Magic-Pro MHP4-09-12, MHP4-09-18, MHP4-09-24, MHP4-10-18, MHP4-9-30 Installation And Maintenance Instructions Manual

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MHP4 Series
Self-Contained Heat Pump
Save these instructions for future reference
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information,
consult a qualied installer or service agency.
Table of Contents
Installation ...................................................................2
Operation .....................................................................7
Maintenance ................................................................9
Accessories ...............................................................10
Wiring Diagrams ........................................................12
WARNING
For your safety, do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any
other appliance. Such actions could result in property damage, personal injury, or death.
WARNING
Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical components. Only trained and
qualied service personnel should install or service
this equipment. Installation and service performed by
unqualied persons can result in property damage,
personal injury, or death.
The unit must be installed with approved wall sleeve and grille accessories for safe operation. Improper installations could result in property damage, personal injury, or death.
A Lennox International Inc. Company
*P506325-01*
WARNING
Manufactured By
Allied Air Enterprises LLC
West Columbia, SC 29170
(P) 506325-01
CAUTION
The installation of this appliance must conform to the requirements of the National Fire Protection Association; the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
506325-01 Issue 1734 Page 1 of 15
Installation
WARNING
Outdoor Ambient Air Temperature °F
Minimum D B Maximum D B
Cool Cool Heat
65 115 75
These units are not approved for mobile home applications. Such use could result in property damage, personal injury, or death.
General
These instructions explain the recommended method of installation of the MHP4 electric cooling unit and associated electrical wiring.
This unit is designed and approved for use as a self­contained air-to-air air conditioning system.
These instructions, and any instructions packaged with mating components and/or accessories, should be carefully read prior to beginning installation. Note particularly any CAUTIONS or WARNINGS in these instructions and all labels on the units.
These instructions are intended as a general guide only,
for use by qualied personnel and do not supersede any
national or local codes in any way. Compliance with all local, state, provincial, or national codes pertaining to this type of equipment should be determined prior to installation.
Units that comply with the maximum cabinet leakage 2% of
rated airow requirements of ANSI/ASHRAE 193 (complies with IECC 2015) are identied on the rating plate.
Indoor Ambient Air Temperature °F
Minimum Maximum
DB/WB DB DB/WB DB
Cool Heat Cool Heat
62/57 50 90/72 80
DB = Dry Bulb
WB = Wet Bulb
Table 1. Application Limitations
Limitations
The unit should be installed in accordance with all national and local safety codes.
Limitations of the unit and appropriate accessories must also be observed.
The outdoor fan is designed to operate against no more than .10” w.c. static pressure.
Minimum and maximum operation conditions must be observed to assure maximum system performance with minimum service required. Refer to Table 1 for the application limitations of the unit.
Location
Inspection
Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier’s freight bill. Take special care to examine the unit inside the carton if the carton is damaged. File a claim with the transportation company. If any damages
are discovered and reported to the carrier do not install the unit, as claim may be denied.
Check the unit rating plate to conrm specications
are as ordered.
WARNING
The unit must be installed with approved wall sleeve and grille accessories for safe operation. Improper installations could result in property damage, personal injury, or death.
For information on wall sleeves and grille accessories, see the Accessories section.
The design is certied for thru-the-wall or up-to-the wall
(inside wall) installation only. The interior portions of the unit may be surrounded by a closet with clearances to combustible material held to 0” at the sides, top, and front of the plenum. All servicing and cleaning of the unit can be performed from the front. If installed in a closet or utility room, provide 25” clearance in front for service if the door to the room is not in line with the front of the unit (see Figure 1). Accessibility clearances must take
precedence over re protection clearances.
Page 2 of 15 506325-01Issue 1734
Plenum
Exterior Wall
Wall Sleeve
(one each side)
Interior Wall
Clearances*
Mounting Strap (one each side)
3/4" Plywood Riser
Floor
Platform (field supplied)-Must be level with sill plate of hole in exterior wall
Front of Unit
Sill Plate
4" Min.
Clearance to combustible materials is 0” at the side, top, and front of plenum. If accessibility clearances are greater than clearances to combustibles, accessibility clearances take precedence.
