magicpac HWC9 Installation Manual

INSTALLATION INSTRUCTIONS
HWC9 V-Series
This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
TM
Models
Table of Contents
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
WARNING
Do not store combustible materials near the furnace or warm air ducts. The material may ignite by spontaneous
combustion creating a re hazard.
WARNING
Unit Dimensions ..........................................................2
Installation ...................................................................3
Electrical Connections .................................................9
Start-Up .....................................................................13
Operation ...................................................................13
Maintenance ..............................................................14
Wiring Diagrams ........................................................20
WARNING
For your safety, do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any
other appliance. Such actions could result in property damage, personal injury, or death.
These units are not approved for mobile home applications. Such use could result in property damage, personal injury, or death.
Installation shall be made in accordance with the requirements of the local utility and other authorities
CAUTION
If these instructions are not followed exactly, a re
or explosion may result causing property damage, personal injury, or loss of life.
Manufactured By
Allied Air Enterprises LLC
215 Metropolitan Drive
West Columbia, SC 29170
Check that equipment complies with all applicable building codes, laws, and regulations for its intended use prior to installation.
507389-03 Issue 2110
having jurisdiction, or with the National Fuel Gas Code, ANSI Z223.1 (latest edition) and the National Electrical Code. Any alteration of internal wiring will void
certication and warranties.
*P507389-03*
CAUTION
(P) 507389-03
Page 1 of 22
27-7/8

Unit Dimensions

Line Voltage Box
Low Voltage
Supply
1/2 Gas Inlet
161
Supply
1-1/2
2-3/4
1-3/4
8
13-3/8
81
Supply
Condensate
18-1/4
2
Drain
(HWC9 Only)
2
43-3/16
Return
2-7/8
Page 2 of 22 507389-03Issue 2110
22
61
Return
29-7/16

