This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in
manuals, be alert to the potential for personal injury or death.
WARNING
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer
to this manual. For assistance or additional information,
For your safety, do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any
other appliance. Such actions could result in property
damage, personal injury, or death.
WARNING
Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
qualied service personnel should install or service
this equipment. Installation and service performed by
unqualied persons can result in property damage,
personal injury, or death.
The unit must be installed with approved wall sleeve
and grille accessories for safe operation. Improper
installations could result in property damage, personal
injury, or death.
A Lennox International Inc. Company
*P506325-01*
WARNING
Manufactured By
Allied Air Enterprises LLC
215 Metropolitan Drive
West Columbia, SC 29170
(P) 506325-01
CAUTION
The installation of this appliance must conform to the requirements of the National Fire Protection Association; the National
Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code Part 1, CSA 22.1
(latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should
be consulted before installation is made. Such applicable regulations or requirements take precedence over the general
instructions in this manual.
506325-01Issue 1734Page 1 of 15
Installation
WARNING
Outdoor Ambient Air Temperature °F
Minimum D BMaximum D B
Cool Cool Heat
6511575
These units are not approved for mobile home
applications. Such use could result in property damage,
personal injury, or death.
General
These instructions explain the recommended method of
installation of the MHP4 electric cooling unit and associated
electrical wiring.
This unit is designed and approved for use as a selfcontained air-to-air air conditioning system.
These instructions, and any instructions packaged with
mating components and/or accessories, should be carefully
read prior to beginning installation. Note particularly any
CAUTIONS or WARNINGS in these instructions and all
labels on the units.
These instructions are intended as a general guide only,
for use by qualied personnel and do not supersede any
national or local codes in any way. Compliance with all local,
state, provincial, or national codes pertaining to this type of
equipment should be determined prior to installation.
Units that comply with the maximum cabinet leakage 2% of
rated airow requirements of ANSI/ASHRAE 193 (complies
with IECC 2015) are identied on the rating plate.
Indoor Ambient Air Temperature °F
Minimum Maximum
DB/WBDBDB/WBDB
CoolHeat CoolHeat
62/575090/7280
DB = Dry Bulb
WB = Wet Bulb
Table 1. Application Limitations
Limitations
The unit should be installed in accordance with all national
and local safety codes.
Limitations of the unit and appropriate accessories must
also be observed.
The outdoor fan is designed to operate against no more
than .10” w.c. static pressure.
Minimum and maximum operation conditions must be
observed to assure maximum system performance
with minimum service required. Refer to Table 1 for the
application limitations of the unit.
Location
Inspection
Upon receipt of equipment, carefully inspect it for possible
shipping damage. If damage is found, it should be noted
on the carrier’s freight bill. Take special care to examine
the unit inside the carton if the carton is damaged. File a
claim with the transportation company. If any damages
are discovered and reported to the carrier do not
install the unit, as claim may be denied.
Check the unit rating plate to conrm specications
are as ordered.
WARNING
The unit must be installed with approved wall sleeve
and grille accessories for safe operation. Improper
installations could result in property damage, personal
injury, or death.
For information on wall sleeves and grille accessories, see
the Accessories section.
The design is certied for thru-the-wall or up-to-the wall
(inside wall) installation only. The interior portions of
the unit may be surrounded by a closet with clearances
to combustible material held to 0” at the sides, top, and
front of the plenum. All servicing and cleaning of the unit
can be performed from the front. If installed in a closet
or utility room, provide 25” clearance in front for service
if the door to the room is not in line with the front of the
unit (see Figure 1). Accessibility clearances must take
precedence over re protection clearances.
Page 2 of 15506325-01Issue 1734
Plenum
Exterior Wall
Wall Sleeve
(one each side)
Interior Wall
Clearances*
Mounting Strap
(one each side)
3/4" Plywood Riser
Floor
Platform (field supplied)-Must be level with sill plate of hole in exterior wall
Front of Unit
Sill Plate
4" Min.