The front of the unit must be accessible for service. If the unit is enclosed, providing a door or access panel opposite the front of the unit is the preferred method of providing access. The door or access panel must be at least 30” wide (centered on the unit) and as tall as the unit. If a return duct is not installed, in order to provide adequate return air the minimum clearance required between the front of the unit and the door or access panel is 4” for 43” tall cabinets and 5” for 48” and 56” tall cabinets.
Top View
Side View
* With no return duct installed, minimum clearances to the front of the unit are 4” for 43” tall cabinets and 5” for 48” and 56” cabinets. If a return duct is installed, enough clearance must be provided for the drain trap installation.
506325-01 Issue 1734 Page 3 of 15
Unit must be supported by platform.
The unit must be installed with approved wall sleeve and grille accessories for safe operation. Improper installations could result in property damage, personal injury, or death.
Figure 1. Minimum Clearances
IMPORTANT
NOTE: Platform must be constructed so that it is level with sill plate of wall opening.
Figure 2. Wall Sleeve and Louver Kit Installed
The outside of the unit may be ush with the face of
the exterior wall, and it should not be obstructed with trees, landscape materials, or building structure. Unit can be installed recessed with appropriate wall sleeve accessories. There is no minimum clearance required on locating the unit to an interior corner of a building.
If the unit is installed in a residential garage, it must be located or protected to avoid physical damage by vehicles. The unit must be installed so that no electrical components are exposed to water.
CAUTION
This unit must be installed level to allow for proper drainage of the unit base pan and indoor drain pan.
Wall Sleeve and Louver Grille Installation
Refer to installation instructions included with the wall sleeve kit and the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louver grille.
CAUTION
The sleeve is not intended as the sole support for the unit. An additional support must be provided for adequate support (see Figure 2).
Installing and Securing Unit to Wall Sleeve
1. Make sure the gaskets attached to the sleeve are not damaged.
2. Verify divider panel is positioned properly. Figure 3 shows the correct position for 48” and 56” tall units
(ange pointing up). For 43” tall units, the divider panel should be positioned so the ange points down.
3. Place the MHP unit into the wall sleeve. Lift leading end of unit and walk unit onto the sleeve. Once in
the sleeve, lower the unit into position. This prevents damage to the base pads. Assure that the unit is level and completely seated against the gaskets on the wall sleeve.
Page 4 of 15 506325-01Issue 1734
Figure 3. Positioning Divider Panel
the bracket to the unit with that screw. Make sure to fasten tight enough that the seal is maintained. Trim off excess bracket if applicable.
5. Inspect the t up of the unit to the wall sleeve. Verify that the gaskets of the wall sleeve make a complete seal to the unit paying particular attention to top and bottom corners of unit to sleeve seal. Caulk if needed.
Ductwork
Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA).
Check unit air supply outlet for debris before making ductwork connections.
It is recommended that supply and return duct connections
at the unit be made with exible joints. If exible ducts are
used, a 6” sheet metal starter collar is required.
4. Use the two installation brackets to secure the unit to the wall sleeve (see Figure 4). The units are shipped with the brackets placed in the return air compartment. Hook each bracket into the front edge of the wall sleeve side. Position the bracket so it can be bent around the front corner of the unit. Remove one of the two screws in that position on the unit. Line up one of the holes in the installation bracket with the screw hole and attach
Model
MHP4-09-12 MHP4-09-18 MHP4-09-24
MHP4-9-30
MHP4-9-36
MHP4-10-18
MHP-10-24
MHP4-10-30
Blower
Speed
Low 450 440 425 400 370
Medium/Low 700 690 680 650 600
Medium/High 810 800 790 770 730
High 940 920 875 850 810
Low 620 600 580 560 535
Medium/Low 840 820 785 750 700
Medium/High 975 940 870 825 760
High 1075 1000 930 880 800
Low 750 720 680 650 620
Medium/Low 1000 980 950 920 880
Medium/High 1100 1080 1050 1020 980
High 1270 1230 1200 1170 1130
Low 450 440 425 400 370
Medium/Low 700 690 680 650 600
Medium/High 810 800 790 770 730
High 940 920 875 850 810
Low 630 620 610 580 550
Medium/Low 900 890 850 800 750
Medium/High 1070 1030 1000 920 840
High 1220 1150 1100 1030 920
0.1 0.2 0.3 0.4 0.5
The supply and return air duct systems should be designed for the CFM and static requirements of the job (see Table
2). They should not be sized to match the dimensions of the duct connections on the unit. The return duct should be sealed to the unit casing (including the casing
slots for aiding lter access) and terminate outside the
space containing the unit.
