Magnetek DSD 412 Technical Manual

Page 1
DSD 412
DSD 412 DC Elevator Drive
To properly use the product, read this manual thoroughly and retain for easy reference, inspection,
Technical Manual
© Magnetek Elevator 2016
CS00407 rev 11
U39 / U40 97SA407x-0010 Rv16 U13 / U14 97SA404x-0008 Rv08
Page 2
Warranty
Standard products manufactured by the Company are warranted to be free from defects in workmanship and material for a period of one year from the date of shipment, and any products, which are defective in workmanship or material, will be repaired or replaced, at the Company’s option, at no charge to the Buyer. Final determination as to whether a product is actually defective rests with the Company. The obligation of the Company hereunder shall be limited solely to repair or replace, at the Company’s discretion, products that fall within the foregoing limitations, and shall be conditioned upon receipt by the Company of written notice of any alleged defects or deficiency promptly after discovery and within the warranty period, and in the case of components or units purchased by the Company, the obligation of the Company shall not exceed the settlement that the Company is able to obtain from the supplier thereof. No products shall be returned to the Company without its prior consent. Products, which the company consents to have returned, shall be shipped prepaid f.o.b. the Company factory. The Company cannot assume responsibility or accept invoices for unauthorized repairs to its components, even though defective. The life of the products the Company depends, to a large extent, upon type of usage thereof and THE COMPANY MAKES NO WARRANTY AS TO FITNESS OF ITS PRODUCTS FOR THE SPECIFIC APPLICATIONS BY THE BUYER NOR AS TO PERIOD OF SERVICE UNLESS THE COMPANY SPECIFICALLY AGREES OTHERWISE IN WRITING AFTER PROPOSED USAGE HAS BEEN MADE KNOWN TO IT. This warranty does not apply to experimental products for which no warranty is made or given and Buyer waives any claim thereto. THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, BUT LIMITED TO, ANY WARRANTY OF MECHANTIBILITY OR OF FITNESS FOR A PARTICULAR PURPOSE AND BUYER HEREBY WAIVES ANY AND ALL CLAIMS THEREFORE.
Limitations Of Liability
IN NO EVENT SHALL MAGNETEK BE LIABLE FOR LOSS OF PROFIT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL DAMAGES WHETHER ARISING OUT OF WARRANTY, BREACH OF CONTRACT OR TORT.
DSD 412 is a trademark of Magnetek, Inc.
All rights reserved. No part of this publication may be reproduced or used in any form or by any means - graphic, electronic, or mechanical including photocopying, recording, taping, or information storage and retrieval systems - without written permission of the publisher.
2016 Magnetek, Inc.
Page 3
Table of Contents
Introduction ............................................................................................................. 11
Drive Description ............................................................................................................................. 11
The Standard Control Display Unit (SCDU) .................................................................................... 11
The Portable Control Display Unit (PCDU) ..................................................................................... 11
Drive Ratings and Specifications ................................................................................................... 11
Basic Drive Specifications ............................................................................................................... 11
Service Conditions .......................................................................................................................... 11
Protective Features ......................................................................................................................... 11
Software Operating Features .......................................................................................................... 12
Power Conversion Unit .................................................................................................................... 17
Description ...................................................................................................................................... 17
Hardware Descriptions .................................................................................................................... 17
DSD 412 Power Supply PCB (A4) .................................................................................................. 17
Armature Interface PCB (A2) .......................................................................................................... 17
SCR's .............................................................................................................................................. 18
Field Interface PCB (A3) ................................................................................................................. 18
Cell snubber PCB (A5) .................................................................................................................... 18
Drive Control PCB (A1) ................................................................................................................... 18
Precautionary Statements ............................................................................................................... 20
How To Contact Magnetek .............................................................................................................. 20
Pre-Installation Considerations ...................................................................................................... 21
Receipt of Shipment ........................................................................................................................ 21
Unpacking Instructions .................................................................................................................... 21
Packing Instructions for Reshipment or Storage ............................................................................ 21
Physical Installation ........................................................................................................................ 21
Selecting, Mounting and Wiring of the Digital Encoder ............................................................... 21
Encoder Selection ........................................................................................................................... 21
Mounting ......................................................................................................................................... 21
Coupling .......................................................................................................................................... 22
Exceeding Operating Specification ................................................................................................. 22
Electrical Hook up ........................................................................................................................... 23
Power Connections ......................................................................................................................... 23
Signal Connections ......................................................................................................................... 23
Grounding ....................................................................................................................................... 23
Pre-power Check ............................................................................................................................ 23
Drive Start up .................................................................................................................................... 24
Drive power-up sequence ............................................................................................................... 24
Abnormal Display Conditions .......................................................................................................... 24
Fan Check ....................................................................................................................................... 24
Verify Parameters ........................................................................................................................... 24
Interconnect Drawings .................................................................................................................... 25
Standard Control/Display Unit Operation ............................................................. 31
General ........................................................................................................................................... 31
Start-Up Operation .......................................................................................................................... 31
After Power-Up ................................................................................................................................ 32
Changing Parameter Functions ...................................................................................................... 32
Viewing Monitor Functions .............................................................................................................. 33
Error Reporting ................................................................................................................................ 33
Fault Display/Clear .......................................................................................................................... 35
Error Display ................................................................................................................................... 35
Non-Volatile Ram Access ............................................................................................................... 36
Load Default Function ..................................................................................................................... 37
1
Page 4
Self Tune Function .......................................................................................................................... 37
Power Conversion Diagnostics ....................................................................................................... 39
Drive Setup & Adjustments .................................................................................... 41
Motor Field Current Control ............................................................................................................ 41
Analog Velocity Follower ................................................................................................................. 41
Internal Preset Speed & Profile Generator ..................................................................................... 41
Serial Link Follower ......................................................................................................................... 41
Armature Voltage Feedback ........................................................................................................... 41
Pre-Torque, Function #114 ............................................................................................................. 41
Current Ramp-Down, Function #85 ................................................................................................ 41
Electronic Motor Over-Load ............................................................................................................ 42
External/Auto Fault Reset, Function #101 ...................................................................................... 42
Over-Speed Test, Functions #80 and #81 ...................................................................................... 42
Brake Control Logic, Functions #186 and #183 .............................................................................. 42
Speed Regulator Adjustment/E-Reg ............................................................................................... 43
Field Regulator Set-Up ................................................................................................................... 45
AC Input Voltage Requirement & Adjustment ................................................................................. 45
Adjustment Function Descriptions ................................................................................................ 59
Display Monitor Functions .............................................................................................................. 76
Miscellaneous Functions ................................................................................................................ 78
Drive Faults ............................................................................................................. 79
Function Error Code Listing ........................................................................................................... 79
Troubleshooting .............................................................................................................................. 80
Input – Output Signal Verification ......................................................................... 89
Maintenance ............................................................................................................ 91
Preventive Maintenance ................................................................................................................. 91
Repair and Replacement Procedures ............................................................................................. 91
Printed Circuit Boards ..................................................................................................................... 91
Drive Control PCB Replacement .................................................................................................... 97
IC Replacement .............................................................................................................................. 97
Testing and Replacement of Power Components. ......................................................................... 97
Testing and Replacement of Power Semiconductors and Snubber Components. ........................ 98
Testing and Replacement of the Motor Field Control Module and PCB ......................................... 98
Repair of the 195Amp Assembly .................................................................................................... 99
Repair of the 300Amp Assembly .................................................................................................. 100
Appendix ................................................................................................................ 104
Drive Ratings for Elevator Applications ...................................................................................... 104
Power Loss ..................................................................................................................................... 105
Wire Terminal Specs ...................................................................................................................... 106
Power Terminal Wire Sizes ........................................................................................................... 106
Ground Wire Sizes ........................................................................................................................ 106
Field Interface Board (TB1, TB4) .................................................................................................. 106
Spare Parts ..................................................................................................................................... 107
Packing Instructions ...................................................................................................................... 110
Outline Drawings ............................................................................................................................ 111
Index ....................................................................................................................... 117
2
Page 5
Quick Reference for Setup Parameters
FNCT. # DESCRIPTION UNIT RANGE DEFAULT SITE SETTING
1 CURRENT LIMIT. % 0 - 300 250
2
3 RTD. ARMATURE AMPS ADC 2.0 - 1250.0 50.0
4 ARMATURE OHMS OHMS 0.001 - 5.000 0.100
6
7 RTD. ARMATURE VOLTS VDC 150 - 550 240
8 I REG CROSSOVER RAD 100 - 1000 500
9 NOMINAL AC INPUT VAC 150 - 525 230
10 ENCODER PPR P/R 600 - 19999 1024
11 RATED MOTOR RPM RPM 50.0 - 1999.0 1150.0
USE SELF- TUNE VALUES
ARMATURE INDUCTANCE
LOGIC 0 - 1 0=OFF
HNY 0.0010 -1.000 0.0100
12 OVERSPEED % % 0.0 - 150.0 110.0
14 V SENSE % % 0.0 - 100.0 25.0
15 T SENSE % % 0.0 - 100.0 5.0
16 ENCDR / MTR RATIO - 1.000 - 19.000 1.000
17 RATED CAR SPEED - 1.0 - 1900.0 400.0
21 EXT ACCEL LIMIT - 2.00 - 10.00 4.20
22 ERROR LIST RESET LOGIC 0 - 1 0=OFF
32 FULL FIELD DETECT % 30 - 90 80
38 ARM VLT RESPONSE RAD 1.0 - 4.0 2.0
39 HI SPEED BANDWIDTH RAD 1.0 – 15.0 6.0
40 LO SPEED BANDWIDTH RAD 1.0 – 15.0 6.0
41 PER-UNIT INERTIA SEC 0.10 - 9.99 2.00
3
Page 6
Quick Reference for Setup Parameters
FNCT. # DESCRIPTION UNIT RANGE DEFAULT SITE SETTING
42 STIFFNESS - 0.2 - 9.9 1.0
49 WEAK FIELD CURRENT ADC 0.20 - 40.00 40.00
50 FULL FIELD CURRENT ADC 0.20 - 40.00 1.90
51 MOTOR FIELD L/R SEC 0.10 - 10.00 0.54
52 RTD. FIELD VOLTS DC VDC 50 - 525 240
53 STANDBY FIELD AMPS % 10 - 100 25
54 FIELD RESPONSE RAD 1.0 - 10.0 5.0
55
63 U/D PICK-UP % 0.01 - 100.00 0.10
64
80 OVER SPEED TEST LOGIC 0 - 1 0=OFF
81 OVER SPEED MULT - 1.00 - 1.50 1.00
82 REFERENCE MULT - -2.000 - 2.000 1.000
83 MOTOR OVERLD TIME SEC 2.0 - 500.0 48.0
84 MOTOR OVERLD LEVEL PU 0.50 – 2.00 1.15
85 I DECAY RAMP SEC 0.01 - 2.50 0.20
86 ANALOG SPD REF ZERO PU -0.2000 - +0.2000 0.0000
87 PRE-TORQUE MULT - 0.25 - 2.00 1.00
FIELD CONTROL AC SOURCE VOLTS
LOW SPEED THRESHOLD
VAC 0 - 525 0
% 0.1 - 100.0 2.0
88 DSPR DELAY TIME MIN 0 - 60 0 (OFF)
89 BRAKE PICK TIMER SEC 0.5 - 5.0 1.0
90 BRAKE DROP TIMER SEC 0.5 - 5.0 1.5
91 MUST STOP TIMER SEC 0.1 - 5.0 2.0
4
Page 7
Quick Reference for Setup Parameters
FNCT. # DESCRIPTION UNIT RANGE DEFAULT SITE SETTING
92 BRAKE AUTO STOP ON LOGIC 0 - 1 0=OFF
93 ANALOG OUT 0 BIAS - -1.00 - +1.00 0.00
94 ANALOG OUT 1 BIAS - -1.00 - +1.00 0.00
95
96
97 ANALOG OUT 0 MULT - 00.10 - 10.00 0.80
98 ANALOG OUT 1 MULT - 00.10 - 10.00 0.80
99
100
101 AUTO FAULT RESET ON LOGIC 0 - 1 0=OFF
102 3S LOOP FLT LOGIC 0 - 1 0=OFF
104 SERIAL GAIN SWITCH LOGIC 0 - 1 0=OFF
105 GAIN SWITCH SPEED PU 0.00 - 1.10 1.10
107 TACH RATE GAIN % 0.0 - 30.0 0.0
ANALOG OUT 0 SELECT TB1(45)
ANALOG OUT 1 SELECT TB1(46)
SPEED ERROR TRIP TIME
SPEED ERROR TRIP LEVEL
NUM 0 - 8 1
NUM 0 - 8 3
SEC 0.20 - 5.00 5.00
% 0.0 - 100.0 100.0
110
111 ARCH TRAV DISABLE LOGIC 0 - 1 1=ON
112 FEEDBACK SELECT NUM 0 - 1
113
114 PRE-TORQUE ENABLE LOGIC 0 - 1 0=OFF
115 RNUP RNDN ENABLE LOGIC 0 - 1 0=OFF
116 DECEL RATE LATCH LOGIC 0 - 1 0=OFF
117 PRETORQUE BIAS PU 0.00 – 1.00 0.00
REFERENCE MODE SELECT
ARM VOLTS @ MAX SPEED
NUM 1 – 5 2
1 =
ENCODER
VDC 0.0 – 650.0 100.0
5
Page 8
Quick Reference for Setup Parameters
FNCT. # DESCRIPTION UNIT RANGE DEFAULT SITE SETTING
120
121
130 ARB MODE NUM 0 – 2 0 (OFF)
131 ARB BANDWIDTH RAD 1.0 – 15.0 6.0
132 ARB DAMPING - 0.01 –20.00 2.00
133 ARB SPD THRESHOLD % 0.0 – 10.0 0.0
150 BINARY SELECT ON LOGIC 0 – 1 1=ON
151 PRESET SPEED #1 - 0.0 – 1900.0 0.0
152 PRESET SPEED #2 - 0.0 –1900.0 0.0
153 PRESET SPEED #3 - 0.0 – 1900.0 0.0
SPEED ERROR DETECT TIME
SPEED ERROR THRESHOLD
SEC 0.0 – 5.0 0.5
% 0.0 – 15.0 2.0
154 PRESET SPEED #4 - 0.0 – 1900.0 0.0
155 PRESET SPEED #5 - 0.0 – 1900.0 0.0
156 PRESET SPEED #6 - 0.0 – 1900.0 0.0
157 PRESET SPEED #7 - 0.0 – 1900.0 0.0
170 ACCEL #1 TIME SEC 1.00 – 15.00 5.00
171 ACCEL #2 TIME SEC 1.00 – 15.00 5.00
172 DECEL #1 TIME SEC 1.00 – 15.00 5.00
173 DECEL #2 TIME SEC 1.00 – 15.00 5.00
174 ACCEL #1 % S % 0.1 – 100.0 25.0
175 ACCEL #2 % S % 0.1 – 100.0 25.0
176 DECEL #1 % S % 0.1 – 100.0 25.0
6
Page 9
Quick Reference for Setup Parameters
FNCT. # DESCRIPTION UNIT RANGE DEFAULT SITE SETTING
177 DECEL #2 % S % 0.1 – 100.0 25.0
178 ACCEL #3 TIME SEC 1.00 – 15.00 5.00
179 DECEL #3 TIME SEC 1.00 – 15.00 5.00
180 ACCEL #3 % S % 0.1 – 100.0 25.0
181 DECEL #3 % S % 0.1 – 100.0 25.0
182 INVERT ALARM RELAY LOGIC 0 – 1 0=OFF
183 K3 LGC OUT SELCT NUM 1 – 4 1
184 K4 LGC OUT SELCT NUM 1 – 4 1
185 K5 LGC OUT SELCT NUM 1 – 4 1
186 K6 LGC OUT SELCT NUM 1 – 4 1
187 K7 LGC OUT SELCT NUM 1 – 4 1
190 NOTCH DEPTH - 0 – 10 0
191 NOTCH PERIOD - 0 – 10 7
192 F413 DETECTION LVL PU 0.05 – 0.50 0.05
Table 1: Drive Parameters
7
Page 10
Read-Out and Control Parameters
FNCT. # DESCRIPTION UNIT
FNCT. # DESCRIPTION UNIT
600 CAR SPEED -
601 MOTOR RPM RPM
602 SPEED REF -
603 PRE-TORQ SIGNL %
609 CEMF VOLTS VDC
610 MOTOR ARM V VDC
611 MOTOR ARM I ADC
612 MOTOR FIELD I ADC
613 MEASURED R OHM
690 PCU - VERSION -
691 PCU - RELEASE -
692 DAY -
693 MONTH -
695 YEAR -
696 BETA “P” -
697 VERSION “SA” -
698 DCU -RELEASE -
699 CUSTOMER ID -
614 MEASURED L HNY
615 MEAS. FIELD L/R SEC
616
617 LINE FREQ HZ
618 HEAT SINK TEMP DEG C
619
620 FIELD TRACKING PU
621 SERIAL COMM ON LOGIC
688 CUBE I.D. -
689 FIELD RANGE -
MEASURED SPEED ERROR
MEASURED AC LINE VOLTS
%
VAC
Table 2: Monitor Functions
FNCT. # DESCRIPTION
22 CLEAR ERRORS LIST
000 VIEW FAULT LIST
800 VIEW ERROR LIST
801 FAULT/ERROR ACTIONS
980 TRACE MONITOR
981 VERIFY I/O
993 CLEAR NV RAM
994 SAVE/RECALL FUNCTION
995 LOAD DEFAULTS
997 SELF TUNE
998 PCU DIAGNOSTICS
Table 3: Misc Commands
8
Page 11
FAULT # DESCRIPTION
Common Fault References
FAULT # DESCRIPTION
97 OVERSPEED TRIP
98 TACH/ENCODER LOSS
99 REVERSE TACH/ENCODER
117/118 SERIAL COM FAULT
400 MOTOR OVERLOAD
401
402 CONTACTOR FAULT
403 5 MIN FULL FIELD FAULT
404
EXCESSIVE FIELD CURRENT
OPEN ARMATURE CIRCUIT FAULT
414
Prot CORRUPTED NV RAM DATA
900 PCU LOOP FAULT
901 PCU IST FAULT
902 POWER SUPPLY FAULT
903 LINE SYNC FAILURE
904 LOW LINE FAULT
905 FIELD LOSS
907 THERMISTOR FAULT
SOFTWARE COMPATABILITY FAULT
405 SAFETY CIRCUIT FAULT
406 10% LOW LINE ALARM
407 DCU CEMF ALARM
408 PCU CEMF FAULT
409 PCU RESET FAULT
410 SPEED ERROR TRIP FAULT
411
413
MAXIMUM AUTO RESETS FAULT
FIELD CURRENT TRACKING FAULT
908 OVER TEMPERATURE
909 EXCESSIVE RIPPLE
910 BLOWN FUSE
915 PARAMETER SETUP
917
919
920
921 BRIDGE RATING FAULT
REVERSE ARM. V. FEEDBACK
RATED VAC. SETTING ERROR
RATED ARM. VOLT. SETTING
9
Page 12
Common Fault References
FAULT # DESCRIPTION
FAULT # DESCRIPTION
923
924
925 FIELD PCB SENSE FAULT
926 PCU WATCHDOG
929
930
931
932
933
RATED ARM. I. SETTING ERROR
RATED FIELD I. SETTING ERROR
IFLD FB CANNOT BE REDUCED TO ZERO DURING SELFTUNE.
IFLD FB CANNOT GET TO RATED
EXCESS OPEN CIRCUIT VOLTAGE DURING SELFTUNE.
ARMATURE CEMF VOLTAGE IN XCESS DURING SELFTUNE.
IARM DOES NOT INCREASE TO NEAR TEST AMPS DURING SELFTUNE.
934
935
936
937
938
939
940
941
CALC ARML IS UNDER RANGE DURING SELFTUNE.
VOLTAGE FEEDBACK AND BUS VOLTAGE DOESN’T MATCH DURING SELFTUNE
ESTOP CONTACT WAS OPENED DURING SELF TUNE
LOW READ BACK VOLTAGE FEEDBACK DURING SELFTUNE
LOW READ BACK FROM DC BUS CIRCUIT DURING SELFTUNE
FAULTY HARDWARE IN THE FIELD INTERFACE CIRCUIT
FIELD A/D READING IS SATURATED
MOTOR THERMOSTAT OPEN
Table 4: Fault References
10
Page 13
Introduction
Drive Description
The DSD 412 Drive is a complete digital system drive that provides individual drive and system control in one compact package. It is of 12SCR Regenerative configuration. The drive uses two microprocessors, one for the Power Conversion Unit (PCU) circuitry, and one for the Drive Control Unit (DCU) circuitry. Interface to other equipment is provided with Local I/O [Input/Output], or RS­232 & RS-422 serial communications. Extensive diagnostics and setup capability are provided through two Control/Display Units. Depending on rating of the unit, the power cube is in one of four chassis sizes. Refer to the outline dimension drawings furnished in section 6. Each power cube is designed for mounting inside a qualified electrical enclosure. Space allowances for air circulation, additional components, outgoing terminals, and wire bends must be provided. Hinged door swing-out clearance is the same as the width dimension.
The Standard Control Display Unit (SCDU)
The SCDU is mounted on the Drive Control PCB and consists of a 4-1/2 digit numeric LED display, four push buttons and READ/WRITE colored LEDs. The SCDU can be used for all setup functions and many diagnostics.
The Portable Control Display Unit (PCDU)
The PCDU is an optional hand-held device that can be plugged into any analog controlled DSD drive and used for all the same functions as the SCDU plus some advanced diagnostics. There exists a version of this PCDU, which will work with the serial version DSD 412, contact Magnetek for more information. The PCDU has two lines of sixteen alphanumeric characters and a thirty-key keypad. Parameters are entered and displayed in common understandable units. The drive can be completely setup prior to actual running and changes can be made during operation. Keypad entry of changed parameters, protected memory, and factory default values allow the operator to modify data with minimum risk to the process.
Introduction
Drive Ratings and Specifications
The DSD 412 Elevator Drive is designed for connection to a three wire ungrounded power system, or a four wire grounded or ungrounded power system.
Basic Drive Specifications
10-300 Amps (Special order up to 1285Amps or 600VAC) 3 Phase, 48/62 Hz Service Factor 150% full load current for one minute 250% full load current for 5 seconds Full-wave six-pulse SCR control Regulation (of set speed) to 0.05% with digital encoder speed feedback Current regulated shunt field control Automatic Field weakening Self-adapting to incoming line power
Service Conditions
Line voltage 150-525 Vac, ±10%, 3 phase. 115 volt, ±10%, 1 phase control power from a separate source Frequency 48-62 Hz Operating Temperature 0-45° C (55° C max at DSD chassis) Altitude to 3300 feet above sea level, derate 5% for each 1,000 ft above 3300 ft
Relative Humidity 95% (noncondensing)
Protective Features
Programmed memory protection Self-protected Control V power supply Fast phase-back of loop current Contactor interlock for E-Stop
2
I
t motor overload protection AC line current limiting fuses Automatic power up test Control power supply loss detection Isolated and grounded electronics Encoder/Tachometer monitoring and loss protection Input line monitoring Phase sequence insensitive dv/dt protection (snubbers) 1400 PRV Thyristors Instantaneous over-current protection Phase loss protection
DC bus fuse
Field current economizer and loss protection
11
Page 14
Introduction
Software Operating Features
The DSD 412 is configured by software to operate geared and gearless elevators and lifts. The SA407 Drive Control software contains desirable feature improvements from the previous version, SA274. Basic features include:
User choice of operating speed reference External analog reference follower Serial link reference follower
Internal reference generator with S-Curve smoothing, to one of 7 preset speeds (8 speeds
including zero)
User choice of ft/min or m/sec speed
programming and display units
User choice between binary or progressive relay
selected internal preset speeds.
Selectable input control logic for Run-Up / Run­Down or Run / Direction relay control with
internal preset speeds.
Magnetek exclusive E-Reg, elevator velocity
regulator
Simplified analog or serial link Pre-Torque
operation to prevent roll-back on starts
Controlled Current Ramp-Down to prevent
elevator brake thumping at stops
Internal frequency notch filter to reject rope
resonance interference.
Closed loop motor field current regulator with simplified motor field weakening and stand-by
adjustments Maintenance Armature Voltage Feedback mode.
User selectable choices for relay logic output,
including:
Drive OK / No Faults relay Invert/Noninvert Alarms Relay Drive operating, OK to release brake Car above/below speed X threshold Car above/below Zero speed threshold Car Moving Up Car Moving Down
Speed Error above/below X threshold for Y seconds. Drive Standby Power Reduction
User selectable analog diagnostic trace outputs
Diagnostic indicator for verifying logic input and
output conditions Analog speed reference zero adjustment
Alarm Relay to indicate important but non-critical
conditions
Motor or transformer thermostat over-
temperature Motor Over-Load Drive Over-Heating Low Utility Line Input
Safety related fault trapping with diagnostics,
including: Motor Over-Current Motor field Malfunction Contactor Failure Severe Utility Line disturbances Encoder Loss Over-Speed Trip
User selectable automatic or external
commanded Fault Reset
New features have been arranged to be compatible with present installations of DSD 412 using General Elevator software SA274. The factory default settings of software SA407 are such that it will act like SA274 software. The user must consciously re-program one or more selectable features to do otherwise. Several new useful features have been added for SA407, plus more diagnostic codes to help pinpoint the cause of problems when things go wrong during commissioning. See the appropriate sections for explanations of Anti­Rollback, Brake Control, Drive Standby Power Reduction, and operation with a Uni-Polar Analog reference. Ramp rates 3 are now activated by external logic command at A1TB1-
10.
12
Page 15
Introduction
CUSTOMER
50/60 Hz UTILITY POWER
SAFETY
CHAIN
DISCONNECT
115 VAC
CONTROL
POWER
XFMR
MOTOR & TRANSFORMER THERMOSTATS
ISOLATION
TRANSFORMER
HOIST
MOTOR
FIELD
L1
L2
L3
+
F1
F2
F3
SNUBBER PCB
AND
COMPONENTS
MOTOR FIELD
CONTROL
FIELD CONTROL
SCR GATING
POWER SUPPLY
K1
PCB
LOW VOLTAGE
POWER
FIELD CURR.
SIGNAL
ME
LOOP
CONTACTOR
LPR
LPR
LOOP
PICK-UP
RELAY
E-STOP
SENSE
K1
CONTACTOR
PILOT
RELAY
HEAT SINK
COOLING FAN
Figure 1: DSD 412 Block Diagram A
SIGNAL
SENSING
CONTACTOR
CONTROL
13
Page 16
Introduction
SCR POWER BRIDGE
12 SCR REGEN
SCR
GATE
SIGNALS
POWER CONVERSION UNIT
MICROPROCESSOR
RAM &
EPROMS
RT1
ARMATURE INTERFACE
PCB
DUAL PORT
MEMORY
DRIVE CONTROL UNIT
MICROPROCESSOR
NV-RAM, RAM
& EPROMS
STATUS
LEDS
RE­SET
DRIVERS
F4
CURRENT
SENSOR
IN-OUT
ME
ME
ME
RESISTOR
+18888
LOCAL CDU
DRIVE CONTROL PCB
DB
RIPPLE FILTER
UN PROT
NV MEM
MEM PROT
SWITCH
MOTOR
ARM.
OPTIONAL
PCDU
PROGRAMMER
RS-232 OR RS-422
SERIAL PORT
OR
TB1 LOCAL CONTROL I / O
OPTIONAL
SERIAL LINK
TO CAR
CONTROLLER
Figure 2: DSD 412 Block Diagram B
CONTROL SIGNAL
WIRING
14
Page 17
Introduction
GROUND LUG
ARMATURE CURRENT TRANSDUCER
INPUT POWER LUGS
AC LINES FUSES F1-3
DC ARMATURE FUSE F4
SNUBBER PCB
CUBE I.D. PCB
BRIDGE THERMISTOR
ARMATURE INTERFACE PCB
DC OUTPUT FIELD SUPPLY
Figure 3: Component Layout Front View
A2TB5
SCR'S
Q7, FIELD SCR
AC INPUT FOR FIELD SUPPLY
15
Page 18
Introduction
POWER SUPPLY COVER
A4 POWER SUPPLY
A4 TB3
A1 MAIN CONTROL PCB
Figure 4: Component Layout Right Side View
16
Page 19
Power Conversion Unit Description
The Power Conversion Unit circuitry has three major functions:
1. It converts three phase AC input power to variable DC voltage for application to a motor armature.
