Self-Powered Wireless Key Card Switch
Mx-EKCS
Product Description
They Key Card Switch saves energy by signally HVAC, lighting, and electrical loads that
a room is unoccupied. It communicates wirelessly with compatible devices in a guest
room when a key card is inserted or removed from the slot.
The Key Card Switch can be mounted on most surfaces using the mounting plate or over
an existing wall box.
Features Include:
• Determines occupancy based on guest room key card being inserted or removed
• Harvests kinetic energy from the card action - no batteries
• Installs easily in new or existing rooms - no wiring
• Transmits room occupancy statues wirelessly to other energy saving devices in the room
• Enables other devices to minimize energy use whenever the room is unoccupied
Package Contents
• Key Card Switch
• Trim Plate
• 2 screws, 2 wall anchors
Tools Required
• Power drill, 3/16” bit
• Screwdriver
• Leveling tool
Specifications
Part numbers (frequency
dependent)
Power Supply Mechanical energy harvesting (power is
Inputs / Outputs • Slot for standard hotel key card
Transmission Range 80 ft. (25 m)
EEP (EnOcean Equipment
Profile)
Card Slot Size
(Hotel Standard)
Dimensions 4.72” H x 3.81” W x 0.43” D (at edge)
Weight 3.5 oz. (99 g)
Environment • Indoor use only
M9-EKCS (902 MHz - North America)
M8-EKCS (868 MHz - Europe and China)
MJ-EKCS (928 MHz - Japan)
generated by the motion of key card moving in
and out
(2.125” W x 3.375” H x 0.034” D)
(54 mm W x 86mm H x 0.9mm D)
• Radio Frequency (RF) transmitter
F6-04-01
4.72” H x 3.8” W x 0.43” D (at edge)
(120mm x 97mm x 11mm)
(120mm x 97mm x 11mm)
• 32° to 131° F (0° to 55°C)
• 5% to 95% relative humidity (non-condensing)
Agency Compliance FCC, IC
Magnum Innovations
5675 Hudson Industrial Pkwy, Suite 3 - Hudson, OH 44236 - phone 330.915.2382 - fax 330.529.5279 - www.magnum-innovations.com - info@magnum-innovations.com
Self-Powered Wireless Key Card Switch
Mx-EKCS
Planning
Take a moment to prepare and ensure optimal communications with
other system components, and for user convenience.
5. Insert the trim plate tabs into the bottom slots of the key card
switch, and then lightly flex the trim plate to insert the top tabs.
• Pick a location near the door where occupants enter and exit
using the key card. A common location is on the wall opposite the
door hinges, 3 ft (92 cm) from the door jamb
• Consider the construction materials in the space and obstacles
that may interfere with RF signals
Installing
1. Decide where you want to mount the key card switch. (The ideal
height is in line with wall switches (49” or 125 cm on center) for
comfortable access.
NOTE: If installing over an existing wall box make sure any bare electrical wires are capped
2. Remove the trim plate from the key card assembly.
3. Using a level and a pencil, lightly mark two small dots to align the
upper edge of the key card switch.
4. Mount the key card switch securely to the wall using the provided
screws and wall anchors
A. Using the pencil marks to ensure it’s level, mark the two
mounting screws drill points
B. Drill two holes for the wall anchors with a 3/16” drill bit
and insert the wall anchors.
C. Insert the top screw loosely and level the Key Card Switch.
D. Insert the bottom screw, and then hand tighten the top
screw.
TIP: To remove the trim plate
without marking it, press down
with a fingernail in the top groove
to ease the tabs out of the slots.
6. Insert a key card to test the mechanism.
TIP: There should be an audible
click each time the key card is
inserted or removed.
Linking
Two or more compatible devices can be linked and configured to
provide the desired control. There are two basic types of devices in
the system; transmitters and transceivers.
Transmit-only: Transmitters are simple energy-harvesting devices that send RF messages to communicate a condition, level, or
state. Transmitters can only be linked to transceivers. Examples >
Self-powered Light Switches, Occupancy Sensors
Transmit & Receive: Transceivers are controlling devices that send
as well as receive RF messages. They also process relevant control
logic, and actuate the appropriate outputs (switching a light on or
o for example). Transceivers can be linked with transmitters as
well as other transceivers. A transceiver can have up to 30 devices
linked to it. Examples > Relays, Gateways
The Key Card Switch is a Transmit-Only Device.
To link the Key Card Switch to a transceiver; the transceiver must
first be powered, within wireless range of the sensor, and set to
accept links.
Magnum Innovations