Magnum CSW412, CSW1012, CSW2012 Owner's Manual

Page 1
CSW Series
Pure Sine Wave Inverter
Owner’s Manual
Page 2
Thank you from all of us at Sensata Technologies for purchasing this CSW Series inverter. The CSW Series includes the CSW412, CSW1012 and CSW2012 inverters; all under the Magnum-Dimensions brand from Sensata Technologies. We understand that you have many purchasing options in the marketplace and are pleased that you have decided on this product.
At Sensata, we are committed to providing you with quality products and services, and hope that your experience with us is pleasant and professional.
Disclaimer of Liability
Since the use of this manual and the conditions or methods of installation, operation, use and maintenance of the CSW Series inverter is beyond the control of Sensata Technologies, this company does not assume responsibility and expressly disclaims liability for loss, damage or expense, whether direct, indirect, consequential or incidental, arising out of or in any way connected with such installation, operation, use, or maintenance.
Note as well that while every precaution has been taken to ensure the accuracy of the contents of this manual, the specifi cations and product functionality may change without notice. Sensata assumes no responsibility for errors or omissions.
Restrictions on Use
The CSW Series inverter may only be used in life-support devices or systems with the express written approval of Sensata Technologies. Failure of the CSW Series inverter can reasonably be expected to cause the failure of that life-support device or system, or to affect the safety or effectiveness of that device or system. If the CSW Series inverter fails, it is reasonable to assume that the health of the user or other persons may be endangered.
Copyright Notice
Copyright © 2015 by Sensata Technologies. All rights reserved. Permission to copy, distribute, and/or modify this document is prohibited without express written permission from Sensata.
Document Information
Description – CSW Series Owner’s Manual Part Number and Revision – 64-0063 Rev C Date Published – July 2015
This manual is printed without color for cost savings. However, this entire manual is available with many of the fi gures in color and can be downloaded at
www.magnum-dimensions.com.
Contact Information
For Magnum-Dimensions products:
Sensata Technologies Phone: 425-353-8833 2211 West Casino Rd. Fax: 425-353-8390 Everett, WA 98204 Web:
Record the unit’s model and serial number in case you need to provide this information in the future. It is much easier to record this information now, instead of trying to gather it after the unit has been installed.
Model: Serial Number:
CSW412 BE CSW1012 AU CSW2012 BD
© 2015 Sensata Technologies i
www.magnum-dimensions.com
Page 3
IMPORTANT PRODUCT SAFETY INSTRUCTIONS
This manual contains safety instructions that must be followed during the installation and operation of this product. Read all instructions and safety information on the inverter and in this manual before installing or using.
Safety Symbols
To reduce the risk of electrical shock, fi re, or other safety hazard, the following safety symbols have been placed throughout this manual to indicate dangerous situations and important safety instructions.
WARNING: Indicates that failure to take a specifi ed action could
result in physical harm to the user.
CAUTION: Indicates that failure to take a specifi ed action could result
in damage to the equipment.
Info: Indicates information that emphasizes or supplements important
points of the main text.
Product Safety Warnings
WARNINGS: Failure to follow the instructions below and in this
manual can result in death or serious injury.
All electrical work must be performed in accordance with local, state and federal electric codes.
This product is designed for indoor/compartment installation. Do not expose to rain, snow, moisture, or liquids of any type.
Use insulated tools to reduce the chance of electrical shock or accidental short circuits. Be sure to remove all jewelry such as rings, watches, bracelets, etc., when installing or performing maintenance on the inverter.
Always disconnect the batteries or energy source prior to installing or performing maintenance on the inverter. Live power may be present at more than one point since an inverter utilizes both batteries and AC.
Do not cover or obstruct any air vent openings and/or install in a zero­clearance compartment - always operate unit in an open area.
When working with electrical equipment or lead acid batteries, have someone nearby in case of an emergency.
Study and follow all the battery manufacturer’s specifi c precautions when installing, using, and servicing the battery connected to the inverter.
While working with batteries, wear eye protection and gloves, and avoid touching your eyes. Keep fresh water and soap on hand in the event battery acid comes in contact with eyes. If this occurs, cleanse right away with soap and water for a minimum of 15 minutes and seek medical attention.
Batteries produce explosive gases, DO NOT smoke or have an open spark or fi re near the system.
Avoid dropping any metal tool or object on the battery. Doing so could create a spark or short circuit which goes through the battery or another electrical tool and may cause an explosion.
Shock Hazard! Keep away from children!
These inverters provide household AC, treat the AC output sockets the same as regular wall AC sockets at home.
Explosion hazard! DO NOT use this inverter in the vicinity of fl ammable fumes or gases (such as propane tanks or large engines).
These inverters contain no user-serviceable parts. See the Warranty section for how to handle service issues.
ii © 2015 Sensata Technologies
Page 4
Table of Contents
1.0 Introduction ............................................................................. 1
1.1 Features - CSW1012 and CSW2012 ............................................. 1
1.2 Features - CSW412 ................................................................... 3
1.3 Regulatory Compliance .............................................................. 4
2.0 Installation .............................................................................. 5
2.1 Pre-Installation ........................................................................ 5
2.1.1 Installation Guidelines ........................................................ 5
2.1.2 Unpacking and Inspection ...................................................5
2.1.3 Tools Required ................................................................... 5
2.2 Locating and Mounting the Inverter ............................................8
2.3 Wiring the Inverter – General Requirements .............................. 11
2.3.1 Wiring Requirements ........................................................ 11
2.3.2 Torque Requirements ........................................................ 11
2.4 DC Wiring ............................................................................. 12
2.4.1 DC Wire Sizing................................................................. 13
2.4.2 DC Overcurrent Protection ................................................. 14
2.4.3 DC Grounding .................................................................. 14
2.4.4 DC Cable Connections ....................................................... 14
2.4.5 Wiring the Battery Bank .................................................... 15
2.4.6 Appliances and Run Time .................................................. 15
2.4.7 Wiring the Inverter to the Battery Bank............................... 16
2.5 Testing the Inverter ................................................................ 18
2.5.1 Inverter Functional Test .................................................... 18
2.5.2 GFCI Function Test ........................................................... 18
3.0 Operation ............................................................................... 19
3.1 CSW412 Operation ................................................................. 19
3.2 CSW1012 and CSW2012 Operation ........................................... 20
3.3 Understanding Loads .............................................................. 21
3.4 System Maintenance ............................................................... 21
4.0 Troubleshooting ..................................................................... 22
5.0 Specifi cations ......................................................................... 23
6.0 Limited Warranty ................................................................... 24
6.1 How to Receive Warranty Service ............................................. 24
© 2015 Sensata Technologies iii
Page 5
List of Figures
Figure 1-1, Front Panel Features (CSW1012 and CSW2012) .................... 1
Figure 1-2, Back Panel Features (CSW1012)..........................................2
Figure 1-3, Back Panel Features (CSW2012)..........................................2
Figure 1-4, Front Panel Features (CSW412) ........................................... 3
Figure 1-5, Back Panel Features (CSW412) ........................................... 4
Figure 2-1, Basic System Diagram ....................................................... 6
Figure 2-2, RV OEM System Diagram ................................................... 7
Figure 2-3, Approved Mounting Positions .............................................. 9
Figure 2-4 CSW412 Dimensions ........................................................... 9
Figure 2-5 CSW1012 Dimensions ....................................................... 10
Figure 2-6 CSW2012 Dimensions ....................................................... 10
Figure 2-7, DC Cable to Battery Terminals ........................................... 17
Figure 2-8, DC Cable to Inverter’s DC Terminals .................................. 17
Tables
Table 2-1, DC Terminal - Torque Requirements .................................... 11
Table 2-2, DC Wire/Overcurrent Device for Rated Use ........................... 13
Table 2-3, Appliance Power Consumption and Run Time ........................ 15
Table 3-1, Examples of Digital Display Readings ................................... 20
Table 4-1, Troubleshooting Guide ....................................................... 22
Table 4-2, CSW1012 and CSW2012 Inverter Error Codes ...................... 22
Table 5-1, CSW Series Specifications .................................................. 23
iv © 2015 Sensata Technologies
Page 6
1.0 Introduction
1.0 Introduction
Congratulations on your purchase of the CSW Series pure sine wave inverter. The CSW Series includes the CSW412, CSW1012 and CSW2012 inverters; under the Magnum-Dimensions brand from Sensata Technologies. The CSW Series inverters are “pure” sine wave inverters designed to be powerful, yet simple to operate, and will provide you with reliable AC power for trouble-free use. Please read this chapter to familiarize yourself with the features and benefi ts of your CSW Series inverter.