Installation

General
These instructions must be hung on or near the furnace in a conspicuous place.
The MagicPak All-In-One™ HVAC system model HWC9
V-Series™ units are self-contained, gas-red heating with electric cooling models. The unit design has been certied
by Intertek Testing Services for compliance with the latest edition of the American National Standard – ANSI Z21.47/ National Standard of Canada – CAN/CGA-2.3 for direct
vent central furnaces. The HWC9 models are certied
to be in compliance with the latest edition of A.H.R.I.
Standard 210/240. All models are design certied for heating operation when red with natural or propane gas.
These installation instructions are intended as a general
guide only, for use by an experienced, qualied contractor.
Inspection
The unit is shipped in one package, completely assembled and wired. The Evaporator drain tubing is in the cooling
compartment behind the lter access panel. Fittings for
furnace condensate drainage are located in the hardware kit bag.
If any damage is found, proper notation should be made on
the carrier’s freight bill. Damage claims should be led with
the carrier as quickly as possible.
Check the rating plate to conrm heating and cooling
capacities. The unit should be operated only with the type of gas and electrical supply noted on the rating plate.
NOTE: Remove the chassis hold down shipping bracket before installation. These brackets are located on the outdoor side of the unit below the louver panels.
Location
The design is certied for indoor installation only. The
interior portions of the unit may be surrounded by a closet with minimum clearances to combustible material of 0” sides, 2” top, and 1” front and plenum. Adequate clearance must be provided to install gas line union and manual
shuto󰀨 valve , condensate drain connections as well as providing accessibility for eld wiring.
NOTE: Approximately 2” of clearance is required if using side exit furnace condensate drain connection. 2” to 4” of
clearance (depending on choice of ttings) is required if
using front exit furnace condensate drain connection. Do not install directly on carpeting, tile, or other combustible
material other than wood ooring.
The grille side of the unit may be ush with, or extend
beyond, the face of the exterior wall, but should not be recessed more than 2” from the face of the building and should not be obstructed with trees, landscape materials, or building structure.
There is no minimum clearance required on locating the unit to an interior corner of a building.
If the unit is to be enclosed, provisions should be made allowing access to the indoor side of the unit for changing
lters and for inspection. At least 29” of unobstructed space
should be provided in front of the indoor side, whether enclosed or not, to permit removal of the cooling chassis should repairs or inspection be required.
If the unit is installed in a residential garage, it must be located or protected to avoid physical damage by vehicles. Unit must be installed so the burners and ignition source
are not less than 18” (457 mm) above the oor. This unit
must be installed so that no electrical components are exposed to water.
WARNING
In the State of Massachusetts:
This product must be installed by a licensed Plumber
or Gas Fitter. When exible connectors are used, the
maximum length shall not exceed 36”. When lever-type
gas shuto󰀨s are used, they shall be T-handle type.
507389-03 Issue 2110 Page 3 of 22
This appliance should be installed in a location such that the vent outlet is located in the following manner:
1. Distances to windows that open, building openings, or public walkways should be consistent with the National Fuel Gas Code Z223.1 or CAN/CGA-B149.1 & .2.
2. For U.S. installations, the vent system shall terminate
a minimum horizontal clearance of 4’ from electric
meters, regulators, and relief equipment. For installations in Canada, refer to the current CAN/ CGA-B149.1 & .2 or with the authorities having local jurisdiction.
3. Flue products will not cause degradation to building materials.
This furnace design is not listed for installation in mobile homes, recreational vehicles, or outdoors.
Use of Furnace as a Construction Heater
Allied Air does not recommended the use of these units as a construction heater during any phase of construction. Very low return air temperature, harmful vapors and
operation of the unit with clogged or misplaced lters will
damage the unit.
Units may be used for heating of buildings or structures under construction, if the following conditions are met:
The unit must be permanently installed per these installation instructions.
A room thermostat must control the furnace. The use
of xed jumpers that will provide continuous heating is
not allowed.
The return air duct must be provided and sealed to the furnace.
Return air temperature range between 60°F (16°C) and 80°F (27°C) must be maintained.
Air lters must be installed in the system and must be maintained during construction.
Air lters must be replaced upon construction completion.
The input rate and temperature rise must be set per the furnace rating plate.
One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction.
The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be thoroughly cleaned following nal construction clean-
up.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be
veried according to these installation instructions.
Installing with a Wall Sleeve
Refer to the installation instructions packed with the wall sleeve and Figure 1 for guidance in assembly and mounting using a wall sleeve.
Make sure the gaskets attached to the sleeve are not damaged.
Seal the space between the wall sleeve and the building opening with non-hardening caulking compound. The seal must be weather-tight to prevent entrance of moisture and water into the building.
Assure that the unit is completely seated against the gaskets on the wall sleeve.
Slide the unit into the sleeve. When properly nested, the angle on top of the unit should line up with the top
ange of the sleeve and should almost touch. Fasten the unit to the sleeve with ve screws furnished with
the sleeve.
CAUTION
The sleeve is not intended as the sole support for the unit. An additional support must be provided near the return opening on the unit for adequate support. The use of vibration isolation material between the unit and the support is recommended.
Wall Sleeve
.
n
" Mi
8
2
F
LO
O
R
Plywood
Figure 1. HWC Installation
Page 4 of 22 507389-03Issue 2110
""
6 x 22 Minimum Opening to Align with Return Air Opening in Unit.
Vibrat ion Isol ating Mater ial
Evaporator Condensate Drain
Install the plastic drain tube (furnished) over the 5/8” O.D.
tting in the center of the Evaporator condensate pan.
Connect other end of the drain tube to the open trap (see Figure 2). The plastic drain connection is provided so that it may be disconnected from the permanent drain tubing in the building in the event it becomes necessary to remove the cooling chassis assembly.
The drain line should pitch gradually downward at least 1”
per 10’ of horizontal run to the open drain trap.
Be certain that the plastic drain tube has free drainage and
is not crimped or attened at any bend.
Drain Pan
Alternative
Method
To Open
Drain Trap
Return
Air Duct
" I .D.
5/8
Plastic Tube
(Suppli ed)
Top of Drain Tube Must be Below Bottom of Drain Pan
Drain Tube - Pit ch 1" for every 10 ft . (Field Supplied)