2. It converts motor generated DC power to three-phase power to feed back to the line.
3. It converts single phase AC input power to a variable DC voltage for application to a motor field.
Two sources of power are required. A three­phase power isolation transformer adjusts the utility mains voltage to that required to operate DSD 412 efficiently with the needs of the DC hoist motor. 115VAC control power from a separate source is used to power the low voltage power supply, cooling fans, relay and contactor logic.
Three phase input power is applied through the AC line fuses to twin 6-SCR power bridges for forward and reverse control. The PCU microprocessor controls armature current based on a reference received from the Drive Control Unit microprocessor. Output from the PCU microprocessor is sent to the Armature Interface PCB, which produces the gating signals for power SCRs. The SCR bridge output is an adjustable DC voltage, which is applied to the motor armature circuit. Power circuit AC and DC measurement signals are routed to voltage dividers on the Armature Interface PCB, and scaled values are sent to the PCU microprocessor. Armature current is also measured and the feedback signal is routed through the Armature Interface PCB to the PCU microprocessor. An over current trip function monitors this signal to initiate an instantaneous static trip (IST) in the event of excessive output current.
Single-phase power is also applied through the AC line fuses to the Field Rectifier Module. SCR gating signals from the PCU microprocessor control the field rectifier SCRs. A separate current measuring device is used to monitor the DC current flowing to the motor field. Additional connections allow for a separate step-up or step-down transformer to be used to power the motor field rectifier from voltage mains different from that for the motor armature.
Introduction
If optional dynamic braking resistors (DBR) are present they are applied across the motor armature to dissipate rotational energy whenever the loop contactor is dropped out. This helps to bring the motor to a stop even when utility power is lost.
The largest component of the PCU is the SCR bridge (Heat Sink Assembly). The heat sink is an extruded aluminum structure that dissipates the heat generated by the SCRs mounted on the front surface (or between heat sink sections, in large size power cubes). The SCRs control the current to the motor armature and in turn are controlled by the Armature Interface PCB mounted in front of the SCRs. Three input power line fuses are provided. A DC Bus fuse protects the motor armature circuit. A thermistor (and thermostat on some ratings) senses heat sink temperature and gives an over-temperature warning if an over­temperature occurs.
Access to the SCR Bridge is obtained by opening the hinged door containing the Drive Control PCB A1.
WARNING
Opening the hinged door with power applied to the drive exposes dangerous voltage levels. The hinged door should only be opened by a qualified service technician, and only when the power to the drive is turned off.
Hardware Descriptions
DSD 412 Power Supply PCB (A4)
Provides +5V, +15V, -15V, and +24V to the control circuits and has fold-back current limit protection. It also provides 115VAC connections for the main contactor, motor thermostat and fans.
Armature Interface PCB (A2)
Provides the interface circuitry between the digital firing pulses generated by the Drive Control PCB and the high current SCR gating pulses controlling the armature current. It also provides feedback signals from the power section to the Drive Control PCB. A small ‘cube ID’ circuit board is attached to the Armature Interface PCB to identify the ampere capacity of the SCR power bridge to the PCU processor.
17
Page 20
Introduction
SCR's
The drive uses different selections of doubler packs or individual “hockey puck” SCRs according to the horsepower ranges specified below:
MOTOR ARMATURE
CURRENT
25A - 195 A Doubler
300 - 1285 A "Hockey Puck"
Field Interface PCB (A3)
Provides the interface circuitry between the digital firing pulses generated by the Drive Control PCB and transformer isolated SCR gating pulses controlling the field current. It also contains the field feedback circuitry and the field SCR snubber circuit.
Cell snubber PCB (A5)
Is provided for SCR protection. These are selected to work efficiently with utility line impedance between 2 and 8 percent, including that of the power input transformer.
Drive Control PCB (A1)
Mounted on the hinged door, this board provides the microprocessors, memory and support circuits needed to control drive operation. Two control circuits are provided on this PCB. One for controlling the Power Conversion Unit (PCU), and another for speed regulation and higher-level functions, called the Drive Control Unit (DCU). These two circuits communicate primarily through a Dual­Port Random Access Memory (DPRAM) IC (integrated circuit) device.
Drive Control Unit
The major element of the DCU is a 16/32-bit Motorola 68000 microprocessor. Random Access Memory (RAM) provides memory space to store values that are maintained only
SCR
TYPE
while power is on. Non Volatile Random Access Memory (NVRAM) maintains drive control parameters for the DCU when the power is off. Two EPROM’s (Electrically Programmable Read Only Memory) devices, U39 & U40, contain the specific drive program instructions for the DCU microprocessor.
Power Conversion Unit Control
The major element of the PCU control circuit is a 16-bit Intel 80C196 microprocessor. Again, RAM and EPROM devices, U13 & U14, provide memory space and computer instructions for the PCU. Any PCU parameters that need to be maintained while power is off are kept in NVRAM of the DCU and passed through the DPRAM.
Local I/O
In an elevator application, the Local I/O [Input/Output] allow the drive to have inputs and outputs (I/O) such as RUN, STOP, Encoder Feedback, Analog Reference Input, Fault condition relay logic output, etc. connected directly to the drive or passing through a serial communications device.
Connection to the Local I/O is made via A1TB1 and/or the serial interface connection at terminal point J1 mounted directly on the Drive Control PCB (A1).
Front Panel Controls and Indicators
The upper right corner of the power cube cover contains the operator controls and indicators. Although accessible with the cover in place, all of these components are part of the Drive Control PCB (A1).
DRIVE RESET Button (S1)
Pressing this button causes the drive to clear critical and non-critical faults and to restore drive operation when faults are present. This button will have no affect when the drive in enabled.
18
Page 21
Introduction
Status LEDs
Located to the right of the RESET button is a vertical strip of six light emitting diodes (LEDs):
READY — Indicates that the drive is ready to
run.
RUN — DC loop contactor is closed and drive
is controlling motor speed.
I LIMIT — Drive operation is demanding current
limit armature current.
OVERLOAD — Motor armature current is in
overload region. If lighted when the drive is stopped, indicates that an over-load trip has occurred.
E-STOP — Drive contactor safety interlock is
detected open. Drive will not run when this light is on.
FAULT — Indicates that a declared drive fault
exists. The Fault/Error Code List defines what conditions the drive will recognize as faults.
Standard Control Display Unit
The major part of the SCDU is a 4-1/2-digit numeric LED display. Each of its four full digits can display the values of 0 to 9 plus limited alphabetic characters. The so-called half digit can display only the value 1 and a plus or minus sign. Underneath this display are a green LED, labeled DATA, a red LED, labeled DATA PEND, and a row of four push buttons.
The DATA and DATA PEND LEDs are used to indicate the significance of the LED display
data, and the four push buttons (DATA/FCTN, › [UP], › [DOWN], and ENTER) are used to operate the SCDU. The functions and capabilities of the SCDU are explained in greater detail on page 25.
Non-Volatile RAM Protection
To the left of the four push buttons of the SCDU there is a red LED labeled MEM UNPROT. This LED is lit when the “protected” portion of the non-volatile random access memory (NVRAM) can be written to. The switch labeled S3, which is located just under the MEM UNPROT LED, determines protection of the NVRAM. When this switch is in the "ON" position, the NV RAM UNPROTECTED LED is off and the protected portion of the NVRAM cannot be written to. This prevents setup parameters and other important constants from being accidentally erased or changed. When these parameters need to be changed the switch can be moved to the "OFF" position, removing the write protection and causing the NV RAM UNPROTECTED LED to be lit. Refer to the section described as saving parameters.
The NV RAM PROTECTION switch should be left in THE "ON" position (UN-PROTECTED NV MEM LED OFF) to protect the NVRAM during the critical power-up and power-down periods.
19
Page 22
Introduction
Precautionary Statements
In addition to notes, the following types of precautionary statements appear in this manual.
IMPORTANT
A statement of conditions that should be
observed during drive setup or operation to
ensure dependable service.
CAUTION
A statement of conditions that must be
observed to prevent undesired equipment
faults or degraded drive system performance
WARNING
A statement of conditions that MUST BE
OBSERVED to prevent personal injury, death,
or serious equipment damage.
How To Contact Magnetek
For additional information contact any Magnetek Representative or contact the DSD 412 Elevator Technical Support Staff at:
Magnetek Elevator Products N50 W13775 Overview Drive Menomonee Falls, Wisconsin 53051 USA
PHONE: 800 236-1705 (all numbers USA) OR 262-252-6999 FAX: 262 790-4142
Magnetek Elevator Products – Europe 20 Drake Mews, Crownhill Milton Keynes, Busck MK8 0ER UK PHONE: +44(0) 1234 756036 FAX: +44(0) 1234 756037
See us on the web at www.elevatordrives.com Or email us at [email protected]
20
Page 23
Installation
Installation
Pre-Installation Considerations Receipt of Shipment
All equipment is tested against defect at the factory. Any damages or shortages evident when the equipment is received must be reported immediately to the commercial carrier who transported the equipment. Assistance, if required, is available from your Magnetek representative. Always refer to the order number, equipment description, and serial number when contacting Magnetek.
Unpacking Instructions
Open Carton and remove the OSB panel located on top of the drive. Remove Foam from carton. Lift drive out of box, grip ONLY sheet metal chassis. Do NOT lift using the door assembly or the Field Interface Board. Unbolt drive from 2x4s.
Packing Instructions for Reshipment or Storage
For long periods of storage, equipment should be covered to prevent corrosion and should be placed in a clean, dry, location. If possible, equipment should be stored in its original packaging. Periodic inspection should be made to ensure that the equipment is dry and that no condensation has accumulated. The equipment warranty does not cover damage due to improper storage.
The drive should be packed in its original shipping container if it is required that it be shipped. Not following the detailed instructions outlined on page 110 will result in damage to the drive. Refer to Packing Instructions on page 110 for proper reshipment.
Selecting, Mounting and Wiring of the Digital Encoder
Encoder Selection
A quality encoder is recommended for use with the DSD 412 controller for speed feedback. The encoder should be a two channel, quadrature, zero speed type device with differential line drivers. The DSD 412 drive supplies +5V power for an encoder, however the encoder and feedback signals may operate from another source, up to 15 volts if desired. The Pulses per Revolution count must be sufficient to provide an adequate frequency feedback at very low speeds, and yet not exceed 300 kHz (per channel) at top speed. For most elevator applications this target will be met when the feedback frequency (per channel) is greater than 50KHz at contract speed. For gearless machines, which have a base speed around 100RPM, a 10,000PPR encoder is a good choice for direct connection to the motor shaft. For geared machines, with motors running at 1750 or 1150RPM, 2500PPR encoder may be used. Direct mounted hollow shaft encoders, electrically insulated from motor shaft and motor frame will yield the best results. The use of an analog AC or DC tachometer is not supported by DSD 412 elevator drives software or hardware.
Mounting
Proper mounting and alignment of the digital encoder used for speed feedback is very critical for the smooth operation of the DSD 412 controller. Even the slightest wobble of the encoder shaft due to misalignment can cause once-per-revolution torque pulsation that have the potential of exciting natural rope resonance frequencies.
Physical Installation
The DSD 412 Elevator Drive is air-cooled. The lowest HP rated units are cooled by convection; all other units are equipped with a fan to ensure adequate airflow. Select a site for installing the drive that is clean and well ventilated. Maintenance will be minimized if the drive is located in a clean atmosphere.
The standard drive is designed for vertical mounting. Attach the drive to a cabinet panel or other vertical structure using the mounting holes provided at the back of the drive. Ensure that the unit is level.
Non-concentric
Figure 5: Common Problems in Encoder
21
Input
Angular Misalignment
End Float
Mounting
Output
Page 24
Installation
The Magnetek recommendation for mounting the encoder used for motor speed feedback is to direct connect it to the motor shaft, usually to the end opposite the drive end. Normally a stub shaft is mounted in the end of the motor shaft. The stub shaft must be absolutely concentric (share the same center) with the motor shaft, and have no angular misalignment. The encoder is normally face mounted to a bracket that is mounted on the motor. A standard NEMA 56 “C” face adapter bracket may be used, or a special fabricated bracket may be designed and used. The encoder should be mounted on the bracket and positioned so that the encoder shaft and the stub shaft are concentric and have no angular misalignment or run-out. The coupling should have electrical insulation to isolate the motor shaft from that of the encoder. The body of the encoder should be electrically insulated from the motor frame.
An alternate method of mounting which has been used in the elevator industry is to drive the encoder with a rubber wheel that runs on the brake surface of the sheave. This approach may be satisfactory for many applications, but it can introduce instability and is not recommended:
1. Excessive bearing wear can occur in the
encoder due to the method of mounting and holding the rubber wheel against the sheave.
2. Lack of concentricity of the measuring wheel.
3. The rubber wheel can develop a flat spot
when it sits idle for an extended time. This goes away after a short time of operation, but it can affect performance while it exists.
4. An angular misalignment can cause the
measuring wheel to skip or hop sideways, causing a disturbance in the feedback signal.
Coupling
Almost regardless of the care used in mounting the encoder, there is likely to be some small amount of misalignment. A good quality coupling between the encoder shaft and the motor stub shaft can help avoid the remaining problems due to shaft runout.
A good coupling will also offer some protection for the encoder against end float, a condition which exists in gearing on direction changes, and which can be transmitted through the motor. Again, the coupling should provide electrical insulation between the motor and encoder shafts.
Encoder Wiring
Wiring between the encoder and the DSD 412 drive should be shielded cable with 3 twisted pairs. The pairs should be made up of A and A, B and B, +5VDC and common. The shield should be insulated from the encoder case, and only connected at the drive end, to A1TB1 (6). This cable should be run in a separate conduit between the encoder and the DSD
412. If the encoder must be connected to two receivers (DSD 412 and car controller), the cable should run from the encoder to the drive (with this portion of the shield connected at the drive) and then from the Drive to the car controller (with the portion of the shield connected to the car controller). Do not tie the two shields together.
Exceeding Operating Specification
Do not exceed the operating specification of the encoder/drive, in order to prevent the encoder from providing incorrect data.
All encoders have inherent mechanical and electronic limitations regarding speed. The combination of several design factors including bearings, frequency response of the electronics, and PPR of the encoder, etc. combine to determine "maximum operating speed". Exceeding the maximum speed may result in incorrect data or premature failure. The encoder manufacturer can provide both the electrical and mechanical encoder specifications.
To determine the encoder's maximum operating speed:
Step 1: Determine maximum electronic operating speed in RPM.
60 x (kHz) response freq. Encoder
RPM
PPR Encoder
Step 2:
A. If the RPM calculated in Step 1 is less than
or equal to the encoder's maximum mechanical RPM specification, then the RPM calculated in Step 1 is the maximum operating speed specification for this particular encoder application.
B. If the RPM calculated in Step 1 is greater
than the encoder's maximum mechanical RPM specification, then the maximum mechanical RPM specification is the maximum operating speed for this encoder application.
22
Page 25
Step 3: Compare the maximum operating speed as
determined in Step 2 above with the application requirements.
To determine if the application exceeds the operating specification of the DSD412:
Calculate the maximum pulses per
revolution (PPR) for this application (using the HPV 900 frequency limit of 300 kHz and 120% of the application’s top speed)
max PPR
60*Hz 300,000
1.2*RPMn applicatiomax
Verify that the selected encoder’s PPR is below the calculated maximum PPR (PPRmax) for this application.
A common grounding stud or bus bar should be provided within the drive enclosure cabinet, electrically bonded to the metal enclosure. A grounding wire should be provided directly from the grounding terminal on the DSD 412 drive chassis to the common grounding stud. A grounding wire should be provided directly from the electrical sub-panel on which the DSD 412 drive is mounted to the common grounding stud. Other electrical equipment, such as fans or relay circuits may be grounded to the electrical sub-panel. A grounding wire should be provided directly from the elevator motor frame to the common grounding stud. A grounding wire should be provided directly from the power isolation transformer frame to the common grounding stud. A grounding wire should be provided directly
Electrical Hook up
Ensure that wire size and disconnect devices conform to the installation contractor’s drawings and to all applicable codes.
Power Connections
The three phase input power to the drive is fuse protected internal to the Drive. However, it is recommended to provide branch circuit protection by means of a circuit breaker in accordance with the National Electrical Code, (USA) or as may be required by other local electrical codes.
from building steel to the common grounding stud. If an armature circuit ripple filter is used, a grounding wire should be provided directly from the ripple filter inductor frame to the common grounding stud. The sub-panel for capacitor mounting within the filter should have a grounding wire to the inductor frame. The secondary side of the power isolation transformer should remain un-grounded. The low voltage circuit common should be grounded by connecting A1TB1-43 or A1TB1-44
to A1TB11.
Signal Connections
All low power, low voltage wiring to the DSD 412 controller should be run separate from the 115VAC or higher power connections and the DC motor armature and field connections. These include:
Encoder Wiring Speed Reference Wiring Pre-Torque Reference Wiring 24 VDC Logic Inputs Analog Outputs Open Collector Logic Outputs
Rewiring these signals in shielded wire is recommended to avoid noise pickup.
Grounding
The DSD 412 controller, the utility power system feeding it and all other connected power equipment should be grounded as follows: The facility power ground and grounding wire sizes should comply with NEC, UL, CSA and other applicable codes for power distribution safety.
Pre-power Check
CAUTION
To prevent damage to the drive, the following
checks MUST BE performed BEFORE
applying 3-PHASE INPUT POWER to the
drive.
A. Inspect all equipment for signs of damage,
loose connections, or other defects.
B. Ensure the three-phase line voltage is
within +10% of the nominal input voltage range of 150 to 525 VAC. The drive is not sensitive to phase sequence. Input power specifications are contained on the drive nameplate or the drive system Schematic Diagram.
C. Remove all shipping devices and relay
wedges. Manually operate all contactors and relays to ensure that they move freely.
D. Ensure that all electrical connections are
secure.
E. Ensure that all transformers are connected
for proper voltage according to the Drive system Interconnection Diagram.
Installation
23
Page 26
Installation
Drive Start up
Refer to the recommended connections shown in the connection diagrams. Attach a voltmeter across the 115VAC source for the control power supply, at A4TB3-1 & A4TB3-7.
Apply the control and three-phase power and verify that the control power is between 103 VAC and 126VAC. Then press the RESET push button on the front of the power cube, and observe the drive power-up sequence as described below.
Drive power-up sequence
The power up sequence can be observed by monitoring the Standard Control/Display Unit (SCDU) on the front of the power cube.
1. First, all of the segments on the digital LED display and all of the LEDs will light for about 1 second.
2. Then the LEDs and display should extinguish. The drive will perform internal checks. The SCDU will display 'tESt' while a self-test is being performed.
3. If the drive passes the self-test, then the SCDU will display 'P-UP'. READY LED will light.
Abnormal Display Conditions
Displays other than those mentioned above may occur. The following is a list of
display conditions
actions necessary to correct the situation:
1. If no digits or LEDs light up, then check for proper voltage between the 115 Vac control power lines, or for blown 115 Vac control power fuses, or for a defective Control Voltage Power Supply in the power cube.
2. If horizontal segment(s) of the SCDU display are lit, then one or more phases of the three-phase power are missing. Measure and verify three phase power input at the drive terminals. Check the three-phase power fuses. See page 25 for descriptions about the standard control/display unit operation for more detailed information about this test.
3. If the FAULT LED lights, and a fault code appears on the SCDU, then refer to the Fault/Error Codes List to see what caused the fault and to find the correct solution. A fault code is the letter 'F' followed by a
that may occur, and the
abnormal
number representing the fault. See section describing standard control/display unit operation for more detailed information about fault reporting and clearing on page
25.
4. If the SCDU displays 'Prot', then the initial checks found that the protected non­volatile RAM (NVRAM) has not been initialized. Move the NV RAM PROTECTION switch to "OFF" in order to allow the microprocessor to initialize the NVRAM with preprogrammed default values. Notice that the NV RAM UNPROTECTED LED is now lit to indicate the NV RAM PROTECTION switch position. Next, press the RESET push button. The drive will go through its power up sequence again; however, this time it will initialize the unprotected NVRAM and load in factory supplied default parameter values.
Fan Check
On drives with a blower motor (power bridge fan), verify that the fans are working.
Verify Parameters
When the READY LED on the SCDU is lit, all the selectable parameter data should be checked and/or verified to the proper values as follows:
1. VERIFY OR CHANGE EACH PARAMETER VALUE for the particular application and motor involved.
2. Perform PCU DIAGNOSTICS Function 998 should to verify armature and field circuitry.
3. Perform SELF-TUNE PARAMETER TEST Function # 997 to measure and verify various motor parameters essential for proper operation.
4. STORE PARAMETERS, Function # 994, so that power can be removed and reapplied without losing the entered parameters.
5. Set the NV RAM PROTECT switch to the protect position (UN PROT NV RAM light is off) to ensure that set up data cannot be corrupted.
6. Operate drive, using external control signal inputs shown on the Interconnection Diagram.
24
Page 27
Interconnect Drawings
3-PH DRIVE
ISOLATION
TRANSFORMER
AS REQ'D
Interconnect Drawings
TB1(82) +24VDC
TB1(78) K4
SEE TABLE 5: RATED MOTOR FIELD CURRENT RANGE
Figure 6: Power Signal Wiring
25
Page 28
Interconnect Drawings
INPUT/OUTPUT
CONNECTIONS USING
ANALOG INTERFACE,
MODEL NUMBER
53STXXXX-3X00.
DRIVE OK/ NO FAULTS RELAY
ENERGIZED WHEN NO
FAULTS ARE
PRESENT.
ALARM RELAY, MAY
BE ENERGIZED OR DE-ENERGIZED ON
ALARMS. SEE TECH
MANUAL, FUNCTION
#182
PROGRAMMABLE
FUNCTION OUTPUTS.
REFER TO F#183 -
187
J2 RJ-12 CONNECTION RS232 (PCDU PORT)
DATA FLOW
Figure 7: Typical Analog Signal Wiring
26
Page 29
Interconnect Drawings
DRIVE OK/ NO FAULTS RELAY
ENERGIZED WHEN NO
FAULTS ARE
PRESENT.
ALARM RELAY, MAY
BE ENERGIZED OR DE-ENERGIZED ON
ALARMS. SEE TECH
MANUAL, FUNCTION
#182
PROGRAMMABLE
FUNCTION OUTPUTS.
REFER TO F#183 -
187
J1 DB9 CONNECTION
RS422
DATA FLOW
Figure 8: Typical Serial Signal Wiring
27
Page 30
Interconnect Drawings
NOTES:
1. ITEMS NOT SUPPLIED BY MAGNETEK ARE INDICATED WITH AN ASTERISK ( * ) OR
(**).
2. THE DC MOTOR CONNECTIONS SHOWN IS FOR CCW ROTATION FACING THE
COMMUTATOR END. TO REVERSE ROTATION, INTERCHANGE A1 AND A2 AT THE MOTOR. DO NOT CONNECT SERIES FIELD (IF SUPPLIED WITH MOTOR).
3. THE DRIVE IS PREWIRED TO HAVE THE
AC SUPPLIED TO THE FIELD RECTIFIER DERIVED FROM L1 AND L2. IF A DIFFERENT VOLTAGE IS REQUIRED MOVE THE ORIGINAL WIRES FROM AC1 AND AC2 TO L1A AND L2A. THE ALTERNATE SUPPLY SHOULD THEN BE BROUGHT INTO AC1 AND
AC2. THIS CONNECTION IS PHASE SENSITIVE (SEE FIG 2.1a, DETAIL A).
4. ITEMS MARKED (**) ONLY APPLY WHEN THE INTERNAL PRESET SPEED OPTION IS
USED.
5. ATTACH TO BUILDING GROUND.
6. INSTALL JUMPER FROM TB1(44) TO TB11(1).
7. CONNECTION MUST BE MADE FOR PROPER DRIVE OPERATION. IF MOTOR THERMOSTAT IS NOT INSTALLED COMPLETE
WITH A JUMPER WIRE.
8. FUNCTION OF CONTACT INPUTS DEPENDS
ON PROGRAMMING OF FUNCTION #115. SEE DIAGRAM THIS PAGE AND DESCRIPTION OF F#115.
Figure 9: Power/Signal Wiring Notes
Figure 10: Run-Up/Run-Down vs. Run w/ Direction
Table 5: Rated Motor Field Current Range
28
Page 31
DSD 412
MAIN PCB
Interconnect Drawings
1N4002
36
K3
37
57 or 80COMM
K6
CONNECTIONS FOR
ELEVATOR BRAKE CONTROL
83
82+24 VDC
RELAY COILS 24VDC
LESS THAN 100 MA
K3x, 24VDC
(BRAKE PICK)
K6x, 24VDC
(LIFT & HOLD)
BRAKE VAC
SUPPLY SOURCE
BRAKE
LIFT
BRAKE
LIFT
CONTROL
K3x
K6x
115 VAC
POWER
BRAKE
PICK
R/C
BRAKE
LIFT
R/C
RECTIFIER
AS REQ'D
R-HOLD BRAKE
PICK
ELEVATOR BRAKE COIL
Figure 11: Drive Brake Control Feature
29
Page 32
Interconnect Drawings
+24V
S4
S3
S2
S1
S0
PROGRESSIVELY
SCANNED RELAY LOGIC
ALTERNATE METHODS TO ACHIEVE PROGRESSIVE SPEED SELECT LOGIC
48
52
54
12
53
11
OR
+24V
48
S4
52
S3
54
S2
12
S1
53
S0
11
USING DIODES (1N4003)
TO YIELD PROGRESSIVE INPUTS
WITH SINGLE RELAY CLOSURES
Figure 12: Speed Select Logic Input Wiring
See detailed descriptions on pages 51 and 69.
30
Page 33
Standard Control/Display Unit Operation
General
The Standard Control/Display Unit (SCDU) is used to change and/or monitor various drive dependent operational set points and perform diagnostics for the Magnetek DSD Elevator Drive. The SCDU is located in the upper right corner of the Drive Control PCB and is accessible through the power cube cover. This Control/Display Unit is present on every Magnetek DSD 412 Elevator Drive.
The SCDU consists of a 4-button keypad, a 4­1/2 digit numeric LED display, red and green colored LEDs, an "NVRAM PROTECT" switch (marked NV RAM PROTECTION on the power cube cover), and a red LED that shows the status of the "NVRAM PROTECT" switch.
Start-Up Operation
When power is first applied to the drive, all of the segments on the 4-1/2-digit display will turn on briefly in order to show that all are
functioning:
Standard Control/Display Operation
software in the drive is changed. C. The NVRAM chip (U56) is changed.
After the LED lamp test has completed, the drive software will now perform a fuse test on each of the three line fuses. If any power conversion fuse is open, the SCDU will indicate this on its display. The SCDU display is arranged in a similar manner to the physical placement of the 3 line fuses in the power cube. The middle segments of the three right­most digits are used to indicate blown fuses. For example, if the left-most line fuse is bad, the SCDU will report it as follows:
If any two or more fuses are blown, the SCDU display will be:
After this lamp test is completed, an internal check is made to determine if the NVRAM chips have ever been used before, or if the EPROM’s are the same as before power down. If not, the drive software will attempt to load the defaults into the NVRAM chips. The
SCDU displays the word ‘Prot’ if the NV RAM PROTECTION switch is in the position that will not allow any updates of the NVRAM:
If the display shows ‘Prot’, it is necessary to move the NV RAM PROTECT switch to the "OFF" position and press the CPU RESET button in order to load defaults into NVRAM
and restart the drive. Then set the NV RAM
PROTECT switch back to "ON". This ‘Prot’ message will only happen when: A. The drive is powered up for the very first time. B. If the
The operator should then identify which fuses have failed.
The drive will not operate unless all three line fuses are functional. If the SCDU indicates a bad fuse, power must be removed from the drive, the fuse replaced and power reapplied.
After the drive has performed all three tests (lamp test, RAM test, and fuse test), the SCDU displays one of two final messages. If there are any faults present at this time, the SCDU will display a Fault code. The display will be similar to:
where the leading ‘F’ indicates a fault and the 3 digits following the ‘F’ indicate the fault number. If however, there are no faults present, the SCDU displays the normal power­up message:
31
Page 34
Standard Control/Display Operation
This ‘P-UP’ display will remain on the SCDU until a key is pressed or a fault occurs.
After Power-Up
After the drive has powered up and the SCDU display is showing ‘P-UP’ or a fault number, it can be used to enter new parameters, monitor drive operation, and/or perform certain drive diagnostics. Every operation that the SCDU can perform is called a ‘function’. There may be up to 1000 functions defined within the DCU.