1.1 Features - CSW1012 and CSW2012
The front panels of the CSW1012 and CSW2012 inverters are similar and are equipped with the following features (see Figure 1-1):
1. Serial Number – the unique identifi cation number assigned to each unit
(with a model-specifi c prefi x). Note: Enter your inverter’s serial number in
the table at the bottom of page i. It is to easier to record this information now, instead of trying to gather it after the unit has been installed.
2. GFCI – a Ground Fault Circuit Interrupter protected AC outlet. The GFCI
outlet quickly stops the fl ow of electricity in the event a ground fault occurs on the device that is plugged into the inverter.
3. Status Indicator – an at-a-glance LED that provides the inverter’s
status—lights green, red, or amber (see Section 3.0 Operation).
4. Digital Display – a three-character alphanumeric display that shows
the inverter’s measured battery voltage, total AC output power, and any error or warning codes.
5. Power/Select Button – a momentary button switch that allows the
inverter to be quickly turned on or off.
6. Remote Port – a RJ11 connector that allows an optional remote switch to
be connected via a remote cable. Note: Remote switch is sold separately
(PN: CSW-RS).
7. USB Port – allows USB-enabled devices to be powered and charged.
1
2
Figure 1-1, Front Panel Features (CSW1012 and CSW2012)
© 2015 Sensata Technologies 1
3
4
5
6
7
Page 7
1.0 Introduction
The back panels of the CSW1012 and CSW2012 inverters are equipped with the following features (See Figure 1-2 and Figure 1-3):
8. Cooling Fan(s) – an intake cooling fan that automatically turns on when
the inverter’s internal temperature rises above 122°F (50°C). The fan turns off when the inverter’s internal temperature falls below 122°F (50°C).
9. Mounting Flanges (front and rear) – used to mount and secure the
inverter to a shelf/wall.
10. DC Negative Terminal (black) – the inverter’s connection to the
negative terminal on the 12 VDC battery bank.
11. DC Positive Terminal (red) – the inverter’s connection to the positive
terminal on the 12 VDC battery bank.
12. Model Number – the model number of the inverter (i.e., CSW1012),
and other information.
13. DC Chassis Ground Connection – the connection that is used to tie
the exposed chassis of the inverter to the DC grounding system. The DC grounding system could be the vehicle’s chassis, the DC grounding bus, or to the engine’s negative bus.
8
9
11
10
10
11
12
13
Figure 1-2, Back Panel Features (CSW1012)
12
8
13
Figure 1-3, Back Panel Features (CSW2012)
2 © 2015 Sensata Technologies
9
Page 8
1.0 Introduction
1.2 Features - CSW412
The CSW412 inverter is equipped with the following front panel features (see Figure 1-4):
1. Power Indicator – an at-a-glance LED that lights green when the inverter
is on. (see Section 3.0 Operation).
2. Fault Indicator – an at-a-glance LED that comes on to indicate an
inverter fault (see Section 4.0 for troubleshooting).
3. USB Port – allows USB-enabled devices to be powered and charged.
4. ON/OFF Power Switch – a 2-position switch that turns the inverter
on and off.
5. Serial Number – the unique identifi cation number assigned to each unit
(with a model-specifi c prefi x). Note: Enter your inverter’s serial number in
the table at the bottom of page i. It is to easier to record this information now, instead of trying to gather it after the unit has been installed.
6. GFCI – a Ground Fault Circuit Interrupter protected AC outlet. The GFCI
outlet quickly stops the fl ow of electricity in the event a ground fault occurs on the device that is plugged into the inverter.
1
2
3
4
5
6
Figure 1-4, Front Panel Features (CSW412)
© 2015 Sensata Technologies 3
Page 9
1.0 Introduction
The back panel of the CSW412 inverter is equipped with the following features (see Figure 1-5):
8. Cooling Fan – an intake cooling fan that automatically turns on when the
inverter’s internal temperature rises above 122 °F (50 °C). The fan turns off when the inverter’s internal temperature falls below 122 °F (50 °C).
9. DC Negative Terminal (black) – the inverter’s connection to the
negative terminal on the 12 VDC battery bank.
10. Mounting Flanges (front and rear) – used to mount and secure the
inverter to a shelf/wall.
11. Model Number – the model number of the inverter (i.e., CSW412), and
regulatory compliance information.
12. DC Positive Terminal (red) – the inverter’s connection to the positive
terminal on the 12 VDC battery bank.
8
9
11
12
10
Figure 1-5, Back Panel Features (CSW412)
1.3 Regulatory Compliance
The CSW Series inverters are intended to be used for land vehicles (RVs or trucks) or marine craft. They are listed to UL Standard 458, 5th Edition (Power Converters/Inverters and Power Converter/Inverter Systems for Land Vehicles and Marine Crafts) for use in the US; and are also certifi ed to CSA Standard C22.2 No. 107.1-01 (General Use Power Supplies) for use in Canada.
