000 watts continuous at 25°C.
• Numerous protection features to provide a safe and peace-of-
mind operation.
• AC transfer switch circuitry; allowing incoming AC power to
continue to pass-thru to power loads even if the inverter is off.
• Dead battery charging for batteries that are extremely low.
• Automatic 4-stage battery charger with power factor correction
and temperature compensation—for optimum battery charging
(using the temperature sensor).
• Modern and aesthetically pleasing design with a large AC wiring
compartment (provides easy access to AC wiring for simple and
quick connections) and 360° DC connection terminals with color
coded insulating covers.
• True RMS output voltage regulation to ensure the inverter will
deliver the correct amount of power—within the DC input voltage
range and the continuous output power level.
• Quick connection accessory and remote ports—easily accepts sev-
eral optional remote controls and the battery temperature sensor.
13. Warning and Information Label – provides pertinent
information for safely using the inverter.
14. REMOTE Port Connection – a RJ11 connector that allows an
optional remote control to be connected.
15. ACCESSORY PORT Connection – a RJ11 connector to allow
the Battery Temperature Sensor (BTS) or MMS accessories (e.g.,
MM-DCLD, MM-ISA) to be connected.
16. Intake Vent – ventilation openings to pull in air to keep the
inverter cool for peak performance.
17. Exhaust Vent – ventilation openings that allow heated air to be
removed by the internal cooling fan.
18. Model/Serial Number Label – includes model/serial number
and provides specifi cations and information on the inverter and
charger. See the MMS Series Specifi cations on page 39 for more
information and the different models available.
A plug-in external Battery Temperature Sensor (BTS) is provided
for units with the battery charger feature. When installed, the BTS
automatically adjusts the battery charger’s BULK, ABSORB, and
FLOAT voltage set-points (based on temperature) for better charging performance and longer battery life. If the temperature sensor is
NOT installed and the batteries are subjected to large temperature
changes, battery life may be shortened.
Before installing the inverter, read the entire Installation section. The
more thorough you plan in the beginning, the better your inverter
needs will be met.
WARNING:Installations should be performed by qualifi ed
personnel, such as a licensed or certifi ed electrician. It
is the installer’s responsibility to determine which safety
codes apply and to ensure that all applicable installation
requirements are followed. Applicable installation codes
vary depending on the specifi c location and the type of
installation.
Info: Review the Important Product Safety Information
on page ii and the Important Battery Safety Instructions
on page iii before any installation.
The basic system diagrams shown in Figures 6 and 7
reviewed to assist you in planning and designing your installation.
2.1.1 Unpacking and Inspection
Carefully remove the MMS inverter/charger from its shipping container
and inspect all contents. Verify the following items are included:
• MMS Series inverter/charger
• Red and black DC terminal covers
• AC access cover with two screws
• Two 5/16-18 hex-head kep nuts (installed on the DC terminals)
• Battery Temperature Sensor (BTS)
• MMS Series Owner’s Manual
• Warning Label
If items appear to be missing or damaged, contact your authorized
Magnum Energy dealer or Magnum Energy.
If at all possible, keep your shipping box. It will help protect your
inverter from damage if it ever needs to be returned for service.
Save your proof-of-purchase as a record of your ownership; it will
also be needed if the unit should require in-warranty service.
should be
Record the unit’s model and serial number in the front of this manual
in case you need to provide this information in the future. It is much
easier to record this information now, instead of trying to gather it
after the unit has been installed.
• Do not mount the inverter near any fl ammable or
combustible fl uid or components.
• Provide adequate clearance/ventilation to the inverter.
• Mount only on a non-combustible surface.
• Maximum ambient temperature around the inverter
must not exceed 77°F (25°C) to meet power specifi -
cations.
The inverter should only be installed in a location that meets the
following requirements:
Clean and Dry – The inverter should not be installed in an area that
allows
ventilation openings. The area also must be free from any risk of
condensation, water,
inverter. The inverter uses stainless steel fasteners, plated copper
busbars, and a power-coated aluminum base. Also, the internal circuit
boards are conformal coated. The above measures are undertaken to
help fi ght the harmful effects of corrosive environments. However,
the life of the inverter is uncertain if used in any of these types of
environments, and inverter failure under these conditions is not
covered under warranty.
dust, fumes, insects, or rodents to enter or block the inverter’s
or any other liquid that can enter or fall on the
Cool – The inverter should be
sun or any equipment that produces extreme heat.
protected from direct exposure to the
The ambient air
temperature should be between 32°F (0°C) and 104°F (40°C); keep
in mind that the inverter’s output specifi cations are rated at 77°F
(25°C), so the cooler the better within this range.
Ventilated – In order for the inverter to provide full output power
and avoid over-temperature fault conditions, do not cover or block
the inverter’s ventilation openings or install this inverter in an area
with limited airfl ow. Allow as much clearance around the inverter’s
intake and exhaust ventilation openings as possible (see Figure 4,
Items 16 & 17). At the minimum, allow an airspace clearance of
3” (7.5 cm) on all sides to provide adequate ventilation.
If installed in an enclosure, a fresh air intake opening must be provided directly to the front side (intake vent) and an exhaust opening on the back side (exhaust vent) of the inverter. This will allow
cool air from the outside to fl ow into the inverter, and heated air to
exit away from the inverter and the enclosure. When mounted in an
enclosed compartment, airfl ow must be at least 59 cfm in order to
maintain no more than a 68°F (20°C) rise in compartment temperature. Minimum clearances can be reduced if airfl ow is increased, but
in no case should clearance around the inverter be less than 2” (5
cm) on all sides.
Safe – Keep any fl ammable/combustible material (e.g., paper, cloth,
plastic, etc.) that may be ignited by heat, sparks, or fl ames at a
minimum distance of 2 feet (60 cm) from the inverter.
WARNING: The MMS inverter/charger is not an ignition-
protection rated device and should not be installed in
any location that requires ignition-protected equipment.
To prevent fi re or explosion, do not install the MMS
inverter in any area with extremely fl ammable liquids
like gasoline or propane; or, in an area that contains
connections between components of a fuel system.
Close to the battery bank – As with any inverter, it should be
located as close to the batteries as possible. Long DC wires tend to
lose effi ciency and reduce the overall performance of an inverter.
However, the unit should not be installed in the same compartment as
the batteries or mounted where it will be exposed to gases produced
by the batteries. These gases are corrosive and will damage the
inverter. Also, if these gases are not ventilated and allowed to collect,
they could ignite and cause an explosion.
Accessible –
Do not block access to the inverter’s remote control
and accessory ports. Also, allow enough room to access the AC and
DC wiring connections, as they will need to be checked and tightened
periodically. See Figure 9 & 10 for the MMS inverter’s dimensions.
Mounting Orientation – To meet regulatory requirements, the MMS
Series inverter/charger can only be mounted
on a horizontal surface
(shelf or table) or a vertical surface (wall or bulkhead) either rightside up or upside-down, as shown in Figure 8. The inverter must be
mounted on a non-combustible surface, and this surface and the
mounting hardware must be capable of supporting at least twice the
weight of the inverter. After determining your mounting position,
use the base of the inverter’s chassis as a template to mark your
mounting screw locations. Remove the inverter and drill pilot holes
into the mounting surface.