External Static Pressure (in. w.c. w/lter)
506325-01 Issue 1734 Page 5 of 15
Table 2. Blower Performance
Figure 4. Securing Unit
Installation
Brackets
Remove and replace screw to secure bracket
(one each side)
CAUTION
Do not screw into the side of the drain pan, or into the indoor coil or heat strip.
Air Filter
All indoor return air must be ltered. A washable lter is
furnished with the unit, located in the return air opening. If return duct is installed, provisions must be made to
accommodate lter servicing. If a lter is installed at a
separate central return location, then the factory furnished
lter must be removed from the unit.
Condensate Drain
Provisions must be made to properly drain the indoor and outdoor drain pans of this appliance.
Indoor drain connection: 1/2” NPT to 3/4” PVC tting
(schedule 40). Outdoor drain connection: 3/4” NPT to 3/4”
PVC tting (schedule 40 minimum). Both drains must be
trapped as shown in Figure 5. The drain line should pitch gradually downward at least 1” per 10’ of horizontal run to open drain.
If local codes require the use of metal condensate lines, do
not thread metal ttings into the unit drain pan. A 1/2” x 3/4”
threaded plastic nipple is available from the manufacturer as a kit (see the Accessories section). Thread the 1/2”
end of the nipple into the unit drain pan and make the eld
connection to the 3/4” end.
CAUTION
Use thread sealant on the threaded ttings. Install threaded ttings by hand only. Do not over torque the
ttings.
Do not thread metal condensate ttings to unit drain
pan.
The lter should be cleaned at least three times during
each of the heating and cooling seasons, or more frequently if unusual conditions are encountered. To clean
the washable lter, shake lter to remove excess dirt and/ or use a vacuum cleaner. Wash lter in soap or detergent water and replace after lter is dry. It is not necessary to oil the lter after washing.
If an installation is made in which it is more desirable to
mount the lter exterior to the unit, in the return duct work or elsewhere, the washable lter can be used or replaced with a disposable lter. If a disposable lter is used, use the
information provided in Table 3 when sizing the disposable
lter.
Model Number Filter Area
MHP*12 192 square inches
MHP*18 288 square inches
MHP*24 384 square inches
MHP*30-36 480 square inches
* 9 and 10 EER Models
Table 3. Minimum Required Surface Area for
Disposable Filters
Figure 5. Condensate Drain Installation
Fresh Air Intake (Fresh Air Models Only)
On fresh air capable models (designated by the FA in the model number – e.g. 7MHP4-10-301FP), up to 5% fresh air is drawn into the unit from outside when the indoor blower comes on.
To access the fresh air intake feature, the threaded cap must be removed from the fresh air intake pipe (see Figure
6). The fresh air intake pipe is located at the rear of the unit return air intake. When not in use, cap should be placed nearby in the air intake area in case it is needed in the future.
Page 6 of 15 506325-01Issue 1734
WARNING
Fresh Air Intake Pipe
Threaded Cap
The location of fresh air capable models must conform to the requirements of National Fire Protection Association NFPA No. 54 in regards to proximity of forced air inlets
to ue gas terminals. Improper installation could result
in personal injury or death.
Figure 6. Fresh Air Intake Pipe and Cap
Thermostat
The room thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure,
or heat from electrical xtures or appliances. Follow
manufacturer’s instructions enclosed with the thermostat for general installation procedures. Color-coded insulated wires (#18 AWG) should be used to connect the thermostat to the unit.
Electrical Connections
All wiring must be done in accordance with the National Electrical Code (NEC), ANSI/NFPA No. 70 (latest edition); Canadian Electrical Code CSA C22.2 Part 1 (latest edition); or local codes, where they prevail. Any alteration of internal
wiring will void certication and warranty.
Units are factory wired for a 230 volt power supply. If power supply is 208 volts, it will be necessary to change a wire connection on unit transformer from 240 volt terminal to 208 volt terminal as shown on the wiring diagram.