All SCDU functions have at least 2 levels, and some functions use 3 levels. The two colored LEDs below the lower left corner of the 4-1/2­digit display are used to indicate which level of a particular function the SCDU is currently at. The top level of the SCDU operation is called the "Function" level. The two colored LEDs
are off when the SCDU is in the "Function" level. The ▲ or ▼keys are used to select a
function number to be accessed while at this level. The ▲ key increments the function number in the display while the ▼ key decrements it. The SCDU will ramp the displayed function number when the ▲ or ▼ key is pressed and held for 1/2 second or longer.
The DATA/FCTN key is used to toggle between the “Data” level and the “Function” level. Press the DATA/FCTN key when the desired function number is in the display. At this point, the SCDU leaves the "Function" level and enters the "Data" level. Note that the green LED is now lit. This operation is consistent for every function on the SCDU, although the data actually displayed while the LED is GREEN is function-number specific. Examples of every type of SCDU function are given in subsequent sections. All function numbers are shared between the SCDU and the PCDU (Portable Control/Display Unit).
There are some functions, however, that can only be performed with the PCDU. When such a function number is selected on the SCDU and the DATA/FCTN key is pressed, the SCDU’s display will change to:
Changing Parameter Functions
SCDU functions are used to modify and/or display setup points that the drive needs for operation. Items that would typically fall into this category are functions such as Accel Times, Regulator Gains, Rated Speed and any other parameters. The following steps show how to modify a given parameter via the SCDU display.
1) Use the ▲ and ▼ keys to select the function number to be accessed. The two colored LEDs remain off during this step. For example, if #040 is chosen:
2) Press the DATA/FCTN key to enter the "Data" level for this function number. The green LED is lit to indicate that the number being shown is the current actual value for this parameter. For example, if Function # 40 is currently set for a value of 10.6, it will be displayed as:
3) Use the ▲ and ▼ keys to ramp the number in the SCDU display to the desired value. Note that the red LED is lit to indicate that the value being displayed is NOT the actual value, but rather is in the process of being changed. Each parameter has an upper and lower limit.
The following display will occur when the lower limit is exceeded:
Similarly, if the upper limit is exceeded, the
SCDU displays:
32
Page 35
The SCDU display will increment from ‘10.6’ to ‘11.0’ if the ▲ key is pressed 4 times:
4) Press the ENTER key to transfer the value in the SCDU display to the actual value used by the drive. Note that the green LED will now light to indicate that this value is now the actual value for this parameter:
If the ENTER key is pressed while the display is indicating that the upper or lower limit has been exceeded, the display will change to the appropriate limit and the green LED will light.
5) Press the DATA/FCTN key to put the SCDU back into the "Function" level. As with the example above, the SCDU display will be similar to:
Standard Control/Display Operation
Viewing Monitor Functions
Items that would typically fall into this category are Speed Feedback, Armature Current and Armature Voltage.
To view one of these values, it must have been previously programmed in the drive. The following steps show how to display a given value on the SCDU display.
1) Use the ▲ and ▼ keys to select the function number (between 600 and 799) to be accessed. The two colored LEDs remain off during this step. For example, if 600 is selected, the SCDU display will be:
2) Press the DATA/FCTN key to enter the "Data" level for this function number. The green LED is lit to indicate that actual data is currently being viewed. If the data for Function # 604 is currently at 20.94 for example, the SCDU display will change to:
The SCDU’s display is updated immediately if the value for the selected function changes.
All changes made become active values upon pressing the ENTER key. They remain active until the next reset, or until the drive is powered down. When the drive is reset or powered up the value reverts to the value stored in NVRAM. If changes are to be permanent, use Function # 994 to save the changed value in NVRAM.
Due to programming considerations it may be possible to access a value that cannot be changed. In this case the CDU function will proceed as described until the ENTER key is pressed to change the value. In this case the value will simply ignore any requested changes and remain the same.
NOTE
Values displayed with these function numbers
cannot be modified.
Error Reporting
The drive has two methods available to report errors and faults. Each error condition may utilize ONE OR BOTH OR NEITHER of the reporting methods.
The most conventional method is called ‘fault recording’. If this method is enabled for a particular error, the red FAULT LED and a unique fault code number will appear on the SCDU at the moment when the error occurs. Each occurrence of a fault is recorded in an area in RAM called the Fault List. The Fault List stores the 16 OLDEST faults and stops recording faults as soon as the 16th fault occurs. This list is erased when the drive is
33
Page 36
Standard Control/Display Operation
powered down or reset. Whether or not the
drive stops or continues to run is dependent on the way the particular fault is implemented. Most standard faults are set up so that the drive will stop if a fault occurs. Faults stored on the Fault List will appear when viewing Function # 0.
The second method for error handling is called ‘error recording’. Error recording differs from fault recording in three respects:
1. The error condition will not be shown on the SCDU or the red Fault LED.
2. The error list stores the 16 most recent errors and always overwrites the oldest error with the newest error.
3. This list is maintained in battery-backed-up RAM and is retained when the drive is powered down or reset. Operation of the drive is totally independent of whether error recording is enabled or not.
4. The Errors List may be viewed at Function # 800.
Function # 801
Used to display or alter the Fault & Error Disposition List. This list is consulted any time an error condition occurs to determine whether it should be reported as an error, a fault, or both. The process for changing the entry in the disposition list for a particular error using the SCDU is as follows:
3) Use the ▲ and ▼ keys to select the error code entry in the Disposition List that is about to be changed/viewed. For example, if the disposition for error code 102 (Numeric Underflow) is to be modified, press the key until the SCDU display changes to:
4) Press the ENTER key when the desired error code is displayed on the SCDU. The red LED now lights, and the SCDU display changes as well to a format of ‘E.xF.y’.
The ‘E’ and ‘F’ are abbreviations for Error and Fault respectively. The ‘x’ and ‘y’ will be either ‘1’ or ‘0’ to indicate which list will record the error. For example, if the display is ‘E.1F.1’, the error is recorded in both lists. If the display is ‘E.0F.1’, the error is recorded in the fault list, but not in the error list. If the display is ‘E.0F.0’, neither list records the error. In the example above, the factory set default disposition for a numeric overflow F#102 is to record the error in the Error List, but not in the Fault List. In this case, the SCDU display is:
1) Use the ▲ and ▼ keys to select
function number # 801 from the function level. The two colored LEDs remain off during this step.
2) Press the DATA/FCTN key to enter the
"Data" level for Function #801. The green LED will light and the error code last modified, with Function #801, will be in the SCDU display. The SCDU displays error code #13 (illegal instruction) initially:
5) Press either the ▲ or ▼ key repeatedly to change the numbers after the ‘E’ and ‘F’ from ‘1’ to ‘0’ and vice-versa. Starting from no declarations, the displays are: ‘E.0F.0’, ‘E.0F.1’, ‘E.1F.0’, and ‘E.1F.1’. For example, if the disposition for this error should be changed so that it is NOT recorded in either the Fault or Error list, press the ▼ key once so the display changes to:
This display indicates that the Numeric Underflow error will now be recorded in the Fault List, but not in the Error List.
34
Page 37
Pressing the ▼ key once more will change the display to:
This is the desired status for the new disposition of the Numeric Underflow error,
which is to not report it to either the Fault or
Error List.
6) Press the ENT key when the new
disposition code is in the display. At this point, the green LED will light, and the SCDU displays the error code again:
Standard Control/Display Operation
2) Press the DATA/FCTN key to enter the
"Data" level for this function. The green LED
is now lit to indicate that the fault codes currently in the Fault List are being displayed. The very first display at this point is the word 'ALL':
The SCDU display always displays the fault code that will be removed if the ENTER key is pressed. If the ENTER key is pressed at this time, every fault currently in the Fault List will
be removed from the list.
Each fault in the Fault List can be shown on the SCDU display and optionally cleared.
IMPORTANT
The ▲ and ▼ keys can now be used to select another error code to be modified, as in step 3.
7) When all changes in the Error Disposition
List are finished, pressing ENTER key will exit back to the function level:
Fault Display/Clear
The drive stores the first 16 faults that have
been reported to the Fault List, Function # 0.
Once the Fault List is filled with 16 faults, it will not accept any more entries. The data in this buffer is not retained when the power is lost. Each time a fault condition occurs, and its entry in the Disposition List is set to record also in the Fault List, the new fault is placed on the list, provided the list is not full.
Function # 0 Reserved for viewing the Fault List. The steps
to view the Fault List are as follows:
1) Use the ▲ and ▼ keys to select
Function # 0. The two colored LEDs remain off during this step. Note that simply pressing the ▲ key once can access this function, if the SCDU display is ‘P-UP’.
The process of clearing a fault from the Fault
List DOES NOT actually clear the condition
that caused the fault.
To view the first fault on the list, press the ▲ key. If there is a Numeric Underflow fault 102 is on the Fault List, for example, the SCDU display will change to:
The contents of the Fault List may be examined by using the ▲ and ▼ keys. The ▼ key moves down the fault list while the ▲ key moves up the fault list. The first fault in the list is the first fault actually declared. The SCDU displays the word 'End'
after the last fault has been displayed:
Error Display
The drive is able to store the most recent 16 errors that have been reported to the Error List. This list is constantly updated, with the newest error overwriting the oldest in the list.
35
Page 38
Standard Control/Display Operation
This list is held in battery-backed-up RAM (NVRAM), so it is retained when power is lost. Each time an error condition occurs, and if its entry in the Disposition List is set to allow recording in the Error List, that new error is placed in the list.
Function # 800 Reserved for viewing the Error List in NVRAM.
The steps to view the Error List are as follows:
1) Use the ▲ and ▼ keys to select
Function # 800. The two colored LEDs remain off during this step.
2) Press the DATA/FCTN key to enter the
"Data" level for the view error function. The green LED is now lit to indicate that an error code is currently being viewed. If the error in this slot is a Numeric Underflow fault 102 for example, the SCDU will display:
perform transfers between the NVRAM parameter list and the active parameter list.
Function # 994 is used to perform the transfer of data between the NVRAM and active parameter lists. The process for copying data to or from the NVRAM parameter list is as follows:
1) Use the ▲ and ▼ keys to select Function # 994 from the function level. The two colored LEDs remain off during this step.
2) Press the DATA/FCTN key to enter the "Data" level for Function # 994. The green LED is now lit to indicate that this function is currently being accessed. It is possible to SAVE the current active parameters in RAM to the NVRAM parameter list, or to RESTORE the current parameters from the NVRAM parameter list to ACTIVE RAM. Note that a
RESTORE is the same operation that occurs inherently every time the drive is powered up.
Upon entering the data level for this function, the SCDU displays:
Other errors currently in the Error List can be
viewed by pressing the ENTER key to display
the Error Code again, then use either the ▲ or ▼ key to move to the next slot in the list. The procedure outlined above should be repeated as necessary to view the Error Code number for other errors in the Error List.
Non-Volatile Ram Access
Every parameter that the drive uses has three separate areas in memory associated with it. There is a factory-set default value for each parameter which is stored in the “read only” EPROM chips. There is an area in the active RAM which the drive uses while it is running. There is also an area in NVRAM reserved for each parameter. The values in the NVRAM area are copied to the active RAM every time the drive is powered up or the reset button is pressed. This split level approach makes it possible to return to the last set of ‘stable’ parameters in NVRAM if some errors are made during fine-tuning of the active drive parameters. The purpose of this function is to
The ▲ and ▼ keys can be used to toggle between the above display, which indicates a pending RESTORE operation, and the following display, which indicates a pending SAVE:
Note that as soon as either the ▲ or ▼ key is pressed, the red LED will light.
3) Press the ENTER key to actually perform the transfer of data. If ENTER is pressed while 'SAVE' is displayed, the SCDU display may change to:
36
Page 39
This display means that the NV RAM PROTECTION switch is in the incorrect position preventing writes to the NVRAM. Move the switch to the "OFF" position, press the DATA/FCTN key, and start over from step
2.
If the SAVE or RESTORE operation was successful, the green LED will light. For example, if a SAVE were performed, the display would be:
Load Default Function
Every parameter in the drive has a factory-set default value that is loaded when the drive is powered up for the very first time. These default parameters may not be optimal values for the drive when actually running, but they will generally allow the drive to function. It is possible to reload these default parameters
with Function # 995 of the SCDU. A re-load
of the defaults would generally be done when the drive is operating erratically and it is suspected that one or more parameters were improperly set.
CAUTION
Use of the LOAD DEFAULTS function will
overwrite EVERY parameter currently being
used by the drive with the factory set default
for each parameter. There is no way to restore
parameters to their previous value once this
function is used.
Function # 995 is used to perform the transfer of data from the default parameter list to the ACTIVE RAM parameter list. The process for accessing the Load Defaults Function is as follows:
1) Use the ▲ and ▼ keys to select
Function # 995 from the function level. The
two colored LEDs remain off during this step.
Standard Control/Display Operation
2) Press the DATA/FCTN key to enter the "Data" level for Function # 995. The green LED is now lit to indicate that this function is currently being accessed. The SCDU will now display:
3) Press the ENTER key to actually perform the Load Defaults transfer. After the transfer has completed, the SCDU displays the word 'dOnE':
4) A cycling of control power is then necessary to implement the default settings onto the display.
Self Tune Function
The DSD 412 Elevator drive has a built-in current regulator SELF TUNING Function #
997. When activated, this feature measures total motor armature circuit resistance, inductance including wiring, and the field L/R time constant. The drive then uses the measured value in conjunction with the parameter entered for “CROSSOVER FREQUENCY” to calculate integral and proportional gains for the current regulator and to set the field regulator gains properly. After running the Self Tune Parameter Measurement function, the values for armature resistance and armature inductance are stored in NVRAM. It is important to note that it is possible to override the values that have been dynamically calculated for Armature Resistance, Armature Inductance, and Field L/R Time Constant by the “USE SELF-TUNE” item in the parameter menu (Function # 2). The dynamically calculated values are used if “USE SELF-TUNE” is set to “ON” while the manually entered values (entered in
37
Page 40
Standard Control/Display Operation
parameter’s 4, 6, and 51) are used if this item is set to “OFF”.
NOTE:
Armature current is circulated through the
armature circuit during parts of the PCU
Parameter Measurement function. The PCU
will reduce the field current to zero on motors
with a shunt field in order to minimize motor
rotation. If the PCU detects significant motor
voltage during the test, the PCU parameter
measurement function will abort.
Ripple Filter Consideration
It is important to note that when applying a
LRC output filter (Ripple Filter), the drive
performance will be affected. For this reason,
it is necessary to run the SELF-TUNE test with
the output configuration that will be used. For
example, if the filter is used with the capacitor fuse installed, then the SELF-TUNE test must
also be run with the filter fuse installed. If the
capacitors are not needed, then the fuse
should be pulled and the SELF-TUNE test
should be run with the fuse pulled.
The process for accessing the PCU PARAMETER MEASUREMENT function is as follows:
to the "OFF" position, and press the DATA/FCTN key again. The SCDU will jump to step #3 when the NVRAM PROTECTION switch is in the correct position upon entering this function.
2) The SCDU displays the word ‘Entr’ to prompt the user to press the ENTER key as further confirmation that the PCU parameter measurement function is about to be performed:
3) Press the ENTER key to actually start the PCU Parameter Measurement function. The PCU will not begin the measurement routine if a SEVERE PCU FAULT exists. The PCU will declare a SEVERE FAULT under several conditions including an IST fault, power supply failure, line sync loss, low line, or DCU failure. If a SEVERE FAULT exists when the PCU starts the parameter measurements, the SCDU displays:
1) Use the ▲ and ▼ keys to select
Function # 997 from the function level. The two colored LEDs remain off during this step.
1) Press the DATA/FCTN key to enter the
"Data" level for Function # 997. The green LED is now lit to indicate that this function is currently being accessed. The SCDU displays the word 'Prot' if the NV RAM PROTECTION switch is in the position that will not allow any updates to the NVRAM:
If the ‘Prot’ message appears, press the DATA/FCTN key to return to the "Function" level, move the NVRAM PROTECTION switch
Severe faults can only be cleared by pressing the reset button on the Drive Control PCB, by cycling power to the drive, or by replacing the bad component if applicable. The SCDU displays the word ‘tESt’ while it is performing the parameter measurements and there were no SEVERE FAULTS when the ENTER key was pressed:
4) Press the DATA/FCTN key to exit the
PCU parameter measurement routine and return to the "Function" level. The SCDU displays:
38
Page 41
Standard Control/Display Operation
6) After completion of SELF-TUNE, enable
Function # 2. (Unless using manual entry)
Power Conversion Diagnostics
The drive has built-in diagnostic routines that can be performed via the SCDU. The PCU diagnostic routines are able to test for four failure modes. The first test that the PCU performs is a test of the three line fuses. Assuming the three line fuses are all OK, the PCU then performs a test for shorted SCRs/ doubler packs. If this test indicates no shorted SCRs/doublers, the PCU then verifies that less than 5% of the value entered for “Rated Field Current” is attainable. The PCU then tests for open SCRs by passing current through the forward bridge followed by the reverse bridge, and finally checks polarity of voltage feedback. The result of the test is displayed on the SCDU after the test completes. The SCDU will light certain unique LED patterns on its display corresponding with the failure (see displays in the procedure that follows). The Fault Codes F910 (Blown Fuse), F911 (Shorted SCR), F912 (Open SCR), and F917 (Reverse Armature Feedback Wires) will not appear on the SCDU if the Error Disposition List is programmed so that they are not reported to the Fault List.
WARNING
Armature current is circulated through the
armature circuit during parts of the PCU
Diagnostics Function. The PCU will reduce
the field current to zero on motors with a shunt
field in order to minimize motor rotation.
However, a PERMANENT MAGNET motor
must have its shaft locked mechanically prior
to running the PCU Diagnostics routine. If the
PCU detects significant motor voltage during
the test, the PCU Diagnostics Function will
abort.
The process for accessing the PCU Diagnostics Function is as follows:
1) Use the ▲ and ▼ keys to select
Function # 998 from the function level. The two colored LEDs remain off during this step.
2) Press the DATA/FCTN key to enter the "Data" level for Function # 998. The green LED is now lit to indicate that this function is currently being accessed. The SCDU prompts the user to press the ENTER key by displaying:
3) Press the ENTER key to actually start the PCU diagnostics. While the PCU is per­forming the Function # 998 Diagnostics test, the SCDU displays:
The PCU will not begin the diagnostic routines if a SEVERE PCU FAULT exists. The PCU will declare a SEVERE FAULT under several conditions including an IST Fault, power supply failure, line sync loss, low line, or DCU failure. If a SEVERE FAULT exists when the PCU starts the diagnostic tests, the SCDU displays:
Severe faults can only be cleared by pressing the CPU reset button on the Drive Control PCB or by cycling power to the drive.
If the display stays on 'tESt' and the contactor doesn't pick up, there is a fault in motor field connections or settings.
If all tests indicate that there are no failed power components (SCRs and fuses), the SCDU displays:
39
Page 42
Standard Control/Display Operation
Press the DATA/FCTN key to exit the PCU Diagnostics routine and return to the "Function" level. The SCDU displays:
If the PCU detects one or more Open AC Fuses, it displays the fault code for a blown fuse (F910):
Remove power from the drive to replace the SCR(s) that are shorted, and repeat this test until the SCDU displays the 'PASS' message.
If the PCU detected one or more open SCR/doubler packs, the SCDU displays the fault code for an open SCR/doubler pack (F912):
Remove power from the drive, consult Section 5, MAINTENANCE, to replace the SCR(s) that are open, and repeat this test until the SCDU displays the 'PASS' message.
If the PCU detects Reversed Armature Feedback wires, it displays the fault code for a Reverse Armature Fault (F917):
If the PCU detects one or more shorted SCR/doubler packs, the SCDU displays the fault code for a shorted doubler (F911):
Remove power from the drive, reverse the Armature Feedback wires, and repeat this test until the SCDU displays the 'PASS' message.
This fault also occurs if the Armature FB wires are not connected.
40
Page 43
Drive Setup & Adjustments
Motor Field Current Control
Motor field current is held at Stand-By amps Function # 53 when the elevator is idle. When the Drive Enable command is given, field current will rise as fast as possible to the level programmed in Function # 50. The drive will not allow a drive start to occur until motor field current rises above the threshold level set at Function # 32. At high speed, the motor field current will automatically weaken to the level set at Function # 49. If the field current feedback fails to track the field current reference by more than 5% for 5 seconds Fault ‘413’ will be declared. The universal motor field control module supplied with DSD 412 can operate motor fields from 0.2 through 40.0 ADC. There are connection provisions for using a user supplied voltage source.
Analog Velocity Follower
The elevator car controller provides an analog velocity reference to the drive at A1TB1-63 and A1TB1-68. The signal may be bi-polar +/­10 VDC to indicate speed and travel direction, or a positive only unipolar signal with the direction of travel selected by logic commands. See descriptions of Function # 110 and # 115. In most cases the signal profile will be adjusted by the car controller for precise landing positioning. The velocity reference passes directly to the E-Reg closed loop velocity controller, except for an internal rate limiter Function # 21 to buffer any unexpected electrical noise. Start and Stop commands are via 24VDC logic inputs. The analog velocity reference signal may be adjusted using Function # 82 'Gain' or Function # 86 'Bias'.
Internal Preset Speed & Profile Generator
The elevator car controller provides 24VDC logic input commands to select one of 7 pre­determined running speeds. The DSD 412 drive generates a smooth S-Curve acceleration profile to transition between speed selections. Either of three separately adjustable ramp times may be selected. The direction of travel is determined by either a single (up/dn) or dual (Run-Up / Run-Dn) logic commands. There are provisions for allowing or disallowing non-stop direction reversals. The internal pre-set speed-operating mode is selected by setting #110 to 2. The speed sensitivity of pre-set speeds is altered by #82. Set #82 to 1.00 for proper calibration.
Drive Setup & Adjustments
Serial Link Follower
The elevator car controller provides the equivalent of an analog reference command over a digital serial link. The drive returns operating status conditions and messages. Primary Start and Stop commands are 24VDC logic for redundant safety. This operating mode is selected by setting #110 to 3. The speed sensitivity of the serial velocity reference may be adjusted using Function #
82. See Preset Speed Logic Sequence on page 50.
Armature Voltage Feedback
A DC motor with rated field current applied produces rated armature voltage when it spins at rated speed. This results in speed regulation in the range of 5%. When in this mode, operation over base speed is not possible since the field weakening is inhibited. When this mode is enabled it is still possible to monitor the feedback from the encoder although it will not used for speed regulation. Due to the nature of this mode of operation, the speed regulator gain is defaulted at 2 radians to prevent unstable operation (it shouldn't require to be changed from this point). A new parameter F#38 was added so it won't be required to modify the normal speed regulator gains F#39 and #40, when it switched. See descriptions for Functions # 112 and # 113 for setting this mode.
Pre-Torque, Function #114
When enabled, the speed error integrator will be pre-conditioned by the supplied pre-torque signal before starting E-Reg. This will cause motor armature current to begin at a magnitude proportional to the pre-torque command to prevent elevator motion or rollback when the elevator brake is released. The pre-torque signal will be from either an analog or serial link digital source as selected by software Mode switch Function # 110.
Current Ramp-Down, Function #85
When the DSD 412 drive is told to cease operation by removal of the Run logic command, (and after Brake Drop time if that function is engaged) the armature current reference ramps down to zero at a constant rate controlled by Function # 85. When armature current ramp-down is complete, the contactor will be opened. In the event that the contactor opens unexpectedly, as reported by the feedback contact at A1TB1-7, or in the
41
Page 44
Drive Setup & Adjustments
event of a severe drive fault, there will be no timed delay for current ramp-down.
Electronic Motor Over-Load
An electronic motor over-load function is provided to take the place of heater type power components. Motor armature current is continuously monitored and the heating effect is calculated over time. A motor overload trip will not automatically stop the drive, but is an important alarm signal to elevator car controller to help prevent equipment damage.
External/Auto Fault Reset, Function #101
An external Fault Reset command signal from the car controller may be applied to logic input A1TB1-49. Or, an automatic Fault Reset will occur 5 seconds after a drive fault occurs, if enabled by Function # 101. This will enable the car controller to quickly recover from a re­settable fault. One Fault will be subtracted from a fault count accumulation every 20 minutes. The maximum number of Auto­Resets that can be accumulated is 5. The Auto-Reset function will then require manual intervention.
Over-Speed Test, Functions #80 and #81
Two adjustment functions are provided to help testing of the elevator governor over-speed trip. Function # 81 defines a reference multiplier value. Logic Function # 80 turns the effect of that multiplier on and off. However, be aware that the Drive Over-Speed trip fault F97, set by Function # 12, is a fixed percent of rated rpm and will also be tested, and indeed should trip. To ensure that the drive Over­Speed Trip does not interfere with the governor test, one must temporarily raise the value set in Function # 12 to be above the trip speed of the governor.
Brake Control Logic, Functions #186 and #183
Two relay control outputs are provided (Brake Lift, Brake Pick) by programmable output selection functions #186 and #183. Three timers are provided, Brake Pick #89, Brake Drop #90, and Must Stop #91. Suggested wiring is shown in . Operation is as follows:
Elevator Start with Brake Control:
1. The drive is started by activating first the ENABLE then RUN command lines. The contactor will pick (pull in), and when acknowledge, the drive will start the current and velocity regulator by priming it to provide pre-torque armature current (if enabled).
The internal velocity reference will always start at zero.
2. Once Start is confirmed, the Brake Lift and Brake Pick lines will both become active. This will apply full voltage to the brake coil and cause the brake to lift.
3. The Brake Pick output will deactivate at the end of Brake Pick time #89, and release the internal velocity reference clamp so that the drive can begin acceleration. The Brake Lift output will remain active. (Dropping of the external Brake Pick relay will reduce voltage to the elevator brake coil.)
Elevator Stop with Brake Control