Clearance to combustible materials is 0” at the side, top, and front of plenum. If accessibility clearances are greater
than clearances to combustibles, accessibility clearances take precedence.
The front of the unit must be accessible for service. If the unit is enclosed, providing a door or access panel opposite
the front of the unit is the preferred method of providing access. The door or access panel must be at least 30” wide
(centered on the unit) and as tall as the unit. If a return duct is not installed, in order to provide adequate return air the
minimum clearance required between the front of the unit and the door or access panel is 4” for 43” tall cabinets and
5” for 48” and 56” tall cabinets.
Top View
Side View
* With no return duct installed, minimum clearances to the front of
the unit are 4” for 43” tall cabinets and 5” for 48” and 56” cabinets.
If a return duct is installed, enough clearance must be provided for
the drain trap installation.
506325-01Issue 1734Page 3 of 15
Unit must be supported by platform.
The unit must be installed with approved wall sleeve and grille
accessories for safe operation. Improper installations could result in
property damage, personal injury, or death.
Figure 1. Minimum Clearances
IMPORTANT
NOTE: Platform must be constructed so that it is level with sill plate of wall opening.
Figure 2. Wall Sleeve and Louver Kit Installed
The outside of the unit may be ush with the face of
the exterior wall, and it should not be obstructed with
trees, landscape materials, or building structure. Unit
can be installed recessed with appropriate wall sleeve
accessories. There is no minimum clearance required on
locating the unit to an interior corner of a building.
If the unit is installed in a residential garage, it must be
located or protected to avoid physical damage by vehicles.
The unit must be installed so that no electrical components
are exposed to water.
CAUTION
This unit must be installed level to allow for proper
drainage of the unit base pan and indoor drain pan.
Wall Sleeve and Louver Grille Installation
Refer to installation instructions included with the wall
sleeve kit and the louver grille kit along with Figure 2 for
guidance in assembling and installing the wall sleeve and
louver grille.
CAUTION
The sleeve is not intended as the sole support for
the unit. An additional support must be provided for
adequate support (see Figure 2).
Installing and Securing Unit to Wall Sleeve
1. Make sure the gaskets attached to the sleeve are not
damaged.
2. Verify divider panel is positioned properly. Figure 3
shows the correct position for 48” and 56” tall units
(ange pointing up). For 43” tall units, the divider panel
should be positioned so the ange points down.
3. Place the MHP unit into the wall sleeve. Lift leading
end of unit and walk unit onto the sleeve. Once in
the sleeve, lower the unit into position. This prevents
damage to the base pads. Assure that the unit is level
and completely seated against the gaskets on the wall
sleeve.
Page 4 of 15506325-01Issue 1734
Figure 3. Positioning Divider Panel
the bracket to the unit with that screw. Make sure to
fasten tight enough that the seal is maintained. Trim
off excess bracket if applicable.
5. Inspect the t up of the unit to the wall sleeve. Verify
that the gaskets of the wall sleeve make a complete
seal to the unit paying particular attention to top and
bottom corners of unit to sleeve seal. Caulk if needed.
Ductwork
Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors
of America (ACCA).
Check unit air supply outlet for debris before making
ductwork connections.
It is recommended that supply and return duct connections
at the unit be made with exible joints. If exible ducts are
used, a 6” sheet metal starter collar is required.
4. Use the two installation brackets to secure the unit to
the wall sleeve (see Figure 4). The units are shipped
with the brackets placed in the return air compartment.