If this unit is used in a mobile application, you may want to place
fl exible washers or bushings between the mounting surface and the
inverter’s mounting fl anges to reduce vibration.
• DC wires and cables should be tied together with wire ties or
electrical tape approximately every 6 inches (15.2 cm). This
helps improve the surge capability and reduces the effects of
inductance, which improves the inverter waveform and reduces
wear on the inverter’s fi lter capacitors.
• Use only copper wires with a minimum temperature rating of
75°C (167°F).
• To ensure maximum performance from the inverter, all connections from the battery bank to the inverter should be minimized
(Exception: the DC overcurrent disconnect in the positive line).
2.2DC Wiring
This section describes the MMS Series inverter’s required DC wire
sizes, the recommended disconnect/overcurrent protection, and how
to make the DC connections to the inverter and the battery bank.
2.2.1 DC Wire Sizing
It is important to use the correct DC wire to achieve maximum effi ciency from the system and to reduce fi re hazards associated with
overheating. Use Table 1 to select the minimum DC wire size needed
based on your inverter model. If the distance from the inverter to
the battery bank is greater than 3 feet (91.4 cm), use Table 2 to
help determine the minimum recommended cable sizes for longer
distances. Always keep your wire runs as short as practical to help
prevent low voltage shutdowns and to keep the DC breaker from
nuisance tripping (or open fuses) because of increased current draw.
Undersized cables can also lower the inverter’s peak output voltage,
as well as reduce its ability to surge heavy loads.
Info: The DC wires must be color coded with colored
tape or heat shrink tubing; RED for positive (+), BLACK
for negative (-), and GREEN for DC ground.
The DC wires must have soldered and crimped lugs, crimped copper
compression lugs, or aluminum mechanical lugs. Soldered connections alone are not acceptable for this application.
If the inverter is expected to operate at a distance greater than 3 feet
(91.4 cm) from the battery bank, the DC wire size will need to be
increased to overcome the increase in resistance—which affects the
performance of the inverter. Continue to use the overcurrent device
and DC ground wire previously determined from Table 1 and then,
refer to Table 2 to determine the minimum DC wire size you need
for various distances based on your inverter model.
2.2.2 DC Overcurrent Protection
For safety and to comply with NEC (National Electrical Code) electrical
code regulations, you must install a DC overcurrent protection device
in the positive DC cable line to protect your DC cables. This DC
overcurrent device can be a fuse or circuit-breaker, but must be DC
rated. It must be correctly sized according to the size of DC cables
being used, which means it is required to open before the cable
reaches its maximum current carrying capability, thereby preventing
a fi re.
See Table 1 to select the DC overcurrent device based on the
minimum wire size for your inverter model.
Table 1, Recommended DC Wire/Overcurrent Device
Inverter Model
MMS1012MMS1012-G
Maximum Continuous
Current¹
DC Grounding
Electrode Wire Size²
Minimum DC Wire Size³
(75˚C rating in free air)
Maximum DC Fuse Size
Note¹ – Maximum Continuous Current is based on the inverter’s continuous
power rating at the lowest input voltage with an ineffi ciency factor.Note² – Per the NEC, the DC grounding electrode conductor can be a #6
AWG conductor if that is the only connection to the grounding electrode and
that grounding electrode is a pipe, rod, or plate electrode.
Note³ – Wire size is based on the requirements needed to increase effi ciency
and reduce stress to the inverter.
Note – The next larger standard size overcurrent device may be used if
the de-rated cable ampacity falls between the standard overcurrent devices
found in the NEC.
133 amps133 amps
#6 AWG
(13.3 mm²)
#2 AWG
(33.6 mm²)
[170 amps]
150 amps with
time delay
#6 AWG
(13.3 mm²)
#2 AWG
(33.6 mm²)
[170 amps]
150 amps with
time delay
Info: The term “in free air” is defi ned by the NEC as not
Electrical systems in mobile installations typically do not require
using a DC disconnect, although an overcurrent protection device is
still required. Because the DC disconnect is not required, a fuse is
usually used as the disconnect device in these installations. These
installations also do not normally use conduit, so the fuse must be
installed in the ungrounded conductor (usually the positive DC cable
line) within 18 inches (45.7 cm) of the battery—to protect the DC
wiring system.
If using a fuse, we recommend using a
This fuse type is rated for DC operation, can
circuit currents, and
allows for momentary current surges from the
class-T type or equivalent.
handle the high short-
inverter without opening.
2.2.3 DC Grounding
The inverter/charger should always be connected to a permanent,
grounded wiring system.
The idea is to connect the metallic chassis
of the various enclosures together to have them at the same voltage
potential, which reduces the possibility for electric shock.
For the
majority of installations, the inverter chassis and the negative battery
conductor are connected to the system’s ground bond via a safetygrounding conductor (bare wire or green insulated wire) at only one
point in the system. Per the NEC, the size for the grounding conductor
is usually based on the size of the overcurrent device used in the DC
system.
Refer to Table 1 to select the appropriate DC ground wire
based on the overcurrent device used for your inverter model.
If the inverter is in a vehicle, DO NOT connect the battery negative
(-) cable to the vehicle’s safety ground. Only connect to the inverter’s
negative battery terminal. If there are any non-factory installed
appliances onboard the vehicle, DO NOT ground them at safety
ground. Only ground them at the negative bus of the DC load center
(as applicable).
2.2.4 DC Cable Connections
When connecting the DC cable to the battery or to the inverter’s DC
terminals, the hardware should be installed in the correct order to
prevent high resistance connections from heating up and possibly
causing the connections to melt. Follow Figures 11 and 12 to stack
the hardware correctly. Tighten the terminal connections from 10
to 12 ft-lbs.
CAUTION: Don’t put anything between the DC cable ring
lug and the battery terminal post or the inverter’s DC
terminal. If antioxidant grease or spray is used, apply
it after all the connections have been made and are
properly tightened.
CAUTION: Overtightening or misthreading nuts on the DC
terminals will cause the bolts to strip and snap/break-off.
WARNING: Lethal currents will be present if the positive
and negative cables attached to the battery bank touch
each other. During the installation and wiring process,
ensure the cable ends are insulated or covered to prevent
touching/shorting the cables.
Info: DO NOT connect the DC wires from the battery
bank to the inverter until: 1) all DC/AC wiring is complete,
2) the correct DC and AC overcurrent protections have
been installed, and 3) the correct DC voltage and polarity
have been verifi ed.
Info: For optimum performance, a minimum battery bank
of 200 AHr is recommended.
Depending upon the type of batteries you use in the installation
(6 or 12 VDC), the batteries must be wired in series, parallel, or
series-parallel (see Appendix B – Battery Information for guidance
on wiring batteries together). The interconnecting DC wires must be
sized and rated exactly the same as those that are used between
the battery bank and the inverter.
Place the batteries as close as practical to the inverter, preferably in
an insulated and ventilated enclosure. Allow adequate space above
the batteries to access the terminals and vent caps (as applicable).
Also, allow at least 1” (2.5 cm) of space between the batteries to
provide good air fl ow. DO NOT mount the batteries directly under
the inverter.