Power supply to the unit must be NEC Class 1 and must comply with all applicable codes. A fused disconnect switch
should be eld provided for the unit. The switch must be
separate from all other circuits. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram. Electrical wiring must be sized to minimum circuit ampacity marked on the unit. Use copper conductors only. Each unit must be wired with a separate branch circuit and be properly fused.
NOTE: Some MHP4 models require two separate power supply circuits. See the unit wiring diagrams and rating
plates for specications.
Operation
Sequence of Operation
Upon initial “power up” to unit, there is a 3-minute time delay to the compressor contactor (R to Y). Any 24V interrupt (R, C) to the defrost control will initiate the 3-minute delay to the contactor.
Cooling
When the thermostat is in the cooling mode, the O circuit is powered which energizes the reversing valve. Upon cooling demand, the thermostat closes circuit R to Y and G. Closing R to Y closes the unit contactor, starting the compressor and outdoor fan. The thermostat automatically closes R to G circuit which also brings on the indoor blower at the same time. Upon satisfying cooling demand, the thermostat will open the above circuits and open the main contactor, stopping the compressor and outdoor fan. The unit is equipped with a time delay; the blower will continue to operate for 90 seconds which improves system
efciency.
Heating
Upon heating demand, the thermostat closes circuit R to Y, which closes the unit contactor, starting the compressor and outdoor fan. The reversing valve is not energized in the heating mode. The thermostat again automatically brings on the indoor fan at the same time. The second stage of the thermostat closes circuit R to W, which closes the unit sequencers, bringing the auxiliary electric heat on. Upon satisfying heating demand, the thermostat opens the above circuits and stops unit operation.
Use wiring with a temperature limitation of 75°F minimum. Run the 208 or 230 volt, 60 hertz electric power supply through a fused disconnect switch to the control box of the unit and connect as shown in the wiring diagram located on the inside of the control access panel.
The unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA No. 70 (latest edition) or CSA C22.2 Part 1 (latest edition).
506325-01 Issue 1734 Page 7 of 15
NOTE: The 7.2 and 10 kW heats strips offer a W1 and W2 thermostat connection. Taking advantage of the two heat strip circuits requires a 3-stage thermostat (Y for heat pump, W1 for electric heat stage 1, and W2 for electric heat stage 2). If a 2-stage thermostat is used, “pigtail” W1 and W2 wires together when connecting the thermostat wires at the unit.
Defrost Cycle
x
30 60 90
TEST
NORM
DLY
NOPS
If the outdoor ambient conditions are such that frost forms on the outdoor coil, the defrost control monitors the need for, initiates, and terminates defrost cycles as necessary to maintain system performance. The defrost control is time/ temperature initiated and temperature terminated with a maximum defrost time (time-out) of 10 minutes. Time between defrost cycles is preset at 60-minute intervals at
the factory, but can be eld adjusted between 30, 60, or 90 minutes. To eld adjust time between defrost cycles, place
defrost time plug in the proper position (see Figure 8).
Figure 7. Defrost Control
The defrost control is also equipped with a set of pins to aid in the troubleshooting of the defrost system (see Figure 8). The following is a brief outline of the testing of the defrost system.
1. Defrost sensor must be closed, 32°F or below. If temperatures are such that the switch will not close, jumper between defrost sensor terminals on the defrost control.
2. Start system in heating operation.
3. Jumper test pins. A 1/4” quick connect terminal crimped onto a solid wire or brazing rod works well for a test jumper. Closing test pins speeds up time interval by a factor of 256.
Defrost Control Setting Defrost Test Cycle Time
30 minutes 7 seconds
60 minutes 14 seconds
90 minutes 21 seconds
Table 4. Defrost Test Cycle Time
After closing test pins and appropriate cycle time has elapsed, the reversing valve should shift to defrost mode and the outdoor fan should stop. After 2 seconds of defrost operation, the reversing valve should shift back to heating operation and the outdoor fan should start.
Figure 8. Defrost Jumpers
Defrost control will initiate a defrost cycle if the time period has elapsed and the defrost sensor sees a temperature below freezing. At the start of a defrost cycle, the defrost control will energize the reversing valve solenoid, shifting the reversing valve and de-energizing the outdoor fan. The defrost relay will also close, energizing auxiliary heat for increased comfort during defrost. The unit will remain in defrost until the defrost sensor has determined that the frost has been removed from the coil or a 10-minute time period has elapsed.