These inverters have been tested and certifi ed to product safety standards by Intertek Testing Services (known as ETL), which is a Nationally Recognized Testing Laboratory (NRTL). NRTLs are qualied organizations that meet Occupational Safety and Health Administration (OSHA) regulations to perform independent safety testing and product certifi cation.
4 © 2015 Sensata Technologies
Page 10
2.0 Installation
2.0 Installation
Review this section and all safety instructions before proceeding with the installation of your inverter.
WARNING: Installations should be performed by qualified personnel, such as a licensed or certifi ed electrician. The installer
determines which safety codes apply and ensures all applicable installation requirements are followed. Applicable installation codes vary depending on the specifi c location and application.
WARNING: Before installing, review the “Important Product Safety
Information” on page ii and adhere to all cautionary markings located on the inverter and on the batteries.
2.1 Pre-Installation
Before proceeding, read the entire Installation section to determine how best to install your CSW Series inverter. The more thorough you plan in the beginning, the better your inverter needs will be met. Depending on your application, there are simplifi ed system diagrams shown in Figure 2-1 and Figure 2-2. These should be reviewed to assist you in planning and designing your installation. These drawings are not intended to override or to restrict any national or local electrical codes, and should not be the determining factor as to whether the installation is compliant, that is the responsibility of the electrician and the onsite inspector.
2.1.1 Installation Guidelines
Before connecting any wires, determine the cable routes throughout the
vehicle or boat, both to and from the inverter.
Always check for existing electrical, plumbing, or other areas of potential
damage BEFORE drilling or cutting into walls.
Make sure all wires have a smooth bend radius and do not become kinked.
If installing this inverter in a boat, RV or truck, ensure the conductors
passing through walls, bulkheads, or other structural members are protected. This minimizes insulation damage (such as chafi ng), which can be caused by vibration or constant rubbing.
2.1.2 Unpacking and Inspection
Carefully remove the inverter from its shipping container and inspect all contents. Verify the following items are included:
CSW Series inverter
CSW Series Owner’s Manual
If items appear to be missing or damaged, contact your authorized Magnum­Dimensions dealer or Magnum-Dimensions directly.
*** Save your proof-of-purchase as a record of your ownership; it
is needed if the unit should require in-warranty service. ***
2.1.3 Tools Required
Installing the inverter is simple and requires the following:
• Adjustable wrench (10-13 mm) • Level • Drill
#10 Mounting screws (x4) • Pencil • Drill bits
• Phillips screwdriver
© 2015 Sensata Technologies 5
Page 11
2.0 Installation
AC Source
(120VAC, 60 Hz Sinewave)
CSW-TS15
Transfer Switch
CSW Series
Inverter
AC IN
AC
Main Panel
(Branch Circuit
Breaker to
Transfer
Switch:
15A max)
AC OUT
DC
Ground
(Vehicle
chassis, DC
grou nd bus,
or engine
neg ative bus)
Battery
Bank
Disconnect
Fuse
AC
Sub-Panel
DC
AC
Outlet
AC Loads
(15A max)
TV
Tools
DVD
Figure 2-1, Basic System Diagram
6 © 2015 Sensata Technologies
Page 12
AC Source
(120VAC, 60 Hz Sinewave)
CSW-TS15
Transfer Switch
AC IN
AC OUT
2.0 Installation
AC
Main Panel
(Branch Circuit
Breaker to
Transfer
Switch:
15A max)
Dedicated
AC Load
(15A max)
CSW Series
DC
Ground
(Vehicle
chassis, DC
grou nd bus,
or engine
neg ative bus)
Battery
Inverter
Fuse
Bank
DC
Disconnect
Notes: The NEC requires overcurrent protection for wiring and equipment in both AC and DC circuits. As shown in this diagram, the RVIA allows the following application where an inverter is installed in a RV.
Pass-thru mode: When the AC source (generator or shore power) powers loads thru a transfer switch (i.e., pass­thru mode), the condu ctor from the transfer switch to the dedicated load will be protected as long as the branch rated circuit breaker at the AC source does not exceed the ampacity of the conductor feeding the dedicated load.
Inverter Mode: When the inverter is powering loads us ing power from the battery (i.e., Inverter mode), the conductor from the inverter output to the dedicated load will be protected as long as the ampacity of the conductor is sized based on the inverter’s AC output rating. In Inverter mode, the inverter has overcurrent protection to limit the output current and to protect the co nductor.
Figure 2-2, RV OEM System Diagram
© 2015 Sensata Technologies 7
Page 13
2.0 Installation
2.2 Locating and Mounting the Inverter
WARNINGS:
• Do not mount the inverter near any flammable or combustible fluid or components.
• Provide adequate clearance/ventilation to the inverter. Do not cover or obstruct any air vent openings and/or install in a zero­clearance compartment.
The inverter should only be installed and mounted in a location that meets the following requirements:
Clean and dry – The inverter should not be installed in an area that allows
dust, fumes, insects, or rodents to enter or block the inverter’s ventilation openings. This area also must be free from any risk of condensation, water, or any other liquid that can enter or fall on the inverter. these conditions is not covered under warranty.
Cool – The inverter should be protected from direct exposure to the sun or
to any equipment that produces extreme heat. The ambient temperature should be between 32° F (0° C) and 104° F (40° C); note that the inverter’s output specifi cations are rated at 77° F (25° C), so the cooler the better.
Ventilated – In order for the inverter to provide full output power and
avoid over-temperature fault conditions, do not cover or block the inverter’s ventilation openings, or install this inverter in an area with limited airflow. Allow a minimum airspace clearance of 3” (7.6 cm) around the unit to provide optimum ventilation.
Safe – Keep any flammable/combustible material (e.g., paper, cloth, plastic,
etc.,) that may be ignited by heat, sparks, or flames at a minimum distance of 2 feet (60 cm) away from the inverter. Do not install in any area that contains extremely flammable liquids like gasoline or propane, or in locations that require ignition-protected devices.
Close to the battery bank – As with any inverter, it should be located as
close to the batteries as possible. Long DC wires tend to lose efficiency and reduce the overall performance of an inverter. However, the unit should not be installed in the same compartment as the batteries or mounted where it will be exposed to gases produced by the batteries. These gases are corrosive and will damage the inverter; also, if these gases are not ventilated and if allowed to collect, they could ignite and cause an explosion.
Accessible – Do not block access to the front or back of the inverter. Allow
room to view any indictors or digital display and to access the AC and DC wiring connections—they will need to be checked and tightened periodically.
Orientating the inverter - When mounted indoors, the CSW Series inverter
can be mounted on/underneath a horizontal surface (shelf or table) or on a vertical surface (wall or bulkhead) with the DC terminals facing left or right. Additionally, the CSW1012 and CSW2012 can be mounted with the DC terminals facing up (CSW412 cannot be mounted with terminal’s facing up or down)—do not mount with the DC terminals facing downward (see Figure 2-3). When mounted in an RV, mount flat on a horizontal surface only.