1. Automatic setting of the Brake and drive shutdown sequence may begin at any speed.
2. The Drive RUN command is released by customer’s logic. This will set the internal reference speed to zero and start the Must Stop Timer. The velocity regulator will continue to control velocity and current, driving the speed to zero via the decel rate.
3. When the drive measures encoder speed as being zero (adjustable by #63) the Brake Lift and Brake Pick outputs will de­energize. The drive velocity regulator will continue to hold zero speed while the brake drops, as set by the Brake Drop Timer #90.
4. When the Brake Drop Timer expires, motor armature current ramp-down will occur, as set by #85. This will gradually transfer torque from motor to brake to help prevent brake ‘thumping’.
5. When Current ramp-down is complete, the drive will cease operating and open the contactor.
6. If Brake Auto Stop #92 is ON, AND a zero speed command is present, AND the drive is stopped, the sequence of 2 – 5 above will be activated. NOTE: The drive will turn OFF with the Drive Run and Enable commands still active. These signals must be cycled to recover and re-start from this auto-stop operation.
If the Must Stop Timer #91 expires before zero speed is achieved, the Brake Lift and Brake Pick relay outputs will be de-energized and the drive will shut down regardless of the actual velocity. This is a secondary back up means of ensuring that the elevator will stop.
42
Page 45
Drive Setup & Adjustments
Speed Regulator Adjustment/E-Reg
The Magnetek DSD 412 drive uses a proprietary velocity regulator called E-Reg. This is a double speed loop encoder feedback regulator designed specifically for elevator / lift applications where the objective is to smoothly follow a repeated accel/decel speed pattern reference with a relatively fixed load. The following characteristics are important: Follow the reference speed with a
consistent tracking delay, see Figure 13: E­REG Tracking Profiles (1).
No overshoot at the end of acceleration Precision speed following, including at zero
speed
Feed forward for inertia forcing Rejection of resonant load characteristics Ability to start with a pre-primed error to
counteract load offset rollback
Velocity
Reference
S P E E D
0
ZERO
SPEED
ACCEL TIME
E-Reg Velocity Tracking with proper PU-Inertia. No over/under shoot
Figure 13: E-REG Tracking Profiles (1)
Primary adjustments for E-Reg are:
High & Low Speed Bandwidth – #39 & 40 Sets the desired drive response from Speed Reference changes to motor speed. Units are Radians/sec of the closed loop crossover frequency bandwidth. The constant time lag characteristic of E-Reg will be 1/Response, in seconds. Increasing the Response setting will increase the gain to improve velocity-tracking performance. A setting of 5.0 – 8.0 for the Response is normal for most elevators. Setting the Speed Bandwidth to a high value in order to compensate for a poor Per Unit Inertia setting is an improper adjustment. There may be some minor interaction between the Bandwidth and Stability adjustments.
RATED SPEED
Speed Feedback with Bandwidth
(#40) set to 10 radians,
100 mSec tracking delay
Speed Feedback with Bandwidth
(#40) set to 5 radians,
200 mSec tracking delay
TIME
43
Page 46
Drive Setup & Adjustments
Velocity
Reference
S P E E D
Speed Feedback with Per-Unit Inertia (#41)
Velocity Overshoot
0
ZERO
SPEED
ACCEL TIME
TIME
E-Reg Velocity Tracking with Per-Unit Inertia Setting TOO LOW, Velocity Over-Shoot
RATED SPEED
set too low,
Figure 14: E-REG Tracking Profiles (2)
RATED SPEED
Velocity
Reference
S P E E D
0
ZERO
SPEED
ACCEL TIME
Speed Feedback with Per-Unit Inertia (#41)
set too high,
Velocity Undershoot
TIME
E-Reg Velocity Tracking with Per-Unit Inertia Setting TOO HIGH, Velocity Under-Shoot
Figure 15: E-REG Tracking Profiles (3)
44
Page 47
Drive Setup & Adjustments
Field Regulator Set-Up
Proper control of motor field current requires knowledge of the motor field resistance, the electrical time constant, and the line voltage available to control power to the motor field. Motor field resistance is calculated from the settings of Rated Field Volts #52 and Full Field Current #50. The time constant and available AC input voltage is supplied by settings #51 and #55. If a separate source of field circuit voltage is used, #55 should be set at that voltage. Otherwise leave #55 set at zero to automatically utilize the main input voltage setting of #9. If #2 is set to ON, the Self-Tune measured value for L/R #615 will be used instead of #51. Verify that the above settings are correct. The scaling of measured motor field current is also important. Verify that the motor field wiring is connected correctly to the proper ampere range tap at TB4, and that SW1 is set accordingly. Check the calibration of measured field current, drive display #612, against that of a separate DC clamp-on ammeter clipped around a motor field wire.
If motor field weakening is not required at top speed leave WEAK FIELD CURRENT #49 set to 40 amps or set it equal to RATED FIELD CURRENT #50. Set STANDBY FIELD CURRENT #53 as desired during drive idle.
If top speed is greater than the motor base speed, set WEAK FIELD CURRENT #49 so that actual motor voltage does not exceed the RATED ARMATURE VOLTS #7 during a high speed, full load run. The crossover point between Full Field and Weak Field current will be automatically calculated. Motor field current will be adjusted by those settings and measured encoder speed. The DSD 412 drive does not directly regulate armature voltage. This is determined by field current adjustment settings and measured rotational speed.
Be sure to adjust motor field current so that rated armature voltage is achieved at top speed before attempting to set Per-Unit Inertia.
Note: If Field Current is set too low, the
necessary motor torque may not be available, resulting in excessive motor armature current or current limiting. If Field Current is set too high, the armature voltage may exceed voltage-limiting points, resulting in faults F407 or F408. Either condition may create an elevator tracking error. To properly set #50 Full Field amps put full load in the elevator and run in the up direction at 20% contract speed while monitoring #611 armature current
feedback. The goal is to run at #3 rated motor amps. Decrease #50 to increase armature
current. Increase #50 to decrease armature current, but be aware that this may cause unwanted motor heating. To set #49 weak field amps run the elevator at balanced load, 100% contract speed, monitor #610 Armature Volts and adjust weak field amps until the motor is running at #7 rated armature volts. Reduce weak field amps #49 to reduce armature volts. Increase Weak Field amps to increase armature voltage. Ensure that the nominal voltage on the secondary of the isolation transformer is 10-20% greater than rated armature voltage #7.
AC Input Voltage Requirement & Adjustment The line-to-line AC RMS input voltage to the drive should be greater than or equal to the rated Full Load Armature Voltage. To adjust the transformer taps, run the elevator at full motoring load and rated motor RPM. (Empty car down) During the constant speed portion of the profile, measure the AC voltage input to the drive (Secondary of Isolation Transformer), #619, and the DC Armature Voltage #610. If the Armature Voltage is greater than the Input Line Voltage, adjust transformer primary taps to get the next higher voltage level on the transformer secondary.
Per-Unit Inertia, Function #41
Be sure to have completed adjustment of the motor field current regulator BEFORE making final adjustments of system inertia. Start with default values for Response Bandwidth #39 &40, Per Unit Inertia #41 and Stability #42. Use a speed profile with a minimal amount of S-Curve smoothing. Select two elevator landings far enough apart so that the elevator can attain maximum speed between stops. [But not the end landings during initial tuning.] It is a good idea to begin at a restricted low speed like inspection speed for initial verification. Run the elevator up and down repeatedly between the same two landings while monitoring car speed via function #600 on the DSD 412 local display. The objective is to have the car speed accelerate right up to the desired speed, so look for speed overshoot or undershoot as the car reaches set speed. If there is speed overshoot – INCREASE the setting for Per Unit Inertia #41 in proportion to the amount of overshoot. If the speed ramps up as expected but slowly creeps up to the final desired speed
45
Page 48
Drive Setup & Adjustments
(undershoot) – DECREASE the setting for Per Unit Inertia. Repeat the above at higher set speeds until the car will accelerate up to rated top speed, or decelerate back down to zero speed, without over/under shoot. Ideally, the Per Unit Inertia should be set with a balanced carload as this represents a typical payload. If initial tests are made with an empty car, increase the setting found with the above method by 10% to estimate the additional effect of passenger payload. Save this setting using the DSD 412 function #994.
Stiffness, Function #42
Sets the gain of internal PI error amplification and inner loop regulator gain. Affects the responsiveness of the drive to ignore or react to load disturbances. Range 0.5 to 9. No calibrated units. Low numeric values will yield smooth performance while following reference changes. High numeric values will yield better response to speed errors and load disturbances, but can cause amplification of elevator rope resonance.
Gain Switch Speed and High Speed Bandwidth, Function #105 and #39
If higher settings of Speed Bandwidth and Stability are necessary to achieve repeatable good floor landing and take-off characteristics, but rope oscillations or other mechanical vibrations occur at higher speeds a good countermeasure is to lower the bandwidth setting (gain) at higher speeds. Set the Gain Switch Speed #105 to a speed below where the vibrations occur. Set High Speed Bandwidth #39 to a value less than that of #40 to help suppress system oscillations.
Gain Reduce, Function #108
The Gain Reduce multiplier function has been replaced by two separate settings, #39 & #40.
Tach Rate Gain, Function #107
This function controls derivative encoder feedback. Increase this setting to suppress rope stretch bouncing or similar other disturbances. Very helpful in high rise buildings for smooth landing performance. However – This feature can sometimes cause amplification of minor vibrations, causing them to become worse. Keep this adjustment set to zero unless demonstrated to provide a useful purpose.
Notch Filter, Function #190 & #191
Some hoist ways may have rope resonance’s that cause occasional vibrations, roughness of ride or continuous oscillations at certain low frequencies (9-14 Hz). There may be critical hoistway locations or payload weight combinations that tend to be more sensitive than others. The effects are often felt rather than heard. The frequency sensitive notch filter, placed in the software path of the torque / armature current reference signal, can be effective to suppress the response of the DSD 412 drive to amplify those frequencies. Adjustments for this filter are via #191, the period, or center frequency of the filter, and #190, the depth of the notch, or its ability to attenuate. See
Table 11: Notch Period Steps.
Use the filter as follows: Determine the approximate frequency of
the oscillations or rope ‘ringing’.
Use Function #191 to set a center
frequency value slightly higher than that of the observed disturbance. The default value of 7 (12 Hz) will be sufficient in many cases.
Increase the value of #190 to suppress
the tendency to respond or amplify rope resonance.
CAUTION
Be aware that the ability of the drive to follow
the speed commanded by the car controller is altered by these adjustments. If the frequency of the filter is set too low, or the notch depth is
set too deep, there may be interference
problems associated with operating the closed
loop velocity regulator or position control loops
within the Car Controller. Typical symptoms
would include position overshoot of floor landings and potentially repetitive speed
oscillations or speed ‘hunting’. If these
symptoms occur, back off on the Notch Depth
setting #190 and/or reduce the setting of
#191 (Notch Period), increasing the notch
center frequency to avoid interference.
46
Page 49
Motor Overload
Motor armature current is sensed and mathematically integrated over time to detect potential over heating caused by a dragging brake shoe or other repeated abuse beyond ratings of the equipment. The calculation formula used for the electronic motor overload
is:
)(2 KoiTt
Where: t = Calculated time to trip in seconds i = Measured Per Unit motor current. Drive Param #3 defines motor Per Unit current in amperes. T = Time to trip setting #83 at motor current of (Ko+0.5) per unit current. Ko = Maximum Per Unit current that will not cause an Overload Trip #84.
The USA National Electric Code (NEC) requires that the overload be adjusted to detect overheating of the motor and motor wiring by using rated motor current as the comparison base. This is not the same as rated current capability of the drive. The NEC requirement is that the overload must trip at
1.15 PU current (no time specified), and after 60 seconds at 1.5 PU current, and after 10 seconds at 2 PU current. It is recommended that the default values of Ko=1.1 and T=50 be used. This will provide no tripping with average motor current of 1.1 PU or less, and a tripping time of 62 sec at 1.5 PU. See the timing graph of Figure 16: Motor Overload
Overload Trip Time
Ko=1.1, To=50
200.0
150.0
100.0
Seconds
50.0
0.0
1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8
Per Unit Current
MOTOR OVERLOAD, Ko=1.1, T=50
Figure 16: Motor Overload
Drive Setup & Adjustments
Start – Stop Timing
A typical elevator run sequence is shown in Figure 17. A descriptive explanation is given below. Start Sequence – Mode 2, internal pre-set speeds
1. Close Drive & Field Enable – Sets field current reference to Full Field, enables drive to operate. This contact must be held closed during entire elevator run, including armature current ramp down. Opening of this contact will disable the drive and cause the loop contactor to be dropped immediately.
2. Close Safety-Chain circuit. – Must be closed for drive to start. Must remain closed during entire elevator run. Otherwise, an F405 fault will result.
3. Select desired direction and speed – Might be done before or after drive is told to Run.
4. Close Hardware Run (or Run-Up or Run­Down contact) – Causes LPR to pick when field current is greater than setting #32. LPR picks contactor, which closes Loop Confirm – Drive will begin running by pre­loading the speed error integrator with the available pre-torque signal, if enabled at Function #114. Logic Output Selection ‘C’, Run Engaged, will become energized to indicate that the drive has control of motor speed. Speed will begin to accelerate toward desired speed, if not set at zero. If contactor fails to pick, F402. If motor
armature circuit is not closed before Loop Confirm closes, an F98 or F901 may occur.
5. Release brake - Timing of actual brake
release must be coordinated with starting the drive and/or changing the target speed. The drive must be running and be either pre-torqued, or starting to accelerate, or have ARB engaged to prevent rollback.
6. A new target speed and or direction
may be selected before or after the drive is started. When speed rises above the setting of #64, the Low Speed logic indicator will turn off. (Output function ‘F’)
47
Page 50
Drive Setup & Adjustments
Stop Sequence
1. Select leveling or zero speed reference – Will cause start of deceleration to new target speed.
2. When speed becomes less than the setting of #64, the Low Speed logic indicator will become active to indicate a door pre-opening speed. (Output function ‘F’)
3. Select zero speed – Will cause drive to decelerate to zero speed & hold car position. When speed drops below the setting of #63, the Zero Speed logic indicator (Output function ‘J or K’) will become active.
4. Set elevator brake – Wait the appropriate amount of time for the brake to drop, or use a brake limit switch to confirm when
the brake is physically set.... Then
5. Open Hardware Run contact (or Run-Up or Run-Down contact) – Will cause drive to stop controlling speed, turn the Run
Engaged logic indicator (Output function ‘C’) off, and ramp armature current down to zero in time set by function #85. Drive will open LPR, contactor, & Loop confirm when Ramp-down is complete. If contactor confirm fails to open, F402 fault will result.
6. Open Safety Chain (if desired) – Must remain closed for current ramp-down to happen. If current ramp-down is not desired, set #85 to minimum. Expect some contactor barking. If Safety Chain opens unexpectedly while drive is running, F405 fault will result. Safety chain may remain closed.
7. Open Drive & Field Enable (if desired) – Will cause field current to go to stand­by/idle value. May remain active if drive will be restarted shortly. However, if drive is not restarted within 5 minutes with Drive & Field Enable active, F403 fault will result.
48
Page 51
SAFETY
CHAIN
DRIVE & FIELD
ENABLE
HARDWARE
RUN
LPR /
CONTACTOR
CONTACTOR
ACK
SPEED
DIRECTION
& RAMP
CMDS
RUN
ENGAGED
ZERO
SPEED
MOTOR
FIELD
CURRENT
MOTOR
ARMATURE
CURRENT
ELEVATOR
VELOCITY
ELEVATOR
BRAKE
PRE-
TORQUE
MUST REMAIN VALID DURING ENTIRE RUN
AS REQ'D DURING RUN
FIELD
WEAKENING
IF REQ'D
AS REQ'D
DURING RUN
ACCEL DECEL
Drive Setup & Adjustments
1
0
1
0
1
0
1
0
1
0
RUN
SPEED
ZERO
SPEED
1
0
1
0
FULL
STAND-BY
OTHER
RAMP DOWN
ZERO
OTHER
ZERO
RELEASED
SET
Figure 17: Elevator Start - Stop Timing
49
Page 52
Drive Setup & Adjustments
Stopping Distance
The internal S-Curve velocity generator of the Magnetek DSD 412 drive is digital in nature and is therefore very repeatable. The Accel/Decel time is fixed per the selected rate adjustment setting. The time setting represents the total acceleration time from zero to rated speed (or vice-versa), and is independent of any S-Curve selection. The starting and stopping distance from and to any other digitally pre-set speed can be pre­calculated and will also be repeatable.
The distance traveled during deceleration to zero or to a lower leveling speed will be:
S = Tsec x DeltaFPM/RatedFPM x (LevelingFPM/5 + DeltaFPM/10) (inches)
Where DeltaFPM is the change in steady state running speed in feet per minute
However there is fixed delay and an uncertainty of actual time to recognize and start obeying a logic command to start the deceleration cycle. The fixed delay is 0.01 seconds and the uncertainty is 0.018 seconds maximum. During this time the elevator will still be moving at running speed, creating an uncertainty in the actual stopping distance.
This delay plus uncertainty distance will be:
Serror ≤ RunningFPM x 0.028 x 12/60 = RunningFPM x 0.0056 (inches)
So the total maximum stopping distance or deceleration distance to leveling speed will be:
Stotal ≤ Tsec x DeltaFPM/RatedFPM x (LevelingFPM/5 + DeltaFPM/10) + RunningFPM x 0.0056 (inches)
For multi-floor runs, the slow-down vane switch must be at least that distance from the landing or the floor may be missed.
For single floor runs, the acceleration distance may be calculated similar to above, without the uncertainty error. The slow-down vane switch for the next landing must be at least that far away from the beginning of the run. The single floor target running speed and/or accel/decel times must be adjusted to meet the above criteria conditions or the landing may be missed.
Note that if minimum flight time is desired a different deceleration rate may be selected to
optimize the result. A longer decel time can result in a faster flight time since less time is spent at leveling speed. A second set of accel/decel parameters may be activated by use of the optional Ramp Rate Select contacts.
An optimizing procedure would be:
1. Set the Accel Time and percent jerk for ride quality.
2. For short runs, (i.e. where the distance from the starting floor to the vane switch is less than the distance from the vane switch to the stopping floor) set the target speed so that the accel distance is less than the distance from the start to the vane switch.
3. Set the Decel Time so that the stopping distance is just a little less than the distance from the vane switch to the stopping floor.
4. For multi floor runs set the speed to contract speed and set the decel time so that the decel distance is just slightly less than the distance from the vane switch to the target floor. Other options certainly exist.
Preset Speed Logic Sequence
Binary - The internal pre-set-speed selector in binary mode (Fctn #150 ON) uses 3 input lines to select 1 of 8 pre-set speeds (including zero), see Table 6. Binary logic reduces the number of control lines but the logic inputs to select those independent speeds may not be properly de-bounced at the sending or receiving end. This may allow an unintended speed to be momentarily selected. To prevent this from happening, the user should consider using 4 pre-set speeds, including zero, selected in a gray scale progressive manner (only one switch changes at a time).
Progressive - An alternate method of one-at-a­time control that has more pre-set speeds and takes advantage different Ramp Rates (R-R) during operation, set #150=Off for Progressive input control, see Table 7. Connect A1TB1-10 to A1TB1-54, and A1TB1-51 to A1TB1-12 to automatically activate R-R 2 with a 1 Floor Run and R-R 3 with Multi-Floor runs. R-R 1 will be activated for leveling and inspection, speed #1. If Decel Rate Latch #116 is ON, these rates will be held active during deceleration.
Note: R-R 3 overrides R-R 2 which overrides
R-R 1.
50
Page 53
Drive Setup & Adjustments
Example:
(With #150=On) S2 S1 S0 Pre-set # Use 0 0 0 none Zero Speed select 0 0 1 1 Leveling Speed 0 1 1 3 1 Floor Run Speed 1 1 1 7 Multi-floor Run Speed 0 1 0 2 Inspection Speed (could also be speed 4, 5, or 6)
NOTE: Always set all other unused pre-set speeds to zero.
Table 6: Binary Input Control
Example:
(With #150 = Off, & #112 = On) S4 S3 S2 S1 S0 Pre-set # Use 0 0 0 0 0 none Zero Speed select 0 0 0 0 1 1 Inspection speed w/ R-R 1 rates 0 0 0 1 0 2 Leveling Speed, w/ R-R 1 0 0 1 1 0 3 1 Floor Run Speed, w/ R-R 2 0 1 1 1 0 4 Multi-floor Run Speed, w/ R-R 3 1 1 1 1 0 5 Express zone speed (optional)
Table 7: Progressive Input Control
Drive & Field Enable
The Drive & Field Enable contact input enables the drive to run and also acts as a command to fully energize the motor field. Closing Drive & Field Enable in advance of the Hardware Run, or Run-Up / Run-Down, command will allow time for the motor field to become fully energized for a minimum of starting delays. When the Drive & Field Enable circuit is open, the motor field circuit will be energized at the stand-by current level. If Field Enable remains ON for more than 5 minutes without running the drive, an F403 will occur and the Full Field condition will be turned OFF.
RUN w/ DIRECTION & RUN-UP / RUN­DOWN
One of two methods may be selected to Run the drive and determine the direction. Use function #115 to select.
1.) Hardware Run & Reverse (#115 = Off) The Hardware Run input starts the drive. The Reverse contact controls the direction. The Drive & Field Enable signal must also be energized and remain so for this to occur. The desired direction command should be stable before a non-zero speed reference is selected. CAUTION – The direction control from this input is not interlocked with any other logic condition. This facilitates direction control while re-leveling or performing a quick reverse while heading for a ‘home landing’, but it also means that an intermittent contact or broken
wire can make the car go in the wrong direction!
2.) Run-Up & Run-Down (#115 = On)
Two separate logic inputs are provided to start the drive in either the up or down direction. The Drive & Field Enable signal must also be energized and remain so for this to occur. If both Up and Down directions are active simultaneously, the drive will not start. This prevents a single relay contact or wiring failure from starting the drive in the wrong direction. Once running, the direction may be reversed by closing the contact for the new direction and releasing that for the old. This is allowed at any speed. If the command contact closures overlap, speed control will remain active and the contactor will not drop.
Using External Velocity Commands
Operation with an external analog velocity command is similar to the sequences above. This mode is programmed via the logic select function #110. Setting #110 to a 1 enables the bi-directional analog follower mode. The actual car direction will always follow the polarity of analog reference. Both the Drive & Field Enable and the Hardware Run signals must be active to cause the drive to run. When function #110 is set to 4, the uni-polar analog follower mode is active. The drive will control the speed of the elevator based on the positive value of the supplied analog reference. The direction of travel will be
51
Page 54
Drive Setup & Adjustments
determined by the status of either the direction select (function #115 =OFF) or Run-Up/Run­Down (function #115=ON) logic input command lines. Both the Drive & Field Enable and the Hardware Run signals must be active to cause the drive to run.
Avoiding Analog Signal Ground Noise
Analog reference wiring is sensitive to electrical noise interference. The reference signal channels are differential and should be wired with twisted pair, shielded cable, as shown in Figure 7: Typical Analog Signal Wiring. Be sure that the cable shield is connected only at the drive end.
CAR
CONTROLLER
PLC
RefOut +
RefOut -
Common
GND
Common mode voltage noise is rejected at differential reciever.
Serial Link Connections
MAGNETEK
Twisted & Shielded
TB1
(68) +
(63) -
N.C.
at PLC end
Vnoise
(66,70) com.
(69) shld
(44 OR 43)
(TB11) GND
Proper connections.
Noise current does not flow through signal wires or shield.
Figure 18: Analog Signal Ground Noise
DSD-412
DC DRIVE
Differential
Input
Circuit
Common
RS-232
TXD RXD
CIRCUIT
COMMON
+5V
J2
RJ-12
1 2 3 4 5 6
Figure 19: Serial Link Connections
52
RS-422
TX+
TX­RX-
RX+
CIRCUIT
COMMON
+5V
J1
DB-9
1
6
2
7
3
8
4
9
5
Page 55
Drive Setup & Adjustments
Serial Communication Specification
See Function #110 to enable this feature. The serial communication link between a host and the DSD 412 consists of two messages. There will be a Demand Velocity/PreTorque Command sent from the host to the DSD 412 every 15 MS. There will be a Demand Velocity Response message sent from the DSD 412 to the host every 45 MS.
After power up the drive will wait 10 seconds for the first Drive Velocity Command (DC) message to be received from the car
COMM FLT (F117) will be declared. Once communications has been established, a valid DC message must be received at least in 150 MS intervals. If this time window expires, a 150 MS COMM FLT (F118) will be declared.
Frame format: 10 bits (N81) @ 19.2K baud. RS232 may be used with the 46S02975-03xx Drive Control PCB at connector J2. RS422 requires the 46S02975-04xx PCB with a DB9 J1 connector. Pin-out is per Figure 19: Serial Link Connections.
controller. If this time expires, a 20 SEC
Demand Velocity Command message from the host is as follows:
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Sync Byte FAh
Bytes 1&2: These bytes will always be set to FAh and 05h respectively. They are used for the
purpose of synchronizing the DSD 412 to the start of an incoming message from the host.
Byte 3: {N259_C001} This byte contains the logic commands sent from the host to the DSD 412. The
bit definitions are listed below: B0: =1 to act as a synchronization bit for incoming messages from the host. B1: =1 to act as a synchronization bit for incoming messages from the host. B2: 0=Stop requested 1=Run requested B3: 0=No request to clear faults 1=Clear fault requested B4: 0=Demand Velocity is not DOWN 1=Demand Velocity is DOWN B5: 0=Demand Velocity is not UP 1=Demand Velocity is UP B6: 0=Idle field command 1=Full field command B7: A rising edge of this signal acts as a latch to capture the Numeric Command and interpret it as a new Pre-Torque value. This signal should be set to a zero by the host before it sends a new Pre­torque value or when the host receives confirmation that the drive is in the run mode.
Byte 4: {N259_C002} This byte contains additional logic commands from the host to the DSD 412.
[Drive function #104 must be set to a 1 for this control to be active.] B0: 0= No gain reduction 1= Velocity loop gain reduction is ON
B1-B7 are spares Bytes 5&6: {N259_C000} These two bytes represent a signed 16 bit numeric value. The
definition of this value is determined by the status of Byte 3, Bit 7. If bit 7 is a 1, the value will be interpreted as a pre-torque signal. If byte 3, bit 7 is a 0, the value will be interpreted as a velocity reference. The limits for this value are: 7FFFh = +1 per-unit, 0000h = zero, 8000h = -1.0 per-unit.
Byte 7: The data in this byte is passed to the PCDU routines and is interpreted as a new PCDU
keystroke. If no 'key' is being pressed (a great majority of the time) the value of this byte will be 00h. It is the responsibility of the host to insure that this byte contains the new non-zero keystroke data for only one 15 MS transmission period. If this is not done, the DSD 412 will act as if a given key is being 'held down' instead of being pressed and released. The host must pace the placement of non-zero data in this byte no more frequently than one character every 250 MS. This is done to give the PCDU routines enough time to transmit the proper response display (possibly up to 32 ASCII characters) before the next keystroke is read.
Sync Byte 05h
Logic command Byte 1
Logic comman d Byte 2
Numeric command (high byte)
Numeric command (low byte)
PCDU keystroke
Checksum
53
Page 56
Drive Setup & Adjustments
Byte 8: This byte contains the calculated checksum of the data within this packet. It is the modulo-
256 sum of bytes 1 through byte 7 inclusive.
Demand Velocity Response message from the DSD 412 is as follows:
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 Byte 11
Sync Byte FAh
Sync Byte 05h
Control Status 1
Control Status 2
Control Status 3
Bytes 1&2: These bytes will always be set to FAh and 05h respectively. They are used for
synchronizing the host to the start of an incoming Demand Velocity Response message from the DSD
412.
Byte 3: {N259_C010} This byte contains 8 logic status signals as defined below:
B0: =1 to act as a synchronization bit for the host B1: =1 to act as a synchronization bit for the host B2: 0=Tach direction is not UP 1=Tach direction is UP B3: 0=Tach direction is not DOWN 1=Tach direction is DOWN B4: 0=No tach overspeed fault 1=Tach overspeed fault F97 B5: 0=No tach loss fault 1=Tach loss fault F98 B6: 0=No reverse tach fault 1=Reverse tach fault F99 B7: 0=No Serial Communications Fault 1=Serial Communications Fault
Byte 4: {N259_C011} This byte contains 8 logic signals to indicate drive faults.