Quiet Defrost Feature
The defrost control in this appliance is equipped with a quiet defrost feature. With the jumper pin set at the DLY position, at the start of the defrost cycle, the defrost control will energize the reversing valve solenoid and de-energized the outdoor fan, and de-energize the compressor circuit a period of 10 seconds. The result is a much quieter defrost cycle.
All units have the jumper pin set at the NORM position. PS1 and PS2 terminals: These appliances are not equipped with a pressure switch in the refrigeration system. Therefore, the jumper on the NOPS pin is factory installed and required.
Page 8 of 15 506325-01Issue 1734
System Performance
For maximum performance of this electric cooling system, the operating temperatures and pressures should be checked and superheat determined at Standard ARI test conditions of 82°F outdoor – 80°F indoor dry bulb/67°F wet bulb. If superheat measured deviates from the values given in Table 5, refrigerant charge should be adjusted accordingly for maximum performance.
Magic-Pak
Model
MHP4-09-12 15-18
MHP4-09-18 9-11
MHP4-09-24 17-19
MHP4-09-30 11-13
MHP4-09-36 23-25
MHP4-10-18 8-10
MHP4-10-24 16-18
MHP4-10-30 24-26
Suction Superheat @ ARI Conditions
82° OD 80° IDDB/67° IDWB
Table 5. Suction Superheat
Maintenance
WARNING
Disconnect all electrical power to the unit before conducting any maintenance procedures. Failure to disconnect the power could result in personal injury or death.
Periodic inspection and maintenance normally consists of
changing or cleaning lters and (under some conditions)
cleaning the coils.
Filter
Inspect the lter once a month. Replace disposable lter or clean the washable lter as necessary (a minimum of three
times each heating or cooling season is recommended).
Do not replace washable lter with a disposable lter unless an installation was made in which the lter was
mounted exterior to the unit.
Motors
The indoor and outdoor fan motors are permanently lubricated and require no maintenance.
Outdoor Coil
Foreign material should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep the coil clean. To clean the coil, remove the lower access panel and blow out debris by using compressed air or water. Be
sure power to unit is shut off before using water to clean the coil.
Care should be used when cleaning the coils so that
the coil ns are not damaged.
Outdoor Base Drain
Foreign material should not be allowed to clog the drain hole. Inspect and clear drain opening prior to heating season.
506325-01 Issue 1734 Page 9 of 15
Accessories
Kit No. Description Used With
LVRPWHT-1 Polypropylene Louver Kit (White) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ALVRPWHT-2 Polypropylene Louver Kit (White) MHP4-10-30/MHP4-09-36
ALVRPSAN-1 Polypropylene Louver Kit (Sandstone) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ALVRPSAN-2 Polypropylene Louver Kit (Sandstone) MHP4-10-30/MHP4-09-36
ALVRPBGE-1 Polypropylene Louver Kit (Beige) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ALVRPBGE-2 Polypropylene Louver Kit (Beige) MHP4-10-30/MHP4-09-36
ALVRPTPST-1 Polypropylene Louver Kit (Toupestone) MHP4-09-12, 18, 24 & 30/MHP4-10-18 & 24