After determining your mounting position, use the base of the inverter’s chassis as a template to mark your mounting screw locations (or, refer to the dimensions in Figures 2-4 thru 2-6). Remove the inverter and drill pilot holes into the mounting surface. Secure the inverter to the surface using the appropriate corrosion-resistant hardware. If this unit is used in a mobile application, you may want to place flexible washers or bushings between the mounting surface and the inverter’s mounting flanges to reduce vibration.
Inverter failure under
8 © 2015 Sensata Technologies
Page 14
For Indoor Use:
Flat on a
horizontal
surface
(right side
up or
upside
down).
2.0 Installation
DC terminals to the right,
left or the top.
Note: The CSW
inverter cannot
be mounted with the DC
terminals facing
down.
For RV Installation:
Mount flat on a
horizontal surface only
Figure 2-3, Approved Mounting Positions
To p
6.9’’ (17.5 cm)
Front (AC Side) Back (DC Side)
5.8’’ (14.7 cm)
6.3’’ (16.1 cm)
7.9’’ (20 cm)
© 2015 Sensata Technologies 9
3.4’’
(8.7 cm)
Figure 2-4 CSW412 Dimensions
Page 15
2.0 Installation
To p
10.3’’ (26.2 cm)
To p
6.9’’ (17.5 cm)
12.6’’ (32.1 cm)
Front (AC Side) Back (DC Side)
3.4’’
(8.4 cm)
Figure 2-5 CSW1012 Dimensions
13.4’’ (34 cm)
6.3’’ (16.1 cm)
9.1’’ (23 cm)
Front (AC Side)
Figure 2-6 CSW2012 Dimensions
10 © 2015 Sensata Technologies
8.5’’ (21.6 cm)
16.5’’ (41.9 cm)
Back (DC Side)
3.5’’
(8.9 cm)
Page 16
2.0 Installation
2.3 Wiring the Inverter – General Requirements
This section describes the requirements and recommendations for wiring the CSW Series inverter. Before wiring the inverter, carefully read all instructions.
WARNING: Wiring should meet all local codes/standards and be performed by qualifi ed personnel (i.e., licensed electrician).
2.3.1 Wiring Requirements
All conductors that are at risk for physical damage must be protected by tape or placed in a raceway.
Always check for existing electrical, plumbing, or other areas of potential damage prior to making cuts in structural surfaces or walls.
Where DC wiring must cross AC or vice-versa, try to make the wires at the crossing point perpendicular (90 degrees) to one another.
DC overcurrent protection must be provided as part of the installation.
Use only copper wires with a minimum temperature rating of 75° C (194° F).
2.3.2 Torque Requirements
All wiring to the DC terminals and DC ground connection should be checked periodically (once a month) for proper tightness. For the torque requirements, refer to Table 2-1. If you don’t have a torque wrench, ensure all connections are tight.
Table 2-1, DC Terminal - Torque Requirements
Inverter
Model
CSW412
CSW1012
CSW2012
DC
Terminals
Hex Cap
screws
M6 x 1.0 Hex nuts
M8 x 1.25
Hex nuts
Torque
Requirements
52 to 58 lbf-in
(5.9 to 6.5 N-m)
79 to 96 lbf-in
(8.9 to 10.9 N-m)
16 to 21 lbf-ft
(22 to 28 N-m)
Torque Wrench
12 mm wrench
10 mm wrench
13 mm wrench
Size Needed
© 2015 Sensata Technologies 11
Page 17
2.0 Installation
2.4 DC Wiring
This section describes the inverter’s required DC wire sizes, the recommended disconnect/overcurrent protection, and how to make the DC connections to the inverter and the battery bank.
WARNING: Even though DC voltage can be regarded as “low voltage”, signifi cant hazards may be present, particularly from short
circuits of the battery system.
CAUTION: The inverter is NOT reverse polarity protected—which
means if the negative and positive battery voltage is connected to the inverter backwards, the inverter will likely be damaged. Use a voltmeter to verify the correct polarity BEFORE connecting the DC wires.
CAUTION: DO NOT connect the battery cables to the inverter until
all wiring is complete and the correct DC voltage and polarity have been verifi ed.
Refer to Figure 2-7 when connecting the DC wires to the battery, and to Figure 2-8 when connecting to the inverter. Also, consider the following requirements to ensure maximum performance:
The DC positive and negative cables connected to the inverter from the battery bank should be tied together with wire ties/straps or electrical tape approximately every 6 inches (15.3 cm). This helps improve the surge capability and reduces the effects of inductance, which improves the inverter waveform and reduces the wear of the inverter’s fi lter capacitors. Keeping the battery cables close together also reduces the chance of radio frequency interference.
Be aware that over-tightening or misthreading the nuts on the DC terminals can cause the bolts to strip and snap/break off.
Make sure cables have a smooth bend radius and do not become kinked. Follow existing wire runs where possible.
Crimped and sealed copper ring terminal lugs with at least a 6 mm (1/4”) bolt hole to connect the DC wires to the inverter’s DC terminals.
The battery bank voltage MUST be between 10.5-15.5 (10.5 - 15.75 for the CSW412) for the inverter to operate. If the voltage exceeds 16.0V, the inverter may be damaged.
To ensure the maximum performance from the inverter, all connections from the battery bank to the inverter should be minimized. The exceptions are the DC fuse and disconnect, or the DC circuit breaker— required at the battery to protect the DC wiring—in the positive line. Any other additional connection will contribute to additional voltage drops, and these extra connection points may loosen during use.
A brief spark or arc may occur when connecting the battery cables to the inverter DC terminals; this is normal and due to the inverter’s internal capacitors being charged.
Before routing the wiring, color code the DC cables/wires with colored tape or heat shrink tubing: RED for positive (+); WHITE for negative (–); and GREEN (or bare copper) for DC ground, to avoid polarity problems.
A cable should be connected directly from the inverter negative terminal to the battery negative connection; this ensures the inverter has a reliable return path directly to the battery. Do not use the chassis in place of the battery negative connection to the inverter.