Info: To ensure the best performance from your inverter
system, do not use old or untested batteries. Batteries
should be of the same size, type, rating, and age.
CAUTION: Install batteries in a well ventilated area. Bat-
teries can produce explosive gasses. For compartment or
enclosure installations, always vent batteries to the outside.
2.3.1 Inverter to Battery Bank Wiring
WARNING: Ensure all sources of DC power (i.e., batter-
ies) and AC power (shorepower or AC generator) are deenergized (i.e., breakers opened, fuses removed) before
proceeding.
CAUTION: The inverter is NOT reverse polarity protected.
If this happens, the inverter will be damaged and will not
be covered under warranty.
from the batteries to the inverter, verify the correct battery
voltage and polarity using a voltmeter. If the positive terminal of the battery is connected to the negative terminal
of the inverter and vice versa, severe damage will result.
If necessary, color code the cables with colored tape or
heat shrink tubing; RED for positive (+), and BLACK for
negative (-) to avoid polarity confusion.
Info: The DC overcurrent device (i.e., fuse or circuit
breaker) must be placed in the positive (RED) DC cable
line between the inverter’s positive DC terminal and the
battery’s positive terminal (RED); as close to the battery
as possible.
DC Ground Wire
Route an appropriately sized DC grounding wire (GREEN or bare
wire) from the inverter’s DC Ground Terminal (see Figure 3, Item
11) to a dedicated system ground. Recommended tightening torque
is 45 in-lbs.
Before connecting the DC wires
DC Negative Wire
Route an appropriately sized DC negative wire (BLACK) from the
negative terminal of the last battery string to the inverter’s negative
terminal (see Figure 21 for reference).
Battery Temperature Sensor
Connect the RJ11 connector end of the BTS to the ACCESSORY PORT
(see Figure 4, Item 15) on the inverter. Connect the other end of the
BTS to the negative terminal of the fi rst battery string (in same place
as the DC negative wire above); refer to Figure 11 for the correct
hardware placement.
DC Positive Wire
Mount the DC fuse block and disconnect (or circuit breaker assembly)
as near as practical to the batteries, and then open the disconnect
(or circuit breaker).
WARNING: DO NOT close the DC fuse/DC disconnect (or
close the DC circuit breaker) to enable battery power to
the inverter at this time. This will occur in the Functional Test after the installation is complete.
Route and connect an appropriately sized DC positive wire (RED)
from the DC fuse block (or circuit breaker assembly) to the inverter’s
positive DC terminal.
Connect a wire (same rating as the DC wires) to one end of the fuse
block and the other end of this wire to the positive terminal of the
fi rst battery string (see Figure 21). This is essential to ensure even
charging and discharging across the entire battery bank.
Ensure the DC wire connections (to batteries, inverter, and fuse lugs/
DC circuit breaker) are fl ush on the surface of the DC terminals, and
the hardware (lock washer and nut) used to hold these connections
are stacked correctly (see Figures 11 and 12).
Verify all DC connections are torqued from 10 to 12 ft-lbs.
Once the DC connections are completely wired and tested, coat the
terminals with an approved anti-oxidizing spray.
Press the red and black terminal covers onto the inverter’s DC con-
nectors to secure them in place.
If batteries are in an enclosure, perform a fi nal check of the hold down
brackets and all connections. Close and secure the battery enclosure.
2.4 AC Wiring
This section describes the MMS Series’ required AC wire size and
overcurrent protection. It also provides information on how to make
the AC connections.
Info: The MMS1012-G model has a power cord for AC
input and dual outlets on top of the inverter for AC output
(has hardwiring capability as well).
WARNING: All wiring should be done by a qualifi ed per-
son or a licensed electrician following all local/NEC codes.
2.4.1 Neutral to Safety Ground Bonding
The NEC/CEC (National Electric Code/Canadian Electrical Code)
provide the standards for safely wiring mobile (RV, boat, or truck)
installations. These wiring standards require the AC source (inverter,
shorepower, or a generator) to have the neutral conductor tied to
ground. These standards also require that the AC neutral be connected to safety ground (often called a “bond”) in only one place at
any time.
If more than one bond is established, currents can circulate
between neutral and ground and cause ground-loop currents. These
“ground-loops” can trip GFCIs and cause an electric shock hazard.
In mobile installations, there may be multiple AC sources (i.e.,
shorepower, generator, or inverter), which means there may be the
potential of having multiple neutral-to-ground connections.
2.4.2 AC Wiring Connections
For the MMS1012 model, the AC input and output wiring is performed
in the AC wiring compartment. This compartment is accessed via the
top panel (Figure 3, Item 8). If the panel cover is installed, remove
the two Phillips screws on the cover to access the AC wiring compartment and locate the inverter’s AC wiring. There is a label located in
the AC access compartment which gives information on which wires
are used for AC input and output. You can also refer to Table 3 to
match the inverter’s AC wires to the appropriate AC wire connection.
The AC wires inside the AC compartment are #16 AWG (1.3 mm²)
with a temperature rating of 105°C (221°F). All AC connections should
be made using an approved connector for your application (e.g., split
bolt, twist-on wire connectors, etc.). Ensure the wire connectors
used are rated for the size and number of wires you are connecting.
After connecting the wires together, gently pull on the wires to ensure
they are securely held together. In a proper connection, no bare wire
should be exposed
.
Info: Per UL certifi cation, non-metallic sheathed cable
(i.e., Romex™) or an SO fl exible cord with listed strain
reliefs are allowed to be used to connect to the inverter;
conduit connections are not allowed.
After all AC wiring in the inverter is complete (and before reattaching the AC access cover), ensure all the connections are correct and
secure.
2.4.3 AC Wire Size and Overcurrent Protection
The AC input and output wiring must be sized per NEC and local electrical safety code requirements
handle the inverter’s
maximum load current. After determining the
to ensure the wire’s ability to safely
proper AC wire sizes, the inverter’s AC input (unless you are using a
fl exible cord) and output wires are required to be protected against
overcurrent and have a means to disconnect the AC circuits.
All inverter AC input and output wiring is required to be protected
by an overcurrent protection device. Overcurrent protection must
be provided by fuses or circuit-breakers, and must
be properly sized
and rated for the wire they are protecting and the appliances being
powered.
Most inverter’s that are hardwired use a service/distribution panel
wired to the inverter’s input (main panel), and a dedicated panel
between the inverter’s output wiring and the AC loads (sub-panel).
These systems use the circuit breakers provided in the panels as the
overcurrent protection and the AC disconnect. If fuses are used, then
separate AC disconnect switches will be needed.
Based on information from the NEC, Table 4 provides the minimum
AC wire size and the suggested breaker size based on inverter model.
H
owever, a larger wire size may be required because of voltage drop.
The
AC wire sizes provided in this table assume using only copper
wire and a temperature rating of 75°C (167°F) or higher. A minimum
of #14 AWG
Table 4, Minimum Wire Size to Circuit-breaker Size
Inverter
Model
(2.1 mm²)is required for all AC wiring.