ALVRPTPST-2 Polypropylene Louver Kit (Toupestone) MHP4-10-30/MHP4-09-36
ALVRAL-1 Extruded Aluminum Louver Kit MHP4-09-12, 18, 24 & 30/MHP4-10-18 & 24
ALVRAL-2 Extruded Aluminum Louver Kit MHP4-10-30/MHP4-09-36
ALVRAL-3 Extruded Aluminum Louver Kit (45” Height) MHP4-09-12, 18, 24 & 30/MHP4-10-18 & 24
ALVRAL-4 Extruded Aluminum Louver Kit (45” Height) MHP4-10-30/MHP4-09-36
ALVRAL-5 Extruded Aluminum Louver Kit (50” Height) MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ALVRAL-6 Extruded Aluminum Louver Kit (50” Height) MHP4-10-30/MHP4-09-36
ASLEEVE-3² Wall Sleeve Kit (45” Louver) MHP4-09-12 & 18
ASLEEVE2-1 2” Wall Sleeve Kit MHP4-09-12, 18, 24, & 30MHP4-10-18 & 24
ASLEEVE2-2 2” Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE6-1 6” Wall Sleeve Kit MHP4-09-12, 18, 24 & 30/MHP4-10-18 & 24
ASLEEVE6-2 6” Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE8-1 8” Wall Sleeve Kit MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ASLEEVE8-2 8” Wall Sleeve Kit MHP4-10-30/MHP-09-36
ASLEEVE10-1 10”Wall Sleeve Kit MHP4-09-12, 18, 24, & 30/MHP4-10-18 & 24
ASLEEVE10-2 10”Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE12-1 12” Wall Sleeve Kit MHP4-09-12, 18, 24 & 30/MHP4-10-18 & 24
ASLEEVE12-2 12” Wall Sleeve Kit MHP4-10-30/MHP4-09-36
ASLEEVE6-3 6” Wall Sleeve for 45” Louver MHP4-09-24 & 30/MHP4-10-18 & 24
ASLEEVE6-4 6” Wall Sleeve for 45” Louver MHP4-10-30/MHP4-09-36
ASLEEVE8-3 8” Wall Sleeve for 45” Louver MHP4-09-24 & 30/MHP4-10-18 & 24
ASLEEVE8-4 8” Wall Sleeve for 45” Louver MHP4-10-30/MHP4-09-36
ASLEEVE10-3 10” Wall Sleeve for 45” Louver MHP4-09-24 & 30/ MHP4-10-18 & 24
ASLEEVE10-4 10” Wall Sleeve for 45” Louver MHP4-10-30/ MHP4-09-36
ASLEEVE12-3 12” Wall Sleeve for 45” Louver MHP4-09-24 & 30/MHP4-10-18 & 24
ASLEEVE12-4 12” Wall Sleeve for 45” Louver MHP4-10-30/MHP4-09-36
AFILTMP-1 Outdoor Coil Filter Kit All Models
AADAPTPVC412-1 Threaded PVC Nipple All Models
* Thru-the-wall installations only
Table 6. Accessories
Page 10 of 15 506325-01Issue 1734
Wall Sleeve Dimensions (in.)
Kit No. A B C D
ASLEEVE2-1 2 29 29-1/8
ASLEEVE2-2 2 32-3/4 32-7/8
ASLEEVE6-1 6 29 29-1/8
ASLEEVE6-2 6 32-3/4 32-7/8
ASLEEVE6-3 6 45 45-1/8
ASLEEVE6-4 6 45 45-1/8
ASLEEVE8-1 8 29 29-1/8
ASLEEVE8-2 8 32-3/4 32-7/8
ASLEEVE8-3 8 45 45-1/8
ASLEEVE8-4 8 45 45-1/8
ASLEEVE810-1 10 29 29-1/8
ASLEEVE10-2 10 32-3/4 32-7/8
ASLEEVE10-3 10 45 45-1/8
ASLEEVE10-4 10 45 45-1/8
ASLEEVE12-1 12 29 29-1/8
ASLEEVE12-2 12 32-3/4 32-7/8
ASLEEVE12-3 12 45 45-1/8
ASLEEVE12-4 12 45 45-1/8
ASLEEVE-3 * 45 45-1/8
* Thru-the-wall installations only
29-1/8
Table 7. Wall Sleeve Dimensions
16
A
1
1/2
Range of
Wall Thickness
C
B
5/8
29
NOTE: Bottom surface of wall opening must be at least 4” off the oor.
16
Figure 9. Wall Sleeve Dimensions
Required Wall Opening
D
The unit must be installed with approved wall sleeve and grille accessories for safe operation. Improper installations could result in property damage, personal injury, or death.
506325-01 Issue 1734 Page 11 of 15
WARNING
NOTE:
Wiring Diagrams
LINE VOLTAGE FIELD
ALL THE WAY TO
COMPRESSOR L1 & L2
208/230-1-60
POWER SUPPLY WITH MIN.