B0: 0=No Motor over-load 1=Motor over-load fault F400 B1: 0=No excessive field current 1=Excessive field current F401 B2: 0=No contactor failure 1=Contactor failure F402 B3: 0=Drive is not at CEMF limit 1=Drive is at CEMF limit F407 or F408 B4: 0=E-STOP circuit is closed 1=E-STOP circuit is open B5: 0=No E-STOP fault 1=E-STOP fault F405 B6: 1=No drive fault exists, READY 0=A drive fault exists, NOT READY B7: 1=Drive NOT READY 0=Drive is READY
Byte 5: {N259_C012} This byte contains 8 logic signals to indicate additional faults:
B0: 0=No Loop fault exists 1=Loop fault exists F900 B1: 0=No PCU IST fault 1=PCU IST fault F901 B2: 0=No line synchronization failure 1=Line synchronization failure F903 B3: 0=No low line fault 1=Low line fault F904 B4: 0=No field loss fault 1=Field loss fault F905 B5: 0=No Line Droop 1=Line Droop below 90% of nominal F406 B6: 0=Speed Regulator not Released 1=Speed Regulator is Released B7: Spare
Bytes 6&7: These two bytes contain an echo of the most recent Numeric Command target value from the host. The format of the value is identical to that previously defined in the Demand Velocity
message.
Bytes 8-10: These 3 bytes contain ASCII display data normally intended for a serial terminal device
connected to the host. The host should simply pass all non-zero data (displayable ASCII characters) that it receives in these two slots to the device that is emulating the PCDU. The host may ignore bytes in these fields if they are set to 00h meaning that the DSD 412 has no data to display at this time. A full PCDU display is 2 rows of 16 characters. Therefore, an update of an entire screen would require several packets.
Byte 11: This byte contains the calculated checksum of the data within this packet. It is the
modulo-256 sum of bytes 1 through byte 10 inclusive.
Numeric Data high byte
Numeric Data low byte
PCDU display 1
PCDU display 2
PCDU display 3
Check­sum
54
Page 57
Using Anti-Rollback (ARB)
Elevator rollback occurs when an elevator motor drive is started and the brake is released but the hoist motor has not yet developed enough torque to prevent gravity from moving the car. The car may move up or down depending on the overall balance of equipment and payload. Velocity regulators normally used for speed regulation will eventually detect unwanted movement and react to halt the car. But there will be a position error accumulated during that process that can represent many inches of unwanted car movement relative to the landing. This effect is most noticeable with low friction gear-less elevators. It may be totally masked by the friction of an elevator driven through worm gears. Rollback by itself does not pose any hazards, but it does give an uneasy, out of control feeling to passengers. In many installations brake release timing is adjusted so that the brake is released just as the car begins to accelerate toward the next landing to mask the rollback effect. This often results in jerky starts as the brake linings release. The correct countermeasure is to weigh the car just as the doors close to determine the degree of gravity unbalance, then pre-torque the motor so that when the brake is released all forces are balanced. This method is very effective, but does require expensive calibrated load weighing equipment. The purpose of the Magnetek Anti-rollback feature is to help prevent rollback on elevators that do not use load weighing or do not use the motor pre-torque capability provided by the Magnetek drive. It uses a double integrator (type 2) regulator when operating at zero speed to hold the elevator car at an average speed of zero and to regulate a constant position as the brake is released. When the velocity reference leaves zero speed to accelerate the car toward the next landing, the active velocity regulator is switched to be E­Reg to precisely track (follow) the velocity reference profile. Be aware that this anti­rollback feature works from encoder/tachometer signals. So there must and will be some movement in order for the feature to function, but the position error generated by elevator movement will recover. The bandwidth gain of the system will determine how much movement will occur. Several new operating options and adjustments are provided. Refer to the individual descriptions for Drive Functions #130 - #132 and #63.
Drive Setup & Adjustments
Set-Up And Tuning Of Anti-Rollback (ARB)
1. The ARB function uses adjustment settings #41 (Per Unit Inertia), and #42 (speed regulator Stability). These settings and others are critical for good performance of the E-Reg velocity regulator. The first step for good ARB performance is to disable ARB by setting #130 to 0 (zero) and to tune all other E­Reg adjustments for a smooth ride and good floor-to-floor elevator performance. Be sure that the car weight and counterweights have been adjusted to be at the final values. Follow the suggested procedures for tuning E-Reg as listed in this Tech Manual. Ignore elevator rollback while adjusting primary elevator performance features. If rope resonance exists, also adjust the notch filter for minimum interference. Then tune up ARB last as necessary to prevent elevator rollback with an unbalanced payload.
2. After all other adjustments are satisfactory, set #130 to a 1 to enable ARB when starting an elevator run. Set up the following initial ARB adjustment values. Be sure to read ADJUSTMENT HINTS and CAUTIONS listed below. a) Set #131, ARB Bandwidth, to 1.5 to 2
times the setting in #40.
b) Set the initial value of #132, ARB
damping, to 0.5.
c) If the drive will be using an internally
generated velocity reference or serial
link commands (#110 set to 2 or 3) set
#133, ARB Speed Threshold to 10.0%.
If the drive will be using an external
analog velocity reference (#110 set to
1), set #133 to a minimum of 1.0%.
3. With the car empty at a convenient landing, prepare to start the elevator drive, call for zero velocity from the car controller via the normal way, release the elevator brake, and observe any car motion. When the car comes to a stop, the observation is complete, set the brake and stop the drive, again through normal control channels. Do so and observe that... a) The contactor picks, and the drive
starts.
b) There may be some initial upward
motion, but the car should return to its original position within a second or so.
c) When motion is halted, there will be
motor armature current producing torque holding the car. This can be
55
Page 58
Drive Setup & Adjustments
observed at #611 on the local display or a separate DC clamp-on ammeter, if available.
d) Set the brake and turn the drive OFF
via normal commands. (In that order, to prevent the car from drifting away!)
4. Repeat #3 several times and.....
a) Increase the setting of #131 (ARB
Bandwidth) to reduce the amount of initial movement as desired. But there may be more jerkiness. Reducing the setting of #131 will allow more movement, but with less jerk. Adjust #131 for a good compromise.
b) Reduce the setting of #132 (ARB
Damping) to speed up the position recovery, or increase the setting for a softer recovery, as desired.
c) If oscillations occur, release the brake
and shut down the drive or reduce the setting of #131 to stop them. This may be a practical limit for position tightness in this particular hoistway. See the hints below for using the notch filter.
5. Change the reference velocity to run the car at normal speeds. Make several empty single or multiple floor runs up and down to observe the complete starting action. The adjustments made so far should not alter landing position accuracy. Ride the car to observe the quality of adjustment.
6. If weights are available, load the car to payload capacity. Repeat the observations and adjustments of #4 with a full load. In this case the initial movement should be downward. Then repeat floor runs as in #5 with a full load. Ride the car to verify smoothness.
Adjustment procedure is complete.
ARB Adjustment Hints And Cautions
1. Caution, the ARB function can increase regulator bandwidth far beyond that required for controlling the speed of the elevator. It does so at only near zero speed, but when the ARB gain bandwidth is boosted it is possible that one or more mechanical resonant frequencies may become excited to produce unacceptable vibration. If an annoying vibration does occur, try to determine the resonant frequency. Then use the notch filter to tune it out if possible. Be aware that the notch filter does cause additional phase
shift lag. This can and will interfere with the operation of E-Reg and ARB. Tune the notch filter to the resonant frequency and adjust notch depth to the smallest value that suppresses the vibration. Then turn ARB off and verify or re-tune E-Reg to yield acceptable performance. Then re­tune ARB settings to control rollback. Some hoist ways may not be compatible with high gain ARB settings.
2. The adjustment settings for Speed Bandwidth, Per-Unit Inertia, and Stability #40, 41, & 42 are used by both the velocity regulator (E-Reg) and the velocity control portion of ARB, therefore adjustment of #40, #41, & #42 will alter the performance of anti-rollback controls. A high setting for Stiffness #42 will help the velocity control respond to changes in load but will cause longer settling times for both velocity and ARB position regulation. Be sure to tune the velocity controls of the elevator BEFORE adjusting controls for ARB Bandwidth and Damping, #131 & #132. Changing any ARB settings, #130 - #133, will not interfere with other velocity control tuning.
3. Elevator rollback is a function of gravity load unbalance of the car. This is what causes the car to move when the brake is released, even though the reference velocity may still be at zero. However, there is a finite time required for ARB to measure unwanted car motion via the encoder, produce a counteracting motor torque, and then return the car to the original position. The reaction time is controlled by #131, ARB Bandwidth. The smoothness and time to settle is controlled by #132, ARB Damping. The need for ARB starts only when the elevator brake is actually released, not when it is told to release. (A subtle difference in electromechanical timing.) But the allotted time for ARB to function will cease as soon as the velocity reference (internal or external) moves away from zero speed and crosses the threshold identified by #133. a) Ideally, there would be adequate dwell
time after release of the brake for ARB settling to occur. But elevator floor-to­floor time specifications do not necessarily allow for any time delay. If the resulting ARB time is cut short by release of the velocity reference
56
Page 59
before position settling is complete, the car will begin to accelerate toward the next landing from wherever it may be in the ARB cycle. The position regulator to speed regulator change­over will be smooth, but the repeatability of velocity profile tracking during acceleration may be altered by the amount of load unbalance and the value of the threshold set in #133. Keep this setting as low as possible for best results.
b) If #133 is set too low ARB may be
terminated too early, particularly when using an external analog reference. This will result in elevator rollback that could have been prevented.
c) If acceleration of the velocity profile is
started and crosses the threshold set by #133 before the elevator brake actually releases, ARB will not function and may result in elevator roll-back as acceleration begins. This, and the jerk or vibration sometimes felt by passengers as the motor pulls through the brake to start the car, is a result of poor velocity reference release Vs brake release timing. With ARB the velocity reference should not be released to move away from zero until after the brake is mechanically released. Otherwise the ARB feature cannot work.
4. Anti-Rollback can be used with external load weighing and pre-torque, as these features are independent of each other. If motor pre-torque values are not precisely correct at the time of starting the elevator drive, as may occur during elevator re­leveling, the features of ARB will intervene to help reduce rollback. If pre-torque is accomplished correctly, Anti-rollback will not need to do anything. However, it can still cause vibration or oscillation if ARB gains are set too high.
5. It is not always convenient to use payload weights during adjustment. Most elevators are counterweighted such that an empty car represents an unbalanced load of 43­57%, with the counterweight being heavier. If Anti-rollback works effectively with an empty car at all landing stops, it should also perform adequately with full payload weight in the car. Step 6 in the adjustment procedure indicates how to verify and
Drive Setup & Adjustments
adjust ARB operation with a full car payload, but it is not always necessary.
6. Anti-rollback may also be used to hold the car at a constant position at the end of an elevator run. Normally this is not required because the velocity regulator, E-Reg, will stabilize and hold an armature current value as necessary to hold the car at a standstill at the end of an elevator run. However, turning ARB back on may be useful to aid car re-level positioning without first setting the brake for a total drive re-start. Set #130 to a 2 to re­enable ARB when the car returns to zero speed at the end of an elevator run. Zero speed in this case is measured by the encoder, not the reference, and defined by #63. ARB will remain enabled until the drive is either shut down by removal of Run or Run-Up/Run-Down or Drive & field Enable logic signals, or the internal velocity reference is increased to again be larger than the threshold set by #133. If #63 is set too high, there may be a jerk felt as the car comes to rest and the control switches to the ARB zero speed / position hold mode. If #63 is set too low, minor disturbances and movement may delay and possibly prevent control transfer to the ARB hold mode because the measured encoder speed over a relatively short measuring time appears to not fall below the threshold value. Set #63 to the lowest value that yields repeatable results.
Using Drive Stand-By Power Reduction (DSPR)
Elevators often sit idle for many hours during a 24-hour day. Even though the DSD 412 drive can be set up to reduce motor field current to a stand-by level, a significant amount of power is continually lost by having the 3-phase main power transformer energized and cooling fans running. Now it is possible to set a timer so that when the elevator has not been used for a length of time, an external contactor can disconnect the main transformer and turn cooling fans off. When car controller logic recognizes that a new elevator call has been placed and asserts the Drive and Field Enable contact at TB1-9, the drive will re-enable the 3­phase primary power, resynchronize to the power line and restart cooling fans. While 3­phase power is OFF motor field current will be zero amperes, regardless of the setting of Standby Amps set at #53.
57
Page 60
Drive Setup & Adjustments
The DSPR feature is programmable by selection of output option P on relay K4. See table 4.2.3. The time delay before power is turned OFF is adjusted at #88, DSPR Delay. This timer is held in reset whenever the drive is enabled, and timing for a delayed shutdown whenever the drive is at rest and the Enable control line is inactive. If the DSPR delay time value at #88 is set to zero (0), the timing function is defeated and power will remain continuously ON. A pilot relay must be added to panel wiring to operate a primary power contactor. 115 VAC control power to the drive must remain ON for this feature to be operative. Refer to installation diagrams supplied in Section 2 at Figure(s) 2.1 for all suggested electrical connections. Normal operation of DSPR when power is first applied or when a Dive Fault Reset is performed is that Relay K4 will be de-energized, or will become de-energized, turning main power OFF. It will
then energize/re-energize to turn 3-phase power ON. Setting DSPR delay at #88 to zero will not change that part of the operation.
If DSPR is not wanted, or other external logic prevents the 3-phase power from actually turning OFF, the drive will not care and continue to respond normally, except that motor field current will go to zero during a DSPR time-out. However, external relay logic must not turn 3-phase power OFF unexpectedly, or the drive will declare an F406, F903 or F904.
NOTE: PCU software in EPROM sockets U13
& U14 must be labeled SA0404 (displayed by function #690), AND the software in sockets U39 & U40 (displayed by function #697) must be labeled SA0407 for the DSPR feature to be available.
58
Page 61
Drive Setup & Adjustments
Adjustment Function Descriptions
Fnct # Description Units Range Default Extended Description
Sets the positive and negative current limit for the
1 Current Limit % 0 - 300 250
Use Self-
2
Tune
Rated Arm
3
Current
Armature
4
Ohms
Armature
6
Inductance
Rated
7
Armature Voltage
I Reg
8
Crossover
Nominal AC
9
Voltage
10 Encoder PPR PPR 600 – 19,999 1024
Logic 0(Off) – 1(On) 0 (Off)
ADC 2.0 – 1250.0 50.0
Ohms 0.001 – 5.000 0.100
Henry 0.0010 – 1.0000 0.0100
VDC 150 – 550 240
RAD 100 – 1000 500
VAC 150 – 525 230
drive. Set as a percent of Rated Armature Amps (Function # 3).
Selects the source of critical numeric value adjustments for tuning the motor armature current regulator. Values for motor resistance, R, motor inductance, L, and motor field time constant L/R may come from either manually entered values or automatically determined by a self-tune measurement. With Function # 2 set to 0, OFF, the settings of Functions #4, #6, and #51 will be used. With Function # 2 set to 1, ON, the values determined by self-tuning and held at display locations 613, 614, and 615 will be automatically used. Note: Setting this function to a 1 will
the values stored in Function # 4, #6, or #51.
The motor nameplate or “Rated Run Current” amps, for the motor used with the drive, specify this entry.
Total armature circuit resistance. The value to be entered is best measured by monitoring MEASURED_R, F613 after the SELF-TUNE function has been completed. This value is used to calculate armature current regulator gains and to calculate motor CEMF.
Value of the motor circuit inductance. If a ripple filter is being used, the value entered should include effects of the ripple filter. The value to be entered is best measured by monitoring F614 ­Measured Motor Circuit Inductance, after the SELF­TUNE function has been completed. This value is used to calculate armature current regulator gains.
Sets the motor nameplate full load, full speed voltage required by the motor used with the drive. It should agree with the motor nameplate VFL
Sets the bandwidth of the current regulator in radians. The nominal setting for this entry for most cases would be 250 radians. The responsiveness of the armature current regulator will increase as this number increases. If this number is too large, the motor current may fluctuate. If this number is too small, the motor response may become sluggish.
Sets the nominal AC line-to-line voltage applied to the drive from the secondary of the isolation transformer. This value should agree with the transformer nameplate value as adjusted by any +/­primary taps, within ±5 volts. This value sets the Low Line and Excessive CEMF detection thresholds.
Sets the per channel pulses per revolution per the encoder nameplate.
not change
59
Page 62
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Sets the motor speed at rated elevator contract speed. The motor RPM X Encoder PPR X Encoder/Motor Ratio is what will actually be speed
11 Motor RPM RPM 50.0 – 1999.0 1150
12 Overspeed % % 0.0 – 150.0 110.0
14 Volt Sense % % 0.0 – 100.0 25.0
Tach Sense
15
16
17
%
Encoder / Motor Ratio
Rated Car Speed
% 0.0 – 100.0 5.0
- 1.000 – 19.000 1.000
- 1.0 – 1,900.0 400.0
regulated. May be used to compensate for minor sheave diameter variations. Adjust this setting to obtain the correct linear speed at 1.0 per unit velocity reference.
Sets the positive and negative overspeed trip point of the motor used on the drive. If the motor speed exceeds this value, the drive will fault. This value is entered as a percent of rated motor speed (RPM).
Sets the minimum armature voltage where the tach loss and reverse tach functions will become operative. This parameter prevents nuisance tach faults at low speeds and high torque loads. For example, if the rated motor armature voltage is 500 Vdc and this input is set at 10%, the tach loss function will become operative only when the armature voltage is above 50 Vdc. This numeric input adjusts the tach loss sensing function ability to ignore motor IR drop.
Sets the percentage of tach feedback below which a tach loss will be declared. But this alone will not result in a tach loss fault being declared. Thus, a tach loss will be declared when the per unit armature voltage is above the level that is the sum of Function # 14 VOLT SENSE %, and Function # 15, TACH SENSE % and the per unit tach feedback is less than the value entered for TACH SENSE %. For example, for default values of 25%, for Function # 14 and 5%, for Function #15, a Tach Loss will be declared when motor voltage is above 30% (25+5) and the encoder speed feedback indicates less than 5% speed.
This is the ratio of encoder RPM to motor RPM. If friction wheel drive is utilized for the encoder, the motor sheave diameter divided by the tach wheel diameter should be entered here. This value will multiply the encoder pulses per revolution to obtain proper motor rpm speed feedback information and regulation. If the encoder is direct coupled to the motor shaft, this function must be set to a value of
1.0.
Sets the calibration factor for internal pre-set speeds and car speed display via Function# 600. The units may be ft/min, m/sec, or cm/sec as determined by the user. However the units used for this parameter must also be used to set all other pre-set speeds. When the motor is turning at rated speed in RPM as programmed in Function #11, then Function #600 will display the number in programmed 17.
60
Page 63
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Maximum acceleration rate for the elevator when an external analog or serial link speed reference is used. This function provides a slew rate limit in the
External
21
Acceleration Limit
Error List
22
Reset
Full Field
32
Detect
Armature
38
Voltage Bandwidth
High Speed
39
Bandwidth
Low Speed
40
Bandwidth
Per-Unit
41
Inertia
- 2.00 –10.00 4.20
Logic 0(Off) – 1(On) 0 (Off)
% 30 – 90 80
RAD 1.0 – 4.0 2.0
RAD 1.0 – 15.0 6.0
RAD 1.0 – 15.0 6.0
Sec 0.10 – 9.99 2.00
event of noise or other discontinuity on the externally supplied reference signal.
must be set higher than that of the incoming speed dictation ramp, or the elevator speed will not track the desired reference velocity.
*** The units will be distance/sec2, where distance uses the same units as Function #17.
This entry resets the F800 error list, removing all faults on the list. This may be used to clear out old data to begin capturing a fresh record.
Sets the threshold for sensing a motor-field-at-full­amps condition. The motor field must be above (Function #50) X (Function #32) for internal logic to recognize that the motor field current is nearly up to the full field value. Motor field current must be above this value before the drive will be allowed to start. If told to start prematurely, the drive will wait for motor field to rise above this value before picking the loop contactor.
Sets the bandwidth when operating in the Armature Voltage Feedback Mode. This parameter is engaged when Function #112 = 0.
Sets the closed loop bandwidth response of the velocity regulator at speeds above the set point identified in #105. The tracking delay between the speed dictation ramp and the actual motor speed during the linear portion of the acceleration or deceleration ramp will be 1/(Function #40) seconds. A setting lower than that of Function #40 is useful to suppress rope vibration effects at high speed. This simplified adjustment takes the place of the ‘Gain Reduce’ function supplied in earlier versions software.
Sets the closed loop bandwidth response of the velocity regulator at speeds below the set point identified in Function #105. The tracking delay between the speed dictation ramp and the actual motor speed during the linear portion of the acceleration or deceleration ramp will be 1/(Function #40) seconds.
Function #40 will make the drive more responsive, but may also cause unwanted amplification of mechanical vibration or rope resonance.
This value is the ratio of the effective inertia of the moving elevator system mass to the rated torque strength of the motor. The units, seconds, would be the time it would take to accelerate the elevator inertia to rated speed using rated motor amps. This value affects the feed-forward gain of the velocity regulator and affects how well it will follow a changing reference speed
This entry
Increasing the value of
61
Page 64
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
This setting affects the proportional gain and Phase Margin of the regulator. Increasing this setting will make the regulator more responsive to correct mechanical load speed variances, but can cause it
42 Stability - 0.2 – 9.9 1.0
Weak Field
49
Current
Rated/Full
50
Field Current
51 Field L/R Sec 0.10 – 10.00 0.54
Rated Field
52
VDC
Standby Field
53
Current
Field
54
Response
Field Source
55
Volts AC
U/D Bit
63
Pickup
ADC 0.20 – 40.00 40.00
ADC 0.20 – 40.00 1.90
VDC 50 – 525 240
% 10 – 100 25
RAD 1.0 – 10.0 5.0
VAC 0 – 525 0
% 0.01 – 100.00 0.10
to amplify unwanted mechanical disturbances. Reducing the setting value will provide smoother operation but at the expense of time-delayed reaction to velocity errors, particularly noticeable when re-leveling.
Motor field current the drive should provide at rated motor RPM. Set this value to produce rated motor CEMF (no load voltage) at rated top speed. NOTE: Motor field current will not exceed the setting of Function #50. Setting or leaving this value at default simply means that the field will not weaken at high speeds.
Motor field current amperes the drive should provide when starting and at low speed. It should agree with Rated / Full / or Forcing Motor Field Current per the motor nameplate.
Motor Field time constant, L/R. It is an important value to determine motor field current regulator gains. See Function #615 after performing the Self-Tune procedure.
Rated Field Voltage necessary to produce Full field amps Function #50. It is used to calculate motor field circuit resistance and determine motor field current regulator gains. Improper adjustment can affect stability
This percent of the full field current amperes that the drive should provide when the elevator system is at rest (i.e. no Run command or Field Enable command received).
Defines the desired motor field current regulator bandwidth in radians per second.
This is the single-phase AC voltage used to power the Field Rectifier module. The factory default value of zero will let the drive automatically select the same value as supplied for the nominal AC voltage as set by Function #9. This conforms to factory supplied wiring supplied at AC1 and AC2 on the field interface PCB. Set this only if an external transformer is used to supply a different voltage to power the motor field circuit, set this value to the nominal VAC provided at terminals AC1 and AC2.
Defines the zero speed threshold for detection of motion via encoder measurement. It controls the Moving-Up/Down, & Zero Speed detector output signals, and determines when ARB will be turned back ON if Function #130 is set to 2. Units are in percent of rated speed.
62
Page 65
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Sets the speed threshold where the At-Low-Speed indicator will turn ON and OFF. This can be used to indicate when the elevator is moving below the
Low Speed
64
Threshold
Over-Speed
80
Test
Over-Speed
81
Multiplier
Reference
82
Multiplier
Motor
83
Overload Timeout
Motor
84
Overload Level
85 I Decay Ramp Sec 0.01 – 2.50 0.20
Analog Speed
86
Reference Zero
% 0.1 – 100.0 2.0
Logic 0(Off) – 1(On) 0 (Off)
- 1.00 – 1.50 1.00
- -2.000 – 2.000 1.000
Sec 2.0 – 500.0 48.0
PU 0.50 – 2.00 1.15
PU -0.2000 – 0.2000 0.0000
door pre-opening speed. See programmable output function F or M at functions 183 through
187. The adjustment value is percent of rated maximum speed as set by Function #17. Hysteresis is 5% of the set value.
This is a logic input that is used to activate an over­speed multiplier value, (Function #81). When running the test increase F#12 to prevent the drive from faulting on Overspeed (Fault 97).
Value of speed reference multiplier that will be used to run an elevator over-speed test when Function #80 is ON. This Function #also multiplies Function #82.
Value is a multiplier for external analog or serial link velocity references. It may be used to adjust the actual calibration of the reference signals or to cause the elevator to run at a different speed from a +/-10 volt analog or other full-scale serial reference command. The elevator will run at Rated Speed (Function #11 and Function #17) from an analog reference of 10V, when Function #82 is set to 1.000, and Function #80 is 'OFF'.
This value shapes the motor overload time-out curve.
Sets the threshold level where the motor overload function will begin to operate. Sustained motor current above this value will eventually cause an overload trip according to the time set in #83.
Controls the rate of decay of motor armature current during normal elevator stops. This helps to prevent brake ‘thumping’ when the drive is shut down and the brake is required to hold the car. The drive Run logic command must remain active until the elevator comes to a stop and the mechanical brake is set. Armature current ramp-down will begin after the RUN command is removed from the drive. When the ramp-down is complete, the contactor will be told to open. NOTE: The Drive Enable command must remain ON and the elevator Safety-Chain must remain closed until after the contactor actually opens for this feature to work properly.
At zero speed if the motor is creeping it may be necessary to adjust this parameter to compensate. Adjust this parameter until motion is stopped at zero speed. After adjusting the low end of the profile it may also be necessary to adjust the reference at the top end of the profile. Refer to Function #82 to set the speed reference gain.
63
Page 66
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Multiplies the available pre-torque reference signal for calibration adjustment. If this is set to 1.0, a +/­10V analog signal or full-scale serial link signal will cause 1 per unit (rated) armature current pre-torque level.
Pre-Torque
87
Multiplier
DSPR Delay
88
Time
Brake Pick
89
Timer
Brake Drop
90
Timer
Must Stop
91
Timer
Brake Auto
92
Stop ON
Analog Out 0
93
Bias Analog Out 1
94
Bias
Analog
95
Output 0
- 0.25 – 2.00 1.00
Min 0 – 60
Sec 0.5 – 5.0 1.0
Sec 0.5 – 5.0 1.5
Sec 0.1 – 5.0 2.0
Logic 0(Off) – 1(On) 0 (Off)
PU -1.00 – 1.00 0.00
PU -1.00 – 1.00 0.00
Logic 0 – 8 1
disabled
Analog
 