Hook each bracket into the front edge of the wall sleeve
side. Position the bracket so it can be bent around the
front corner of the unit. Remove one of the two screws
in that position on the unit. Line up one of the holes in
the installation bracket with the screw hole and attach
Model
MHP4-09-12
MHP4-09-18
MHP4-09-24
MHP4-9-30
MHP4-9-36
MHP4-10-18
MHP-10-24
MHP4-10-30
Blower
Speed
Low450440425400370
Medium/Low700690680650600
Medium/High810800790770730
High940920875850810
Low620600580560535
Medium/Low 840820785750700
Medium/High975940870825760
High10751000930880800
Low750720680650620
Medium/Low1000980950920880
Medium/High1100108010501020980
High12701230120011701130
Low450440425400370
Medium/Low700690680650600
Medium/High810800790770730
High940920875850810
Low630620610580550
Medium/Low900890850800750
Medium/High107010301000920840
High1220115011001030920
0.10.20.30.40.5
The supply and return air duct systems should be designed
for the CFM and static requirements of the job (see Table
2). They should not be sized to match the dimensions of the duct connections on the unit. The return duct
should be sealed to the unit casing (including the casing
slots for aiding lter access) and terminate outside the
space containing the unit.
External Static Pressure (in. w.c. w/lter)
506325-01Issue 1734Page 5 of 15
Table 2. Blower Performance
Figure 4. Securing Unit
Installation
Brackets
Remove and replace screw to secure bracket
(one each side)
CAUTION
Do not screw into the side of the drain pan, or into the
indoor coil or heat strip.
Air Filter
All indoor return air must be ltered. A washable lter is
furnished with the unit, located in the return air opening.
If return duct is installed, provisions must be made to
accommodate lter servicing. If a lter is installed at a
separate central return location, then the factory furnished
lter must be removed from the unit.
Condensate Drain
Provisions must be made to properly drain the indoor and
outdoor drain pans of this appliance.
Indoor drain connection: 1/2” NPT to 3/4” PVC tting
(schedule 40). Outdoor drain connection: 3/4” NPT to 3/4”
PVC tting (schedule 40 minimum). Both drains must be
trapped as shown in Figure 5. The drain line should pitch
gradually downward at least 1” per 10’ of horizontal run to
open drain.
If local codes require the use of metal condensate lines, do
not thread metal ttings into the unit drain pan. A 1/2” x 3/4”
threaded plastic nipple is available from the manufacturer
as a kit (see the Accessories section). Thread the 1/2”
end of the nipple into the unit drain pan and make the eld
connection to the 3/4” end.
CAUTION
Use thread sealant on the threaded ttings. Install
threaded ttings by hand only. Do not over torque the
ttings.
Do not thread metal condensate ttings to unit drain
pan.
The lter should be cleaned at least three times during
each of the heating and cooling seasons, or more
frequently if unusual conditions are encountered. To clean
the washable lter, shake lter to remove excess dirt and/
or use a vacuum cleaner. Wash lter in soap or detergent
water and replace after lter is dry. It is not necessary to oil
the lter after washing.
If an installation is made in which it is more desirable to
mount the lter exterior to the unit, in the return duct work
or elsewhere, the washable lter can be used or replaced
with a disposable lter. If a disposable lter is used, use the
information provided in Table 3 when sizing the disposable
lter.
Model NumberFilter Area
MHP*12192 square inches
MHP*18288 square inches
MHP*24384 square inches
MHP*30-36480 square inches
* 9 and 10 EER Models
Table 3. Minimum Required Surface Area for
Disposable Filters
Figure 5. Condensate Drain Installation
Fresh Air Intake (Fresh Air Models Only)
On fresh air capable models (designated by the FA in the
model number – e.g. 7MHP4-10-301FP), up to 5% fresh
air is drawn into the unit from outside when the indoor
blower comes on.
To access the fresh air intake feature, the threaded cap
must be removed from the fresh air intake pipe (see Figure
6). The fresh air intake pipe is located at the rear of the unit
return air intake. When not in use, cap should be placed
nearby in the air intake area in case it is needed in the
future.
Page 6 of 15506325-01Issue 1734
WARNING
Fresh Air Intake Pipe
Threaded Cap
The location of fresh air capable models must conform to
the requirements of National Fire Protection Association
NFPA No. 54 in regards to proximity of forced air inlets
to ue gas terminals. Improper installation could result
in personal injury or death.
