Magnum Standard Control Installation Manual

Page 1
MAGNUM Standard Control
On/O Thermostat Installation manual
PLEASE READ THIS MANUAL CAREFULLY BEFORE INSTALLATION, AND STORE WITH OTHER WARRANTEE FORMS.
The MAGNUM Standard Control is an electronic thermostat with four functions: Room sensor, oor sensor, power regulator and room sensor with max./min. limiter. This thermostat can also be set up for setback temperature.
1. Startup
Remove the adjustment wheel with a screwdriver. The front cover can the be removed by pushing in the locking clips on each side of the thermostat (as shown in g.2). Be careful when doing this in order not to damage the thermostat. When the thermostat has been connected to the power source, push the on/o button. Never dismantle the thermostat when the power is switched on.
2. Sensor choice
When choosing a sensor type, the thermostat should not be connected to a power source.
• Floor sensor (standard)
Jumper placement: Covering the two pins on the left. Application: The temperature is regulated by the oor sensor.
• Room sensor
Jumper placement: Covering the two pins in the right Application: The temperature is regulated by the room sensor.
• Room sensor with limiter
Jumper placement: Covering the two pins on the right + the oor sensor connected Application: The temperature is regulated by the room sensor, but the oor sensor overrides the room sensor if the oor temperature exceeds the maximum limit temperature. The limiter can be regulated between 20°C and 30°C. For parquet ooring, a maximum of 27°C is recommended by most ooring manufac­turers. Please follow the recommendations provided by your manufacturer.
• Power regulator
Jumper placement: Covering the two center pins Application: The eect regulator has a 30 min cycle. The desired on/o interval can be set from 0 to 10, where each level increases the on-time by 3 minutes. Example: When the thermostat is set to level 3, the heating element is switched on for 9 minutes, then o for 21 minutes in the 30 minute cycle. If the thermostat is set to level 6, the heating element is switched on for 18 minutes, then o for 12 minutes.
Fig.2
Bi-LED diode
Adjustment wheel
Fig.1
123 4567
HEATING L
SENSOR
PILOT WIRE
L
HEATING N
N
Fig.2
Fig.1
123 456 7
HEATING L
SENSOR
PILOT WIRE
L
HEATING N
N
Fig.2
Fig.1
123 456 7
HEATING L
SENSOR
PILOT WIRE
L
HEATING N
N
3. Connecting the thermostat
The termostat must be connected to the power source according to the connection diagram. All heating systems must be equipped with a residual current disrupter with 30mA. Max load for the thermostat is 16A/3600W at 230V. If the load is higher, the thermostat must be con­nected to a contactor. The thermostat does not have galvanic insulation between high and low current. The sensor must therefore be considered as live (230V) and needs to be installed in accordance with the rules for high current installations and national installation requirements.
Caution: When reattaching the thermostat cover, make sure the ven­tilation on the top and bottom of the thermostat is not covered up.
4. Setback temperature
The Multireg thermostat does not have a built-in setback temperature option, but by connecting an external timer to the S and L clamps, the temperature can be lowered by 3°C at desired times.
5. Calibrating the temperature
When connecting the oor heating system for the rst time, the tem­perature should be set at a maximum of 15°C to 20°C. The thermostat should be calibrated after 2-3 days. Pull out the adjustment wheel carefully (without turning it) until it comes loose. Use a thermometer to check the actual temperature, and push the adjustment wheel back onto the thermometer in accordance with the measured temperature. If the oor heating has been switched o during the summer, this procedure should be repeated when it is switched back on.
6. Bi-LED diode
• Green light when the thermostat is in a standby mode.
• Constant red light when the relay is engaged and the power is on.
• Blinking red light when there is a sensor malfunction or the oor sensor is disconnected.
7. Technical data
Voltage 230 VAC AC ± 15% 50 Hz Max. load 3600W (resistive load) Max. current 16 Amp Power consumption 0,5W IP-class IP 21 Power regulator Time cycle: 0-30 min Min/Max inst. temp. -20°C - +60°C Min/Max oper. temp. 0° - 50°C Temperature intervals Floor sensor: 5°C - 40°C Room sensor 5°C - 40°C Hysteresis 0.5°C Sensor values 0°C 29,1 Kohm 10°C 18,6 Kohm 15°C 15,1 Kohm 20°C 12,2 Kohm 25°C 10,0 Kohm Switch 2-pole switch Colors White RAL 9010 (5430333) White RAL 9003 (5430444) Floor sensor Length 3 meters. The cable can be extended 10 meters by using a proper installation cable.
123 4567
HEATING
L
SENSOR
PILOT WIR
E
L
HEATING
N
N
Torque: Max. 2Nm Clamp 1+ 2Sensor - Floor sensor Clamp 3: Pilot wire (connected to L for setback temperature) Clamp 4: Heating L Clamp 5: L Clamp 6: Heating N Clamp 7: N
123 456 7
HEATING L
SENSOR
PILOT WIRE
L
HEATING N
N