Magnum Energy ME-AGS-N User Manual

ME-AGS-N
Automatic Generator Start for Network Versions
Owner’s Manual
Version 5.0
For use with the following remote controls: ME-RC Revisions 1.5 – 2.612 ME-ARC Revisions 2.0 – 2.4 ME-RTR Revisions 2.1 – 2.2
Disclaimer of Liability
Since the use of this manual and the conditions or methods of installation, operation, use and maintenance of the ME-AGS-N (Auto Generator Start ­Network) is beyond the control of Magnum Energy, Inc., this company does not assume responsibility and expressly disclaims liability for loss, damage or expense, whether direct, indirect, consequential or incidental, arising out of or anyway connected with such installation, operation, use, or maintenance.
Note as well that while every precaution has been taken to ensure the accuracy of the contents of this manual, the specifi cations and product functionality may change without notice. Magnum Energy, Inc. assumes no responsibility for errors or omissions.
Restrictions on Use
The ME-AGS-N may only be used in life-support devices or systems with the express written approval of Magnum Energy, Inc. Failure of the ME-AGS-N can reasonably be expected to cause the failure of that life-support device or system, or to affect the safety or effectiveness of that device or system. If the ME-AGS-N fails, it is reasonable to assume that the health of the user or other persons may be endangered.
Copyright Notice
Copyright © 2012 by Magnum Energy, Inc. All rights reserved. Permission to copy, distribute, and/or modify this document is prohibited without express written permission by Magnum Energy, Inc.
Document Information
Description – ME-AGS-N Owner’s Manual Part Number and Revision – 64-0039 Rev A Date Published – March 2012
This manual is printed without color for cost savings. However, this en­tire manual is available for download under the Document Library tab at
www.magnumenergy.com with many of the diagrams available in color.
Contact Information
Magnum Energy, Inc. 2211 West Casino Rd. Everett, WA 98204 Phone: 425-353-8833 Fax: 425-353-8390 Web:
www.magnumenergy.com
Statement of Appreciation
From all of us at Magnum Energy – Thank you for purchasing this AGS module (ME-AGS-N). We understand that you have many purchasing options in the marketplace,
and are pleased that you have decided on a Magnum Energy product. This AGS module was proudly assembled and tested in the United States in our Everett, Washington, facility.
At Magnum we are committed to providing you with quality products and services, and hope that your experience with us is pleasant and professional.
Magnum Energy® is a registered trademark of Magnum Energy, Inc.
© 2012 Magnum Energy, Inc. i
Important Safety Instructions
This manual contains safety instructions that must be followed during the installation and operation of this product. Read all instructions and safety information contained in this manual before installing or using this product.
Safety Symbols
To reduce the risk of electrical shock, fi re, or other safety hazard, the fol- lowing safety symbols have been placed throughout this manual to indicate dangerous and important safety instructions.
WARNING: Symbol indicates that failure to take a specifi ed action
could result in physical harm to the user.
CAUTION: Symbol indicates that failure to take a specifi ed action
could result in damage to the equipment.
Info: Symbol indicates information that emphasizes or supplements
important points of the main text.
Remedy: Symbol provides possible solutions for related issues.
Product Safety Alerts
WARNING:
All electrical work must be performed in accordance with local, state, and federal electrical codes.
This product is designed for indoor/compartment installation – do not expose to rain, snow, moisture, or liquids of any type.
Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
WARNING: Severe personal injury, death, and equipment dam-
age can result from operating the generator in a garage, building, or confi ned space. The generator produces dangerous fumes when it is running. If the generator is installed in an RV, disable the AGS system to prevent the generator from starting when the RV is in a garage, building, or a confi ned space.
WARNING: ENGINE EXHAUST GASSES CAN BE DEADLY. Install a reli-
able carbon monoxide alarm in your vehicle, building, or home before starting a generator or enabling the AGS. All engine exhaust contains carbon monoxide: an odorless, colorless gas that can cause severe personal injury or death. Symptoms of CO poisoning include:
• Dizziness, headache or throbbing temples
• Weakness or muscular twitching
• Sleepiness or confusion
• Nausea or vomiting
If you experience any of these symptoms, get to fresh air immediately. If symptoms persist, seek medical attention. Shut down the generator and do not operate until the unit is inspected and repaired.
WARNING: With an Automatic Generator Starting system installed;
exhaust CO, electrical shock, and moving parts hazards are pos­sible due to unexpected engine-generator starting. Disconnect the engine-generator starting battery cables or the AGS connection to the engine-generator before working on the generator or any other electrical system powered by the generator.
ii © 2012 Magnum Energy, Inc.
List of Contents
1.0 Introduction .............................................................................1
1.1 ME-AGS-N Module ..................................................................... 1
1.2 ME-AGS-N System Requirements ................................................ 2
1.3 ME-AGS-N Components ............................................................. 2
2.0 Installation ...............................................................................4
2.1 Installation Requirements ..........................................................4
2.2 Required Materials and Tools ......................................................6
2.3 Mounting Procedure ..................................................................6
2.4 Connecting the Cables ............................................................... 7
2.5 ME-AGS-N Terminal Block Wiring Connections ............................. 10
2.6 Common Generator Wiring Diagrams ......................................... 15
2.7 Warning Label ........................................................................ 15
3.0 ME-AGS-N Module Setup .........................................................19
3.1 Confi guring the Internal ME-AGS-N Settings ............................... 19
4.0 ME-AGS-N Module Functional Tests .........................................21
4.1 Power-up Test ........................................................................ 21
4.2 Generator Wiring Test .............................................................. 21
5.0 ME-AGS-N Module Operation ...................................................22
5.1 ME-AGS-N Module TEST Pushbutton .......................................... 22
5.2 ME-AGS-N Module LED Indicators .............................................. 22
6.0 ME-AGS-N Module Troubleshooting ......................................... 23
6.1 Using the ME-AGS-N’s LED Indicators ........................................ 23
6.2 Generator Starting/Running Troubleshooting ............................... 24
7.0 Using a Remote with the ME-AGS-N ........................................26
7.1 AGS to Inverter Compatibility ................................................... 26
7.2 Software Differences Between AGS Revisions .............................. 27
8.0 Using the ME-RC Remote ........................................................28
8.1 ME-AGS-N Setup using the ME-RC ............................................. 28
8.2 ME-AGS-N Functional Tests using the ME-RC ............................... 33
8.3 ME-AGS-N Operation/Monitoring using the ME-RC ....................... 34
8.4 Enabling the ME-AGS-N using the ME-RC ................................... 36
8.5 Starting and Stopping the Generator using the ME-RC ................. 36
8.6 ME-AGS-N Menu Map using the ME-RC ....................................... 37
9.0 Using the ME-ARC Remote ......................................................39
9.1 ME-AGS-N Setup using the ME-ARC ........................................... 39
9.2 ME-AGS-N Functional Tests using the ME-ARC ............................. 52
9.3 ME-AGS-N Operation/Monitoring using the ME-ARC...................... 53
9.4 Enabling the ME-AGS-N using the ME-ARC .................................. 56
9.5 Starting and Stopping the Generator using the ME-ARC ................ 56
9.6 ME-AGS-N Menu Map using the ME-ARC ..................................... 58
© 2012 Magnum Energy, Inc. iii
List of Contents (cont.)
10.0 Using the ME-RTR Router ......................................................61
10.1 ME-AGS-N Setup using the ME-RTR ......................................... 61
10.2 ME-AGS-N Functional Tests using the ME-RTR ........................... 73
10.3 ME-AGS-N Operation/Monitoring using the ME-RTR .................... 75
10.4 Enabling the ME-AGS-N using the ME-RTR ................................ 78
10.5 Starting and Stopping the Generator using the ME-RTR .............. 78
10.6 ME-AGS-N Menu Map using the ME-RTR ................................... 80
11.0 ME-AGS-N Remote Status Messages ..................................... 84
11.1 AGS Remote Operational Statuses ........................................... 84
11.2 AGS Remote Start Statuses .................................................... 86
11.3 AGS Remote Fault Statuses .................................................... 87
11.4 General Notes ....................................................................... 88
12.0 ME-AGS-N Remote Troubleshooting ...................................... 89
12.1 AGS Fault Message Screens for Magnum Remotes ..................... 89
12.2 Resolving Operational Statuses ............................................... 90
12.3 ME-AGS-N Faults using your Remote ........................................ 90
13.0 Appendix ..............................................................................94
13.1 Other Accessories and Equipment ............................................ 94
14.0 Limited Warranty ..................................................................95
14.1 How to Receive Repair Service ................................................ 96
List of Tables
Table 3-1, Gen Type Settings ............................................................. 20
Table 6-1, ME-AGS-N Module Troubleshooting Guide ............................. 23
Table 7-1, AGS Compatibility Matrix Chart ........................................... 26
Table 7-2, AGS Revision Differences ................................................... 27
Table 8-1, ME-RC Autostart/Autostop Matrix ........................................ 28
Table 8-2, Software Differences Between ME-RC Revisions .................... 29
Table 8-3, Battery AmpHrs Capacity to Suggested Gen Run Time ........... 30
Table 9-1, ME-ARC Autostart/Autostop Matrix ...................................... 40
Table 9-2, Software Differences Between ME-ARC Revisions ............. 40-41
Table 10-1, ME-RTR Autostart/Autostop Matrix .................................... 62
Table 11-1, AGS Remote Operational Statuses ................................ 84-85
Table 11-2, AGS Remote Start Statuses .............................................. 86
Table 11-3, AGS Remote Fault Statuses .............................................. 87
iv © 2012 Magnum Energy, Inc.
List of Figures
Figure 1-1, Components of the ME-AGS-N Module .................................. 3
Figure 1-2, Remote Temp Sensor Cable ................................................ 3
Figure 2-1, ME-AGS-N System Diagram ................................................ 5
Figure 2-2, ME-AGS-N Dimensions ....................................................... 6
Figure 2-3, Remote Temp Sensor Connection ........................................ 7
Figure 2-4, Network Communication Cable ............................................ 7
Figure 2-5, Connecting the AGS to a Magnum Inverter (Small) ................ 8
Figure 2-6, Connecting the AGS to a Magnum Inverter (Large) ................ 8
Figure 2-7, Multiple Network Devices – Star Configuration ...................... 9
Figure 2-8, Multiple Network Devices – Daisy Chain Configuration ............ 9
Figure 2-9, Connected Devices at the Same Potential ........................... 10
Figure 2-10, Generator Run Sense Options.......................................... 12
Figure 2-11, Wiring to the ME-AGS-N Module’s Terminal Block ............... 14
Figure 2-12,
Warning Label ............................................................... 15
Figure 2-13, Two-wire Control Type Generators .................................... 16
Figure 2-14, Three-wire Momentary Control Type Generators ................ 17
Figure 2-15, Three-wire Maintain Control Type Generators .................... 18
Figure 3-1, Inside the ME-AGS-N Module ............................................ 19
Figure 3-2, DC Voltage Settings ......................................................... 19
Figure 5-1, ME-AGS-N Front Panel Controls and Indicators .................... 22
Figure 8-1, ME-RC’s AGS Configuration Access Buttons ......................... 28
Figure 8-2, AGS Menu Maps in ME-RC Remote (Section 1) .................... 37
Figure 8-3, AGS Menu Maps in ME-RC Remote (Section 2) .................... 38
Figure 9-1, ME-ARC’s AGS Configuration Access Buttons ....................... 39
Figure 9-2, AGS Menu Maps in ME-ARC Remote (Section 1) ................... 58
Figure 9-3, AGS Menu Maps in ME-ARC Remote (Section 2) ................... 59
Figure 9-4, AGS Menu Maps in ME-ARC Remote (Section 3) ................... 60
Figure 10-1, ME-RTR’s AGS Configuration Access Buttons ...................... 61
Figure 10-2, AGS Menu Maps in ME-RTR Router (Section 1) .................. 80
Figure 10-3, AGS Menu Maps in ME-RTR Router (Section 2) .................. 81
Figure 10-4, AGS Menu Maps in ME-RTR Router (Section 3) .................. 82
Figure 10-5, AGS Menu Maps in ME-RTR Router (Section 4) .................. 83
Figure 12-1, ME-AGS-N Fault Message – RC and ARC Screens ............... 89
Figure 12-2, ME-AGS-N Fault Message – RTR Screens ........................... 89
© 2012 Magnum Energy, Inc. v