Figure 6. Fresh Air Intake Pipe and Cap
Thermostat
The room thermostat should be located on an inside
wall where it will not be subject to drafts, sun exposure,
or heat from electrical xtures or appliances. Follow
manufacturer’s instructions enclosed with the thermostat
for general installation procedures. Color-coded insulated
wires (#18 AWG) should be used to connect the thermostat
to the unit.
Electrical Connections
All wiring must be done in accordance with the National
Electrical Code (NEC), ANSI/NFPA No. 70 (latest edition);
Canadian Electrical Code CSA C22.2 Part 1 (latest edition);
or local codes, where they prevail. Any alteration of internal
wiring will void certication and warranty.
Units are factory wired for a 230 volt power supply. If power
supply is 208 volts, it will be necessary to change a wire
connection on unit transformer from 240 volt terminal to
208 volt terminal as shown on the wiring diagram.
Power supply to the unit must be NEC Class 1 and must
comply with all applicable codes. A fused disconnect switch
should be eld provided for the unit. The switch must be
separate from all other circuits. If any of the wire supplied
with the unit must be replaced, replacement wire must be
of the type shown on the wiring diagram. Electrical wiring
must be sized to minimum circuit ampacity marked on the
unit. Use copper conductors only. Each unit must be
wired with a separate branch circuit and be properly fused.
NOTE: Some MHP4 models require two separate power
supply circuits. See the unit wiring diagrams and rating
plates for specications.
Operation
Sequence of Operation
Upon initial “power up” to unit, there is a 3-minute time delay
to the compressor contactor (R to Y). Any 24V interrupt (R,
C) to the defrost control will initiate the 3-minute delay to
the contactor.
Cooling
When the thermostat is in the cooling mode, the O circuit
is powered which energizes the reversing valve. Upon
cooling demand, the thermostat closes circuit R to Y and
G. Closing R to Y closes the unit contactor, starting the
compressor and outdoor fan. The thermostat automatically
closes R to G circuit which also brings on the indoor
blower at the same time. Upon satisfying cooling demand,
the thermostat will open the above circuits and open the
main contactor, stopping the compressor and outdoor
fan. The unit is equipped with a time delay; the blower will
continue to operate for 90 seconds which improves system
efciency.
Heating
Upon heating demand, the thermostat closes circuit R to
Y, which closes the unit contactor, starting the compressor
and outdoor fan. The reversing valve is not energized in
the heating mode. The thermostat again automatically
brings on the indoor fan at the same time. The second
stage of the thermostat closes circuit R to W, which closes
the unit sequencers, bringing the auxiliary electric heat on.
Upon satisfying heating demand, the thermostat opens the
above circuits and stops unit operation.
Use wiring with a temperature limitation of 75°F minimum.
Run the 208 or 230 volt, 60 hertz electric power supply
through a fused disconnect switch to the control box of the
unit and connect as shown in the wiring diagram located
on the inside of the control access panel.
The unit must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the
National Electrical Code ANSI/NFPA No. 70 (latest edition)
or CSA C22.2 Part 1 (latest edition).
506325-01Issue 1734Page 7 of 15
NOTE: The 7.2 and 10 kW heats strips offer a W1 and
W2 thermostat connection. Taking advantage of the two
heat strip circuits requires a 3-stage thermostat (Y for heat
pump, W1 for electric heat stage 1, and W2 for electric
heat stage 2). If a 2-stage thermostat is used, “pigtail” W1
and W2 wires together when connecting the thermostat
wires at the unit.