12 © 2015 Sensata Technologies
Page 18
2.0 Installation
CSW412 CSW1012 CSW2012
38 amps 94 amps 187 amps
46 amps 113 amps 224 amps
#8 AWG
(8.36 mm²)
#8 AWG
(8.36 mm²)
#8 AWG
(8.36 mm²)
#10 AWG
(5.26 mm²)
[50 amps]
#2 AWG
(33.6 mm²)
[170 amps]
#3/0 AWG
(85 mm²)
[310 amps]
50 amps with
time delay
150 amps with
time delay
300 amps with
time delay
▼▼▼
5 - 10 feet
(1.5 - 3 m)
#8 AWG
(8.36 mm²)
#1 AWG
(42.4 mm²)
#4/0 AWG
(107 mm²)
10 - 15 feet
(3 - 4.6 m)
#6 AWG
(13.3 mm²)
#1/0 AWG
(53.5 mm²)
Not
recommended
Note 1 - Maximum Continuous Current is based on the inverter’s continuous power rating at the lowest input voltage with an inefficiency factor. Note 2 - The grounding conductor for the DC system shall meet the sizing requirements specified in the NEC for the application, but must be no smaller than 8 AWG copper. In some applications, the DC grounding conductor is required to be no less than the wire size of the DC positive/negative cables.
Inverter Model
Full Load C urrent
Maximum C ontinuous
Current¹
Minimum DC Ground
Wire Size
2
Minimum DC Wire Size
[75˚C rating in free air]
Maximum DC Fuse Size
Increased
size for
longer
distance
2.4.1 DC Wire Sizing
It is important to use the correct sized DC wire to achieve maximum effi ciency from the system and to reduce fi re hazards associated with overheating. Always keep your wire runs as short as practical to prevent low voltage shutdowns and to keep the DC breaker from nuisance tripping (or open fuses) because of increased current draw. See Table 2-2 to select the minimum DC wire size (and corresponding overcurrent device) required based on your inverter model. The cable sizes listed in this table are required in order to reduce stress on the inverter, minimize voltage drops, increase system effi ciency, and ensure the inverter’s ability to surge heavy loads.
If the distance from the inverter to the battery is >5 feet (1.5 m), the DC wire will need to be increased. Longer cable distances affect the performance of the inverter. See the lower part of Table 2-2 to determine the minimum DC wire size needed for various distances greater than 5 feet—based on your inverter model.
DC Wire Size Exception: In an OEM RV application, smaller DC wire (with
appropriate overcurrent protection) may be used if the inverter will only be connected to a dedicated load (as shown in Figure 2-2), and the inverter and dedicated load have been thoroughly tested and sold together by the OEM as a complete system.
Table 2-2, DC Wire/Overcurrent Device for Rated Use
© 2015 Sensata Technologies 13
Page 19
2.0 Installation
2.4.2 DC Overcurrent Protection
For safety reasons and to comply with electrical code regulations, DC overcurrent protection must be provided as part of the installation. The DC overcurrent protection device must be installed in the positive DC cable line, it can be a fuse (with a disconnect switch) or a circuit breaker and must be DC-rated. It must be correctly sized according to the size of DC cables being used, which means it is required to open before the cable reaches its maximum current carrying capability, thereby preventing a fi re. The NEC requires both overcurrent protection and a disconnect switch.
Because batteries can deliver thousands of amps in an instant during a short, you are required to install a DC-rated fuse (or circuit breaker) that has a interrupt current rating (known as Amps Interrupting Current or AIC) that can withstand the short-circuit current without explosion or damage. If a fuse is used as an overcurrent device, a Class-T type or equivalent is highly recommended when used with inverters. A Class-T fuse is rated for DC operation, can handle very high short-circuit currents (up to 100,000 amps), and has a time delay that allows for momentary current surges from the inverter without opening the fuse. In some installations, if the combined short-circuit current of all the batteries in the bank is determined to be 2,700 amps or less, then an ANL type of fuse may be used—if in doubt, use a Class-T fuse. See Table 2-2 for the fuse size (coordinated with the DC wire size) recommended for your CSW inverter.
2.4.3 DC Grounding
The inverter should always be connected to a permanent, grounded wiring system. The idea is to connect the metallic chassis of the various enclosures together to have them at the same voltage potential, to reduce the possibility for electric shock. For most installations, the inverter chassis and the negative battery conductor are connected to the system’s ground bond via a safety grounding conductor (bare wire or green insulated wire) at only one point in the system. The grounding conductor for the DC system shall meet the sizing requirements specifi ed in the NEC for the application, but must be no smaller
than 8 AWG copper. For instance: An inverter used in a marine application under
ABYC guidelines requires the size of the DC grounding conductor to be of an ampacity equal to or one size less than that of the DC positive conductor. See
Table 2-2 for the minimum ground wire size recommended for your inverter.
Info: If the inverter is installed in a vehicle, connect the battery
negative cable directly to the inverter’s negative terminal. DO NOT connect the negative battery cable meant for the inverter to the vehicle’s frame/safety ground.
2.4.4 DC Cable Connections
Do not put anything between the battery cable ring lug and the battery post (see Figure 2-7), or the fl at metal part of the inverter’s DC terminal (see Figure 2-8). When connecting the battery cable, it should be placed directly against the battery post or inverter terminal. Incorrectly installed hardware causes a high resistance connection which could lead to poor inverter performance, and may melt the cable and terminal connections. See Table 2-1 for the torque requirements.
Info: The DC terminal and Hex nuts on the CSW1012 and CSW2012
are made of stainless steel, which has a high likelihood of galling or thread seizing while being tightened—causing the bolts to strip or to snap/break off. To reduce this risk, use an anti-seize lubricant, tighten the fasteners slowly (at low rpms) without interruption, and apply only light pressure.
14 © 2015 Sensata Technologies
Page 20
2.0 Installation
2.4.5 Wiring the Battery Bank
WARNING: Lethal currents will be present if the positive and
negative cables attached to the battery bank touch each other. During the installation and wiring process, ensure the cable ends are insulated or covered to prevent touching/shorting the cables.
Info: DO NOT connect the DC wires from the battery bank to
the inverter until 1) all DC wiring is complete, 2) the correct DC overcurrent protection has been installed, and 3) the correct DC voltage and polarity have been verifi ed.
Depending upon the voltage of the batteries (6 or 12 VDC), the batteries must be wired in series, parallel, or series-parallel to provide the correct voltage. The interconnecting DC wires must be sized and rated exactly the same as those used between the battery bank and the inverter.
Place the batteries as close as practical to the inverter, preferably in an insulated and ventilated enclosure. Allow adequate space above the batteries to access the terminals and vent caps (as applicable). Also, allow at least 1” (2.5 cm) of space between the batteries to provide good air fl ow. DO NOT mount the batteries directly under the inverter.
CAUTION: Install batteries in a well ventilated area. Batteries
can produce explosive gasses. For compartment or enclosure installations, always vent batteries to the outside.
Info: To ensure the best performance from your inverter system,
batteries should be of the same size, type, rating, and age. Do not use old or untested batteries.
2.4.6 Appliances and Run Time
The CSW Series inverters can power a wide range of household appliances including small motors, hair dryers, clocks, and other electrical devices. As with any appliance using batteries for power, there is a certain length of time that it can run—this is called “run time.” Table 2-3 below provides estimates of power consumption and run time for various appliances using a 12V-120AH battery bank.