AC InputAC Output
Input
Breaker
Minimum
Wire
Size
Suggested
Breaker
Size
Output
Breaker
Minimum
Wire
Size
Suggested
Breaker
Size
MMS1012
MMS1012
-G
20 amps
20 amps
#12 AWG
(3.3 mm²)
#12 AWG
(3.3 mm²)
20 amps15 amps
20 amps15 amps
#14 AWG
(2.1 mm²)
#14 AWG
(2.1 mm²)
15 amps
15 amps
2.4.4 AC Input Wiring
Your inverter has an AC transfer feature that passes the AC input
power to the inverter’s output. Connection to the AC input is made
by hardwiring from a distribution panel as described below:
1. Run an appropriately sized 2-conductor plus ground cable (from
the AC distribution panel) through the strain relief clamp on the AC
IN opening (Figure 3, Item 10). Refer to Table 4 for minimum wire
size and overcurrent protection required for the AC input wiring.
2. Remove about two inches of the insulating jacket from the AC
cable, and then separate the three wires and strip about 3/4”
(1.9 cm) of insulation from each wire.
3. Using approved AC wire connectors, connect the incoming Hot
In, Neutral In, and Ground wires to the MMS Series’ AC wires
colored black (HOT IN), white (NEUT IN), and green (AC GROUND)
respectively.
4. After making the AC input connections, secure the AC input cable
by tightening the strain relief clamp.
The AC input wiring in the inverter is complete. Review all AC wiring
to ensure all connections are correct and secure.
CAUTION: The inverter’s AC output must never be con-
nected to an AC power source. This will cause severe
damage to the inverter and is not covered under warranty.
Info: When using the MMS Series inverter in an RV appli-
cation, under certain conditions and provided that the wire
is properly sized for the protecting breaker; RVIA wiring
standards will permit the breaker in the Main distribution
panel and/or the supplemental breakers on the inverter
to provide adequate protection for the AC output wiring.
For more information on these requirements, refer to the
RVIA (www.rvia.org).
Follow the steps below to hardwire the AC output of the MMS Series
inverter:
1. Remove the 1/2” knockout on the AC Output Connection
(Figure 3, Item 9)—use a utility knife to cut thru the round slot.
2. Discard this knockout and install a 1/2” strain relief in the AC OUT
opening. You may need to fi le the opening edge for proper fi t.
3. Run a 2-conductor plus ground cable through the strain relief in
the AC OUT opening. Refer to Table 4 for the minimum wire size
and the overcurrent protection required for the AC output wiring.
4. Remove about two inches (5.1 cm) of the insulating jacket from
the AC cable, and then separate the three wires and strip about
3/4” (1.9 cm) of insulation from each wire.
5. Using approved AC wire connectors, connect the outgoing Hot
Out, Neutral Out, and AC Ground wires to the inverter’s AC wires
colored red (HOT OUT), white with black stripe (NEUT OUT), and
green (AC GROUND) respectively. Gently pull on the wires to
ensure they are securely held together, and check to see that
no bare wire is exposed.
6. After making the AC output connections, secure the AC output
cable by tightening the strain relief.
7. Connect the outgoing AC wires to either:
a) an AC load sub-panel equipped with overcurrent protection
(e.g., circuit breakers), or
b) directly to the circuit (if following RVIA requirements that
permit using breakers from the main distribution panel or the
breakers on the inverter under certain conditions).
The AC output wiring in the inverter should be complete. Before
reattaching the AC access cover, review all AC wiring to ensure all
connections are correct and secure.
In compliance with UL standards, Magnum Energy tested the following GFCIs and found that they function properly when connected to
the inverter’s AC output:
Shock Sentry
Lock #8899-A, and Hubbel #GF520EMBKA.
WARNING: Risk of electric shock. Use only the
GFCIs [receptacles or circuit breaker(s)] specifi ed in this
manual. Other types may fail to operate properly when
connected to this inverter.
be installed in the recreational vehicle’s wiring system to
protect all branch circuits.
Inverter Warning Label
The warning label (see Figure 15) is provided to inform all personnel that an inverter is installed in your electrical system. Affi x this
label in a clearly visible location at the electrical panel that is being
powered by the inverter. This is necessary because it might be falsely
assumed that the panel is no longer “hot” after AC power has been
shut off—when in fact power may actually still be available due to
the inverter automatically powering the panel.
TM
#XGF15V-SP, Leviton Smart
This electrical system is equipped with an
Automatic Generator Starting (AGS) device and/
or an inverter. Disconnect all AC and DC power to
the AGS and/or inverter before performing any
service to the electrical system. Failure to do so
can result in shock causing serious injury or death.
PN: 62-0002 Rev A
Figure 15, Warning Label
2.5 Functional Test
After all electrical connections to the inverter, batteries, AC source
and loads (using a sub-panel)
steps to test the installation and the inverter’s operation.
1. Check the battery voltage and polarity before connecting the
batteries to the inverter. Use a multimeter to verify 10 to 14 VDC
at the batteries’ positive and negative terminals.
2. Apply battery power to the inverter by switching the DC disconnect ON (or close the DC circuit-breaker). The inverter will remain
OFF, but the green status indicator on the front of the inverter will
quickly blink once to indicate that DC power has been connected
and is ready to be turned on.
3. Prior to turning on the inverter, make sure all connected loads
(e.g., appliances) are switched OFF or disconnected from the
AC outlets.
4. a) If a remote switch is connected, press the ON/OFF switch to
turn the inverter on.
b) If there is no remote switch connected, lightly press and release
the inverter’s ON/OFF power switch—located on the top of the
inverter—to turn the inverter on.
Verify the inverter’s status indicator is blinking—indicating the
inverter is providing AC power.
5. Connect a 10-25 watt light bulb to the inverter output and verify
it comes on and shines normally. DO NOT connect anything
larger than a 25-watt light bulb until all wiring and voltages are
confi rmed to be correct.
Info: The inverter’s AC output voltage will not be correct
until a load greater than 5 watts (default setting) is
connected to the inverter; or, Search mode is turned off
with a remote display (ME-RC, ME-ARC, or ME-RTR). A
10-25 watt bulb is used as it is a suffi cient load to bring
the inverter out of Search mode and up to full voltage.
6. Check the AC output voltage of the inverter by connecting a true
RMS multimeter to the outlets powered by the inverter. Verify the
voltage is 120 VAC +/- 5 VAC. If not using a true RMS meter, the
output AC voltage could indicate from 90 to 130 VAC depending
on the battery voltage.
7. Press the remote ON/OFF switch to turn the inverter off. If the
remote is not used, press and release the inverter’s ON/OFF power
switch to turn the inverter off. The inverter’s status indicator and
the connected load should go off.
8. Apply AC power to the inverter’s AC input. After the AC input
power is qualifi ed (approximately 15 seconds), the incoming AC
power will transfer through the inverter to the inverter’s AC output and power the connected light bulb. Verify that the inverter’s
status indicator and the connected light bulb come on.
9. Even though the connected light bulb is on, the inverter is currently disabled/off. Press the remote’s ON/OFF switch (or press
and release the ON/OFF power switch on the inverter) to enable/
turn on the inverter.
10. Disconnect the incoming AC power to the inverter. Verify the light
bulb remains on, but now is powered by the inverter.
If the inverter passes all the steps, the inverter is ready for use. If the
inverter fails any of the steps, refer to the Troubleshooting section.