Defrost Cycle
x
30
60
90
TEST
NORM
DLY
NOPS
If the outdoor ambient conditions are such that frost forms
on the outdoor coil, the defrost control monitors the need
for, initiates, and terminates defrost cycles as necessary to
maintain system performance. The defrost control is time/
temperature initiated and temperature terminated with
a maximum defrost time (time-out) of 10 minutes. Time
between defrost cycles is preset at 60-minute intervals at
the factory, but can be eld adjusted between 30, 60, or 90
minutes. To eld adjust time between defrost cycles, place
defrost time plug in the proper position (see Figure 8).
Figure 7. Defrost Control
The defrost control is also equipped with a set of pins to aid
in the troubleshooting of the defrost system (see Figure 8).
The following is a brief outline of the testing of the defrost
system.
1. Defrost sensor must be closed, 32°F or below. If
temperatures are such that the switch will not close,
jumper between defrost sensor terminals on the
defrost control.
2. Start system in heating operation.
3. Jumper test pins. A 1/4” quick connect terminal
crimped onto a solid wire or brazing rod works well for
a test jumper. Closing test pins speeds up time interval
by a factor of 256.
Defrost Control SettingDefrost Test Cycle Time
30 minutes7 seconds
60 minutes14 seconds
90 minutes 21 seconds
Table 4. Defrost Test Cycle Time
After closing test pins and appropriate cycle time has
elapsed, the reversing valve should shift to defrost mode
and the outdoor fan should stop. After 2 seconds of defrost
operation, the reversing valve should shift back to heating
operation and the outdoor fan should start.
Figure 8. Defrost Jumpers
Defrost control will initiate a defrost cycle if the time period
has elapsed and the defrost sensor sees a temperature
below freezing. At the start of a defrost cycle, the defrost
control will energize the reversing valve solenoid, shifting
the reversing valve and de-energizing the outdoor fan. The
defrost relay will also close, energizing auxiliary heat for
increased comfort during defrost. The unit will remain in
defrost until the defrost sensor has determined that the
frost has been removed from the coil or a 10-minute time
period has elapsed.
Quiet Defrost Feature
The defrost control in this appliance is equipped with a
quiet defrost feature. With the jumper pin set at the DLY
position, at the start of the defrost cycle, the defrost control
will energize the reversing valve solenoid and de-energized
the outdoor fan, and de-energize the compressor circuit a
period of 10 seconds. The result is a much quieter defrost
cycle.
All units have the jumper pin set at the NORM position.
PS1 and PS2 terminals: These appliances are not
equipped with a pressure switch in the refrigeration system.
Therefore, the jumper on the NOPS pin is factory installed
and required.
Page 8 of 15506325-01Issue 1734
System Performance
For maximum performance of this electric cooling system,
the operating temperatures and pressures should be
checked and superheat determined at Standard ARI test
conditions of 82°F outdoor – 80°F indoor dry bulb/67°F
wet bulb. If superheat measured deviates from the values
given in Table 5, refrigerant charge should be adjusted
accordingly for maximum performance.
Magic-Pak
Model
MHP4-09-1215-18
MHP4-09-189-11
MHP4-09-2417-19
MHP4-09-3011-13
MHP4-09-3623-25
MHP4-10-188-10
MHP4-10-2416-18
MHP4-10-3024-26
Suction Superheat @ ARI Conditions
82° OD 80° IDDB/67° IDWB
Table 5. Suction Superheat
Maintenance
WARNING
Disconnect all electrical power to the unit before
conducting any maintenance procedures. Failure to
disconnect the power could result in personal injury or
death.
Periodic inspection and maintenance normally consists of
changing or cleaning lters and (under some conditions)
cleaning the coils.
Filter
Inspect the lter once a month. Replace disposable lter or
clean the washable lter as necessary (a minimum of three
times each heating or cooling season is recommended).
Do not replace washable lter with a disposable lter
unless an installation was made in which the lter was
mounted exterior to the unit.
Motors
The indoor and outdoor fan motors are permanently
lubricated and require no maintenance.