1.0 Introduction

1.0 Introduction
Congratulations on purchasing your ME-AGS-N. The ME-AGS-N is the ‘net­work’ version of Magnum Energy’s Automatic Generator Start (AGS) mod­ules. This AGS is set up and operated via a Magnum Energy inverter and remote control (i.e., ME-RC, ME-ARC, or ME-RTR). Using the AGS, your gen­erator can automatically start and stop based on the following conditions:
• Battery Voltage: Continuously monitors battery voltage. Autostarts
the generator when the battery voltage falls to a certain level, and autostops the generator when the battery voltage either rises to a high­er level or goes into the Float Charge stage – depending on the remote control.
Time of Day: Starts and stops the generator daily based on selectable
start/stop times (determined by the time on the remote control’s clock).
Inverter Load Amps: Starts/stops the generator based on the loads
powered by the inverter (assists inverter with larger loads).
Note: Only applicable to MS-PAE and MS-PE Series Magnum inverters.
• Rising Temperature: Continuously monitors the temperature of the
surrounding area and automatically starts the generator whenever pow­er is needed to run an air conditioner or to cool down an area.
• Battery SOC: Monitors your battery system and automatically starts
the generator when the battery requires charging – based on the actual SOC (State of Charge) of the battery.
Note: Battery SOC is a more accurate method than using battery volt-
age as a criteria to determine when a battery requires charging.
Info: The SOC autostart/autostop feature requires the optional ME-BMK
or ME-BMK-NS (Battery Monitor Kit) accessory to accurately determine the battery’s SOC.