The MMS Series inverter/charger has two normal operating routines. Inverter mode, which powers the loads using the batteries,
and Standby mode, which transfers the incoming AC power (i.e.,
shorepower or a generator) to power the loads and to recharge the
batteries. This inverter also includes an extensive protection circuitry
that shuts down the inverter under certain fault conditions.
3.1.1 Inverter Mode
When the inverter is fi rst powered up, it defaults to the OFF mode.
The momentary ON/OFF power switch (Figure 3, Item 2) must be
lightly pressed to turn the inverter ON. Subsequently pressing this
switch alternately turns the inverter OFF and ON.
• Inverter OFF – When the inverter is OFF, no power is used
from the batteries to power the AC loads and
be OFF. If AC power from an external source (shorepower or
generator) is connected and qualifi ed on the inverter’s AC input,
this AC input power will pass through the inverter to power the
AC loads. However, if this AC power is lost, the AC loads will no
longer be powered because the inverter is OFF.
the status LED will
When the inverter is turned ON, it operates either by “Searching”
or “Inverting”, depending on the connected AC loads.
• Searching – When the inverter is fi rst turned ON, the automatic
Search feature is enabled. This feature is provided to conserve
battery power when AC power is not required. In this mode, the
inverter pulses the AC output looking for an AC load (i.e., electrical
appliance). Whenever an AC load (greater than 5 watts) is turned
on, the inverter recognizes the need for power and automatically
starts inverting. When there is no load (or less than 5 watts) detected, the inverter automatically goes back into Search mode to
minimize energy consumption from the battery bank. When the
inverter is “Searching”, the inverter’s green LED fl ashes.
Info: The factory default value for the Search feature is 5
watts. It can be turned off or adjusted from 5 to 50 watts
using the ME-RC50 remote display.
• Inverting –
the inverter output, the MMS Series “inverts” the DC power from
the battery and supplies 120 VAC power to your sub-panel. The
inverter’s green LED fl ashes once every 2 seconds to indicate it
is inverting. The
providing power is directly related to the amount of AC loads that
are connected and the capacity of the battery bank.
The MMS Series features an automatic transfer relay and an internal
battery charger when operating in Standby mode. Standby mode
begins whenever AC power (shorepower or generator) is connected
to the inverter’s AC input. Once the AC voltage and frequency of the
incoming AC power is within the AC input limits, an automatic AC
transfer relay is activated. This transfer relay passes the incoming AC
power through the inverter to power the AC loads on the inverter’s
output. This incoming power is also used to activate a powerful internal battery charger to keep the battery bank charged in case of
a power failure.
Battery charging
– The MMS Series models are equipped with an
active Power Factor Corrected (PFC) multi-stage battery charger. The
PFC feature is used to control the amount of power used to charge
the batteries in order to obtain a power factor as close as possible to
1 (or unity). This causes the battery charger to look like a resistor to
the line (forces the charge current waveshape to mirror the voltage
waveshape). This feature maximizes the real power available from
the AC power source (shorepower or generator), which translates
into less power wasted and a greater charging capability than most
chargers available today.
When an AC power source is connected to an inverter that has a
battery charger, the inverter monitors the AC input for acceptable
voltage. Once the inverter has accepted the AC input, the AC transfer
relay will close and charging will begin. Once charging, the DC voltage
is monitored to determine the charging stage. If the DC voltage is low
(≤12.9 VDC), the charger begins bulk charging. If the DC voltage is
high (>12.9 VDC), the charger skips the initial Bulk/Absorb Charging
stages and goes directly to fl oat charging.
The multi-stage charger can use up to fi ve different charging stages
to help monitor and keep the batteries healthy.
The fi ve stages
include an automatic 4-stage charging process (Bulk, Absorb, Float,
and Full Charge), and a manual Equalization (EQ) charge stage. The
automatic 4-stage charge process provides complete recharging and
monitoring of the batteries without damage due to overcharging (see
Figure 16). The Equalization stage (requires the ME-RC50 remote)
is used to stir up stratifi ed electrolyte and reverse any battery plate
sulfation that might have occurred.
While charging, the unit may go into Charger Back-off protection
which automatically reduces the charge current to the batteries.
This is caused by:
1. The internal temperature is too hot – the charger automatically
reduces the charge rate to maintain temperature; or,
2. The AC input voltage falls < 85 VAC – the charger reduces the
charge current to zero to help stabilize the incoming AC voltage; or
• Bulk Charging: This is the initial stage of charging. While bulk
charging, the charger supplies the battery with constant current.
The charger remains in bulk charge until the absorption charge
voltage is achieved (14.6 VDC)* —as determined by the Battery
Type selection**.
• Absorb Charging: This is the second charging stage and begins
after the bulk voltage has been reached. Absorb charging provides the batteries with a constant voltage and reduces the DC
charging current in order to maintain the absorb voltage setting.
The absorb charging time is 120 minutes—as determined by the
Battery AmpHrs selection**.
• Float Charging: The third charging stage occurs at the end of
the absorb charging time. While fl oat charging (also known as a
maintenance charge), the batteries are kept fully charged and
ready if needed by the inverter. The Float Charging stage reduces
battery gassing, minimizes watering requirements (for fl ooded
batteries), and ensures the batteries are maintained at optimum
capacity. In this stage, the charge voltage is reduced to the fl oat
charge voltage (13.4 VDC)* —as determined by the Battery Type
selection** — which can maintain the batteries indefi nitely.
• Full Charge (Battery Saver™ mode): The fourth stage occurs
after four hours of fl oat charging. The Full Charge stage maintains
the batteries without overcharging, preventing excessive loss of
water in fl ooded batteries or drying out of GEL/AGM batteries. In
this stage, the charger is turned off and begins monitoring the
battery voltage. If the battery voltage drops low (≤12.7 VDC),
the charger will automatically initiate another four hours in fl oat
charge.
* These voltage settings are based on the Battery Temperature Sensor
(BTS) being disconnected, or at a temperature of 77°F (25°C). If the
BTS is installed, these voltage settings will increase if the temperature
around the BTS is below 77°F (25°C), and decrease if the temperature
around the BTS is higher than 77°F (25°C).
** The MMS Series uses changeable settings (see Table 6, Inverter
Default Settings) that are adequate for most installations. However,
if you determine that some of your operating parameters need to
be changed, the ME-RC50 remote control can be purchased to allow
changes to those settings.
Transfer time – While in Standby mode, the AC input is continually
monitored. Whenever AC power falls below the VAC dropout voltage
(80 VAC, default setting), the inverter automatically transfers back
to Inverter mode with minimum interruption to your appliances—as
long as the inverter is turned on. The transfer from Standby mode
to Inverter mode averages approximately 16 milliseconds. While the
MMS Series is not designed as a computer UPS system, this transfer
time is usually fast enough to hold them up. However, the VAC dropout
setting has an effect on the ability of the loads to transfer without
resetting. The lower this setting, the longer the effective transfer
will be and therefore, the higher the probability for the output loads
to reset. This occurs because the incoming AC voltage is allowed to
fall to a level that is so low that when the transfer does occur, the
voltage on the inverter’s output has already fallen to a low enough
level to reset the loads.