Outdoor Coil
Foreign material should not be allowed to accumulate on
the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep the coil
clean. To clean the coil, remove the lower access panel
and blow out debris by using compressed air or water. Be
sure power to unit is shut off before using water to
clean the coil.
Care should be used when cleaning the coils so that
the coil ns are not damaged.
Outdoor Base Drain
Foreign material should not be allowed to clog the drain
hole. Inspect and clear drain opening prior to heating
season.
ASLEEVE10-410” Wall Sleeve for 45” LouverMHP4-10-30/ MHP4-09-36
ASLEEVE12-312” Wall Sleeve for 45” LouverMHP4-09-24 & 30/MHP4-10-18 & 24
ASLEEVE12-412” Wall Sleeve for 45” Louver MHP4-10-30/MHP4-09-36
AFILTMP-1Outdoor Coil Filter KitAll Models
AADAPTPVC412-1Threaded PVC NippleAll Models
* Thru-the-wall installations only
Table 6. Accessories
Page 10 of 15506325-01Issue 1734
Wall Sleeve Dimensions (in.)
Kit No.ABCD
ASLEEVE2-122929-1/8
ASLEEVE2-2232-3/432-7/8
ASLEEVE6-162929-1/8
ASLEEVE6-2632-3/432-7/8
ASLEEVE6-364545-1/8
ASLEEVE6-464545-1/8
ASLEEVE8-182929-1/8
ASLEEVE8-2832-3/432-7/8
ASLEEVE8-384545-1/8
ASLEEVE8-484545-1/8
ASLEEVE810-1102929-1/8
ASLEEVE10-21032-3/432-7/8
ASLEEVE10-3104545-1/8
ASLEEVE10-4104545-1/8
ASLEEVE12-1122929-1/8
ASLEEVE12-21232-3/432-7/8
ASLEEVE12-3124545-1/8
ASLEEVE12-4124545-1/8
ASLEEVE-3*4545-1/8
* Thru-the-wall installations only
29-1/8
Table 7. Wall Sleeve Dimensions
16
A
1
1/2
Range of
Wall Thickness
C
B
5/8
29
NOTE: Bottom surface of wall opening must be at least 4” off the oor.
16
Figure 9. Wall Sleeve Dimensions
Required Wall Opening
D
The unit must be installed with approved wall sleeve
and grille accessories for safe operation. Improper
installations could result in property damage, personal
injury, or death.
506325-01Issue 1734Page 11 of 15
WARNING
NOTE:
Wiring Diagrams
LINE VOLTAGE FIELD
ALL THE WAY TO
COMPRESSOR L1 & L2
208/230-1-60
POWER SUPPLY WITH MIN.
COPPER WIRE
75
CIRCUIT 1
CAPACITOR-RUN
FAN
COM HERM
VIOLET
BROWN
BROWN
CAPACITOR
BLOWER
MH
ML
BLOWER
MOTOR
VIOLET
BROWN
C
H
L
CIRCUIT 2
L2
YELLOW
RED
ORANGE
SEE
CHART
FOR WIRING
10 KW
L1
BLACK
RED
CONDENSER FAN
BLACK
BLUE
RED
BLACK
LINE VOLTAGE-FACTORY
LINE VOLTAGE-FIELD
LOW VOLTAGE-FACTORY
LOW VOLTAGE-FIELD
BLUE
EL. HEAT MOTOR SPEED TAP SEE CHART
BLACK
1
2
LIMIT
BLACK
3
RED
4
5
6
C
C
SEQ
BLACK
4
5
RED
BLACK
RED
BLUE
X-FRmR
X-FRmC
C
NO
NC
BLOWER CONTROL
LIMIT
CONTACTOR
T1
T2
R
FUSE
COM
1
3
BLUE
C
C
SEQ
C
S
COMP
R
G
HTR
HTR
IF ANY OF THE ORIGINAL
WIRES ARE REPLACED THE
SAME SIZE AND TYPE WIRE
MUST BE USED.