1.1 ME-AGS-N Module

Info: This manual is for the ME-AGS-N with a software revision of
5.0 or higher. Refer to your Magnum remote control manual or the remote control’s specifi c section in this manual for assistance in determining the AGS’s software revision#.
Info: If you require an AGS module, but are not using a Magnum in­verter/charger, use the ME-AGS-S (AGS – Standalone version).
The AGS is compatible with most AC or DC generators with either 2-wire or 3-wire start controls, such as: Onan, Generac, Martin, Kohler, Honda, Yamaha, and many others. A list of generators that have been successfully used with the AGS (and their respective wiring diagrams) can be found at:
http://www.magnumenergy.com/service/genwiringdiagrams.htm
The AGS is equipped with the following operational features:
Allows manual on and off control (ME-ARC and ME-RTR only) and auto­matic control of generator
Compatible with 12, 24, or 48-volt systems
Easily adjustable settings using the inverter’s remote control menus (i.e., ME-RC, ME-ARC, or ME-RTR)
Quiet Time setting to prevent generator operation during nighttime hours
1 © 2012 Magnum Energy, Inc.
1.0 Introduction
TEST button immediately confi rms if installation wiring correct
Removable 8-port terminal block for easy wiring and powering down
Front panel LED indicators for gen start/stop status and gen fault

1.2 ME-AGS-N System Requirements

The AGS requires several other components to operate correctly.
Automatic Start Generator – The generator should have automatic starting
capability. The generator must have start and stop controls [i.e., an electric starter and electric choke (for gasoline units)], and the safety sensors to be able to start and stop automatically. These safety items include: low oil pressure, high temperature, engine start over-crank, over/under frequency (speed), low coolant level, etc. The generator should also supply a “generator run signal”, which the AGS uses to detect whether the generator is running. The generator run signal must be from 10 to 40 volts DC, and can be provided from a generator hour meter signal or a switched B+ terminal.
Info: A generator run signal is not required when using Gen Type:
2-Wire Standby Mode and an AGS with a revision of 5.2 or higher.
Remote Control – A separate remote control (i.e., ME-RC, ME-ARC, or ME-
RTR) is required to confi gure the AGS and to monitor generator starting and stopping activity. Some of the more advanced generator start/stop features are not available on the standard ME-RC and require the ME-ARC or ME-RTR advanced controllers. Refer to your Magnum remote control manual or the remote control’s specifi c section in this manual to determine your available AGS autostart and autostop features.
Magnum Inverter – A Magnum inverter is required to communicate net-
work information from the Magnum remote control to the AGS. The inverter must also have the internal software to work with the remote control and to allow the desired AGS feature. See Section 7.1 for help in determining your inverter’s compatibility level.

1.3 ME-AGS-N Components

The ME-AGS-N is shipped with the following:
• AGS module • Network Communications cable
• Remote Temp Sensor cable • ME-AGS-N Owner’s Manual
• Warning label • Mounting screws (x4)
1.3.1 ME-AGS-N Features
The AGS module provides the generator’s wiring connections and the following components (refer to Figure 1-1):
STATUS Indicator – a bi-color (green or red) LED indicator that
1
illuminates to provide information on the AGS’s operation.
TEST Button – a momentary pushbutton that allows the AGS
system to be tested for correct wiring and generator start/stop
2
operation.
Wiring Terminal Block – an 8-port friction- t connector that powers
3
the AGS and connects the generator’s start/stop and run sense wires.
Mounting Flange – used to secure the AGS to a shelf or a wall. Four
black oxide #8 x 3/4 Phillips drive, Pan head screws are provided
4
to mount the AGS.
© 2012 Magnum Energy, Inc. 2
1.0 Introduction
READY Indicator – a green LED indicator that illuminates to signal
5
that the AGS is powered (blinks if the optional temp sensor is not connected).
NETWORK Connection Port (green label) – a RJ14 port (6P4C
- 6 position, 4-contact female connection) which provides the
6
connection point for the network communication cable.
REMOTE Connection Port (purple label) – a RJ14 port (6P4C - 6
position, 4-contact female connection) that provides the connection
7
point for the remote temperature sensor cable (see Figure 1-2).
Internal Access Screws – four #6-32 x 3/8 Phillips screws that
8
must be removed to access the DC Input Jumper and the 4-position DIP Switch.
4
1
5
2
8
3
6 7
Figure 1-1, Components of the ME-AGS-N Module
Temperature Sensor
Figure 1-2, Remote Temp Sensor Cable (60 ft.)
3 © 2012 Magnum Energy, Inc.
2.0 Installation

2.0 Installation

Installing the AGS is a simple process. Before installing, read this entire section so you can thoroughly plan the details to ensure the overall system requirements are accomplished. To assist you in planning and designing your installation, review the basic system diagram shown in Figure 2-1.
WARNING: The AGS is not an ignition-protection rated device and
should not be installed in any location that requires ignition-protected equipment. To prevent fi re or explosion, do not install the AGS module in any area with extremely fl ammable liquids like gasoline or pro- pane, or in an area that contains connections between components of a fuel system.
CAUTION: Installations should be performed by qualifi ed personnel,
such as a licensed or certifi ed electrician. It is the installer’s respon- sibility to determine which safety codes apply and to ensure that all applicable installation requirements are followed. Applicable installa­tion codes vary depending on the specifi c location and application.
CAUTION: Review the “Important Safety Instructions” in the front
of this manual before any installation.

2.1 Installation Requirements

Review the following requirements prior to performing the installation:
For the AGS to automatically start and stop the generator properly, the
generator must include an electric start and an automatic choke. To pre­vent generator damage and to ensure reliable operation, use generator models designed for unattended operation. These models should also be equipped with remote operation connections and have protective systems that shut down the generator when low oil pressure, over-temperature, starter lockout, or over-crank conditions occur.
• The AGS is connected to a Magnum inverter by a 10-foot communications
cable. Before installing the AGS and connecting any wires, fi rst determine:
1) the communications cable route throughout the home or vehicle/boat from the AGS module to the inverter, 2) the start/stop signal wire route from the AGS module to the generator, and 3) the wire route from the AGS module to the monitored battery bank.
Always check for existing electrical, plumbing, or other areas of potential
damage BEFORE drilling or cutting into walls.
If installing the AGS in a boat, RV or truck, ensure the conductors pass-
ing through walls, bulkheads, or other structural members are protected to minimize insulation damage such as chafi ng, which can be caused by vibration or constant rubbing.
Do not mount the AGS module in a closed battery compartment or in
an area where water (any liquid) can enter the AGS and cause shorting or corrosion.
The AGS, if possible, should be wired so as not to interfere with the
manual start/stop switches on your generator, or with your air conditioner controls if the high temp start feature is used to power the air conditioner.
© 2012 Magnum Energy, Inc. 4
2.0 Installation
Magnum remote
PWR
FAULT
Inverting
CHG INV
ON/OFF
CHARGER
ON/OFF
DC 12.6V 5A
AGS METER SETUPSHOREINVERTER
SELECT
TECH
ME-AGS-N
* Normally the inverter’s
Battery voltage
(12v/24v/48v)
battery bank
Magnum inverter
+
Monitored
Battery
Bank*
Battery bank’s
negative and
generator battery’s
negative must be
connected
Generator
Autostart Generator
start/stop
wiring
Generator run signal
Gen
Battery
-
+
+
Figure 2-1, ME-AGS-N System Diagram
5 © 2012 Magnum Energy, Inc.
2.0 Installation
5 8
3
7 8
4
3
4
2
1 4
4
3 8
3 8
5
1 4
3
3 8
2
3
16
(31.8 mm)
1 4
1
(82.6 mm)
(92.8 mm)
(136.6 mm)
(108 mm)
(123.9 mm)
(9.5 mm)
(50.8 mm)
(69.9 mm)
(9.5 mm)
(4.8 mm)