COPPER WIRE
75
CIRCUIT 1
CAPACITOR-RUN
FAN
COM HERM
VIOLET
BROWN
BROWN
CAPACITOR
BLOWER
MH
ML
BLOWER
MOTOR
VIOLET
BROWN
C H
L
CIRCUIT 2
L2
YELLOW
RED
ORANGE
SEE CHART FOR WIRING
10 KW
L1
BLACK
RED
CONDENSER FAN
BLACK
BLUE
RED
BLACK
LINE VOLTAGE-FACTORY LINE VOLTAGE-FIELD LOW VOLTAGE-FACTORY LOW VOLTAGE-FIELD
BLUE
EL. HEAT MOTOR SPEED TAP SEE CHART
BLACK
1
2
LIMIT
BLACK
3
RED
4
5
6
C
C
SEQ
BLACK
4
5
RED
BLACK
RED
BLUE
X-FRmR
X-FRmC
C
NO
NC
BLOWER CONTROL
LIMIT
CONTACTOR
T1
T2
R
FUSE
COM
1
3
BLUE
C
C
SEQ
C
S
COMP
R
G
HTR
HTR
IF ANY OF THE ORIGINAL WIRES ARE REPLACED THE SAME SIZE AND TYPE WIRE MUST BE USED.
WHITE
GREY
L1
L2
RED
TRANSFORMER
BLUE
RED
BLACK
COM
CONNECTOR BLOCK
208 V
240 V
GRAY
BLACK
CIRCUITS ENERGIZED
OPERATING MODE CIRCUIT ELECTRIC HEAT
HEAT PUMP
COOLING FAN R-G
YELLOW
RED
BLUE
BLUE
R
W
GREEN
C
Y
G
ORANGE
WHITE
THERMOSTAT
C
R
W
Y
G
OO
R-W R-G-Y
R-G-Y-O
BLOWER MOTOR SPEEDS
MODELS
10MHP4-(9,10)*181P-1
10MHP4-(9,10)*241P-1
7MHP4-(9-10)*301P-1
10MHP4-(9,10)*301P-1
7MHP4-09-361P-1
10MHP4-09-361P-1
HEATER ANTICIPATOR SETTING:
10MHP4 - 0.4
COOLING/
HEATING
MED/LOW
MED/LOW
MED/HIGH
MED/LOW
HIGH
HIGH
ELECTRIC
HEAT
MED/HIGH
MED/HIGH
MED/LOW
MED/HIGH
MED/LOW
MED/HIGH
COOLING MOTOR SPEED TAP SEE CHART
LIGHT BLUE
PS2
PS1
BLACK
BLACK
DEFROST CONTROL
Figure 10. Connection Diagram
#537246-01
DF1
DF2
PINK
C
C
RVG
CNT
RV
RED
BLACK
BLACK
REVERSING
VALVE
O
Y
W
R
DFS2
DFS1
BLACK
BLACK
DEFROST
THERMOSTAT
Page 12 of 15 506325-01Issue 1734
L1 TERMINAL BLOCK
REPLACEMENT FUSE SPEC: ATC-3 BLADE TYPE 32 VOLT 3 AMP
L1
CONTACTOR
CIRCUIT 2
SEQ
4
3
SEQ
5
4
CIRCUIT 1
208/230V-1 -60HZ
R
T1
COMPRESSOR
C
S
208/230V-1
-60HZ
LIMIT
LIMIT
HTR
HTR
CAPACITOR
H
DUAL
3
6
SEQ
SEQ
C
5
1
T2 L2
L2 TERMINAL BLOCK
GROUND
SCREW
DEFROST RELAY
DF
COM
DEFROST CONTROL
DF
NO
NC
SEQ
FUSE
RX
XFMR
CX
C
BLOWER CONTROL
C
RVG
PS2
CC
PS1
RV
COOLING
HEATING
R
G
C
O
Y
W
F
FAN
MOTOR
HIGH
MED/HIGH
MED/LOW
240
24 V.
LOW
COM208
REVERSING
VALVE COIL
BLOWER
MOTOR
TRANSFORMER
{10 MHP)
C
SEQ HEATER
CONTACTOR
COIL
BLOWER CAP.
W
W
O
Y
W
2
1
R
G
C
506325-01 Issue 1734 Page 13 of 15
R
DFS
DFS
Figure 11. Schematic
#537246-01
DEFROST SENSOR
HEATER ANTICIPATOR SETTING:
3MHP4 - 0.2 5MHP4- 0.4 7MHP4 - 0.4
MODELS
3MHP4-9-121P-1
5MHP4-9-121P-1
7MHP4-9-121P-1
3MHP4(9,10)*181P-1
5MHP4(9,10)*181P-1
7MHP4(9,10)*181P-1
5MHP4(9,10)*241P-1
7MHP4(9,10)*241P-1
5MHP4(9,10)*301P-1
5MHP4-9-361P-1
208/230-1-60
POWER SUPPLY WITH MIN.