WHITE
GREY
L1
L2
RED
TRANSFORMER
BLUE
RED
BLACK
COM
CONNECTOR
BLOCK
208 V
240 V
GRAY
BLACK
CIRCUITS ENERGIZED
OPERATING MODE CIRCUIT
ELECTRIC HEAT
HEAT PUMP
COOLING
FAN R-G
YELLOW
RED
BLUE
BLUE
R
W
GREEN
C
Y
G
ORANGE
WHITE
THERMOSTAT
C
R
W
Y
G
OO
R-W
R-G-Y
R-G-Y-O
BLOWER MOTOR SPEEDS
MODELS
10MHP4-(9,10)*181P-1
10MHP4-(9,10)*241P-1
7MHP4-(9-10)*301P-1
10MHP4-(9,10)*301P-1
7MHP4-09-361P-1
10MHP4-09-361P-1
HEATER ANTICIPATOR SETTING:
10MHP4 - 0.4
COOLING/
HEATING
MED/LOW
MED/LOW
MED/HIGH
MED/LOW
HIGH
HIGH
ELECTRIC
HEAT
MED/HIGH
MED/HIGH
MED/LOW
MED/HIGH
MED/LOW
MED/HIGH
COOLING MOTOR
SPEED TAP
SEE CHART
LIGHT BLUE
PS2
PS1
BLACK
BLACK
DEFROST CONTROL
Figure 10. Connection Diagram
#537246-01
DF1
DF2
PINK
C
C
RVG
CNT
RV
RED
BLACK
BLACK
REVERSING
VALVE
O
Y
W
R
DFS2
DFS1
BLACK
BLACK
DEFROST
THERMOSTAT
Page 12 of 15506325-01Issue 1734
L1 TERMINAL
BLOCK
REPLACEMENT
FUSE SPEC:
ATC-3 BLADE TYPE
32 VOLT 3 AMP
L1
CONTACTOR
CIRCUIT 2
SEQ
4
3
SEQ
5
4
CIRCUIT 1
208/230V-1 -60HZ
R
T1
COMPRESSOR
C
S
208/230V-1
-60HZ
LIMIT
LIMIT
HTR
HTR
CAPACITOR
H
DUAL
3
6
SEQ
SEQ
C
5
1
T2L2
L2 TERMINAL
BLOCK
GROUND
SCREW
DEFROST RELAY
DF
COM
DEFROST CONTROL
DF
NO
NC
SEQ
FUSE
RX
XFMR
CX
C
BLOWER CONTROL
C
RVG
PS2
CC
PS1
RV
COOLING
HEATING
R
G
C
O
Y
W
F
FAN
MOTOR
HIGH
MED/HIGH
MED/LOW
240
24 V.
LOW
COM208
REVERSING
VALVE COIL
BLOWER
MOTOR
TRANSFORMER
{10 MHP)
C
SEQ HEATER
CONTACTOR
COIL
BLOWER CAP.
W
W
O
Y
W
2
1
R
G
C
506325-01Issue 1734Page 13 of 15
R
DFS
DFS
Figure 11. Schematic
#537246-01
DEFROST SENSOR
HEATER ANTICIPATOR SETTING:
3MHP4 - 0.2
5MHP4- 0.4
7MHP4 - 0.4
MODELS
3MHP4-9-121P-1
5MHP4-9-121P-1
7MHP4-9-121P-1
3MHP4(9,10)*181P-1
5MHP4(9,10)*181P-1
7MHP4(9,10)*181P-1
5MHP4(9,10)*241P-1
7MHP4(9,10)*241P-1
5MHP4(9,10)*301P-1
5MHP4-9-361P-1
208/230-1-60
POWER SUPPLY WITH MIN.