2.2 Required Materials and Tools (not included)

To properly install the AGS module you will need to supply the following:
Required Materials
• 16 to 12 AWG wire for connecting the AGS to the generator start/stop circuit and to the battery bank
• In-line fuse holders (with a 5-amp DC fuse)
Required Tools
• Phillips screwdriver (#2)
• Flat-blade screwdrivers (1/4” and 1/8” blades)
• DC voltmeter
• Cut-out tool (knife/saw)
• Drill bits (7/64” & 1/8”)
• Drill
• Wire stripper
• Pencil

2.3 Mounting Procedure

Select an inside mounting location that is clean, dry, and protected from extreme temperatures
Info: The AGS module can be mounted in any direction. However,
be sure to allow ample room to the NETWORK and REMOTE ports
1. Remove the 8-port terminal block from the module (Figure 1-1, Item
3). The terminal block is friction-fi t, remove by pulling it straight out.
Note: Do not plug the terminal block back into the AGS module until
the installation is complete and you are ready to perform the functional tests (per directions in Section 4.0).
2. Mount the AGS module using the supplied #8 x 3/4” screws (x4).
. Refer to Figure 2-2 for the AGS module’s dimensions.
access the 8-port terminal block, and
.
Figure 2-2, ME-AGS-N Dimensions
© 2012 Magnum Energy, Inc. 6
2.0 Installation
12
3
4
12
3
4
TAB
TAB
same color
same
color
ME-AGS-N
Remote
Temp Sensor
cable

2.4 Connecting the Cables

The AGS comes with two cables: the temp sensor cable is required if using the temperature autostart feature; the network communication cable is required for communicating with the inverter/remote.
2.4.1 Connecting the Remote Temp Sensor Cable
If using the temperature autostart feature, connect the plug-in end of the temp sensor cable to the REMOTE (purple) port of the AGS module, and then place the other end (with sensor) in the area you wish to monitor (see Figure 2-3). The temp sensor cable is 60 feet long.
If you are not using the temperature autostart feature, the temp sensor cable does not need to be connected.
Note: The AGS’s READY light will blink if the temp sensor cable is not
connected – this is normal.
Figure 2-3, Remote Temp Sensor Connection
2.4.2 Connecting the Network Communication Cable
The network communication cable is a 10-foot, 4-conductor, fl at, telephony standard with 6P4C (6-position/4-conductor) connectors on each end. When the 6P4C connectors are held side by side with both of the connector tabs facing the same way, the color of the conductors in each connector is the opposite from top to bottom (as shown in Figure 2-4).
Note: The network communication cable can be extended up to a length of
200 feet without data degradation.
4-conductor
telephone-type
opposite colors
from top to
bottom (tabs
facing toward you)
Figure 2-4, Network Communication Cable
7 © 2012 Magnum Energy, Inc.
2.0 Installation
Connecting the AGS to a Magnum inverter: Connect one end of the
communication cable to the AGS’s RJ14 NETWORK (green) port, and then:
• Small inverter (MM/MMS Series) – connect the other end of the
communication cable to a phone splitter, and then connect the splitter to the REMOTE (blue) port on the small Magnum inverter (see Figure 2-5); or,
• Large inverter (ME, RD, MS, MS-PAE Series) – connect the other
end of the communication cable to the RJ14 Network port (green) on the large Magnum inverter (see Figure 2-6).
Small Magnum inverter
Phone splitter that connects
AGS network cable (from
AGS’s green NETWORK port)
and remote’s cable to
inverter’s Remote (blue) port
ME-AGS-N
Inverting
DC 12.6V 5A
Remote
Figure 2-5, Connecting the AGS to a Magnum Inverter (Small)
ME-AGS-N
Network Communications
cable from AGS NETWORK
(green) port to inverter’s
Network (green) port
Large Magnum inverter
Remote
Inverting
DC 12.6V 5A
Remote cable to
inverter’s Remote
(blue) port
Figure 2-6, Connecting the AGS to a Magnum Inverter (Large)
© 2012 Magnum Energy, Inc. 8
2.0 Installation
2.4.3 Cable Connections with Multiple Devices
If you are using more than one Magnum networked device, a 4-wire phone splitter is required to connect the devices. There are two options for inter­connecting the devices – either in a Star or Daisy Chain confi guration.
Info: Before deciding on which confi guration to use, review the dif-
ferences in installation and ease of troubleshooting.
• Star Con guration – In this arrangement, all the network devices con-
nect to the inverter’s Network port via a phone splitter, using individual cable runs (Figure 2-7). Since each device is independently connected to the inverter’s Magnum Net or Network port, problems in a cable or a device can be easily isolated; and, if there is a cable failure to one device it does not bring down all the devices.
Remote Control
PWR
FAULT
Inverting
CHG
DC 12.6V 5A
INV
ON/OFF
CHARGER
ON/OFF
AGS METER SETUPSHOREINVERTER
SELECT
TECH
Magnum Inverter/Charger
ME-BMK
ME-AGS-N
Phone splitter
Figure 2-7, Multiple Network Devices – Star Confi guration
• Daisy Chain Con guration – In this arrangement, the network de-
vices are linked in a series (Figure 2-8). If using this confi guration, the ME-AGS-N must be the fi rst device connected to the inverter’s Magnum Net or Network port – followed by the second network device.
ME-AGS-N (1st device)
Remote Control
PWR
FAULT
Inverting
CHG
DC 12.6V 5A
INV
ON/OFF
CHARGER
ON/OFF
INVERTER
SHORE
AGS
METER SETUP
SELECT
TECH
Magnum Inverter/Charger
Phone
splitter
ME-BMK (2nd device)
Figure 2-8, Multiple Network Devices – Daisy Chain Confi guration
9 © 2012 Magnum Energy, Inc.
2.0 Installation
2.4.4 Ensure all Negative Connections are Connected Together
When connecting devices together (via a network communication cable), the return path (i.e., battery negative) of each battery powered device must be at the same potential (i.e., electrically common with each other). This prevents a high-impedance path developing between the connected devices, which can cause the network cable to become the DC return path to the battery – possibly resulting in permanent damage to all connected devices on the network. This also requires that the battery negative connection of each device be always connected before connecting/disconnecting any bat­tery positive.
Inverter
AGS Inverter
Figure 2-9, Connected Devices at the Same Potential
Inverter
Battery
Battery
Network cable