The disadvantage of a higher VAC dropout setting is that smaller
generators (or large generators with an unstable output) may nuisance transfer. This commonly happens when powering loads that
are larger than the generator can handle—causing the generator’s
output voltage to constantly fall below the inverter’s input VAC dropout threshold.
Info: You must use the ME-RC50 or ME-ARC50 remote to
adjust the VAC dropout setting—which in turn determines
the VAC dropout threshold.
Info: When switching from Inverter mode to Standby
mode, the inverter waits approximately 15 seconds to
ensure the AC source is stable before transferring.
Operation
3.2 Battery Temperature Sensor Operation
The plug-in Battery Temperature Sensor (BTS) is used to determine
the battery temperature around the batteries. This information allows
the multi-stage battery charger to automatically adjust the battery
charge voltages for optimum charging performance and longer battery life.
When the BTS is installed, if the temperature around the BTS is below
77°F (25°C) the absorb and fl oat charge voltage increases. If the
temperature around the BTS is higher than 77°F (25°C), the absorb
and fl oat charge voltage decreases. See Figure 17
much the charge voltage changes (increases or decreases) as the
temperature reading of the BTS changes. For example, the nominal
absorb charge voltage for a fl ooded battery at 77°F (25°C) is 14.6
VDC. If the battery temperature is 95°F (35°C), the absorb charge
voltage would decrease to 14.3 VDC (14.6 VDC - 0.3 change).
If the temperature sensor is NOT installed, the charge voltages will
not be compensated and the battery will maintain the charge it had
at a temperature of 77°F (25°C). The life of the batteries may be
reduced if they are subjected to large temperature changes when
the BTS is not installed.
to determine how
Info: When the BTS is connected, the battery charger
uses a value of -5mV/°C/Cell from 0-50°C to change the
charge voltage based on temperature.
Temperature Compensation using BTS
12VDC units
+0.75V
+0.6V
+0.45V
+0.3V
+0.15V
No Change
-0.15V
-0.3V
-0.45V
-0.6V
-0.75V
0C
32F5C41F
10C
50F
15C
59F
20C
68F
Change to battery charging voltage
Temperature reading from BTS
25C
77F
30C
86F
no BTS
connected
40C
35C
104F
95F
45C
113F
50C
122F
Figure 17, BTS Temperature to Charge Voltage Change
The inverter is protected against fault conditions, and in normal usage
it will be rare to see any. However, if a condition occurs that is outside
the inverter’s normal operating parameters, then it will shut down
and attempt to protect itself, the battery bank, and your AC loads. If
there is a condition that causes the inverter to shut down, it may be
one of the conditions listed below. Refer also to the Troubleshooting
section to diagnose and clear the fault.
• Low Battery – The inverter will shut off whenever the battery
voltage falls to the Low Battery Cut Out (LBCO) level to protect
the batteries from being over-discharged. After the inverter has
reached the LBCO level and turned off, the inverter will automatically restart after one of the following conditions:
1. AC power is applied and the inverter begins operating as a
battery charger.
2. Battery voltage rises to the Low Battery Cut In (LBCI) level.
The inverter’s status LED turns off when a low battery fault condition occurs. Refer to Table 5 to determine the LBCO and LBCI
levels for your particular inverter model.
• High Battery – In the event the battery voltage approaches the
High Battery Cut Out (HBCO) level, the inverter will automatically
shut down to prevent the inverter from supplying unregulated
AC output voltage. The inverter’s status LED turns off when a
high battery fault condition occurs. The inverter will automatically
restart when the battery falls to the High Battery Cut In (HBCI)
level. Refer to Table 5 to determine the HBCO and HBCI levels
for your particular inverter model.
Info: High battery voltage may be caused by excessive or
unregulated voltage from solar panels or other external
charging sources.
• Overload – During Inverter and Standby operation modes, the
inverter monitors the DC and AC current levels. In the event
of a short-circuit or an overload condition for more than a few
seconds, the inverter will shut down. To start operating after this
fault, the inverter would need to be restarted (turned back on)
after the inverter’s AC loads are reduced/removed.
• Over-temperature – If internal power components begin to
exceed their safe operating temperature level, the inverter will
shut down to protect itself from damage. The inverter’s status
LED turns OFF to indicate the over-temperature fault condition.
The inverter will automatically restart after the units cools down.
• Internal Fault – The inverter continually monitors several inter-
nal components and the processor communications. If a condition
occurs that doesn’t allow proper internal operation, the inverter
will shut down to protect itself and the connected loads. The
inverter will need to be reset to start operating.
Table 5, Inverter Battery Turn On/Off Levels
Inverter Battery
Inverter Model
Turn On/Off
Levels
MMS1012MMS1012-G
HBCO>15.8 VDC>15.8 VDC
HBCI15.5 VDC15.5 VDC
LBCI≥12.5 VDC≥12.5 VDC
LBCO
(one minute
delay)
LBCO
(immediate)
10.0 VDC
(9.0 - 12.2 VDC)
(9.0 - 12.2 VDC)
8.5 VDC8.5 VDC
10.0 VDC
3.4 Inverter Startup
ON/OFF Switch – The inverter can be turned on and off by lightly
pressing and releasing the Power ON/OFF switch on the front of the
inverter. When the inverter is fi rst connected to the batteries, or when
its automatic protection circuit has turned the inverter off, the ON/
OFF switch will need to be pressed to start the unit. Once the inverter
has been turned on, pressing the Power ON/OFF switch alternately
turns the inverter on and off.
WARNING: The Power ON/OFF control switch does not
turn on or off the charger feature. If AC power (utility or
generator) is connected and qualifi ed on the AC input,
this AC power will also be available on the AC output and
is not controlled by the Power ON/OFF switch.
Status LED Indicator – The status indicator is a green LED (Light
Emitting Diode) that provides information on the operational mode
of the inverter. Watch this indicator for at least 10 seconds to determine the inverter’s operational condition from the information below:
Inverter Mode
Off – Indicates the inverter is off; there is no AC power from
the inverter, shorepower, or generator at the inverter’s output
terminals.
Blinks On (once every second) – The inverter is on and is using
energy from the battery. The inverter is either providing full power
to the loads connected to the inverter, or it’s in Search mode and
ready to supply AC power to the connected loads.
There are fi ve fault conditions that will cause the inverter to shut
down: Low Battery, High Battery, Over-temperature, AC Overload,
and Internal faults. If your inverter has shut down, monitor the
status indicator and count the number of blinks that occur every
four seconds to determine the particular reason for the shutdown.
Refer to the Troubleshooting section to help diagnose/clear the
fault condition.
• Blinks on x1 every four seconds – Low Battery fault.
• Blinks on x2 every four seconds – High Battery fault.
• Blinks on x3 every four seconds – Over-temperature fault.
• Blinks on x4 every four seconds – AC Overload fault.
• Blinks on x5 every four seconds – Internal fault.
Charge Mode
The green LED status indicator provides additional information:
• Blinks off every four seconds – The unit is charging the
batteries connected to the inverter. The external AC power
(shorepower or generator) connected to the inverter’s input is
passing through the inverter and is powering the AC loads connected to the inverter’s output.