COPPER WIRE
75
L2
CAPACITOR-RUN
FAN
COM HERM
BROWN
BROWN
CAPACITOR
BLOWER
BLOWER MOTOR
SPEEDS
COOLING
LOW
LOW
LOW
MED/LOW
MED/LOW
MED/LOW
MED/HIGH
MED/HIGH
MED/HIGH
HIGH
L1
VIOLET
MH
ML
BLOWER
MOTOR
EL. HEAT
MED/LOW
MED/LOW
MED/LOW
MED/HIGH
MED/LOW
MED/LOW
MED/LOW
MED/LOW
VIOLET
BROWN
C
H
L
LOW
LOW
BLACK
RED
BLACK
RED
CONDENSER FAN
YELLOW
RED
BLACK
ORANGE
SEE CHART FOR WIRING
LINE VOLTAGE-FACTORY
LINE VOLTAGE-FIELD LOW VOLTAGE-FACTORY LOW VOLTAGE-FIELD
1
3
5
C
SEQ
BLUE
4
1
C
SEQ
BLACK
RED
C
S
COMP
R
BLUE
RED
COOLING SPEED TAP
SEE CHART
REPLACEMENT FUSE SPEC:
ATC-3 BLADE TYPE
BLUE
EL. HEAT MOTOR SPEED TAP SEE CHART
BLACK
2
LIMIT
BLACK
4
RED
6
C
7 MHP ONLY
BLACK
5
3
C
G
BLACK
RED
BLUE
X-FRmR
X-FRmC
R
C
FUSE
NO
COM
NC
BLOWER CONTROL
BLACK
BLACK
32 VOLT 3 AMP
LIMIT
T1
T2
RED
CONTACTOR
HTR
HTR
NOTE:
IF ANY OF THE ORIGINAL WIRES ARE REPLACED THE SAME SIZE AND TYPE WIRE MUST BE USED.
WHITE
GREY
L1
L2
RED
TRANSFORMER
BLUE
RED
LIGHT BLUE
BLACK
PS2
PS1
DF1
DF2
DEFROST CONTROL
CONNECTOR BLOCK
COM
PINK
C
DFS2
DFS1
RVG
CNT
208 V
CIRCUITS ENERGIZED
OPERATING MODE CIRCUIT ELECTRIC HEAT
HEAT PUMP COOLING
FAN R-G
THERMOSTAT
C
R
W
Y
G
YELLOW
ORANGE
GREEN
WHITE
RED
BLUE
GRAY
BLACK
240 V
C
RV
BLUE
RED
BLACK
BLACK
REVERSING
VALVE
C
R
W
Y
G
OO
R-W
R-G-Y
R-G-Y-O
O
Y
W
R
BLACK
BLACK
DEFROST
THERMOSTAT
Figure 12. Connection Diagram
Page 14 of 15 506325-01Issue 1734
#537245-01
L1 TERMINAL BLOCK
208/230V-1
SEQ
3
4
-60HZ
LIMIT
HTR
SEQ
6
5
L2 TERMINAL BLOCK
GROUND
SCREW
L1
CONTACTOR
COM
T1
DEFROST RELAY
DF
NO
NC
7 MHP ONLY
DF
COOLING
SEQ
HEATING
FUSE
RX
XFMR
CX
C
BLOWER CONTROL
SEQ
5
4
R
COMPRESSOR
C
S
HIGH
MED/HIGH
MED/LOW
LOW
240
208
R
G
24 V.
COM
BLOWER
MOTOR
C
TRANSFORMER
SEQ HEATER
LIMIT
FAN MOTOR
HTR
H
F
BLOWER CAP.
(7 MHP)
(3 & 5 MHP)
DUAL
CAPACITOR
SEQ
1
3
T2 L2
C
W
2
W
1
R
G
DEFROST CONTROL
PS2
PS1
C
C
RVG
CC
RV
O
Y
W
R
DFS
DFS
REVERSING
VALVE COIL
CONTACTOR
COIL
C
O
Y
W
Figure 13. Schematic
#537245-01
506325-01 Issue 1734 Page 15 of 15
Loading...