2.5 ME-AGS-N Terminal Block Wiring Connections

With the AGS already mounted, remove the green 8-port terminal block before proceeding with wiring the generator. Refer to Figure 2-11 and the info below to wire the AGS’s terminal block to the generator.
CAUTION: DO NOT plug in the 8-port terminal block until all the
wiring to the module is complete and you are ready to perform the functional tests (per instructions in Section 4.0).
CAUTION: A fuse rated at 5 amps or less must be used to protect
all power circuits connected to the AGS (do not fuse ground connec­tions). Ensure the fuse is correctly rated for the wire size used. Refer to national and local codes for rating and type. Normally, a minimum #16 AWG wire is required in order to use a 5-amp fuse.
Info: The green 8-port terminal block accepts CU/AL conductors from
#30 to #12 AWG (0.05 to 3.3 mm2).
2.5.1 Power Connections (Terminals 3 & 4)
Terminals #3 (positive) and #4 (negative) on the 8-port terminal block are connected to the monitored battery bank*. These terminals are used to power the AGS module and to monitor the inverter’s battery voltage (when used to autostart the generator based on low battery voltage).
Info: The AGS requires a DC input of 8.5-70 volts in order to operate
the internal relays. An input voltage greater than 70 volts will cause damage to the AGS and is not covered by the product warranty.
* Monitored Battery Bank – When autostarting the generator based on battery voltage (i.e., start VDC), the inverter’s battery bank must be connected to Termi­nals #3 (positive) and #4 (negative). If autostarting based on any other condition (i.e., temperature, amps, etc.), either the inverter battery bank or the generator’s battery may be used to power the AGS module. However, the negative terminal of every battery bank must be connected together to prevent damage to the AGS (see Section 2.4.4).
© 2012 Magnum Energy, Inc. 10
2.0 Installation
To make power connections from the monitored battery bank to AGS:
1. Route and connect a wire (black) from the monitored battery bank’s negative terminal to Terminal #4 on the 8-port terminal block.
2. Route and connect a wire (red) with a 5-amp in-line fuse from the moni­tored battery bank’s positive terminal to Terminal #3.
2.5.2 Generator Run Sense Connection (Terminals 2 & 4)
A generator run sense signal/voltage is required as it alerts the AGS that the generator is running; which prevents another starter crank to the generator. If the gen run sense signal is not provided to the AGS, the AGS commands the generator to autostop (in case the generator is actually running), and then attempts another autostart sequence (up to four start attempts before a gen start fault occurs). The Gen Type switch setting (under Section 3.1) determines the required gen run sense signal/voltage that must be provided to the AGS.
Gen Type is 2-Wire Standby Mode* – If your generator is fully auto-
matic and can start, run, and stop using only two wires, you may be able to use the 2-Wire Standby setting (see Gen Type settings under Section 3.1). When using this setting, the gen run sense signal is communicated from the inverter to the AGS thru the network cable. The AGS determines that the generator is running when the inverter/charger communicates that it is in a charge state (i.e., Charging, Bulk Charge, Absorb Charge, etc.).
* Requires ME-AGS-N with revision 5.2 to use 2-Wire Standby mode.
When using the 2-Wire Standby setting (and the generator is autostarted by the AGS), the generator runs and connects to the input of the inverter. This causes the inverter to begin charging, which in turn communicates to the AGS (via the network cable) that the generator is running – pre­venting another starter crank command from the AGS.
Gen Type is not 2-Wire Standby Mode – For all other Gen Type set-
tings (other than 2-Wire Standby mode), the generator run sense must be 10 to 40 VDC – only while the generator is running. The gen run sense voltage from the generator is connected to Terminal #2 (positive) and Terminal #4 (negative) on the green 8-port terminal block on the AGS; and can be a switched B+ source from the generator, a positive signal from the generator’s hour meter, or the generator’s running light.
To install the generator’s run sense voltage to the AGS:
1. Connect a wire (preferably not black or red) from the generator’s run sense output to Terminal #2 on the 8-port terminal block.
2. Connect the negative terminal of the monitored battery bank to Terminal #4 (power negative) on the 8-port terminal block. Ensure the negative terminal on the generator battery is referenced/connected to the nega­tive terminal on the monitored battery.
Info: The negative terminal of the monitored battery bank must be in
common with the negative side of the gen run sense signal from the generator. This ensures that the positive battery voltage (to Terminal #3) and the positive gen run sense voltage (to Terminal #2) have a common negative reference (to Terminal #4), and are correctly sensed/measured by the AGS.
What if my generator does not have a gen run sense output? If your
generator is not equipped with a generator run sense output (10 to 40 VDC ­only while the generator is running), review the alternative options as shown in Figure 2-10 to provide this gen run sense voltage to the AGS.
11 © 2012 Magnum Energy, Inc.
2.0 Installation
Alternative Option 1 – Tap into the positive side of the generator’s hour
meter or running lamp; ensure the voltage is 10 to 40 VDC only while the generator is running.
AGS Terminal Block Ports:
1 2 3 4 5
run sense
negative
7 8
6
Inside Generator
Generator
Battery
OR
0123
DC Fuse
(5A max)
Generator
Hour
Meter
Generator
Running
Lamp
Alternative Option 2 – Use a 120 VAC to 12 VDC step-down transformer
(normally used to charge power equipment batteries) and plug it into the generator’s 120 VAC output. The step-down transformer provides 12 VDC output only while the generator is running.
On Generator
AGS Terminal Block Ports:
1 2 3 4 567 8
120VAC Outlet
run sense
negative
120VAC IN
12VDC OUT
TRANSFORMER
DC Fuse
(5A max)
Alternative Option 3 – Use an external 120 VAC coiled relay to bring the
generator’s battery voltage to the AGS gen run sense terminal (AGS terminal block – Terminal #2) only while the generator is running. The generator’s battery voltage must be 10 to 40 VDC.
AGS Terminal Block Ports:
1 2 3 4 567 8
run sense
negative
NC
NO
COM
(5A max)
HOT
NEU
120 VAC Coil Relay
Inside Generator
Generator
Battery
DC Fuse
On Generator
120VAC Outlet
Figure 2-10, Generator Run Sense Options
© 2012 Magnum Energy, Inc. 12
2.0 Installation
2.5.3 Gen Start/Stop Connections (Terminals 1, 5, 6, 7, & 8)
This section covers the control relays inside the AGS module, and provides information about wiring these relays to the generator’s start/stop circuit. You must identify the generator’s start and stop wiring requirements in order to determine: how many relays you require, the number of wires you connect, and in what combination.
When the generator is equipped with a remote control terminal or connector, it is much easier to make the connections to the AGS control relays if the generator‘s optional remote control is purchased. Connecting to the generator’s remote also eliminates the need to make connections inside the generator (and possibly violating the generator’s warranty).
The AGS module provides three control relays (RY1, RY2, and RY3) to operate the autostart/autostop functions of your generator. These relays are dry contacts (they do not provide any voltage or current), and operate only as switches that turn low amperage devices (5 amps) on and off. They are not intended to directly provide power to starter motors or to ignition systems. Rather, the relays are used to send a signal to operate the coil of another higher amperage device, which does the actual switching of power.
CAUTION: A fuse rated at 5 amps or less must be used to protect each of the relays. The warranty does not cover damage to these relays. Fuses should be located as close as possible to the generator
connection. A fuse must be used, even if the circuit is providing only a “dry contact” or “ground” connection – it will prevent damage if the connection is miswired or damaged.
Info: To set the generator type — which determines the operation
of the AGS relays — see the Gen Type setting info in Section 3.1.
Info: Due to the different generator types and the various starting/
stopping wiring confi gurations used by generator manufacturers, detailed wiring instructions are not provided in this manual. Please refer to your generator’s documentation for wiring details.
Info: For more information, and to view diagrams on connect-
ing the AGS to the start/stop circuit on many generators, go to
http://www.magnumenergy.com/service/genwiringdiagrams.htm.
Depending on your generator’s start and stop wiring requirements, you may only need to use one relay (RY1) for fully automatic 2-wire generators; two relays (RY1 and RY2) for 3-wire generators; or all three relays (RY1, RY2, RY3) for generators that require an independent bypass or preheat circuit.
The connection points to each relay are as follows (see Figure 2-11):
Relay 1 (RY1) and Relay 2 (RY2)
Terminal #5: the Normally Open (N.O.) position of the RY1 relay
Terminal #6: the Common (COM) position of both Relay 1 (RY1) and Relay 2 (RY2)
Terminal #7: the Normally Open (N.O.) position of Relay 2 (RY2)
Relay 3 (RY3)
Terminal #1: the Common (COM) position of Relay 3 (RY3)
Terminal #8: the Normally Open (N.O.) position of Relay 3 (RY3)
13 © 2012 Magnum Energy, Inc.
2.0 Installation
Relays inside the AGS controller
1
RY1
COM
NO
2 3 4
5 6
RY2 RY3
NONC
COM
NC
COM
NONC
8
7
Normally Open (N.O.)
8
contact on Relay 3 (RY3)
Normally Open (N.O.)
7
contact on Relay 2 (RY2)
Common (COM) contact on
6
Relay 1 (RY1) and Relay 2 (RY2)
Normally Open (N.O.) contact
5
on Relay 1 (RY1)
Negative DC voltage input
4
[negative terminal from monitored battery bank (positive side connected to Terminal 3), and the negative side of the run sense signal (positive side connected to Terminal 2)]
Positive DC voltage input
3
[positive terminal from monitored battery bank (8.5 to 70 volts DC from the positive terminal of the monitored battery bank); negative side is connected to Terminal #4]
Positive run sense input (10 to 40 volts DC
2
only when generator is running; negative side is connected to Terminal #4)
Not required if Gen Type setting is 2-Wire Standby mode
Common (COM) contact on Relay 3 (RY3)
1
Figure 2-11, Wiring to the ME-AGS-N Module’s Terminal Block
© 2012 Magnum Energy, Inc. 14
2.0 Installation