Table 2-3, Appliance Power Consumption and Run Time
Load Consumption Estimated Run Time
Cordless Phone 5W 180 hrs
Clock/Radio 8W 135 hrs
Table Lamp 40W/60W 27 hrs/18 hrs
Freezer (8.8 cu ft) 80W 15 hrs
20” LCD TV 100W 11.5 hrs
Refrigerator (18 cu ft) 120W 9 hrs
Sump Pump (1/2 hp) 350W 3 hrs
Microwave (mid-size) 1000W 49 min
Coffee Maker 1200W 37 min
© 2015 Sensata Technologies 15
Page 21
2.0 Installation
2.4.7 Wiring the Inverter to the Battery Bank
CAUTION: The inverter is NOT reverse polarity protected—if the
positive terminal of the battery is connected to the negative terminal of the inverter and vice versa, severe damage to the inverter will
occur and this will void the warranty. Before connecting the DC wires
from the batteries to the inverter, verify the correct battery voltage and polarity using a voltmeter. If necessary, color code the cables (with colored tape): red for positive (+), and white for negative (-) to avoid polarity confusion.
Info: The DC overcurrent device (i.e., circuit breaker or fuse) must
be placed in the positive (red) DC cable line between the inverter’s positive DC terminal and the battery’s positive terminal (red)—as close to the battery as possible. For maximum protection, install it within 18 inches (45 cm) of the battery.
Follow the steps below to wire the inverter to the battery bank:
1. Route an appropriately sized DC negative wire (marked white) from the negative terminal of the battery bank to the inverter’s negative terminal (Item 10, Figures 1-2 and 1-3; Item 9, Figure 1-5).
2. Mount the fuse/disconnect assembly (or circuit breaker) as near as practical to the batteries and leave open (i.e., no power to inverter).
WARNING: DO NOT close the DC circuit breaker or connect the
fuse to connect battery power to the inverter at this time. This will occur after the installation is complete.
CAUTION: If connecting live battery cables to the inverter DC
terminals, a brief spark or arc may occur; this is normal and due to the inverter’s internal capacitors being charged.
3. Route and connect an appropriately sized DC positive wire (marked red) from the inverter’s positive DC terminal (Item 11, Figures 1-2 and 1-3; Item 13, Figure 1-5) to one end of the fuse/disconnect assembly (or circuit breaker).
4. Connect a short wire (same rating as the DC wires) to the other side of the DC circuit breaker (or one end of the fuse/disconnect assembly) and the other end of that short wire to the positive terminal of the battery bank (see Figure 2-1 or Figure 2-2 for reference). This is essential to ensure even discharging across the entire battery bank.
5. Ensure the DC wire connections (on the batteries, inverter, and DC circuit breaker/fuse) are fl ush on the surface of the DC terminals, and all hardware used to hold these connections are stacked correctly (see Figures 2-7 and 2-8). Verify all DC connections on the inverter are torqued correctly (see Table 2-1), and the total cable distance from the inverter to the battery is within the requirement of Section 2.4.1 (DC Wire Sizing).
6. Once the DC connections are completely wired and tested, coat the terminals with an approved anti-oxidizing spray.
7. If the batteries are in an enclosure, perform a fi nal check of the connections to the battery terminals, then close and secure the battery enclosure.
8. Route an appropriately sized DC ground wire (see Table 2-2) from the inverter’s DC chassis ground connection to a dedicated system ground.
9. Once the entire installation is complete and all connections verifi ed, close the fuse disconnect (or circuit breaker) to provide power to the inverter.
16 © 2015 Sensata Technologies
Page 22
2.0 Installation
battery
post
nut
lock washer
DC cable
with ring lug
BATTERY
battery terminal
flat wa sher
bolt
DC cable lugs are flush
with the battery terminals.
Figure 2-7, DC Cable to Battery Terminals
Verify that the
M6-1.0 hex nut
lock washer
#12 flat washer
DC cable
with ring lug
Inverter’s DC
+ terminal
CSW1012
Inverter
Ensure nothing is placed
CAUTION:
between the DC terminal
and the ring lug.
Figure 2-8, DC Cable to Inverter’s DC Terminals
© 2015 Sensata Technologies 17
Page 23
2.0 Installation
2.5 Testing the Inverter
Before proceeding, you must fi rst test whether the inverter was successfully installed. Use the functional test below to test the inverter, and then perform the GFCI test that follows to ensure the protection device is functioning properly.
2.5.1 Inverter Functional Test
After all electrical connections to the inverter and batteries have been completed, plug a small AC load (e.g., 40W light bulb or small appliance) into the GFCI’s outlet, and follow these steps to test the installation and the inverter’s operation.
• CSW412 inverters:
1. Toggle the ON/OFF Power Switch to the ON (I) position to turn the unit on.
2. The Power Indicator will turn on to indicate that the AC output power is available.
3. Check that the AC load is on (i.e., the bulb lights).
Note: If the bulb does not light, the GFCI may have tripped. Reset the GFCI by pressing the RESET button.
CSW1012 and CSW2012 Inverters:
1. Press and hold the Power/Select button until a beep sound is heard (about 1 second). The Status light turns on.
2. Check that the digital display alternately shows the inverter’s measured battery voltage and output power.
3. Check that the AC load is on (i.e., the bulb lights).
Note: If the bulb does not light, the GFCI may have tripped. Reset the GFCI by pressing the RESET button.
If the inverter passes all steps, it is functioning properly and ready for use.
If the inverter fails any of the steps, refer to the troubleshooting information in Section 4.0.
2.5.2 GFCI Function Test
Use the steps below to periodically test the GFCI to ensure it is functioning properly.
1. Turn the inverter on.
2. Plug a small AC load (e.g., 40W light bulb) into the GFCI’s outlet.
3. Check that the AC load is on (i.e., the bulb lights).
4. Press the GFCI’s TEST button. The GFCI’s RESET button should pop out, and the power should shut off (light bulb goes out).
Note: If the bulb remains lit or the RESET button does not pop out, the GFCI may not be functioning properly.
5. Press the RESET button. The AC load should come back on (bulb lights again).
18 © 2015 Sensata Technologies
Page 24
3.0 Operation
3.0 Operation
When the inverter is properly connected to batteries and turned on, the direct current (DC) from the batteries is transformed into a pure sine wave alternating current (AC). This AC is similar to the voltage provided by your utility and is used to power any electrical appliances (i.e., AC loads) connected to the inverter’s output.
3.1 CSW412 Operation
The CSW412 inverter uses a front panel that contains a power on/off switch, two LED indicators, a USB port, and a GFCI AC output receptacle.
