Magnum M9-RSB-12, MJ-RSB-12, M8-RSB-12 Installation/configuration Manual

MAGNUM SENSOR CONTROL BOARD
INSTALLATION & CONFIGURATION
PRODUCT CASING & DIMENSIONS
5.5625” 4.4375”
TECHNICAL DATA
Part Numbers (Frequency Dependant) M9-RSB-12 (902 MHz - North America)
TOP VIEW:
2.75”
LEFT SIDE:
1”
*PATENT PENDING
M8-RSB-12 (868 MHz - Europe and China) MJ-RSB-12 (928 MHz - Japan)
Input Power 24 VAC
Digital Relay Output Channels (3) N.O. Dry Contracts Rated for 24 VAC 2A
Analog Output Channels (1) 0-10 VDC Rated for 30mA
Digital Input Channels (2) (24 VAC / 24 DC) (Source / Sink)
Pressure Measurement (2) (3 Wire / Pressure Transducer) (Source / Sink)
Temperature Measurement (9) (2 Wire NTC 10K)
Humidity Measurement (1) (3 Wire / Humidity Sensor 0-100%) (Source / Sink)
Wireless Protocol EnOcean Wireless Standard
Wireless Range 150 (50-150 typical)
Enclosure ABS Plasc
Dimensions 5.5625” x 2.75” x 1”
Operang Temperature -40°F to 125°F (-40°C to 51.667°C)
Storage Temperature 32°F to 104°F (0°C to 32°C)
Magnum Innovations
5675 Hudson Industrial Pkwy, Suite 3 - Hudson, OH 44236 - phone 330.915.2382 - fax 330.529.5279 - www.magnum-innovations.com - info@magnum-innovations.com
MAGNUM SENSOR CONTROL BOARD
INSTALLATION & CONFIGURATION
INPUT / OUTPUT OVERVIEW:
T1
GND
T2 GND
T3 GND T4
GND
T5 GND
T6 GND
T7 GND T8 GND
T9 GND
T10 GND
Temp
Humidity
GND 0-10V Relay Out 3
Relay In 3 Relay Out 2
Relay In 2 Relay Out 1 Relay In 1
GND Pressure 2
24VDC GND Pressure 1 24VDC Digital Input 2 24VDC Digital Input 1 24VDC 24VAC Input, COMM 24VAC Input, HOT
Pressure 2
Pressure 1
Digital 2
Digital 1
Power
CONNECTING INPUTS & OUTPUTS
1. BEFORE INSERTING ANY SENSORS OR WIRES INTO DEVICE, BE SURE TO LOOSEN SCREWS THROUGH THE HOLES ON THE TOP OF THE DEVICE.
2. INSERT WIRES INTO CORRECT RECEPTACLE ON THE SIDE OF THE DEVICE (see images above), AND THEN TIGHTEN SCREWS TO SECURE THE WIRES.
Magnum Innovations
5675 Hudson Industrial Pkwy, Suite 3 - Hudson, OH 44236 - phone 330.915.2382 - fax 330.529.5279 - www.magnum-innovations.com - info@magnum-innovations.com
MAGNUM SENSOR CONTROL BOARD
INSTALLATION & CONFIGURATION
1 INTRODUCTION
The Magnum Temperature / Humidity / Pressure Sensor Control Board includes 2 digital inputs, 3 digital outputs and 1 analog output.
When a 24 VAC power source is connected to the Magnum Sensor Control Board, the controller automacally makes the 3 relays,
pressure sensors, 0-10 Volts, and two digital inputs available.
The Control Board Includes:
- 24VAC / 24 VDC power connecons
- 9 NTC 10K Temperature sensor input channels / 1 Humidity
- 2 Digital inputs
- 3 Digital outputs
- 1 Analog output
2 INSTALLATION
1. BEFORE POWERING DEVICE , connect all sensors and digital inputs / outputs (SEE INPUT / OUTPUT OVERVIEW BELOW)
2. Connect device to a power source
(Green LED should light up to conrm device is powered “ON” as shown in image below)
LED is GREEN
(POWER IS “ON”)
3. Device Mounng:
NOTE: Mounng environment should have a typical ambient temperature (32°F - 104°F (0°C - 32°C) and relave humidity
levels (20% - 95% non-condensing).
- Device can be wall mounted or mounted directly on the refrigeraon case (on top or side of case)
- Use 1/8” screws to mount device to desired locaon
- See image below for proper screw locaon on the plasc casing.
1/8” Screw
Locaon
1/8” Screw
Locaon
Magnum Innovations
5675 Hudson Industrial Pkwy, Suite 3 - Hudson, OH 44236 - phone 330.915.2382 - fax 330.529.5279 - www.magnum-innovations.com - info@magnum-innovations.com
MAGNUM SENSOR CONTROL BOARD
INSTALLATION & CONFIGURATION
3 DEVICE CONFIGURATION
AIRCONFIG™ IS REQUIRED TO CONFIGURE THIS DEVICE. PLEASE FOLLOW THE STEPS BELOW TO DOWNLOAD AIRCONFIG™ AND BEGIN YOUR DEVICE’S CONFIGURATION
Step One
• Download airConfig™, based on your operating system, to your computer at download.magnum-innovations.net
Step Two
• Insert USB stick, specifically programmed by Magnum Innovations, into your computer
Step Three
• Power up your device prior to configuration
Step Four
• Your laptop / computer (with provided USB stick) must be within radio range to configure device
Step Five
• Start airConfig™ and select “Advanced” tab
Magnum Innovations
5675 Hudson Industrial Pkwy, Suite 3 - Hudson, OH 44236 - phone 330.915.2382 - fax 330.529.5279 - www.magnum-innovations.com - info@magnum-innovations.com
MAGNUM SENSOR CONTROL BOARD
INSTALLATION & CONFIGURATION
4 RESPONSIBILITY & RESIDUAL RISKS
Magnum Innovaons shall not be liable for damages caused by or aributed to the user including, but not limited to the following:
• Unauthorized installaon and / or use that does not comply with the safety standards specied in applicable regulaons and
/ or in this document.
• Use on equipment that does not guarantee adequate protecon against electric shocks, water or dust when assembled.
• Use on equipment that allows dangerous parts to be accessed without the use of tools.
• Installaon and / or use on equipment that is not compliant with the current standards and regulaons in force.
5 DISCLAIMER
Magnum Innovaons shall not be liable for damages originated from the installaon and / or use of the soware that does not com­ply with the instrucons of this manual.
While reasonable eorts have been made in the preparaon of this document to ensure accuracy, Magnum Innovaons assumes no liability resulng from the informaon contained herein.
To the maximum extent permied by law, Magnum Innovaons assumes no liability for special, accidental, direct, indirect, con­sequenal, exemplary or punive damages (including, without any limitaon whatsoever, the loss of income or prots, interrupon of work, loss of data or goodwill) originang from the use or failure of the soware or equipment or from the supply or failure to supply
technical support, even when informed of the likeliness of said damages.