2.6 Common Generator Wiring Diagrams

The most common generator starting/run/stop circuits can be divided into three major types – 2-wire control, 3-wire momentary control, or 3-wire maintain control. The following gen wiring diagrams are provided as examples:
Info: The term “3-wire” refers to the minimum number of wires
required to control the starter motor and to run the generator; more than three wires may actually be needed.
Two-wire control generator types: These generator types integrate the
control circuits for start-up, running, and stopping (Figure 2-13). The gen­erator starts and runs when two control wires are connected, and then stops when they are disconnected.
Three-wire momentary control generator types: These generator types
use a three-position momentary type switch that controls their operation (Figure 2-14). To start the generator, the switch is momentarily held in the START position. This energizes the ignition system and cranks the starter motor. Once the engine has started, the switch is released and it returns to a center position (i.e., “momentary” run control). To shut down the generator, the switch is held in the STOP position until the engine dies. Once the switch is released, it returns to the center position (i.e., “momentary” stop control).
Three-wire maintain control generator types: These generator types use
an automotive type starting circuit (Figure 2-15). To start the generator, an operating switch is fi rst turned to a RUN position and then momentarily held to a START position. Once the engine starts, the switch is released and it returns to the RUN position (i.e., “maintain” run control). To shut down the genera­tor, the switch is moved to the OFF position (i.e., “maintain” stop control).

2.7 Warning Label

It might be falsely assumed that it is safe to perform maintenance on the generator or the electrical panel once the generator is off. However, the AGS system can automatically turn on the generator and power the panel.
A warning label (Figure 2-12) is provided to inform all personnel that an automatic generator starting device is installed in your electrical system. Place the label in a clearly visible location at the generator (ensure it is especially visible at the generator cabinet or at the enclosure that guards electrical shock or moving parts hazards).
WARNING: To prevent harm to servicing personnel, ensure the gen-
erator and AGS are properly disabled (i.e., remove the starting battery from the generator, and remove all power to the AGS by u
the green 8-port terminal block from the AGS module) prior to per-
forming maintenance on the generator or electrical panel.
nplugging
WARNING
This electrical system is equipped with an Automatic Generator Starting device and/or an inverter. Disconnect all AC and DC power to the ME-AGS-N and/or inverter before performing any service to the electrical system. Failure to do so can result in shock causing serious injury or death.
PN: 62-0002 Rev A
Figure 2-12, Warning Label
15 © 2012 Magnum Energy, Inc.
2.0 Installation
Input DC Voltage
Jumper - set to
INSIDE
INSIDE
Connected via
communication cable to
inverter’s Network port
monitored battery
bank voltage
12/24/48V
(on 24V setting)
Gen Type
4321
(2-Wire
Maintain
ON
Mode)
5
amp
fuse
Inside Generator
Run / Off Switch
Gen
Battery
RUN
Monitored
battery bank
(12V/24V/48V)
GEN AND POWER I/O
Relay 1
(Terminals 5 & 6)
Relay 2
(Terminals 6 & 7)
Relay 3
(Terminals 1 & 8)
R2 (Relay 2) Time
Delay time
5
amp
fuse
5 amp fuse
Ground
GEN RUN PERIOD
OFF
R2
Delay
Timing Information
10 sec.
4 sec.
Time between start attempts
Total start attempts 4
Relay timing for Gen Type: 2-Wire Maintain Mode
0 1 2 3
Gen
Hour Meter
OFF
2 min.
Figure 2-13, Two-wire Control Type Generators
© 2012 Magnum Energy, Inc. 16
2.0 Installation
5
amp
5
amp
fuse
fuse
INSIDE
communication cable to
5 amp fuse
inverter’s Network port
Inside Generator
INSIDE
Connected via
Input DC Voltage
Jumper - set to
monitored battery
bank voltage
12/24/48V
(on 24V setting)
4321
Gen Type
(5-Wire
ON
Mode)
PREHEAT
5 amp fuse
Monitored
battery bank
(12V/24V/48V)
GEN AND POWER I/O
Relay 1
(Terminals 5 & 6)
Relay 2
(Terminals 6 & 7)
Relay 3
(Terminals 1 & 8)
STOP Time
START Time
PREHEAT Time 25 sec.
Start Delay Time 14 sec.
Relay timing for Gen Type: 5-Wire Mode
0 1 2 3
Gen
Hour Meter
START
Start
STOP
Delay
PREHEAT
Delay
Timing Information
10 sec. 10 sec.
Time between start attempts
Gen
Battery
GEN RUN
PERIOD
Preheat delay time
Total start attempts
STOP
STOP
START
4 sec.
2 min.
4
Figure 2-14, Three-wire Momentary Control Type Generators
17 © 2012 Magnum Energy, Inc.
2.0 Installation
Input DC Voltage
Jumper - set to
INSIDE
INSIDE
Connected via
communication cable to
inverter’s Network port
monitored battery
bank voltage
12/24/48V
(on 24V setting)
4321
Gen Type
(Portable
ON
Mode)
5
amp
fuse
5 amp fuse
Monitored
battery bank
(12V/24V/48V)
GEN AND POWER I/O
Relay 1
(Terminals 5 & 6)
Relay 2
(Terminals 6 & 7)
Relay 3
(Terminals 1 & 8)
5
amp
fuse
Inside Generator
0 1 2 3
Gen
Hour Meter
Delay
START
Delay
T1
19
50
30
Gen
Battery
RUN
GEN RUN PERIOD
50
OFF RUN
START
19
Switch
30
30 50 19
OFF
Timing Information
START Time
T1 Time
10 sec.
5 sec.
Time between start attempts
Total start attempts 4
2 min.
Delay Time 2 sec.
Relay timing for Gen Type: Portable Mode
Figure 2-15, Three-wire Maintain Control Type Generators
© 2012 Magnum Energy, Inc. 18