Determines the power OFF delay time for DSPR. If
0
set to zero (0), DSPR will be disabled. Power will then remain ON at all times.
Adjusts the ON time for the Brake Pick relay to be energized each time elevator brake lift should be started. The internal velocity reference will remain at zero during the Brake Pick time. Set to the actual time to complete lifting of the brake to prevent pulling through the brake during an elevator start.
The time for the elevator brake to drop and set when de-energized by the Lift and Pick relays. Adjusts the time for the drive to keep holding the car at zero velocity while the brake drops.
Establishes a limit on how long the drive may continue to run after the Run command logic line is released. This is a back-up means to cause the drive to stop in case zero speed is not achieved for any reason. Used only when elevator brake control is engaged.
When ON, causes the controlled stop and Brake sequence to commence when the speed reference is set to zero...OR when the hardware Run logic input is de-energized. A brake function output must also be enabled.
Provides an offset adjustment for analog output channel 0.
Provides an offset adjustment for analog output channel 1.
Sets the specific analog output signal to be observed at TB1-45 and TP41. Selections are:
The voltage measured will be a function of the operating level of the parameter being displayed and the signal multiplier Function #97. Signal range is limited to and will saturate at ±10V.
 
Input
PreTorque
Voltage
 
Bias
10
(F#117)
 
0 = Trace Buffer 0 1 = Raw Speed Command 2 = Ramped Speed command 3 = Encoder Feedback 4 = Armature Current Reference 5 = Measured Armature Current 6 = Measured Armature Voltage 7 = Field current Reference 8 = Measured Field Current
 
 
PreTorque
(F#87)Mult
 
 
 
signal drive software uses
 
 
 
64
Page 67
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Sets the specific analog output signal to be observed at TB1-46 and TP44. Selections are:
0 = Calculated CEMF 1 = Raw Speed Command 2 = Ramped Speed command 3 = Encoder Feedback
Analog
96
Output 1
Analog Out 0
97
Multiplier
Analog Out 1
98
Multiplier
Speed Error
99
Trip Time
Speed Error
100
Trip Threshold
Auto Fault
101
Reset
3 Second
102
Loop Fault
Logic 0 – 8 3
PU 0.10 – 10.00 0.80
PU 0.10 – 10.0 0.80
Sec 0.20 – 5.00 5.00
% 0.0 – 100.0 100.0
Logic 0(Off) – 1(On) 0 (Off)
Logic 0(Off) – 1(On) 0 (Off)
The voltage measured will be a function of the operating level of the parameter being displayed and the signal multiplier Function #98. Signal range is limited to and will saturate at ±10V.
Sets the specific multiplier value for Analog Output #0. A value of 0.8 will set 8.0 volts of output for a 1 per unit signal, with some headroom to show over­scale.
Sets the specific multiplier value for Analog Output #1. A value of 0.8 will set 8.0 volts of output for a 1 per unit signal, with some headroom to show over­scale.
Sets the time sensitivity of the Speed Error Trip detection function. Speed errors larger than Function #100, for longer than Function #99 seconds will cause a Speed Error Trip and automatic drive shut down with Fault F410.
Sets the magnitude sensitivity of the Speed Error Trip detection function. Speed errors larger than Function #100, for longer than Function #99 seconds will cause a Speed Error Trip and automatic drive shut down with Fault F410.
Allows the Drive to automatically reset drive faults that caused a shutdown without an external Fault Reset command. When turned ON, the drive will attempt an automatic fault reset 5 seconds after the fault occurs. If successful, the drive may then be restarted. This feature is made inoperable by setting Function #101 to 0 (off).
Note: A Fault count total is accumulated. One fault
count is removed from the total every 20 minutes. An accumulation of 5 counted faults will cause fault 411 Maximum Resets Attempted and the need for a manual reset for continued operation.
Selects the detection time for loop contactor faults. These occur when the contactor acknowledge feedback contact fails to open or close according to the commanded state of the contactor coil driver. Small contactors should operate within 450 milliseconds and should use the default value, 0, or OFF. If large contactors are used with large hp drives, set this value to ON to yield a 3 second fault detection time.
4 = Armature Current Reference 5 = Measured Armature Current 6 = Measured Armature Voltage 7 = Field current Reference 8 = Measured Field Current
65
Page 68
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Selects the source of the gain switch control to be from local or serial link commands. If an analog
Serial Gain
104
Switch
Gain Switch
105
Speed
Tach Rate
107
Gain
Reference
110
Mode Select
Arched Travel
111
Disable (Jerk Abort)
Logic 0(Off) – 1(On) 1 (On)
PU 0.00 – 1.10 1.10
% 0.0 – 30.0 0.0
Logic 1 – 5 2
Logic 0(Off) – 1(On) 1 (On)
reference velocity or pre-set speed selects are used, set this value to 0, off. If a gain switch will be from the serial link, set this value to 1, ON. [Function #104 on and Function #110 set for analog or pre-set speeds results in no gain switching.]
This function is only used if Function #104 is off. The value determines the speed where velocity regulator gain is switched. If the speed reference is below the value of Function #105, the closed loop gain will correspond to that set by Function #40. If the speed reference value is above set point Function #105, then closed loop bandwidth will be as set in Function #39.
This value adjusts the gain of differential encoder/tach rate feedback. It can be useful to help attenuate vibration and rope resonance effects. Disable this function by setting the value to zero. If using this feature, keep the setting as low as possible consistent with good operation.
Allows the user to select the source of the velocity reference signal.
Setting this value to 1 enables the drive to follow
the magnitude and direction polarity of an external analog reference, and external ramp/slew limit rates Function #21.
Setting this value to 2 (default) enables the 1 of 7
internal pre-set speed selects via Function #151 through 157 (preset speeds) and Function #170 through 181 (accel/decel, jerk rates). See also Function #115 for direction control and Function #150 for speed selects.
Setting this value to 3 enables serial link control of
the velocity reference, and external ramp/slew limits rates of Function #21.
Setting this value to 4 enables a uni-polar analog
reference to be used with external direction logic commands. External ramp/slew limit rates of #21 will also be used.
Setting this value to 5 enables serial link control of
the velocity reference, and Functions #170,172,174,176 (accel/decel, jerk rates #1 only!).
Previously named Jerk Abort Enable. When ON, changing the speed reference to a value less than or equal the actual speed will cause the S-Curve reference generator to immediately stop acceleration, and begin to decel if appropriate. When OFF, changing the reference to a lower speed will cause a jerk-out (of any existing accel) and jerk-in to a decel sequence. If done while accelerating, Arched Travel will be the result.
66
Page 69
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Setting this value to 0, off, enables the Armature Voltage Feedback Mode to operate. This parameter must be set to 1 for normal operation of the drive. When in this mode the encoder feedback monitor Function #601 will still be active to allow for troubleshooting, however this signal will not affect speed regulation. This mode is intended for maintenance and troubleshooting only.
This parameter will control the speed, which the motor will reach when operating in the Armature Voltage Feedback Maintenance Mode. The theory is the motor will operate up to this level of VDC if given a 100% speed command. The speed can be increased or decreased by either raising (Increase Speed) or lowering (Decrease Speed) this number or reducing (Increase Speed) or increasing (Decrease Speed) Function #50 'Rated Field Current'.
Setting this value to 1, on, enables the pre-torque function to operate. The pre-torque value from the analog pre-torque input will be multiplied by Function #87 and used to pre-stress the velocity error integrator to that armature current per unit value upon starting. If Function #110 is set to 3 for serial link control, the pre-torque reference input will be from the serial link message. The adjusted pre­torque value used at the start of an elevator run may be viewed during the run via Function #603...If pre-torque is not used, leave this function set to 0, 'OFF'.
Selects how the drive will determine the RUN Direction when REF-MODE Function #110 is set for internal pre-set speeds. When this is set to 0 (OFF) 24V relay logic input A1TB1-8 will be a Hardware RUN command. A1TB1-50 will be the UP (Logic low or OFF), or Down (+24V or ON) command. When this is set to 1 (ON), 24 V relay logic input at A1TB1-8 will be a Run-Up command A1TB1-50 will be a Run-Down command. If REF-MODE Function #110 is set to 1 or 3 for following bi-directional external analog or serial link velocity commands, the polarity of that signal will always be followed. In that case, either A1TB1-8 or A1TB1-50 may be used as a Hardware Run command input (but not both).
When On, this control bit causes the decel ramp rate active at the start of decel to remain in effect until the decel sequence is completed. This function will momentarily override logic input commands at A1TB1-10 and A1TB1-51.
Used in conjunction with F#87, Pretorque Multiplier.
Analog Input Voltage
10
 
PreTorque
 
(F#117)
 
Bias
 
112
113
114
115
116
117
Encoder Feedback Enable
Armature Voltage @ Max Speed
Pre-Torque Enable
Run-Up/ Run­Down Select
Decel Rate Latch
PreTorque Bias
Logic 0(Off) – 1(On) 1 (On)
VDC 0.0 – 650.0 100.0
Logic 0(Off) – 1(On) 0 (Off)
Logic 0(Off) – 1(On) 0 (Off)
Logic 0(Off) – 1(On) 0 (Off)
PU 0.00 – 1.00 0.00
 
 
PreTorque
(F#87)Mult
 
 
 
signal drive software uses
 
 
 