3.5 Factory Default Settings
The MMS Series inverter/charger uses default settings that are
adequate for most installations (see Table 6). However, you can
adjust these parameters using Magnum’s optional ME-RC50 remote. The settings once programmed are saved in non-volatile
memory and are preserved until changed—even if DC power to
the inverter is lost (the ME-RC50 must always be connected).
The following information can help you determine if you need the
ME-RC50 remote*.
01 Search Watts: This setting allows you to turn off the power-
saving Search mode circuitry and to adjust the power level at which
the inverter will “wake up” and start inverting.
02 Low Battery Cut Out: This setting determines when the inverter
will turn off based on low battery voltage. The inverter turns off
automatically after the battery voltage has been below this setting
for more than one minute. This protects the batteries from overdischarge and the AC loads from unregulated power (brown-outs).
03 Battery AmpHrs: This setting allows you to input the battery
bank size in amp hours. This provides information to the charger
on how long to charge the batteries in the Absorb Charging stage.
* Visit www.magnumenergy.com for more information.
04 Battery Type: This setting identifi es the type of batteries being
used in the system. This provides information to the charger to
determine what voltage level to use to charge the batteries.
05 Charge Rate: T
his setting can be used to turn off the charger, or
limit the amount of current that the charger can use (leaving more
current available to power loads); or, to ensure small battery banks
are not overheated because of a charge rate that is too high.
06 VAC Dropout: Sets the minimum AC voltage that must be pres-
ent on the AC input before the unit transfers from Standby mode to
Inverter mode. This protects the AC loads from utility outages and
brown-outs.
The ME-RC50 remote also provides the following features:
• allows you to enable an equalize charge for certain battery types
• displays the inverter/charger’s operating status
The MMS Series inverter/charger is designed to provide you with years
of trouble-free service. Even though there are no user-serviceable
parts, it is recommended that every 6 months you perform the following maintenance steps to ensure optimum performance and extend
the life of your batteries.
WARNING: Prior to performing these checks, switch both
the AC and DC circuits OFF.
• Visually inspect the batteries for cracks, leaks, or swelling –
replace if necessary.
• Use baking soda to clean and remove any electrolyte spills or
buildups.
• Check and tighten all battery hold-down clamps.
• Clean and tighten (10 to 12 ft-lbs) all DC terminals
(battery and inverter) and connecting cables.
• Check/fi ll battery water levels (liquid lead acid batteries only).
• Check individual battery voltages (replace those that vary
more than 0.3 VDC from each other).
• Check all cable runs for signs of chafi ng – replace if necessary.
• Check the inverter’s cooling vents – clean as necessary.
4.2 RV/Marine Off-Season Storage
When placing your coach or boat into seasonal storage, it is recommended that you perform the following to ensure the system is
properly shut down (or properly confi gured for seasonal storage).
This is especially important for maintaining the batteries.
• Perform the recommended maintenance steps noted above.
• Fully charge the batteries.
• Connect shorepower (if available) and verify that the breaker to
the battery charger is switched ON.
The MMS Series inverter/charger is a fairly simple device to troubleshoot. There are only two active circuits (AC and DC), as well as a
charging circuit. The following chart is designed to help you quickly
pinpoint the most common inverter and charger faults.
Table 7, Troubleshooting Guide
SymptomPossible CauseRecommended Solution
Low Battery Voltage
(the status indicator
blinks x1 every 4 secs)
The battery voltage level has dropped
below the Low Battery Cut Out
(LBCO) set-point for more than one
minute (10.0 VDC = LBCO default
setting).
Battery voltage is too low. Check fuses/
circuit-breakers and cable connections.
Check battery voltage at the inverter's
terminals. Your batteries may need
to be charged, this fault condition will
automatically clear when the battery
voltage exceeds 12.5 VDC.
High Battery Voltage
(the status indicator
blinks x2 every 4 secs)
Over-temperature
condition
(the status indicator
blinks x3 every 4 secs)
AC Overload
(the status indicator
blinks x4 every 4 secs)
Internal fault
(the status indicator
blinks x5 every 4 secs)
Inverter's status light
is off.
AC input won't connect
(AC IN on remote
blinks)
Appliances turn off and
on; or there is low AC
output power.
Inverter AC output
voltage is too low or too
high when using an AC
voltmeter.
While charging, the DC
charge voltage is higher
or lower than expected.
The battery voltage is above 15.5
VDC. The inverter automatically
resets and resumes operation when
the battery voltage drops below 15.5
VDC.
The internal temperature of the
inverter has risen above acceptable
limits; caused by loads too great for
the inverter to operate continuously,
or by lack of ventilation to the
inverter. When the unit has cooled, it
will automatically reset and resume
operation.
The inverter has turned off because
the connected loads are larger than
the inverters output capacity or the
output wires are shorted.
This fault occurs when an internal
fault is detected.
Inverter is switched OFF or there is
no DC voltage (battery) connected to
inverter.
The incoming AC voltage will not
be accepted if it is below the VAC
Dropout setting (80VAC = VAC
Dropout default setting).
Loose AC output connections. Tighten AC output connections.
Loose / corroded battery cables. Clean and tighten all cables.
Low batteries.Recharge or replace batteries.
Wrong type of voltmeter used (will
display 90 VAC to 130 VAC depending
on the battery voltage).
If the Battery Temperature Sensor is
installed, it will increase or decrease
the DC voltage level depending on
temperature around the battery
sensor.
This condition usually occurs only when
an additional charging source (alternator,
solar panels or other external charging
sources) is used to charge the battery
bank. Reduce or turn off any other
charger to the inverter batteries to allow
the voltage level to drop.
Reduce the number of electrical loads
that you are operating, this will avoid a
repeat Over-temp shutdown if the cause
was too many loads for the ambient
conditions.
Check ventilation around the inverter,
ensure cool air is available to pass-thru
the inverter.
Reduce the AC loads connected to the
inverter or remove all AC output wiring
and restart the inverter.
To clear this fault, an inverter reset
is required. Remove DC power to the
inverter or press and hold down the
power switch on the inverter for 15
seconds (until the green Status LED
comes on). If this fault does not clear, the
unit will need to be serviced.
Switch the inverter ON. Connect a battery
with correct voltage to the inverter.
Check the incoming AC voltage to the
input of the inverter, ensure it is present
and above the VAC dropout level.
Most meters are made to read Average
AC voltage. The AC output of the MM is a
ed" waveform which requires using
"modifi
a “true” RMS voltmeter to correctly read
the output voltage.