3.0 ME-AGS-N Module Setup

3.0 ME-AGS-N Module Setup
This section covers the AGS’s internal settings and how to configure them.
3.1 Confi guring the Internal ME-AGS-N Settings
Unscrew the AGS module’s four top screws and remove the plastic cover to access the Input DC Voltage Jumper and the 4-position DIP (Dual In-line Pack­age) switch (Figure 3-1).
Input DC
Voltage
Jumper Setting
(Default: 12V
12/24/48V
Setting)
DIP Switch
4321
Gen Type
Setting
(Default: QD
Mode Setting)
RY1 RY2 RY3
12/24/48V
4321
2
ON
134
ON
Figure 3-1, Inside the ME-AGS-N Module
Input DC Voltage Jumper Setting – This setting is determined by connecting
two small pins with a small, black plastic box (i.e., jumper). This setting can be confi gured for 12, 24 or 48 VDC operation (Figure 3-2), which is determined by the nominal DC voltage connected to Terminals #3 and #4 on the AGS.
For 12-volt DC operation, position the jumper on the bottom two pins.
For 24-volt DC operation, position the jumper on the middle two pins.
For 48-volt DC operation, position the jumper on the top two pins.
12 VDC Operation
(jumper on bottom
two pins)
24 VDC Operation
(jumper on middle
two pins)
48 VDC Operation
(jumper on top
two pins)
**default setting**
Figure 3-2, DC Voltage Settings
DIP Switch Gen Type Setting The Gen Type setting is determined by a
DIP switch, which is actually four small switches that can be turned to the ON or OFF positions. The position of each of these switches is used to determine the open and close timing sequence for the three internal AGS relays (RY1, RY2 and RY3). The multiple positions of the DIP switch allow a wide range of generator start/stop circuit confi gurations.
After determining the appropriate start/stop timing sequence for your generator, use Table 3-1 to determine the correct Gen Type setting for your generator’s start/stop requirements.
For examples and further assistance, view the generator wiring diagrams at:
http://www.magnumenergy.com/service/genwiringdiagrams.htm.
Info: This switch is shipped with a thin yellow plastic fi lm covering.
You can just punch through this thin fi lm to set your gen type.
19 © 2012 Magnum Energy, Inc.
3.0 ME-AGS-N Module Setup
Table 3-1, Gen Type Settings
Gen
Type
4321
ON
QD Mode
(default)
4321
ON
Wire
3-
Mode
4321
ON
Portable
Mode
4321
ON
2-Wire
Momentary
Mode
4321
ON
2-Wire
Maintain
Mode
4321
ON
2-Wire
Standby
Mode*
4321
ON
5-Wire
Mode
Relay Timing/Operation (RY1/RY2/RY3)
RY1
(N.O.)
RY2
(N.O.)
RY3
(N.O.)
Generator: Quiet Diesel Series (Onan). HDZAA model is not compatible with the AGS-N module – damage may occur.
RY1
(N.O.)
RY2
(N.O.)
RY3
(N.O.)
Generators: Marquis, Emerald, and Microquiet (Onan); Pack Series (Generac).
RY1
(N.O.)
RY2
(N.O.)
RY3
(N.O.)
Generator: EM Series with remote control (Honda).
RY1
.O.)
(N
RY2
(N.O.)
RY3
(N.O.)
Generator: PT-ECU-63 controller with 2-wires (Powertech).
RY1
(N.O.)
RY2
(N.O.)
RY3
(N.O.)
Generators: RMY Series (Kohler); DynaGen controllers.
RY1
(N.O.)
RY2
(N.O.)
RY3
(N.O.)
Generators: Two-wire start (does not require gen run voltage signal to Terminal #2).
RY1
(N.O.)
RY2
(N.O.)
RY3
(N.O.)
Generators: Diesel), NL-673 (Northern Lights).
* ME-AGS-N Revision 5
T2
T3
T3
T1
T2
T2
T1
BTDA / BEG (Westerbeke), 205-DS (Martin
T2
T1
T1
T1
T3
T1
T2
T1
GEN RUN PD.
GEN RUN PD.
GEN RUN PD.
T2
T1
T3
GEN RUN PD.
GEN RUN PD.
GEN RUN PD.
T1
GEN RUN PD.
T4
.2 or higher required
T3
T3
Quiet
T2
T1
Time
Period
T1 =
20 sec.
T2 =
4 sec.
T3 =
10 sec.
T1 =
5 sec.
T2 =
2 sec.
T3 =
10 sec.
T1 =
2 sec.
T2 =
10 sec.
T3 =
5 sec.
T1 =
2 sec.
T2 =
10 sec.
T1 =
4 sec.
T2 =
10 sec.
T1 =
4 sec.
T2 =
10 sec.
T1 =
10 sec.
T2 =
14 sec.
T3 =
4 sec.
T4 =
25 sec.
© 2012 Magnum Energy, Inc. 20

4.0 ME-AGS-N Module Functional Tests

4.0 ME-AGS-N Module Functional Tests
After all electrical connections to the AGS module, batteries, and generator have been completed (and prior to reconnecting the green 8-port terminal block), perform the following tests to verify that the AGS system is function­ing correctly and the wiring from the AGS to the generator is correct. Once the AGS module passes the functional tests, you can set up the AGS for your autostart and autostop requirements (refer to: Section 8.0 for a ME-RC controller, Section 9.0 for a ME-ARC, or Section 10.0 if you have a ME-RTR).
Note: The communication cable from the inverter to the green NETWORK
port on the AGS is not required in order to perform these tests.

4.1 Power-Up Test

1. Before connecting the 8-port terminal block into the AGS module, use a multimeter to verify the correct polarity and that the voltage to Terminals #3 (positive) and #4 (negative) is correct according to the position of the input DC voltage jumper (refer to Figure 3-2).
2. Apply power to the AGS module by plugging in the green 8-port terminal block into the module, and then verify that the green READY LED comes on and the STATUS LED blinks green once.
Info: The green READY LED will come on (solid) when the AGS module
is powered and the temperature sensor is connected, and will blink if the temperature sensor is not connected or detected. A connected temperature sensor is not required unless the temperature autostart feature is needed.

4.2 Generator Wiring Test

This start/stop test is used to confi rm that all wiring from the generator to the AGS module is correct and the Gen Type setting (Table 3-1) is confi gured correctly for your generator type.
1. Press and release the red TEST button on the AGS (see Figure 5-1).
2. The STATUS LED on the AGS module will begin to blink green and the generator should start (a blinking green STATUS LED means the AGS has initiated an automatic generator start/stop sequence).
3. Once the generator starts, it should run for approximately 30-60 seconds before automatically turning off (ensure the it will not try to restart within the next two minutes). View the STATUS LED and ensure it turns solid green (a solid green STATUS LED means the generator has started suc-
cessfully and is providing the gen run sense signal to the AGS module¹).
Note: If the generator attempted to start but did not run, continue to wait,
the AGS will attempt to start the generator 3 more times. If your AGS/generator system passes all steps above (may attempt an auto-
start 4 times), then the wiring from the AGS to the generator is correct. You are now ready to set up and activate the AGS using your remote control panel.
Info: The AGS attempts to start the generator 4 times. If after 4
attempts the generator fails to start, the STATUS LED turns red – indicating a fault.
If the generator did not start, or the STATUS LED shows a fault condition (solid red LED indication), refer to Section 6.0 “ME-AGS-N Module Troubleshooting”.
Note¹: The gen run sense signal from the generator to Terminal #2 on the
AGS is not required when using the 2-Wire Standby Mode (Gen Type setting).
21 © 2012 Magnum Energy, Inc.
5.0 ME-AGS-N Module Operation

5.0 ME-AGS-N Module Operation

This section details the operation of the ME-AGS-N module (independent of the remote control operation).