Turning the Inverter on and off
The ON/OFF Power switch is used to turn the inverter on and off. To turn the unit on, toggle the switch to the ON (I) position. The Power indicator lights green to indicate that the AC output power is available. Press the ON/OFF switch to the OFF (O) position to turn the unit off.
WARNING: The Power ON/OFF Switch is not a power disconnect
switch and will not remove the DC power from the inverter. Disconnect all power to the inverter before working on the unit.
LED Indicators
The LED indicators on the front panel are used to indicate the inverter’s status:
Power LED (green)– the inverter has power and is turned on.
• Fault LED (red) – an inverter fault has been detected which caused the
inverter to shut down. If the fault indicator comes on:
1. Determine and resolve the fault condition (e.g., high or low voltage, load too large, or over-temperature).
2. Reset the inverter by toggling the ON/OFF Power Switch off, then back on.
USB Port
The USB Port enables you to power and charge a USB-enabled device (provides 5 VDC/750 mA).
CAUTION: Some USB-powered products may be damaged when
connected to this USB port. If in doubt, check with the product’s manufacturer.
GFCI Outlet
The two GFCI-protected AC outlets are used to plug in and power an AC load. It protects the user against hazardous electrical shocks.
© 2015 Sensata Technologies 19
Page 25
3.0 Operation
3.2 CSW1012 and CSW2012 Operation
The CSW1012 and CSW2012 inverters use a front panel that contains a power/select button, a status indicator, a digital display for viewing system status, a remote port, a USB port, and a GFCI AC output receptacle.
Turning the Inverter on and off
The Power/Select button is used to turn the inverter on and off. To turn the unit on, press and hold the button for 1 second until you hear a “beep”. The digital display alternately shows the unit’s measured battery voltage and AC output power, and the status indicator lights green. Press the power/select button to turn the unit off.
WARNING: The power/select button is not a power disconnect
switch and will not remove the DC power from the inverter. Disconnect all power to the inverter before working on the inverter.
Status Indicator
The Status indicator on the front panel may light green, amber, or red to indicate the inverter’s status. When the status indicator lights:
• Green – the inverter is operating normally.
• Amber – a warning has been detected. The inverter will shut down at
any time. Check the error code on the digital display.
• Red – an error has been detected and the unit has shut down. Check
the error code on the digital display.
When the status indicator lights amber or red, use the digital display and the troubleshooting tables in Section 4.0 to resolve the issue.
Digital Display
The Digital Display has one line of three alphanumeric characters that alternately shows the inverter’s measured battery voltage (in volts) and AC output power (in kilowatts) under normal operating conditions. It also displays error/warning codes that alert you to problems with the unit, and are used in conjunction with the troubleshooting tables in Section 4.0 to resolve any issues with the inverter’s operation. See Table 3-1 below.
Table 3-1, Examples of Digital Display Readings
Display Meaning
12.5 Measured battery voltage.
0.80 Total AC output power in kW (800W as shown).
E01 Error or warning code. See Troubleshooting section for details.
Remote Port
The Remote Port is used to connect an optional ON/OFF remote switch (sold separately) that works in parallel with the power/select button.
USB Port
The USB Port enables you to power and charge a USB-enabled device (provides 5 VDC/750 mA).
CAUTION: Some USB-powered products may be damaged when
connected to this USB port. If in doubt, check with the product’s manufacturer.
GFCI Outlet
The two GFCI-protected AC outlets are used to plug in and power an AC load. It protects the user against hazardous electrical shocks.
20 © 2015 Sensata Technologies
Page 26
3.0 Operation
3.3 Understanding Loads
The inverter can power most loads within its power rating, however, there are special conditions that can cause a load to behave differently than expected. Following are some common problems encountered when using this inverter.
USB loads – When using the USB connector, be sure that the device you will
be connecting will accept 5 volts ( 750mA) and can be charged or powered using another power source. The USB port can safely power and charge alot of devices such as: MP3 players, mobile phones, and portable video game players. However, some devices such as GPS receivers and some cameras may not work and may even be damaged. Refer to the owner’s guide for each device to determine its compatibility.
Motor loads not starting – Some appliances, particularly those with
induction motors, require a much higher start-up surge than they do when running. Pumps, freezers and refrigerators (compressors) are the most common. The inverter may not be able to start some of these appliances even though their rated current draw is within the inverter’s limits. If you have the CSW1012 or CSW2012 and a motor-operated appliance refuses to start, observe the VOLTS indicator on the digital display while you are trying to start the appliance. If the display shows a battery drop below 11 volts while the inverter is trying to start the motor, this may explain why the appliance won’t run. Make sure the length and diameter of the battery cables are appropriate. Check that the battery connections are good and that the battery is fully charged. If the cables are sized correctly, the connections are good, and the battery is charged, you may need a larger battery bank (see Loads turning on and off).
Loads turning off and on – If a load starts but quickly turns off, then the
battery may not be able to deliver the necessary amperage to drive the load. If the battery bank cannot deliver the necessary amperage to drive a heavy load, the inverter will shut OFF due to low voltage (<10.5 VDC). The battery voltage can then slowly rise back above the low voltage reconnect voltage (11.8 VDC) causing the inverter to resume operation. As soon as the heavy load draws the batteries down, this cycle will continue unless the load is reduced or more batteries are added.
Loads too large – Although the CSW Series inverter can provide high
surge power up to two times the rated output power, some appliances may still trigger the inverter shutdown/protection system. In these instances, a higher power inverter may be required.
Running several loads at once – Sometimes the total surge requirement
of all the loads is higher than the CSW Series inverter can deliver. You may want to turn them on individually to ensure that the inverter does not have to deliver the starting current for all the loads at once.
3.4 System Maintenance
Battery Charging
When possible, recharge your batteries when they are about 50% discharged or earlier. This gives them a much longer life cycle than recharging when they are almost completely discharged.
Inverter Maintenance
Routine maintenance is required to keep the CSW Series inverter operating properly. Periodically you should:
• Clean the exterior of the unit with a damp cloth to prevent the accumulation of dust and dirt.
• Tighten the screws on the DC input terminals.
© 2015 Sensata Technologies 21
Page 27
4.0 Troubleshooting
4.0 Troubleshooting
Use Table 4-1 to troubleshoot your inverter. For CSW1012 or CSW2012 inverters, also use Table 4-2 to view the unit’s digital display to determine what condition triggered the error/warning code and what corrective action is needed.
Table 4-1, Troubleshooting Guide
Problem Symptom Solution
No AC output. Status indicator is off.
No AC output. Status indicator is green.
No AC output. Fault indicator is on.
The unit is off. Turn on the unit. See Operation
instructions.
No power to inverter.
GFCI was tripped.
Unit has detected a fault and has shut down.
For CSW1012 and CSW2012:
Check if fuse or disconnect switch (if installed) is either blown or turned off.