Input battery voltage9 to 17 VDC
Nominal AC output voltage120 VAC +/- 5%
Output frequency and accuracy60 Hz +/- 0.1 Hz
1msec surge current 38 AAC
100msec surge current21 AAC
5 sec surge power (real watts)1750
30 sec surge power (real watts)1600
5 min surge power (real watts)1200
30 min surge power (real watts)1050
Continuous power output at 25° C1000 VA
Max. continuous input current133 ADC
Inverter effi ciency (peak)0.87
Transfer time16 msecs
AC transfer capability15A
Search mode (typical)5 watts
No load (120 VAC output, typical)19 watts
WaveformPure Sine Wave
Charger Specifi cations
Continuous output at 25° C50 ADC
Charger effi ciency84%
Power factor> 0.95
Input current at rated output7 AAC
Battery temp compensationYes, 15 ft Battery Temp Sensor standard
General Features and Capabilities
Protection circuitryLow/High Battery, Over-temp & Overload
Corrosion protectionPCB’s conformal coated, powder coated chassis
AC OutputHardwireGFCI outlet
AC InputHardwire3 ft cord
Output circuit breaker15A
Input circuit breaker20 AAC
Internal coolingYes, 0 to 59 cfm variable speed
Optional remotes availableMM-RC or ME-RC50
UL listing
Environmental Specifi cations
Operating temperature-20°C to +60°C (-4°F to 140°F)
Non-operating temperature-40°C to +70°C (-40°F to 158°F)
Operating humidity0 to 95% RH non-condensing
Physical Specifi cations
Dimensions (L x W x H)16.6”x 8.4”x 4.7” (42cm x 21cm x 12cm)
MountingShelf or wall (no vents facing downward)
Weight23 lbs. (10.4 kg)
Shipping weight25 lbs. (11.3 kg)
Specifi cations @ 25° C - Subject to change without notice
The following Magnum Energy components are available for use
with the MMS Series inverter/charger. Some of these items are required depending upon the intended use of the inverter.
Smart Battery Combiner
The Smart Battery Combiner (ME-SBC
charge a second battery using a portion of the current that is charging
the main battery. The ME-SBC eliminates a signifi cant voltage drop,
and provides automatic turn-on and turn-off based on adjustable
voltage set-points. This allows different batteries to be charged from
a single charging source, and prevents overcharging/undercharging.
Basic Remote Control
The ME-RC50 Remote Control panel is simple to use; an LCD screen
and “at a glance” LEDs display complete inverter/charger status. Soft
keys provide simple access to menus and a rotary encoder knob allows you to scroll through and select a wide range of settings.
Auto Generator Start Controller
The ME-AGS-N Automatic Generator Start controller (Network version) is designed to automatically start your generator based on low
battery condition or high temperature. It works
volt battery banks and includes a 4-position DIP (Dual In-line Package) switch which provides the ability to change the relay timing
confi gurations to allow compatibility with a wider range of generators.
TM
) is designed to monitor and
with 12, 24, and 48
Battery Monitor Kit
The ME-BMK Battery Monitor Kit is a single battery bank amp-hour
meter
that monitors the condition of the battery and provides information to let you know how much energy you have available and to
plan your electrical usage to ensure the battery is not being overdischarged. The ME-BMK-NS version does not include
a DC shunt—
order the ME-BMK to receive a 500A/50mv DC shunt.
Fuse Block/Fuses
The Magnum Fuse/Fuse-blocks are used to protect the battery bank,
inverter, and cables from damage caused by DC short circuits and
overloads. They include a slow-blow fuse with mounting block and
protective cover. The 125 and 200-amp models use an ANL type fuse
and the 300 and 400-amp models use a Class-T fuse.
DC Load Disconnect
The MM-DCLD (DC Load Disconnect) pigtail adapter is designed to
provide a means to DISABLE the inverter function when a 12-volt
DC signal is removed.
Ignition Switch Activate
The MM-ISA (Ignition Switch Activate) is a pigtail adapter is designed
to automatically ENABLE the inverter function when a 12-volt DC
signal is supplied.
The size of the battery bank determines how long the inverter can
power the AC loads without recharging. The larger the battery bank,
the longer the run time. Size your battery bank to the system’s AC
load requirements and the length of time required to run the load
from the batteries. In general, the battery bank should not be discharged more than 50%.
Battery Types
Batteries are available in different sizes, amp-hour ratings, voltage,
and chemistries; they also come in liquid or gel, vented or nonvented, etc. They are also available for starting applications (such
as an automobile starting battery) and deep discharge applications.
Only the deep cycle types are recommended for inverter applications.
Choose the batteries best suited for the inverter installation and cost.
Use only the same battery type for all batteries in the bank. For best
performance, all batteries should be from the same lot and date.
This information is usually printed on a label located on the battery.
Battery Confi guration
The battery bank must be wired to match the inverter’s DC input voltage specifi cations. In addition, the batteries can be wired to provide
additional run time. The various wiring confi gurations are:
Series Wiring
bank output voltage. A series connection combines each battery in a
string until the voltage matches the inverter’s DC requirement. Even
though there are multiple batteries, the capacity remains the same.
In the example below (Figure 19), two 6 VDC/200 AHr batteries are
combined into a single string—resulting in a 12 VDC/200 AHr bank.
– Wiring batteries in a series increases the total battery
Parallel Wiring – Wiring the batteries in parallel increases the total
run time the batteries can operate the AC loads. A parallel connection
combines overall battery capacity by the number of batteries in the
string. Even though there are multiple batteries, the voltage remains
the same. In the example below (Figure 20), four 12 VDC/100 AHr
batteries are combined into a single 12 VDC/400 AHr battery bank.
Figure 20, Parallel Battery Wiring
Series-Parallel Wiring – A series-parallel confi guration increases
both voltage (to match the inverter’s DC requirements) and capacity
(to increase run time for operating the loads) using smaller, lowervoltage batteries. In the example below (Figure 21), four 6 VDC/200
AHr batteries are combined into two strings resulting in a 12 VDC/400
AHr battery bank.
Magnum Energy, Inc., warrants this MMS Series inverter/charger
to be free from defects in material and workmanship that result in
product failure during normal usage, according to the following terms
and conditions:
1. The limited warranty for the product extends for 24 months
beginning from the product’s original date of purchase.
2. This warranty extends to the original purchaser of the product
and is not assignable or transferable to any subsequent purchaser.
3. During the limited warranty period, Magnum will repair or replace
(with factory new or remanufactured replacement items) at Magnum’s
option any defective parts, or any parts that will not properly operate
for their intended use—if such repair or replacement is needed
because of product malfunction or failure during normal usage. The
limited warranty does not cover defects in appearance (cosmetic or
decorative), or any structural or non-operative parts. Magnum’s limit
of liability under the limited warranty shall be the actual cash value
of the product at the time the original purchaser returns the product
for repair, determined by the price paid by the original purchaser.
Magnum shall not be liable for any other losses or damages.
4. Upon request from Magnum, the original purchaser must prove the
product’s original date of purchase by a dated bill of sale, itemized
receipt.
5. The original purchaser shall return the product prepaid to Magnum
Energy in Everett, WA. After the completion of service under this
limited warranty, Magnum will return the product prepaid to the
original purchaser via a Magnum selected non-expedited surface
freight within the contiguous United States and Canada; this excludes
Alaska and Hawaii.
6. If Magnum repairs or replaces a product, its warranty continues for
the remaining portion of the original warranty period or 90 days from
the date of the return shipment to the original purchaser, whichever
is greater. All replaced products and parts removed from repaired
products become the property of Magnum Energy.
7. This limited warranty is voided if:
• the product has been modifi ed without authorization
• the serial number has been altered or removed
• the product has been damaged through abuse, neglect
accident, high voltage, or corrosion
• the product was not installed and operated according to the
owner’s manual
OBTAIN A RETURN MATERIAL AUTHORIZATION (RMA) NUMBER