5.1 ME-AGS-N Module TEST Pushbutton

The front of the module (Figure 5-1) has a red pushbutton to test the AGS system operation. When the red TEST pushbutton is pressed and released, the AGS initiates an automatic generator start/stop sequence. This test attempts to turn the connected generator on and to have it run for at least 30 seconds before turning off. This start/stop test is used to confi rm that all wiring from the generator to the AGS is correct and that the AGS is confi gured correctly for your generator type.
Note: If the generator is running from an autostart condition when the AGS
module’s TEST button is pressed, the AGS will turn the generator off and initiate an automatic generator start/stop test sequence (running 30-60 seconds) – using 4 autostart attempts if needed.

5.2 ME-AGS-N Module LED Indicators

The front of the module (Figure 5-1) has two LED indicators for viewing system operation.
5.2.1 STATUS LED Indicator
Blinking Green: Indicates that the AGS system is initiating a generator
start sequence. This happens when the TEST button (on the AGS) has been pressed and released, or a remote control has communicated to the AGS to autostart the generator.
Solid Green: Indicates the generator has started successfully and is providing
the gen run sense signal/voltage to the AGS module.
Solid Red: Indicates a fault condition in which the generator either has not
started, or has not provided the correct run gen sense signal/voltage to the AGS module – after four start attempts.
5.2.2 READY LED Indicator
Solid Green: Indicates the AGS module has power and the temperature sen-
sor cable is detected. This indicates normal AGS system operation.
Blinking Green: Indicates that the AGS module has power, but the tempera-
ture sensor is not detected. This can mean the temperature sensor cable is either not connected, incorrectly connected, or is defective.
Note: The temperature sensor is not required to be connected unless the
temperature autostart feature is needed.
STATUS
Indicator
(green/red)
TEST
Button
READY
Indicator
(green)
Figure 5-1, ME-AGS-N Front Panel Controls and Indicators
© 2012 Magnum Energy, Inc. 22

6.0 ME-AGS-N Module Troubleshooting

6.0 ME-AGS-N Module Troubleshooting

6.1 Using the ME-AGS-N’s LED Indicators

The two LEDs on the front of the AGS controller indicate how the AGS is operating and help you troubleshoot the AGS system. The STATUS LED is bi­color (green or red) and indicates the AGS’s status. The READY LED is green, and lights if the AGS has power and the remote temp sensor is connected.
The AGS controller performs a “self test” when power is fi rst applied. The green READY LED lights up (solid) and the STATUS LED blinks green once. If the self-test is successful, test the AGS system for proper operation by press­ing and releasing the TEST button. The STATUS LED blinks green, and the AGS should start the generator. Once the generator starts, the STATUS LED lights solid green and the generator runs for approximately 30-60 seconds, and then shuts off (will not try to restart within the next two minutes). If the generator does not start and stop as expected, refer to Table 6-1 below to help fi nd a solution.
WARNING: Completely unplug the green 8-port terminal block from
the AGS module before performing maintenance on the electrical or generator system to prevent harm to servicing personnel.
Table 6-1, ME-AGS-N Module Troubleshooting Guide
LED
Indication
STATUS is on red = Gen fault
STATUS is blinking green = Gen start initiated
STATUS is on solid green = Gen run
READY is off = No power con­nected to the AGS module
READY is blinking = The tempera­ture sensor is not detected
Note: Temp sen­sor is not required to be connected unless the temp autostart feature is needed.
READY is on (solid) = Power and temp sensor connected
Symptom Solution
1. Gen won’t start; or
2. Gen won’t run. It starts, but is stopped by the AGS (B+ or gen run sense voltage not sensed to Terminal #2).
Gen start initiated.
Gen is running.
DC voltage to Termi­nals #3 (+) and #4 (-) on module miss­ing or incorrect.
The temp sensor is not sensed or plugged into the purple REMOTE port.
The temp sensor is connected to the purple REMOTE port.
Refer to Section 6.0 “ME-AGS-N Module Troubleshooting” for assistance.
Unplug/remove and reconnect the green 8-port friction-fi t terminal block to reset the STATUS (fault) indicator.
No problem – normal operation.
No problem – normal operation.
1. Check fuse, check DC wiring.
2. Check the DC voltage under the AGS TECH menu.
1. Check the temp sensor cable and its connection to the purple REMOTE port, or
2. Check the temp sensor cable for any damage.
3. Obtain another temp sensor cable.
4. Check the DC voltage under the AGS TECH menu.
No problem – normal operation.
23 © 2012 Magnum Energy, Inc.
6.0 ME-AGS-N Module Troubleshooting

6.2 Generator Starting/Running Troubleshooting

This section helps troubleshoot the generator system when the AGS’s STA­TUS LED shows a fault condition (solid red LED indication), or the remote control displays a generator autostart fault.
Press the TEST button on the AGS module, or start the generator from the remote (refer to Section 8.2.1.2 - RC, 9.2.1.2 - ARC, and 10.2.1.3 - RTR).
6.2.1 If the Generator will not Start or Run
If the generator does not start after pressing the AGS module’s TEST button, follow the steps below.
1. Ensure the green READY indicator on the AGS module is on (blink-
ing or solid) to indicate that the AGS module is getting power (see Figure 5-1).
2. Check the generator for fuel or for any fault codes, or check the gen-
erator’s operating manual for troubleshooting tips to resolve why the generator will not start or run.
3. Check that the start/stop wiring has not come loose and is correctly con-
nected for your generator model. A wiring diagram for your particular brand and model of generator may be available, check our website at:
http://www.magnumenergy.com/service/genwiringdiagrams.htm
4. Your generator may require a higher amperage start signal than what
our AGS relays are rated (approx. 5 amps); in that case, you will need to supply a higher-rated external relay.
5. If the generator tries to start as soon as you initiate a test (instead of
waiting for the initial stop signal before attempting to start), check the start and stop wire connections, it is possible that they are reversed.
6. Remove the generator start/stop wires from the AGS’s 8-port terminal.
Simulate the AGS relays by physically connecting the start wires fi rst to ensure the generator starts and runs. Then, connect the stop wires and ensure the generator stops. If the generator does not start or stop as it should, recheck and troubleshoot the start/stop wiring to the generator.
6.2.2 STATUS LED does not go Solid
If the generator is running, but the STATUS LED on the AGS module is not on solid, then:
1. Ensure the AGS is not in warm-up (STATUS LED should go solid once the
warm-up period is over).
2. Confi rm you are getting the correct gen run sense signal based on your
Gen Type setting.
Info: Refer to the Gen Type Setting section (page 19) and Table 3-1
(page 20) to determine your Gen Type setting.
Gen Type is 2-Wire Standby Mode – When using 2-Wire Standby
mode, the gen run sense signal is communicated from the remote con­trol to the AGS thru the remote control cable. The AGS determines that the generator is running when the remote communicates that it is in a charge state (i.e., Charging, Bulk Charge, Absorb Charge, etc.).
Note: In order to perform the 2-Wire Standby mode tests: the remote
control must be connected to the inverter, and the green Network port on the inverter must be connected with the communication cable to the green NETWORK port on the AGS.
© 2012 Magnum Energy, Inc. 24
Loading...
+ 73 hidden pages