COPPER WIRE
75
L2
CAPACITOR-RUN
FAN
COM HERM
BROWN
BROWN
CAPACITOR
BLOWER
BLOWER MOTOR
SPEEDS
COOLING
LOW
LOW
LOW
MED/LOW
MED/LOW
MED/LOW
MED/HIGH
MED/HIGH
MED/HIGH
HIGH
L1
VIOLET
MH
ML
BLOWER
MOTOR
EL. HEAT
MED/LOW
MED/LOW
MED/LOW
MED/HIGH
MED/LOW
MED/LOW
MED/LOW
MED/LOW
VIOLET
BROWN
C
H
L
LOW
LOW
BLACK
RED
BLACK
RED
CONDENSER FAN
YELLOW
RED
BLACK
ORANGE
SEE
CHART
FOR WIRING
LINE VOLTAGE-FACTORY
LINE VOLTAGE-FIELD
LOW VOLTAGE-FACTORY
LOW VOLTAGE-FIELD
1
3
5
C
SEQ
BLUE
4
1
C
SEQ
BLACK
RED
C
S
COMP
R
BLUE
RED
COOLING SPEED TAP
SEE CHART
REPLACEMENT FUSE SPEC:
ATC-3 BLADE TYPE
BLUE
EL. HEAT MOTOR SPEED TAP SEE CHART
BLACK
2
LIMIT
BLACK
4
RED
6
C
7 MHP ONLY
BLACK
5
3
C
G
BLACK
RED
BLUE
X-FRmR
X-FRmC
R
C
FUSE
NO
COM
NC
BLOWER CONTROL
BLACK
BLACK
32 VOLT 3 AMP
LIMIT
T1
T2
RED
CONTACTOR
HTR
HTR
NOTE:
IF ANY OF THE ORIGINAL
WIRES ARE REPLACED THE
SAME SIZE AND TYPE WIRE
MUST BE USED.
WHITE
GREY
L1
L2
RED
TRANSFORMER
BLUE
RED
LIGHT BLUE
BLACK
PS2
PS1
DF1
DF2
DEFROST CONTROL
CONNECTOR
BLOCK
COM
PINK
C
DFS2
DFS1
RVG
CNT
208 V
CIRCUITS ENERGIZED
OPERATING MODE CIRCUIT
ELECTRIC HEAT
HEAT PUMP
COOLING
FAN R-G
THERMOSTAT
C
R
W
Y
G
YELLOW
ORANGE
GREEN
WHITE
RED
BLUE
GRAY
BLACK
240 V
C
RV
BLUE
RED
BLACK
BLACK
REVERSING
VALVE
C
R
W
Y
G
OO
R-W
R-G-Y
R-G-Y-O
O
Y
W
R
BLACK
BLACK
DEFROST
THERMOSTAT
Figure 12. Connection Diagram
Page 14 of 15506325-01Issue 1734
#537245-01
L1 TERMINAL
BLOCK
208/230V-1
SEQ
3
4
-60HZ
LIMIT
HTR
SEQ
6
5
L2 TERMINAL
BLOCK
GROUND
SCREW
L1
CONTACTOR
COM
T1
DEFROST RELAY
DF
NO
NC
7 MHP ONLY
DF
COOLING
SEQ
HEATING
FUSE
RX
XFMR
CX
C
BLOWER CONTROL
SEQ
5
4
R
COMPRESSOR
C
S
HIGH
MED/HIGH
MED/LOW
LOW
240
208
R
G
24 V.
COM
BLOWER
MOTOR
C
TRANSFORMER
SEQ HEATER
LIMIT
FAN MOTOR
HTR
H
F
BLOWER CAP.
(7 MHP)
(3 & 5 MHP)
DUAL
CAPACITOR
SEQ
1
3
T2L2
C
W
2
W
1
R
G
DEFROST CONTROL
PS2
PS1
C
C
RVG
CC
RV
O
Y
W
R
DFS
DFS
REVERSING
VALVE COIL
CONTACTOR
COIL
C
O
Y
W
Figure 13. Schematic
#537245-01
506325-01Issue 1734Page 15 of 15
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.