67
Page 70
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Sets the time sensitivity of the Speed- Error-is-Low detector. This is a useful indicator to tell when/if the drive is following the velocity reference properly.
Speed Error
120
Detect
Speed Error
121
Threshold
130 ARB Mode - 0 – 2 0
ARB
131
Bandwidth
ARB
132
Damping
ARB Speed
133
Threshold
Sec 0.0 – 5.0 0.5
% 0.0 – 15.0 2.0
RAD 1.0 – 15.0 6.0
- 0.01 – 20.00 2.00
% 0.0 – 10.0 0.0
Exceeding the set limits of this detector does not shut the drive down. The detector results can be sent to a logic output. See also, Function #99, 100, 121 and the description of logic outputs 183 through 187.
See Function #120. This value sets the magnitude sensitivity of the Speed-Error-is-Low Detector. Units are a percent of rated speed Function #17.
Selects between 3 possible Anti-Rollback operating modes.
"0" to disable all Anti-Rollback features. Only E-
Reg will be engaged
"1" to enable Anti-Rollback when the drive is
started.
"2" to enable Anti-Rollback when starting the drive
and when the velocity again comes to a stop at the next landing.
Determines the gain of the velocity and position regulator when ARB is ON. This is the unity gain crossover frequency in Radians/sec. Increasing this setting will cause the position loop to respond faster with less accumulated position error.
Adjusts damping of the position regulator when ARB is ON. Increasing this setting will cause a smoother but slower recovery of position error. Reducing this setting will let ARB recover a position error more quickly and abruptly.
Determines the reference speed where ARB will be turned OFF and E-Reg will be engaged when the drive is started, if Function #130 is set to 1 or 2. This setting should be as low as possible to prevent regulator transfer bumps when starting, but it must be set high enough to remain engaged during re­leveling or to ignore a small analog zero reference offset when using an external analog signal reference. In percent of rated speed
68
Page 71
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Determines the method for selecting pre-set speeds from external relay logic applied to A1TB1­11, 12, 52, 53 and 54
Binary Speed Selects
S4 S3 S2 S1 S0 SPD # ADJ #nn X X 0 0 0 ZERO NONE X X 0 0 1 1 (151) X X 0 1 0 2 (152) X X 0 1 1 3 (153) X X 1 0 0 4 (154) X X 1 0 1 5 (155) X X 1 1 0 6 (156) X X 1 1 1 7 (157)
Binary / Progressive
150
Pre-Set Speed Select
Logic
0 (Progressive)
– 1 (Binary)
1
Table 8: Binary Preset Speed Selects
Progressive Speed Selects
S4 S3 S2 S1 S0 SPD # ADJ #nn 0 0 0 0 0 ZERO NONE 0 0 0 0 1 1 (151) 0 0 0 1 0 2 (152) 0 0 1 1 0 3 (153) 0 1 1 1 0 4 (154) 1 1 1 1 0 5 (155)
Table 9: Progressive Preset Speed Select
Note 1: When Progressive Speed Select mode is used, any combination of S0-S4 not shown in Table will result in zero speed being selected. Note 2. When Reference Mode Select #110) is set for Analog or Serial velocity reference control, inputs S0-S4 have no affect.
See figure 12 on page 30.
(Function
69
Page 72
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
These function values specify the elevator car speed for each individual pre-set speed setting. The units must agree with that set for Rated Car Speed in Function #17. [If feet per minute is used at Function #17, then the units for Function #151through 157 shall also be feet per minute.] No value for Function #151through 157 should be larger than that for Function #17. All values are positive numbers. The selected reference speed and direction will be determined by the setting of Function #110, 115, 150, and 24V relay logic inputs. It is certainly possible to connect the selection of one or more pre-set speed logic input control lines to also activate a different Ramp Rate #2 or #3. See also the Decel Rate Latch, Function #116. With careful thinking, one can obtain many specific combinations of pre-set speeds and Ramp Rates with a minimum of relay contacts.
Note 3: Switch select inputs S0-S4 are 24V logic input signals available on A1TB1 with the following assignments:
S0 = A1TB1-11 S1 = A1TB1-53 S2 = A1TB1-12 S3 =A1 TB1-54
S4 = A1TB1-52 Note 4: For S0 – S4... +18 - 24VDC (ON) = 1 <5VDC (OFF) = 0 Note 5: Connecting A1TB1-10 to A1TB1-11 will automatically select Ramp #3 with selection of pre­set speed #1.
Total acceleration time in seconds for S-curve ramp #1 to occur from zero speed to rated elevator speed. Effective only when internal pre-set speeds are used.
Total acceleration time in seconds for S-curve ramp #2 to occur from zero speed to rated elevator speed. Effective only when internal pre-set speeds are used.
Total deceleration time in seconds for S-curve ramp #1 to occur from rated speed to zero speed. Effective only when internal pre-set speeds are used.
Total deceleration time in seconds for S-curve ramp #2 to occur from rated speed to zero speed. Effective only when internal pre-set speeds are used.
The percent of time that will be spent in the controlled jerk or S-portion of the timed ramp curve during ramped acceleration #1. A percent S of
0.1% corresponds to almost all-linear acceleration. A percent S of 100% will make the S-curve #1 smooth with no linear acceleration portion. Effective only when internal pre-set speeds are used.
151 –
157
170
171
172
173
174
Pre-Set Speeds 1 through 7
Acceleration #1 Time
Acceleration #2 Time
Deceleration #1 Time
Deceleration #2 Time
Acceleration #1 %S
- 0.0 – 1900.0 0.0
Sec 1.00 – 15.00 5.00
Sec 1.00 – 15.00 5.00
Sec 1.00 – 15.00 5.00
Sec 1.00 – 15.00 5.00
% 0.1 – 100.0 25.0
70
Page 73
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
The percent of time that will be spent in the controlled jerk or S-portion of the timed ramp curve during ramped acceleration #2. A percent S of
175
176
177
178
179
180
181
Acceleration #2 %S
Deceleration #1 %S
Deceleration #2 %S
Acceleration #3 Time
Deceleration #3 Time
Acceleration #3 %S
Deceleration #3 %S
% 0.1 – 100.0 25.0
% 0.1 – 100.0 25.0
% 0.1 – 100.0 25.0
Sec 1.00 – 15.00 5.00
Sec 1.00 – 15.00 5.00
% 0.1 – 100.0 25.0
% 0.1 – 100.0 25.0
0.1% corresponds to almost all-linear acceleration. A percent S of 100% will make the S-curve #1 smooth with no linear acceleration portion. Effective only when internal pre-set speeds are used.
The percent of time that will be spent in the controlled jerk or S-portion of the timed ramp curve during ramped deceleration #1. A percent S of
0.1% corresponds to almost all-linear deceleration. A percent S of 100% will make the S-curve #1 smooth but with no linear deceleration portion. Effective only when internal pre-set speeds are used.
The percent of time that will be spent in the controlled jerk or S-portion of the timed ramp curve during ramped deceleration #2. A percent S of
0.1% corresponds to almost all-linear deceleration. A percent S of 100% will make the S-curve #2 smooth with no linear deceleration portion. Effective only when internal pre-set speeds are used.
Total acceleration time in seconds for S-curve ramp #3 to occur from zero speed to rated elevator speed. Effective only when logic input A1TB1-10 is active. Selecting this ramp rate will override Rates 1 or 2.
Total deceleration time in seconds for S-curve ramp #3 from rated speed to zero speed. Effective only when logic input A1TB1-10 is active. Selecting this ramp rate will override Rates 1 or 2.
The percent of time that will be spent in the controlled jerk or S-portion of the timed ramp curve during ramped acceleration #3. A percent S of
0.1% corresponds to almost all-linear acceleration. A percent S of 100% will make the S-curve #3 smooth with no linear acceleration portion.
The percent of time that will be spent in the controlled jerk or S-portion of the timed ramp curve during ramped deceleration #3. A percent S of
0.1% corresponds to almost all-linear deceleration. A percent S of 100% will make the S-curve #1 smooth with no linear deceleration portion.
71
Page 74
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Alarms are classified as non-critical faults detected by the DSD 412 that pose no immediate need to stop operation. The Alarm output relay K2 (on the Drive Control PCB, A1) is reserved for non-critical fault indications. It has a normally open contact wired to A1TB1-38 and 39). With Function #182 set to 0 (OFF), the default, relay K2 will pick-up, closing the contact on the occurrence of a non­critical fault. With Function #182 set to a 1 (ON), the relay will be picked-up during normal operating conditions and drop out on the occurrence of a non­critical fault or Alarm. Alarms are presently identified as drive over­temperature or thermistor failure, motor or transformer thermostat over-temperature, and motor overload trip. Other conditions may be selectable to be alarms or critical faults.
182
Invert Alarm Relay
Logic 0(Off) – 1(On) 0 (Off)
Output Circuit A1TB1 CONNECTION SELECTED FUNCTION Output K3, Controlled by Function #183 N.O. Relay Output K4, Controlled by Function #184 Open Collector Type Output K5, Controlled by Function #185 Open Collector Type Output K6, Controlled by Function #186 Open Collector Type Output K7, Controlled by Function #187 Open Collector Type
183-
Logic Output
187
Selects
Logic
FUNCTION SELECT SETTING 1 (DEFAULT) 2 3 4
A1TB1-36&37
A1TB1-78
A1TB1-79
A1TB1-83
A1TB1-84
A
B
C
D
E
F
A
G
J
F
Table 10: Programmable Output Selections
The function of relay and open-collector logic output channels, K3-K7 on the Drive Control PCB, are programmable. Each output has several choices of functions. The descriptions below identify how
See Table 10:
Programmable
Output
Selections
each option works. Table 10: Programmable Output Selections identifies how to map a particular
1
function to a particular output channel. [For example to program output K6, A1TB1-83 to indicate when the drive is at zero speed, option “J”, set Function #186 to be “2”.] The factory default values (1) will program K3-K7 to the same function as older software SA274.
C
G
H
K
I
N
P
I
L
M
72
Page 75
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Setting Desc. Extended Description
Relay K3 is picked during normal operating conditions with N.O. contact closed. Relay K3 drops and contact opens if measured motor field current ever exceeds
Excessive Field
A
Current
High CEMF or Low
B
Line
C Run Engaged
D Moving Up
E Moving Down
F Low Speed
G Field is UP
H Speed Error is Low
I Speed Error is High
J Zero Speed
K Moving
L Lift Brake
M High Speed
N Brake Pick
P DSPR Control
125% of Rated Field current, Function #50. When programmed to control output K4, the output will be active during normal operation, and become inactive if motor field current ever exceeds 125% of Rated Field current, function #50. This function can be used as a warning of a malfunction condition that could cause damage to the motor field.
Active if motor CEMF becomes greater than 1.09 X drive VAC input, or if VAC input falls below 0.9 X Rated VAC, Function #9. This is a warning indication that there may be problems associated with too much CEMF or a drooping power line.
Active when the drive speed regulator is in operation. Inactive during armature current ramp-down or if the contactor is open. May be used as an indication that the drive is in control and that the elevator brake may be released.
Output becomes active when encoder velocity is greater than the setting of function 63 in the UP direction. May be used to verify proper car direction.
Active when encoder velocity is greater than the setting of Function #63 in the DOWN direction. May be used to verify proper car direction.
Output becomes active when encoder speed is less than the setting of Function #64. May be used to indicate low speed for door pre-opening logic.
Active when motor field current has risen above the threshold value programmed in Function #32, or drive is in operation. May be used to indicate when the drive Start command will function without delay.
Active when Speed Error is less than Function #121 for longer than Function #120 seconds. May be used to indicate that the drive is correctly following the programmed velocity profile.
Active when Speed Error is greater than Function #121 for longer than Function #120 in seconds. May be used to indicate that the drive is not following the programmed velocity profile. This is the opposite logical state of H.
Active when encoder speed is below the setting of Function #63 in either direction. May be used to indicate that deceleration is complete and the brake may be set without any bumps.
Output becomes active when encoder speed is greater than the setting of Function #63 in either direction. This is the opposite logical state of J.
Output K6 becomes active when elevator brake should be lifted. Will de­energize when the brake should be dropped.
Output becomes active when encoder speed is greater than the setting of Function #64 in either direction. This is the opposite logical state of F. May be used to prevent or enable door pre-opening logic.
Output K3 becomes active for time Function #89 each time a Brake Lift sequence is started. Will be de-energized when the brake should be dropped.
Output K4 is active to pull in an external power control relay when the drive is supposed to be powered up for operation. Output becomes inactive after a DSPR time delay time-out. See Function #88.
73
Page 76
Drive Setup & Adjustments
Fnct # Description Units Range Default Extended Description
Controls the depth of the notch filter used for a rope
190 Notch Depth - 0 – 10 0
191 Notch Period - 0 – 10 7
F413 Detect
192
Level
PU 0.05 – 0.50 0.05
resonance counter-measure. When set to zero, the filter is not active. Increase the setting toward 10 as required to suppress system resonance.
Controls the center frequency of the rope resonance notch filter. This is not a continuous adjustment as the frequency is selected in steps as in Table 11: Notch Period Steps
ENTRY NUMBER NOTCH FREQ
0 100 Hz 1 50 2 33 3 25 4 20 5 17 6 14 7 12 8 11 9 10
10 9
Table 11: Notch Period Steps
Sets the level of difference of the field current reference and the feedback at which the drive will display the F413 warning. If all of the criteria is correct in the field circuit and in the parameter setup the F413 warning should not appear. The tracking error can be monitored on F620. If the error is out of tolerance due to low or sagging line voltage and the issue cannot be resolved increase this parameter to eliminate the warning. This level is in PU where #50 rated field amps = 1.0PU i.e.
0.05 would correlate with 5% difference between the feedback and the reference.
Table 12: Adjustment Function Descriptions
74
Page 77
J
J
CONTROLLED
ACCEL JERK OR ‘S’
PORTION
#174, #175, #180 =0.1%
LINEAR ACCEL REGION
LINEAR DECEL REGION
CONTROLLED ACCEL
ERK OR ‘S’
Figure 20: S-Curve Accel/Decel Cycle
CONTROLLED DECEL
ERK OR ‘S’
Drive Setup & Adjustments
CONTROLLED DECEL JERK OR ‘S’ PORTION
FULL SPEED
ZERO SPEED
Figure 21: S-Curve Accel with minimum %S
#174, #175, #180 = 100%
ACCEL TIME
FULL SPEED
Figure 22: S-Curve with 100% S
75
Page 78
Drive Setup & Adjustments
Display Monitor Functions
Fnct # Description Units Extended Description 600 Car Speed ­601 Motor Speed RPM 602
603 Pre-Torque Input %
609 CEMF VDC VDC 610 Motor Armature Voltage VDC
611 Motor Armature Current ADC 612 Motor Field Current ADC
613 614 615 616 Speed Error %
617 AC Line Frequency Hz 618 Heatsink Temp °C
619 AC Line Voltage V RMS
620 F413 Tracking Level PU
621
Dictated Speed Reference
Measured Motor Resistance Measured Motor Inductance Measured Field L/R Time Constant
Serial Communication Control Enabled
Ohms Henry
Sec
Logic
Measured velocity of the elevator. Units are as set in function 17.
Measured elevator motor RPM. Reference velocity after accel/decel rate control
-
conditioning. Units are as set in function 17. This display is the pre-torque reference as applied to starting the velocity regulator. The value is latched to display the pre-torque value used at the start of a run. Prior to a start, the displayed value is that of the analog or serial link input. This function works only when pre­torque enable control, functions 114 is turned ON. Units are a percent of Rated Motor Amps. This display is the CEMF of the motor calculated from measured motor voltage, current and armature circuit resistance functions 4. Measured voltage output to the motor armature circuit. Measured drive output to the motor armature circuit. Measured motor field current. Measured motor armature circuit resistance calculated during self-tune. Measured motor armature circuit inductance calculated during self-tune.
Motor field time-constant measured during self-tune.
This displays the difference between the speed reference and speed feedback. Measured frequency of the 3-phase AC line. Measured heat sink temperature of the drive in °C. This display is the measured 3-phase AC input line-line voltage. The difference between the Field Current reference and the Feedback. F413 warning will result if higher than F192 for 5 seconds. This logic will be ON if RS422 (or RS232) control communications is enabled for drive control. Does not include use of PCDU.
76
Page 79
688 Cube I.D. -
689 Field Range -
Drive Setup & Adjustments
Cube I.D. No.
1 002, 003 525 3 005, 007 525 6 010, 015 525 9 020, 025, 030 525 12 040, 050, 060 525 15 075, 100, 125 525 18 150 525 21 200 525 24 250 525 28 300 525 31 400 525 34 500 525 37 600 525 40 700 525 43 800 525 44 040, 050, 060 600 45 075, 100, 125 600 46 200 600 47 300 600 48 400 600 49 600 600 50 800 600
*** This number should agree with the DSD 412 drive data nameplate.
FIELD CURRENT RANGE (2 - 200HP) Indicates actual SW1 setting
#689 SW1 Read-Back
1 0.2 1.9 3 7.0 16.0 6 2.0 6.9
8 16.1 40.0 FIELD CURRENT RANGE (250 - 800HP) Indicates actual SW1 setting
#689 SW1
Read-Back
3 2.0 16.0
8 16.1 40.0
HP 53ST*** Max Input VAC
Table 13: Cube I.D. Number
Minimum Rated Field Amps DC
Minimum Rated Field Amps DC
Maximum Rated Field Amps DC
Maximum Rated Field Amps DC
690 U13/U14 “97SAXXX” ­691 PCU Release ­692 Day ­693 Month ­695 Year ­696 Beta “P” ­697 U39/U40 “97SAXXX” ­698 DCU – Revision ­699 Customer Version I.D. -
Table 14: Field Current Range
-
-
-
-
-
-
-
-
-
Table 15: Display Monitor Functions
77
Page 80
Drive Setup & Adjustments
Miscellaneous Functions
FNCT. # DESCRIPTION REFERENCE PAGES
22 CLEAR ERRORS LIST
000 VIEW FAULT LIST
800 VIEW ERROR LIST
801 FAULT/ERROR ACTIONS See Error Reporting on page 33.
980 TRACE MONITOR -
981 VERIFY I/O
993 CLEAR NVRAM
994 SAVE/RECALL FUNCTION
995 LOAD DEFAULTS
997 SELF TUNE
998 PCU DIAGNOSTICS
Table 16: Miscellaneous Functions
See Input – Output Signal
Verification on page 89.
See Non-Volatile Ram Access
See Non-Volatile Ram Access
See Self Tune Function on page
See Power Conversion
Diagnostics on page 39.
-
-
-
on page 36.
on page 36.
37.
78
Page 81
Drive Faults
Drive Faults
The following Faults are custom to the SA407 Generation 2 DSD 412 software.
Function Error Code Listing
*** DCU ERRORS ***
DISPLAY # - DESCRIPTION 13 = ILLEGAL INSTRUCTION 14 = LINE 1010 EMULATOR 15 = LINE 1111 EMULATOR 16 = PRIVELEGE VIOLATION 17 = DIVIDE BY ZERO 21 = WATCHDOG TIMEOUT 22 = RESERVED INTERRUPT 23 = UNINITIALIZED INTERRUPT 24 = TRACE EXCEPTION 26 = SPURIOUS EXCEPTION 97 = OVERSPEED TRIP 98 = TACH/ENCODER LOSS 99 = REVERSE TACH/ENCODER 100 = NOT A NUMBER 101= MATH OVERFLOW 102 = MATH UNDERFLOW 103 = FLOATING POINT DIVIDE BY ZERO 104 = SIGN ERROR IN SPEED REG 112 = BAD PCDU POINTER 113 = MISSING PCU 114 = LOCKED UP QUEUES 115 = MULTIPLEXER CONFIG. ERROR 117 = 20 SEC COMM. START FAULT 118 = 150 MSEC COMM. MSG FAULT 220 = DCU ROM BUS ERROR 221 = DCU RAM BUS ERROR 222 = DCU NVRAM BUS ERROR 223 = DCU DPRAM BUS ERROR 232 = UNKNOWN BUS ERROR 240 = DCU ROM BUS ERROR 241 = DCU RAM ADDRESS ERROR 242 = DCU NVRAM ADDRESS ERROR 243 = DCU DPRAM ADDRESS ERROR 252 = UNKNOWN ADDRESS ERROR
***DRIVE FAULTS/ERRORS***
DISPLAY # - DESCRIPTION 400 = MOTOR OVERLOAD 401 = EXCESSIVE FIELD CURRENT 402 = CONTACTOR FAULT
403 = 5-MIN FULL FIELD FAULT 404 = OPEN ARMATURE CIRCUIT FAULT 405 = SAFETY CIRCUIT FAULT 406 = 10% LOW LINE ALARM 407 = EXCESSIVE DCU CEMF ALARM 408 = EXCESSIVE PCU CEMF FAULT 409 = UNEXPECTED PCU RESET 410 = SPEED ERROR FAULT 411 = MAX AUTO-RESETS ATTEMPTED 413 = FIELD CURRENT TRACKING FAULT 414 =
SOFTWARE COMPATABILITY FAULT
*** PCU ERRORS***
DISPLAY # - DESCRIPTION 900 = PCU LOOP FAULT 901 = PCU IST FAULT 902 = POWER SUPPLY FAULT 903 = LINE SYNC FAILURE 904 = LOW LINE FAULT 905 = FIELD LOSS 906 = DCU FAILURE 907 = THERMISTOR FAULT 908 = OVER TEMPERATURE 909 = EXCESSIVE RIPPLE 910 = BLOWN FUSE 911 = SHORTED SCR 912 = OPEN SCR 915 = PARAMETER SETUP FAULT 916 = FORCING FAULT 917 = REVERSE ARM. V. FEEDBACK 919 = RATED VAC. SETTING ERROR 920 = RATED ARM. VOLT. SETTING 921 = BRIDGE RATING FAULT 923 = RATED ARM. I. SETTING ERROR 924 = RATED FIELD I. SETTING ERROR 925 = FIELD PCB SENSE FAULT 926 = PCU WATCHDOG TIMEOUT FAULT 929 = FIELD CURR. WON’T GO TO ZERO 930 = FIELD CURR. WON’T GO TO RATED 931 = OPEN CIRCUIT CEMF FAULT 932 = CLOSED CIRCUIT CEMF FAULT 933 = ARM CURRENT WON’T INCREASE 934 = LOW ARM INDUCTANCE 935 = WRONG BUS VS ARM VOLTS FBK 936 = E-STOP OPENED DURING TEST 937 = LOW ARMATURE VOLTS FBK 938 = LOW BUS VOLTS FBK 939 = FIELD FB HARDWARE FAILURE 940 = FIELD A/D OVERFLOW FAILURE 941 = MOTOR THERMOSTAT OPEN Prot = CORRUPTED NV RAM DATA
79
Page 82
Drive Faults
Troubleshooting
ERROR/FAULT CODE
400
401
402
403
404
405
406
407
PROBABLE CAUSE/ — CORRECTIVE ACTION
MOTOR OVERLOAD FAULT --- Indicates that the drive has delivered excess
motor amps for a significant period of time.
Refer to #83 and #84 for proper set-up. Check for dragging elevator brake or weakened motor field.
A motor overload fault does not automatically shut down the drive, but is annunciated via the ALARM relay output K2. See #182
EXCESSIVE FIELD CURRENT --- Indicates that measured motor field current
exceeded 125% of rated current #50. – Causes:
Partially shorted motor field coil. Check motor field. Wrong data entry causing unstable motor field current regulator. Review and
verify settings for #49, 50, 51, 52, 54, & 55.
Mis-wiring of module A3. Verify that phasing is correct. Wrong current tap at A3, TB4, or A3 SW1 setting. Verify. Malfunction of motor field power circuit. Check module A3.
LOOP CONTACTOR FAULT— The Loop Contactor auxiliary contact does not
pick up or drop out within the designated time as requested by the DSD 412 drive. See #102. – Causes:
Defective Loop Contactor Aux. Check for proper feedback at TB1-7.  Defective Contactor. Check for open coil or mechanical binding.  Defective Pilot Relay LPR.  Interference from other elevator relay contact circuits.
FIVE-MINUTE FULL FIELD – Indicates that the Drive and Field Enable control
circuit at TB1-9 was active for 5 minutes without starting the drive. This can
cause motor field burnout. Check car controller relay logic. OPEN ARMATURE CIRCUIT – A large current error existed for ½ second.
Check the DC link fuse F4. Check motor armature circuit wiring. Check power poles in the DC loop contactor.
SAFETY CIRCUIT FAULT—The Drive has detected that the Safety Circuit wired
between TB3-1 and TB3-6 on the Power supply opened unexpectedly while the drive was in the run mode. The safety chain must be closed at least 100ms prior
to enabling the drive. Check for intermittent connections in the Safety Chain. LOW LINE ALARM – Indicates that the input AC line voltage sagged more than
10% below nominal line volts as set at #9. This does not shut down the drive but may be an indication that work is needed to avoid future Low Line shut down faults, F904.
DCU CEMF FAULT - The CEMF of the motor exceeded 109% of measured AC
input voltage to the Drive. This is a warning only and does not cause an automatic drive shut down. – Causes:
3 Phase Input AC Line Voltage drooped or is too low. CEMF on motor rises above VAC input voltage. Motor field current set too high. Verify weak field set point #49 Vs desired
motor voltage at top speed.
Check & correct motor field control tuning to prevent CEMF overshoot.
Review and verify settings for #49, 50, 51, 52, 54, & 55.
80
Page 83
ERROR/FAULT CODE
408
409
410
411
413
414
13-17, 21-26, 100-104, 112-114, 220-234, 240-254, 926
117 / 118 SERIAL COMMUNICATION FAULT
PROBABLE CAUSE/ — CORRECTIVE ACTION
PCU CEMF FAULT - The CEMF of the motor exceeded 118% of the rated VAC
input voltage to the Drive. This fault causes a drive shut down to prevent fuse blowing. – Causes:
3 Phase Input AC Line Voltage is low. Check and correct. Incorrect motor field current setting or field regulator miss-operation causing
excessive CEMF. Check & correct.
Excessive drive speed overshoot. Correct with velocity regulator
adjustments.
Check and correct motor field control dynamic tuning to prevent CEMF
overshoot. Review and verify settings for #49, 50, 51, 52, 54, & 55.
PCU RESET — PCU processor was unexpectedly reset. Verify that correct PCU
software and revision level is being used. Possible problem with main circuit card hardware. Look for external noise interference. Ensure that equipment and signal grounding connections are proper. Correct as necessary. If problem remains, replace Drive Control PCB.
SPEED ERROR TRIP FAULT --- Indicates that a large speed error existed for a
significant period of time. Look for dragging brake or weak motor field. See the
explanations for #99 & #100. MAX AUTO-RESETS ATTEMPTED --- Indicates that more than 5 automatic
resets were necessary in less than 20 minutes of accumulated time. See the explanation for #101.
FIELD CURRENT TRACKING FAULT --- Indicates that the ACTUAL field current
is failing to track the field current COMMAND by more than F192 (Default = 0.05) for 5 seconds. This is not a shut down fault.
Check AC voltage on AC1 and AC2 – Typically 1.5 to 2.5 times VAC (min),
where VACmin = VDC/0.9 or (Full Fld Amps * Field resistance)/0.9
Drives not using correct self-tune values and/or field response set incorrectly.  3. Monitor F620 Fld Trkg Diff, it should be less than F192 "F413 Detection
Level". By setting F192 higher it can eliminate this warning, Caution should be observed prior to doing this. If the proper conditions exist the data on F620 display should not exceed 0.05PU for over 5 seconds.
SOFTWARE COMPATABILITY FAULT --- Indicates that the PCU (U13, U14)
Version and or Revision won’t operate with the DCU (U39, U40) installed in the drive.
Contact Magnetek
MISC FAULTS - Problem with either hardware or software on the Drive Control
PCB. See list at Section 4.5. Check and/or replace U13, U14, U39, U40 (EPROM’s). Replace Drive Control PCB A1.
117 = Serial comm. not started within 20 seconds after drive reset or power up. 118 = Valid serial comm. message not received for more than 150 MS.
Ensure that host is connected and sending valid messages.  Look for and correct electrical grounding noise interference problem.  If Serial comm. is not being used do not set #110 to selection 3.
Drive Faults
81
Page 84
Drive Faults
ERROR/FAULT CODE
97
98
99
900
901
902
903
904 LOW LINE VOLTAGE FAULT
PROBABLE CAUSE/ — CORRECTIVE ACTION
OVERSPEED FAULT - The motor speed has exceeded the trip level set in
function #12, as measured by the encoder. #12 is a percentage of the motor speed value set in #11. Possible cause
Incorrect setting of #10, #11 or #12.  Poor speed regulator tuning - Check #40, 41 & 42  Velocity reference set above rated speed.  Intermittent velocity encoder.
TACH LOSS FAULT - The drive does not see the encoder velocity in proportion
to armature voltage indication of speed. Refer to Function explanations for #14 and #15.
Ensure that the encoder is working. Look for loose connections. Raise the value for #14 if motor has high resistance. Ensure that the contactor feedback circuit at A1TB1-7 does not close before
the armature power poles. See timing diagram on page 49.
REVERSED TACH FAULT — The digital encoder and motor voltage signals do
not agree in direction of rotation. Probable cause: Encoder leads are reversed. Reverse connections for A and A/NOT.
PCU LOOP FAULT - The contactor did not close or opened unexpectedly. Or
the motor voltage exceeded 30% of rated motor voltage #7 during Self-Tune #997. When this occurs, the Severe Fault flag is set and the DSD 412 current reference is forced to zero. This fault will shutdown the drive.
Check the contactor aux feedback circuit to TB1-7.  Check contactor and LPR coils for proper operation.  Check that power is being applied to LPR from the power supply at TB3- 5.
(Will be momentary until F900 occurs.) If not there, suspect an internal relay failure. Replace A4, Power Supply PCB.
PCU IST FAULT – Current flow in excess of 300% of rated armature current
detected. Check for:
Ground fault or intermittent connection in motor armature circuit. Faulty current measuring module. Poor current regulator tuning.
POWER SUPPLY FAULT (CPU Reset Required)
The Low Voltage Power Supply (A4) output has dropped below 60% of the rated voltage. This fault will shutdown the drive. Possible causes:
Loss of 115VAC power. Short circuits in +5V, +/-15V, or +24V circuits, possibly external to the drive. Failed Power Supply Blown fuse internal to power supply.
LINE SYNCRONIZATION FAULT (CPU Reset Required)
The Phase Locked Loop has lost synchronization with the 3 Phase AC input power supply. When this occurs, the Severe Fault flag is set and the current reference is forced to zero. Generally this is caused by AC input power problems and is self-correcting. This fault will shutdown the Drive.
This fault will often occur with a F904 fault.
The AC input power has dropped below 80% of the Nominal AC Line Voltage #9 for 3 consecutive cycles or lower than 50% for one cycle. When this occurs, the Severe Fault flag is set and the DSD 412 current reference is forced to zero. This
fault will shutdown the Drive.
82
Page 85
ERROR/FAULT CODE
905
906
907
908
909
910
911
912
Drive Faults
PROBABLE CAUSE/ — CORRECTIVE ACTION
FIELD LOSS FAULT This fault will shutdown the Drive.
The field current feedback has dropped below 80% of the expected current during the following conditions: #49 when Drive is in Field Weakening Mode (Top speed). #50 when Drive is in Full Field Mode (Accel or Decel). #53 when Drive is in Standing Field Mode (not running). Probable causes are:
Open circuit failure of motor field or motor field wiring. Hardware failure of motor field control circuitry. Loss of power or incorrect phasing to Field Rectifier.
DCU FAILURE FAULT (DSD 412 Power down is required.)
The update of the Dual Port RAM from the Drive Control Unit (DCU) is unreliable. This requires the replacement of the Drive Control PCB, A1. This fault will
shutdown the drive. THERMISTOR FAULT The thermistor is found to be open or shorted. Check
and/or replace the thermistor. It should measure between 2K – 10K ohms at 20C room temperature. A Thermistor Fault will also occur if the machine room ambient temperature is below 0C as the resistance it detected is too high to be measured. An open thermostat on larger drives will also indicate F907. This fault
will not shutdown the Drive. OVER TEMPERATURE FAULT - The calculated SCR junction temperature is
above 125 degrees Centigrade. This is calculated from the thermistor heat sink measurement and measured armature output current heating effects of SCRs. Possible causes:
Ambient temperature too high. Check for cause. Clogged air filter in cabinet. Clean or replace air filter. Clogged heat sinks. Clean Heatsink fins. Cooling fan failure. Replace defective cooling fan(s) in power cube.
Note: This fault will not shutdown the Drive. RIPPLE FAULT - Repeated high peak to average motor armature current. The
cause of this condition may be defective hardware that can be discovered through the PCU Diagnostics CDU function, #998. It may also occur due to poor
regulator tuning or other oscillatory operation condition. BLOWN FUSE FAULT - One or more of the three AC line fuses is open. This
condition is checked on power-up and upon request through the PCU F#998 PCU Diagnostics function. Detection is accomplished by measurements via voltage dividers on the Armature Interface PCB, A2. Possible causes are;
One or more of AC input fuses are blown. Power wiring problem-check wiring. Faulty DSPR power relay.
SHORTED SCRS/DOUBLER FAULT (DSD Power Down is required.)
One of the SCR/Doubler packs has a short circuit between the SCRS. This condition is checked only upon request through the PCU #998 Diagnostics CDU
function. The optional handheld PCDU will also identify which SCR pair is bad. OPEN SCR FAULT (DSD Power Down is required.)
One of the SCRs does not conduct current. This condition is checked only upon request through the PCU #998 Diagnostics CDU function. The optional handheld PCDU will also identify which SCR pair is bad. Check for faulty SCR gating
leads.
83
Page 86
Drive Faults
ERROR/FAULT CODE
915
916
917
919
920
921
923
924
925
PROBABLE CAUSE/ — CORRECTIVE ACTION
PARAMETER SETUP FAULT (DSD power down is required.)
One of the following parameters is not within the range of the chassis hardware. Rated Volts #7 or #9 Rated Current #3 or #50 Corrective action: Enter correct parameter data, save to NVRAM. Reset the
drive & re-start. FORCING FAULT – The prohibit rotation bit was removed with the loop picked-
up. This fault can only occur when using the handheld PCDU. REVERSE ARMATURE POLARITY - (DSD power down is required.)
This fault will show up when doing the F998 PCU Diagnostics Test. It indicates that the polarity of the Armature Voltage Feedback wires is reversed or missing. Check connections on A1TB5-1 and A1TB5-2 of the Armature Interface PCB, A2.
F909 faults and/or very poor drive/ride performance may occur if not corrected. LINE VOLTAGE SETTING FAULT (DSD power down is required.)
This fault is declared if a number is entered for the Rated Line Voltage, #9 that is outside the acceptable range of 150 to 525VAC. If 0 is entered, the rated line
voltage defaults to 230 or 460 VAC depending on the line voltage sensed. LOAD VOLTAGE SETTING FAULT (DSD power down is required.)
Declared if the Rated Armature Voltage, #7 value is outside the acceptable range
of 150 to 700 VDC. BRIDGE RATING FAULT (DSD power down is required.)
The bridge type is determined by reading a sense resistor on the Cube ID PCB plugged into the A2 Armature Interface PCB. The resistor value identifies the ampere rating and current feedback scaling of the physical hardware. This failure occurs if the computer cannot identify the drive size. Possible causes:
J14 on Main Control PCB is not seated properly.  Missing or wrong Cube ID PCB.  Wrong PCU software in U13 & 14.  Faulty Armature Interface PCB – replace PCB.  Faulty Drive Control PCB – replace PCB.
LOAD CURRENT SETTING FAULT - (DSD power down is required.)
This fault is declared if a number is entered for Rated Armature Current, #3 that is outside the acceptable range of 0.125 to 2.0 times the bridge current rating as determined by the bridge sense resistor on the Cube ID PCB, on the Armature
Interface PCB. FIELD CURRENT SETTING FAULT (DSD power down is required.)
This fault is declared if a number is entered for Rated Field Current #50 that is outside the acceptable range of the Field Interface board, A3 current rating as determined by the field sense resistor selected by SW1 on the Field Interface
PCB. FIELD SENSE FAULT - (DSD power down is required.)
The field bridge rating is determined by reading a sense resistor on the Field Interface board selected by SW1. This resistance identifies the motor field current feedback scaling for the A/D converter. If the resistance value is not recognized a Field Sense Fault is declared. This indicates that there is a hardware fault on the Field Interface PCB, Drive Control PCB, or within the interconnecting cables and hardware. Check that J13 is seated properly and that the cable is not defective.
84
Page 87
Drive Faults
ERROR/FAULT CODE
926
Prot
" P.L. "
" – – – "
929 Motor field current does not reduce to near zero within 6 seconds. Verify
PROBABLE CAUSE/ — CORRECTIVE ACTION
PCU WATCHDOG - (DSD power down is required.)
This fault is declared when the PCU is reset via its own software watchdog timer. It is an indication of a PCB hardware problem more so than a DCU or PCU software problem. A likely cause is severe electrical interference. Check for:
Faulty EPROM’s or socket connections at U13, U14, U39 or U40. Ensure that all panel relays have working R/C coil suppression. Include
relays that may be operating door opener equipment.
Look for relays where the +24V and 115VAC signals are being switched in
the same relay. There must be arc barriers between contact poles to avoid “spark splash” from 115 VAC circuits into 24 VDC logic.
Check for intermittent grounds in the power circuit and in 24Vdc signal wiring. Noise generated over the encoder feedback, power supply, or Drive Control
PCB can cause this fault. Verify all connections and verify that the Drive Control PCB is properly grounded.
This fault is usually caused by electrical noise causing the DSD 412
microprocessor to malfunction. If this occurs when the car is stationary, the car controller can quickly reset it. An elevator passenger doesn’t see any
effect.
CORRUPTED NVRAM DATA – The NVRAM has lost parameter set up data.
This fault will occur if the battery within NVRAM chip U56 is weak. The drive
display will show ‘Prot” if a loss of data is detected when power has been re-
applied, and the processor attempts to load in default values while the NV-Protect
switch is in the ‘safe’ ON position. Replace U56 every 8 years. POWER LOSS - Loss of 115 VAC control power. — Check cable connection at
TB3 of Power Supply Assembly A4. Ensure that control power is always above 92 VAC.
BLOWN FUSES or loss of 3 phase input power. – Check for blown line fuses. If
fuses are not blown, verify that AC input voltage to drive is present. Verify that power supply voltages are valid at TP1, 2, 3, & 4 on the main PCB. Check connections to the Armature Interface PCB and ribbon cable at J4.
motor field current with an independent clamp-on DC ammeter.
Probable causes: Incorrect phasing of Vac supply to field control module. Provide correct single
phase supply wiring per connections shown in Figure 9 of this manual.
Faulty SCR/Rectifier power module for motor field. Replace. *May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
85
Page 88
Drive Faults
ERROR/FAULT CODE
930 Motor field current does not increase to near rated amperes within 6
931 Excessive open circuit voltage to motor armature circuit. Measured
932 Armature CEMF volts >20% of rated during test.
933 Motor armature current does not increase to near test amps within 6
934
935 Calibration of bus voltage and armature voltage feedback circuits does not
936 E-Stop contact was opened during test. Test data is not valid. Jumper E-
PROBABLE CAUSE/ — CORRECTIVE ACTION
seconds. Verify motor field current with an independent clamp-on DC ammeter.
Probable causes:
Motor field not connected.  Not enough voltage available to achieve rated field current. Maximum Vdc
output to motor field is 0.9 X Vac input at terminals A3TB1, AC1 & AC2. At – 10% low line, the maximum Vdc output is 0.8 x Vac. If this voltage is not enough to produce rated field current through the resistance of the motor field winding, reconnect the field windings for lower voltage (and higher current) or provide a step-up transformer for the motor field circuit as shown in Figure 6 of this manual.
Improper settings for the connected motor field. Insure that the proper current
tap at A3TB4 is used, and that calibration switch A3S1 is set correctly, and that adjustments #49, #50, #52, and #55 are set correctly.
Faulty SCR/Rectifier power module for motor field. Replace.
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
armature voltage is greater than 10% of rated volts #7.
Probable Causes:
Motor is rotating, producing CEMF. Unbalanced SCR leakage with low voltage setting of #7. Increase #7 for test. Damaged SCR(s)
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
Probable causes:
Motor rotating during the test producing CEMF. High motor armature resistance. Ensure that brush commutator is clean.
Temporarily increase Rated Armature Volts, #7 during the test.
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
seconds.
Probable causes:
Faulty motor armature circuit. Check wiring and motor for open circuit.  Open SCR or missing SCR gating. Perform Self-Diagnostics to verify.
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
Calculated armature inductance is less than 0.00017 Henry. The drive will
not Self Tune with less than 170 micro-henries of load inductance. Verify that inductance is really that low. Verify that Vac value at #9 is correct. Manually enter the minimum value into #5. Parameter #2 must be set to OFF.
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
match.
Probable causes:
Missing wire to bus or armature voltage feedback circuits. Component problem - Feedback voltage divider ratios do not match.
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
Stop circuit and re-test.
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
86
Page 89
ERROR/FAULT CODE
937 Low read-back volts from motor armature circuit.
938 Low read-back volts from DC bus circuit.
939 Faulty Field Control Hardware.
940 Field Current Feedback A/D Saturated
941
PROBABLE CAUSE/ — CORRECTIVE ACTION
Probable Causes: Missing or reversed wires to armature voltage feedback at A2TB5-1 &
A2TB5-2.
Component problem – Feedback voltage divider ratio does not match that
identified in Cube ID PCB.
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
Probable Causes: Missing wire to bus voltage feedback. (Discrete wires on drives larger than
300 amps DC.)
Component problem – Feedback voltage divider ratio does not match that
identified in Cube ID PCB.
*May occur during Self-Tune (Fctn #997) or Self-Diagnostic (Fctn #998).
Probable Causes:
Component problem – Replace Field Interface Board. If fault is still present replace the Main Control Board.
*May only occur during power-up.
Field A/D reading is saturated for more than 15 seconds. Probable Causes: Component problem – Replace Field Interface Board and Ribbon Cable (J33)
If fault is still present replace the Main Control Board. MOTOR THERMOSTAT FAULT --- Indicates that the drive has sensed that the
motor thermostat is open at A4TB3(2) to A4TB3(8). A motor thermostat fault does not automatically shut down the drive, but is annunciated via the ALARM relay output K2. See #182 Causes: If the point is closed but the fault is still present replace the power supply.
Drive Faults
Table 17: Fault Code Descriptions
87
Page 90
Drive Faults
OTHER CONDITIONS NO LED DISPLAY WITH
POWER ON
LOSS OF STORED PARAMETER DATA
DRIVE DISPLAY INDICATES BLOWN FUSES WHEN ALL FUSES TEST GOOD WITH OHMMETER
REPEATED FALSE OVER­TEMPERATURE INDICATIONS
PROBABLE CAUSE / CORRECTIVE ACTION
No power at TB3 or failed power supply.
Verify 115 Vac control voltage at TB3(1 & 7) Verify that cable J11 is seated properly. Short circuit on external wiring dragging down the power supply. Verify by temporary removal of wires at TB1(48, 82, & 1). If display operation is restored. Fix external problem. Short circuit internal to current measuring transducer. Verify by removal of J27. If display operation is restored, replace the current transducer. DO NOT RUN THE DRIVE WITH CURRENT TRANSDUCER DISCONNECTED.
5. Faulty or missing EPROM’S or faulty socket connections at U13, 14, 39, 40.
Severe electrical disturbance with NV-Protect switch in OFF position, or failure to actually save the data, or weak battery within U56.
Remember to SAVE the data when parameters are changed. See Page 36. Return NV-Protect switch to ON when parameter data changes are completed. Magnetek recommends replacing U56 every 8 years.
Control power applied before 3-phase armature supply. Short circuit in +/-15 V wiring circuits prevents analog circuit measurements from working.
Verify that 3-phase power and control power are supplied simultaneously. Or that drive faults will be RESET by external circuits after 3-phase power is applied. Read power supply voltages at test points near the top front of PCB A1. TP8 is circuit common. TP1, 2, 3, & 4 (just below J11, to right of silver metal can U8) should be +24V, +15V, -15V, +5V, +/-5% respectively. If voltages in step 2 are low, unplug ribbon cables at J13 and J14 (A1 PCB, lower left). If power supply voltages are restored, pursue cause of short circuit on those cables. Suspect faulty current transducer or cable. Remove power supply cover. Disconnect power supply at J11. Re­measure voltages at marked test points on power supply PCB. If voltages are OK with J11 disconnected and fault was not found in step 3, replace main PCB.
Leakage current between the thermistor on the heat-sink and the thermistor leads can cause an elevated temperature to be measured. Replace failing thermistor and/or thermostats. Conditions out of the range specified temperature range.
Table 18: Other Faulting Conditions
88
Page 91
Input – Output Signal Verification
)
Input – Output Signal Verification
The Control Display Unit (CDU) function #981 may be used to directly read and track the status of logic input and output signals at DSD 412 drive terminals. This is an easy way to verify the integrity of input and output logic signals to the drive. Refer to specific connection diagrams for your application to confirm the definition of how each signal is being used. The I/O indicator technique as described below will work regardless of whether or not the particular terminals and signals are used by internal software logic or actually wired into your application. Function #981 does not work with the Portable Control display Unit.
Here’s how to use this valuable troubleshooting tool:
1. Press the Up ▼ or Down ▲ keys and go to F#981.
2. Press the DATA FCTN KEY. The green light should turn ON to indicate that data is being displayed.
3. Segments on the local Control Display Unit will light up to indicate active input and output logic actions. Vertical segments represent input signals and horizontal segments represent output signals as identified below. For more information, see appropriate Figure depending on whether the drive is being run serially or analog.
S1 TB1(53)
TB1(53)
LPR AUX TB1(7)
TB1(7)
S2 TB1(12)
TB1(12)
FAULT RESET
TB1(49)
TB1(49)
K1
TB1(40,41,42)
TB1(40,41,42)
K5
TB1(79)
TB1(79)
I N P U T L O G I C D A T A B I T S
S3 TB1(54)
TB1(54)
RUN OR RUN UP
TB1(8) TB1(50) TB1(9)
TB1(8)
E-STOP
TB3(6)
DOWN OR RUN DWN TB1(50
K2
TB1(38-39)
TB1(38,39)
K6
TB1(83)
TB1(83)
THRMST
TB3(8)
DRIVE ENABLE TB1(9)
N-A N-A N-AN-A
N-A N-A N-A N-A
RAMP 2 SEL
TB1(51) TB1(10) TB1(11)
TB1(51)
K3
TB1(36-37)
TB1(36,37)
K7
TB1(84)
TB1(84)
O U T P U T L O G I C D A T A B I T S
RAMP 1 SEL TB1(10)
S4
TB1(52)
TB1(52)
K4
TB1(78)
TB1(78)
S0 TB1(11)
LPR
TB3(5)
Figure 23: I/O Analog Monitor Function
89
Page 92
Input – Output Signal Verification
TB1(53)
TB1(12)
LPR AUX
TB1(7)
TB1(7)
TB1(49)
K1 TB1(40,41,42)
TB1(40,41,42)
K5 TB1(79)
TB1(79)
I N P U T L O G I C D A T A B I T S
TB1(54)
RUN
TB1(8) TB1(50) TB1(9)
TB1(8)
K2 TB1(38-39)
TB1(38,39)
SERIAL GAIN SWITCH
O U T P U T L O G I C D A T A B I T S
E-STOP
TB3(6)
K6 TB1(83)
TB1(83)
THRMST
TB3(8)
SERIAL
N-A N-A N-AN-A
RUN UP
SERIAL
N-A N-A N-A N-A
RUN
TB1(51) TB1(10) TB1(11)
K3
TB1(36-37)
TB1(36,37)
SERIAL FAULT RESET
K7
TB1(84)
TB1(84)
SERIAL RUN DOWN
SERIAL PRE ­TORQUE
TB1(52)
K4 TB1(78)
TB1(78)
ENABLE
LPR
TB3(5)
FULL FIELD
SERIAL
FIELD
Figure 24: I/O Serial Monitor Function
90
Page 93
Maintenance
Maintenance
Preventive Maintenance
WARNING
HAZARDOUS VOLTAGES MAY EXIST IN
THE DRIVE CIRCUITS EVEN WITH DRIVE
CIRCUIT BREAKER IN OFF POSITION.
NEVER ATTEMPT PREVENTIVE
MAINTENANCE UNLESS INCOMING
THREE-PHASE AND CONTROL POWER IS
DISCONNECTED AND LOCKED OUT.
Preventive maintenance is primarily a matter of routine inspection and cleaning. The rectifier bridge heat sinks should be kept clean by brushing while using a vacuum cleaner. Excess dust and dirt accumulation on the heat sinks can cause overheating of the SCRs.
Periodically check all electrical connections; tighten as required.
Repair and Replacement Procedures
Replacement parts are listed on page 109. Either the common name or reference designator of a particular part may be used to locate the item in the Recommended Spare Parts Table to find a replacement part number. Be sure to use the proper table corresponding to the ampere rating on the drive nameplate.
Printed Circuit Boards
IMPORTANT
When replacing any printed circuit board
(PCB) or any integrated circuit (IC) in the DSD
drive, proper Electro-static Discharge (ESD)
procedure MUST be followed.
Repair of printed circuit boards requires
special techniques and test equipment. For
this reason, field repair is not authorized, and replacement of a suspect board is recommended.
Periodically check air filters on enclosure doors, if applicable; clean if dirty, replace as necessary.
Periodically clean the cooling fans to prevent dirt buildup. At the same time, check that the impellers are free and not binding in the housing. Each fan motor is permanently lubricated; the fan should be replaced if the shaft does not spin freely.
If/When drive faults occur, follow those aids based on the observed Error/Fault code. In some instances, the fault tracing required to determine the necessary repairs is too extensive to list in detail in this manual; for those faults, it is recommended that Magnetek be called for assistance.
Some of the probable causes in Table 17: Fault Code Descriptions mention problems at connectors, all of which are on the Drive Control PCB. Table 19: Connector Definitions describes the basic function of each connector, and Figure 25: Connector and E-prom Locations on the board.
Defective or questionable printed circuit boards should be returned to MagneTek, for repair and test. The printed circuit board should be ESD protected, then individually protected with an inch thickness of soft wrapping material before it is packed in a suitable carton. MagneTek assumes no responsibility for printed circuit boards returned without proper return tags and forms. Contact your Magnetek sales representative for proper return tags and forms.
91
Page 94
Maintenance
CONNECTOR TYPE FUNCTION
Provides interface to connections for external
J1 DB-9
J2
J11 20-Pin Header
J13 10-Pin Header
J14 40-Pin Header
J31 10-Pin Header
J32 4-Pin Header
J33 10-Pin Header Connects J13 to Signal Interface PCB, A3.
RJ-12 Phone jack plug 6-pin
RS422 serial link controls. J1 and J2 are mutually exclusive. Provides interface connection for external RS232 devices. The optional PCDU plugs into this connector. J1 and J2 are mutually exclusive. Provides power supply voltages and control signals to the Drive Control PCB from the DSD 412 Power Supply PCB. Provides power supply and board sensing connections to the DSD401 Signal Interface PCB, A3. [This cable is the same as that used to connect the standard DSD 412 field Interface PCB.] Provides control and feedback signal connections to the Armature Interface PCB Connects TB1 logic signals to Signal Interface PCB A3. Connects analog output signals from TB1 to Signal Interface PCB A3.
Table 19: Connector Definitions
92
Page 95
U13 U14 J11
Maintenance
S3 NV RAM PROTECT SWITCH
U39
U40
U50
J14
J13
J2 J1
ONLY ONE PRESENT AT
J12
Figure 25: Connector and E-prom Locations
93
Page 96
Maintenance
A
p
A
A
A
A
A
A
A
A
A
A
TP19-21 N
TP40
TP40 Follow
Follow
TP40 Follow
TP29 BALag
TP28 CBLag
TP40 Follow
TP24 Common
TP30
V
TP3
-15V
TP1 +24V
TP2 +15V
TP22 /ARM
TP4 +5V
TP36 +10VR
TP37
RMFB
TP39
RMIFBF
TP47 Common
TP7 Low
TP5
en
SO
TP6 Thst Open
TP23 WDOG DIS
TP43 MAI2
TP42 MAI1
TP35
-10VREF
TP34
TP33
IN2
IN3
TP8 Common
TP13 LAN
TP44 MAO1
TP46 FI
TP14 E/O
TP31
IN0
TP1
TP1
TP1 +24V
+24V
+24V
TP9-12
TP16 E Scan
TP15 F Scan
TP45 MAI0
TP41 MAO0
TP32
-D Scan
TP17 ABCDE Scan Time
TP25 Common
TP38 ANA_ TACH_FB
TP27
O0
TP26
O1
IN1
Figure 26: Test Point Locations
94
Page 97
Maintenance
TEST POINT FUNCTION DESCRIPTION
TP1 +24V SUPPLY +24V SUPPLY
TP2 +15V SUPPLY +15V SUPPLY
TP3 -15V SUPPLY -15V SUPPLY
TP4 +5V SUPPLY +5V SUPPLY
TP5 EMERGENCY STOP OPEN HI = EMERGENCY STOP IS OPEN
TP6 THERMOSTAT OPEN HI = THERMOSTAT IS OPEN
TP7 LOW PWR SUPPLY WARN HI = LOW 115VAC TO PWR SUPPLY
TP8 COMMON COMMON
TP24 COMMON COMMON
TP25 COMMON COMMON
TP47 COMMON COMMON
TP9 A SCAN TIME HI = DCU A SCAN IS RUNNING
TP10 B SCAN TIME HI = DCU B SCAN IS RUNNING
TP11 C SCAN TIME HI = DCU C SCAN IS RUNNING
TP12 D SCAN TIME HI = DCU D SCAN IS RUNNING
TP13 LAN Chip select for Lan mode; High = Active
TP14 E/O EVEN/ODD Address Select; High = +5V
TP15 F SCAN TIME HI = DCU F SCAN IS RUNNING
TP16 E SCAN TIME HI = DCU E SCAN IS RUNNING
TP17 ABCDE SCAN TIME HI = DCR ABCDE or F SCAN IS RUNNING
TP18 BUS DIR N/A
TP19 RESERVED FOR TESTING N/A
TP20 RESERVED FOR TESTING N/A
TP21 RESERVED FOR TESTING N/A
TP22 ARMATURE DISABLE Logic 1 when Forward or Reverse Bridge is firing.
Jumper to COMMON to disable Bridge.
TP23 WATCHDOG DISABLE Logic 0 during POWER-UP CPU RESET;
Otherwise Logic 1.
TP26 ANALOG OUTPUT, TB1-26 Analog Output Signal on TB1-26
TP27 ANALOG OUTPUT, TB1-27 Analog Output Signal on TB1-25
TP28 CB LAG C-B PHASE SIGNAL
TP29 BA LAG B-A PHASE SIGNAL
TP30 ARMATURE VOLTAGE SCALING = 100/1 (100VDC ON ARMATURE =
1VDC ON TP30)
TP31 ANALOG INPUT ANALOG INPUT SIGNAL ON TB1-58
TP32 ANALOG INPUT ANALOG INPUT SIGNAL ON TB1-59
TP33 ANALOG INPUT ANALOG INPUT SIGNAL ON TB1-60
TP34 ANALOG INPUT ANALOG INPUT SIGNAL ON TB1-61
95
Page 98
Maintenance
TEST POINT FUNCTION DESCRIPTION
TP35 -10V REFERENCE OUTPUT -10V REF OUTPUT AT TB1-29
TP36 +10V REFERENCE OUTPUT +10V REF OUTPUT AT TB1-28
TP37 ARMATURE CURRENT
FEEDBACK
TP38 ANALOG TACH FEEDBACK ANALOG TACH SIGNAL (when used)
TP39 ARMATURE CURRENT
FEEDBACK
TP40 DIFF ANALOG INPUT +/- 10V DIFF INPUT ON TB1-63, 68 OR +/-600MV
TP41 ANALOG OUTPUT #0 Analog Output to TB1-45
TP42 DIFF ANALOG INPUT, +/-
10V, OR +/- 0-600MV
TP43 DIFF ANALOG INPUT +/-
10V
TP44 ANALOG OUTPUT #1 ANALOG OUTPUT to TB1-46
TP45 DIFF ANALOG INPUT, +/-
600MV
TP46 FIELD CURRENT FEEDBACK 1.9A Term, TP46 = [email protected]
3V @ 1 PU (Use Shielded Probe to avoid noise pick-up. Noise will cause erratic Drive operation) See TP39.
Filtered Armature Current Feedback Signal. Average of Armature Current.
DIFF INPUT ON TB1-64, 67
DIFF INPUT, +/-10V TO TB1-71, 76 OR +/- 0­600MV DIFF INPUT TO TB1-72, 75
DIFF INPUT, +/- 10V TO TB1-30, 31
+/- 600MV TO TB1-34, 35
6.9A Term, TP46 = [email protected]
16.0A Term, TP46 = [email protected]
40.0A Term, TP46 = [email protected]
Table 20: Test Point Definitions
96
Page 99
Drive Control PCB Replacement
1. Release the front cover of the drive by pulling out the four corner fasteners, approximately 1/4 inch, until they snap; then remove the cover.
2. Mark each cable and wire to ensure proper reconnection; before disconnecting them.
3. Disconnect all cables and wires from the Drive Control PCB. Remove nine screws holding the Drive Control PCB to the swing out door chassis from the front, and remove the Drive Control PCB from the power cube.
4. If there is an optional circuit board attached to the back of the Drive Control PCB, disconnect the Local I/O cable from J12 on the Drive Control PCB. Then remove the mounting screws which secure the Local I/O PCB to the back of the Drive Control PCB. Re-attach the same Local I/O PCB to the replacement Drive Control PCB using the same hardware in reverse order. Re-attach the J12 cable.
5. Mount the new Drive Control PCB into the power cube by reversing procedure in steps 1 through 3. Be sure to re-use the small diameter flat washers under the screw heads on the Drive Control PCB to maintain proper electrical clearances.
6. Remove integrated circuits (ICs) U13, U14, U39, U40 as appropriate, from the defective Drive Control PCB. Install into the same positions on the new board. Ensure that polarity notch on IC is aligned with the silkscreen notch on the board. Each IC is marked with the proper “U” number in the bottom left hand corner of its label.
7. Perform Start-Up Procedure.
IC Replacement
IMPORTANT
When replacing any printed circuit board
(PCB) or any integrated circuit (IC) in the DSD
drive, proper Electro-static Discharge (ESD)
procedure MUST be followed.
EPROM Replacement
To replace an EPROM (U13, U14, U39, U40), first check that the new device has the same “U” number on its label as the defective device. Remove the existing device and install the
Maintenance
replacement in the same position. Then perform the Start-Up Procedure in Drive Start .
NVRAM Replacement
To replace an NVRAM device (U56), remove the defective device and install the replacement in the same position. Then perform the Start-Up Procedure. If you have kept a record of the parameter settings you should be able to re-load all parameter values, save the data and go. If you do not have a record of the working drive parameter settings, you must re-enter and re-tune all parameters
by repeating all drive adjustment procedures.
Testing and Replacement of Power Components.
Fuse Replacement
Whenever attaching a fuse, wire or bus bar to another component to achieve an electrical connection, always apply a thin coating of electrically conductive joint compound to all contacting surfaces. Magnetek recommends using Joint-Al-Z compound for all bolted electrical power connections.
Diagnosis of fuses — The input AC fuses are
checked when power is initially applied during the Start-Up sequence of the drive, and again when a PCU DIAGNOSTICS #998 is performed. The output DC fuse is checked only when a PCU DIAGNOSTICS #998 is performed. When running, blown fuses may cause an F910 or F404. With input power disconnected, the fuses may be checked with an ohmmeter while still in place in the circuit. Replace any fuse that indicates a resistance reading of more than a fraction of an ohm. Re check that the fuse is indeed open/blown when removed from the circuit. Be aware that other circuitry may cause a low resistance reading to appear across a blown fuse. If there are doubts about the fuse being good or bad, remove connections to at least one end before measurement. For maximum assurance to prevent callbacks, Magnetek recommends replacing all three AC line fuses even when only one or two are blown.
If the drive blows AC input fuses, check for shorted SCRs before power is re-applied. While the input fuses are removed for replacement, measure circuit resistance from each AC line to AC line on the SCR power bridge side of the fuse connections, and from each AC line to the DC output busses. If
97
Page 100
Maintenance
resistance readings are less than 100 K-ohms, suspect shorted or badly damaged SCRs. Replace those faulty parts before attempting to power up again with fresh fuses.
There is a small fuse inside the Drive Power Supply, A4. This fuse may blow if 115 Vac control power has surged above 135 volts. If there is voltage at A4TB3-1 & A4TB3-7, but the power supply does not appear to work, this fuse may be checked by removing the power supply cover. A blown power supply fuse does not necessarily mean that the power supply is faulty as the fuse also protects a transient surge suppressor contained within. External surges on the 115VAC control voltage power source can cause this fuse to blow.
Testing and Replacement of Power Semiconductors and Snubber Components.
If SCRs are suspect, test for short circuits before disassembly to help locate the problem. Refer to specific instructions in this manual for the drive ampere size. Perform the suggested ohmmeter tests to verify that there are no direct short circuits. Then perform the PCU DIAGNOSTICS #998. These tests will perform shorted and open SCR tests to help indicate which SCRs need replacement.
Several different DSD 412 power circuit configurations exist in order to handle rated currents from 25 to 1350 amperes. Refer to the proper sub-section in this manual according to rated drive current as listed on the nameplate for specific service information for the individual power conversion units.
Testing and Replacement of the Motor Field Control Module and PCB
Components of the DSD 412 for control of motor field consist of the A3 PCB and associated SCR/Rectifier module Q7 located under the PCB. Input power is single phase voltage supplied to A3TB1 terminals AC1 and AC2. Motor field current DC amperes are measured by a current transducer (CT) located on the PCB. Connecting the F1 (+) field wire to TB4 selects the full scale current range. Switch A3S1 is used to tell the microprocessor what ‘tap’ is being used.
nominal value. This voltage is phase sensitive and must be derived as shown in drawing of Figure 2.1a.
2. Verify motor field current flow calibration by reading motor current with a separate clamp-on DC ammeter. Compare the reading with that of #612. If these two readings do not correspond, verify that A3S1 is correctly set and that the F1(+) lead is connected to the right tap.
3. Read and verify VDC output to the motor field between A3TB4 F2(-) and A3TB4F1(+).
4. Turn all power off. Temporarily remove one power feed wire from A3TB1-AC1 and test the SCR/Rectifier module for shorts with an ohmmeter between each screw connection to the PCB. If short circuits exist, replace the module AND the PCB.
Field Control A3 PCB Replacement
1. Label and disconnect all power wires to terminals on the PCB. Disconnect ribbon connector J13.
2. Disconnect wires G1 & G2 from the SCR/Rectifier module. Remove 4 screws holding PCB to SCR/Rectifier module. Remove PCB at each plastic post by gently pulling straight out.
3. Reverse the above procedure to reassemble. Torque the 4 SCR/Rectifier module screws to 18 in-lbs.
Field Control SCR/Rectifier Replacement
1. Remove the A3 PCB according to the above.
2. Remove the 2 cap screws securing the module to the heatsink and remove the damaged module.
3. Wipe the mounting surface clean. Use a new thermal mounting pad or a thin coating of thermal grease on the bottom of the replacement module. Orient the module with AC1 & AC2 terminals toward the right side of the unit. Use cupped washers under the mounting screw heads. Tighten mounting hardware to 18 inch-lbs.
4. Reassemble the A3 PCB and all electrical connections.
If the desired motor field current cannot be obtained:
1. Verify that the proper AC voltage is available at terminals A3TB1-AC1 & A3TB1AC2. Verify that #55 is set to this
98
Loading...