Check the connected load and reset the GFCI.
Determine and resolve the fault condition (e.g., high or low voltage, load too large, or over-temperature).
Check error code on the display and use Table 4-2 to correct.
Table 4-2, CSW1012 and CSW2012 Inverter Error Codes
Code Condition Corrective Action
E01
Unit has sensed the input voltage is low (<10.5 VDC) and will shut down in 30 seconds.
Immediately recharge the battery (to at least 11.8 VDC), and then restart unit.
Unit has sensed the input
E02
E03
E04
E05
E06
E07
22 © 2015 Sensata Technologies
voltage is high and has shut down.
Unit output has sensed an overload or short circuit and was shut down.
Unit has sensed the internal temperature was high and has shut down.
Unit has sensed the input voltage is low and has initiated a warning alarm (@11.2 VDC).
Unit has sensed that the connected load is close to the overload shutdown limit.
Unit has sensed the internal temperature is high and is close to the thermal shutdown limit.
Check the battery voltage, or if an external charger is connected to the battery bank.
Check the load connected to the output. Reduce the load and restart the unit.
Turn the unit off and wait 15 minutes before restarting. Check if the air fl ow is being blocked.
Recharge the battery (to at least 11.8 VDC) as the unit will shut down shortly.
Reduce the connected load.
Reduce the load and check if any of the unit’s ventilation is blocked.
Page 28
5.0 Specifi cations
Table 5-1, CSW Series Specifi cations
5.0 Specifi cations
Model
CSW412 CSW1012 CSW2012
Electrical Specifi cations
Continuous Power Surge Power (Peak)
1
2
400 W 1000 W 2000 W
800 W 2000 W 4000 W AC Output Voltage (12.5V) 120 VAC RMS ± 5% AC Output Current 3.3 AAC 8.3 AAC 16.6 AAC AC Output Voltage Range 104-127 VAC AC Output Frequency 60 Hz ± 0.5 Hz AC Output Waveform
) Pure sine wave (<3% THD)
AC Output Receptacle NEMA 5-15, Dual GFCI with LED indicator Optimum Effi ciency >90% DC Input Voltage (Nominal) 12.5 VDC
3
DC Operation Voltage Range
10.5 - 15.75 10.5 - 15.5 VDC DC Input Current (Full Load) 38 DCA 94 DCA 187 DCA DC Input Current (No Load) <0.8 ADC <1.2 ADC <1.2 ADC DC Output (USB port) 5V, 750 mA
Protection
Low Voltage Alarm 11.0 VDC 11.2 VDC Low Voltage Shutdown 10.5 VDC Low Voltage Recovery 12.0 VDC 11.8 VDC High Voltage Shutdown
3
15.75 VDC 15.5 VDC Output Power Warning NA Yes, with warning code Output Power Shutdown Yes Yes, with shutdown code Output Power Shutdown Yes Yes, with shutdown code Temperature Warning NA Yes, with warning code Temperature Shutdown Yes Yes, with shutdown code
Display Specifi cations
LED Status Indicator Yes (Power, Fault) Digital display NA volts in, power out, error codes
General Specifi cations
Operating Temperature 32° F to 104° F (0° C to 40° C) Inverter Weight 3.8 lb (1.7 kg) 6.6 lb (3.0 kg) 11.5 lb (5.2 kg)
CSW412: 7,9 x 6.9 x 3.4” (20 x 17.5 x 8.7 cm)
Inverter Size (L x W x H)
CSW1012: 12.6 x 6.9 x 3.4” (32.1 x 17.5 x 8.7 cm) CSW2012: 16.5 x 9.1 x 3.5” (41.9 x 23.0 x 8.9 cm)
Warranty One Year
Regulatory Approval
Conforms to UL STD 458, Certified to CSA STD C22.2 No. 107.1
1: Specifications met when DC voltage at nominal (12.5V) and temp at 25°C. 2: Surge ratings are based on resistive load (output voltage may drop). 3: Damage can occur if input voltage exceeds 16 VDC.
© 2015 Sensata Technologies 23
Page 29
6.0 Service and Warranty Info
6.0 Limited Warranty
Sensata Technologies warrants the CSW Series inverter to be free from defects in material and workmanship that result in product failure during normal usage, according to the following terms and conditions:
1. The limited warranty for this product extends for a maximum of 12 months from the product’s original date of purchase.
2. The limited warranty extends to the original purchaser of the product and is not assignable or transferable to any subsequent purchaser.
3. During the limited warranty period, Sensata will repair or replace at our option any defective parts, or any parts that will not properly operate for their intended use, with factory new or remanufactured replacement items if such repair or replacement is needed because of product malfunction or failure during normal usage. The limited warranty does not cover defects in appearance, or cosmetic, decorative, structural or non-operative parts. Sensata’s limit of liability under this warranty shall be the actual cash value of the product at the time the original purchaser returns the product for repair, determined by the price paid by the original purchaser. Sensata shall not be liable for any other losses or damages.
4. Upon request from Sensata, the original purchaser must prove the product’s original date of purchase by a dated bill of sale, itemized receipt.
5. The original purchaser shall return the product prepaid to Sensata in Everett, WA. After the completion of service under this limited warranty, Sensata will return the product prepaid to the original purchaser via a Sensata selected, non-expedited surface freight within the contiguous United States and Canada; this excludes Alaska and Hawaii.
6. If Sensata repairs or replaces a product, its warranty continues for the remaining portion of the original warranty period or 90 days from the date of the return shipment to the original purchaser, whichever is greater. All replaced products and parts removed from repaired products become the property of Sensata.
7. This limited warranty is voided if:
the product has been modifi ed without authorization.
the serial number has been altered or removed.
the product has been damaged from abuse, neglect, accident, high voltage or corrosion.
the product was not installed/operated according to instructions.
6.1 How to Receive Warranty Service
If your product requires warranty service, contact Sensata (Magnum­Dimensions) at:
Telephone: 425-353-8833, or
• Email:
MagnumWarranty@Sensata.com
If returning your product directly to Sensata (in Everett, WA), you must:
1. Return the unit in the original, or equivalent, shipping container.
2. Receive a Return Materials Authorization (RMA) number from Sensata prior to the return of the product for service.
3. Place RMA numbers clearly on the shipping container or the packing slip.
When sending your product for service, please ensure it is properly packaged.
Damage due to inadequate packaging is not covered under warranty.
We recommend sending the product by traceable and insured service.
BEFORE RETURNING ANY UNIT, A RETURN MATERIAL
AUTHORIZATION (RMA) NUMBER IS REQUIRED
24 © 2015 Sensata Technologies
Page 30
Magnum-Dimensions Products
Web: www.Magnum-Dimensions.com
PN: 64-0063 Rev C