Open Drain Trap
Figure 2. HWC Evaporator Condensate Drain
Installation
Furnace Condensate Drain
The HWC9 furnace is provided with an internal condensate
drain and drain tting. A street elbow, a hose barb and a spigot adapter for connection to the drain tting are factory­supplied in the manual bag. All other piping is eld-supplied
to suit the installation and local codes.
If the furnace is installed in an unconditioned space, the condensate drain elbow outside the unit cabinet must have heat tape suitable for PVC pipe installed, and the
elbow insulated. This heat tape and insulation are eld-
supplied from standard hardware items that are available locally, and they must be installed in accordance with the instructions provided by their manufacturers.
Units are shipped with the drain tting installed for side-exit condensate drainage. The drain tting can be repositioned
for front-exit condensate drainage if desired. Do not relocate or remove the internal condensate trap.
If unit will be started immediately upon completion of installation, the drain must be primed as described in the procedure outlined in the “Start-up” section.
Field-installed piping from the furnace must slope downward
a minimum of 1/2” per foot toward the oor drain.
Piping for Side-Exit Condensate Drain
Determine whether the installation better suits a side-exit or a front-exit furnace condensate drain. For side condensate drain, see Figure 3 for component locations and additional details. A 2” clearance to the cabinet side is required for
service access to the condensate drain tting when using
the side location.
1. Install the factory-supplied street elbow to the drain
tting by threading into place. Use a thread sealant
suitable for PVC; do not use thread tape.
2. Use the appropriate primer and solvent cement to
bond eld-supplied drain line piping or ttings to the
PVC street elbow. Do not use copper tubing or existing copper condensate lines for drain line.
3. Route the piping to an open oor drain. Do not connect directly to evaporator condensate drain line.
Side Panel
Upper Drain Hose (from Collector Box)
Lower Drain Hose
(to drain tting)
Condensate Trap
Drain Fitting
Install threaded street elbow into
drain tting. Solvent weld piping to
street elbow.
Figure 3. Furnace Condensate Drain Component Locations - Side Exit
507389-03 Issue 2110 Page 5 of 22
Condensate
Trap
Install threaded hose barb or
threaded spigot adapter into
drain tting
Threaded Hose Barb
Side Panel
Upper Drain Hose
(from Collector Box)
Lower Drain Hose
(to drain tting)
Drain Fitting (repositioned to front)
Grommet Plug
(remove from access panel and use here)
5/8” ID Tubing
(eld provided)
Figure 4. Furnace Condensate Drain Component Locations - Front Exit
Piping for Front-Exit Condensate Drain
For front condensate drain, see Figure 4 for component locations and additional details. Use the factory-supplied
hose barb with eld-supplied exible tubing or spigot and
hose coupling for these installations. A 2” or 4”(depending
of choice of ttings) clearance to the cabinet front is
required for service access when using the front location.
The modications necessary to convert to front-exit
condensate drain are:
1. Disconnect the lower drain hose from the drain tting.
2. Remove the screw securing the drain tting to the division panel.
3. Remove the drain tting and rotate it so that it faces the front of the furnace.
4. Replace the securing screw.
5. Disconnect lower drain hose from drain trap and rotate the hose so that the angled end will connect to the
drain tting in its new orientation.
Spigot adapter with hose coupling and clamps
6. Reconnect the lower drain hose to the drain trap and
drain tting. Verify hose level to allow drainage.
7. Remove the grommet plug from the front access panel and insert it into the oval opening in the side panel.
8. Remove the perforated insulation from inside the front access panel around the oval opening. Be sure the area is clean and free of insulation and glue, as it will
be used as a sealing surface for the drain tting gasket.
9. Prior to setting the unit into operation, replace the access panel.
10. Install the factory-supplied hose barb or spigot adapter
to the drain tting by threading into place. Use a thread
sealant suitable for PVC; do not use thread tape.
11. For the hose barb tting, a󰀩x a suitable length of
exible tubing and route to an open oor drain. Secure
the end of the tubing to the drain. Do not connect directly to evaporator condensate drain line.
Page 6 of 22 507389-03Issue 2110
12. For the spigot adapter, attach the provided rubber coupling and then route 3/4” PVC pipping to an open
oor drain. Do not connect directly to evaporator
condensate drain line.
Combustion Air
This unit is a direct-vent furnace which obtains all air needed for combustion from outdoors.
WARNING
Insu󰀩cient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Venting
The venting system is an integral part of the appliance.
The venting system must not be modied or added on
to.
The unit contains a combustion inducer. The inducer draws the combustion products out of the heat exchanger and forces them from the unit to the outside. No special provisions are required for supplying air for combustion, nor is a chimney required.
appliances connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows between the space in which the appliances remaining connected to the common venting system are located and other spaces in the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer
exhaust fan. Close replace dampers.
4. Following the lighting instructions, place the unit being inspected in operation. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft control relief opening after
5 minutes of main burner operation. Use the ame of
a match or candle.
6. Follow the preceding steps for each appliance connected to the common venting system.
7. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, replace dampers,
and any other fuel burning appliance to their previous condition of use.
8. If improper venting is observed during any of the above tests, the common venting system must be corrected. See National Fuel Gas Code, ANSI Z223.1 (latest edition) or CAN/CGA B149.1 & .2 Canadian Installation Codes to correct improper operation of common venting system.
Gas Connections
The gas line to the unit should be adequately sized to
prevent undue pressure drop and should never be smaller than the manual valve used. Consult the local utility or National Fuel Gas Code for complete details on special
requirements in sizing gas piping.
The vent outlet must not be altered or extended.
The venting system is designed for proper operation under all weather conditions and for winds up to 31 m.p.h.
Removal of Unit from Common Venting System
When an existing furnace is removed from a common venting system serving other appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted with each appliance while the other
507389-03 Issue 2110 Page 7 of 22
The units supplied for operation with natural gas contain a gas regulator which must be operated with inlet gas
pressures specied on the rating plate. If gas line pressure exceeds this gure, an additional high pressure regulator
must be installed to reduce this pressure.
Units for operation with propane must be converted with a kit supplied by the manufacturer and require for operation an inlet pressure of 11” W.C. minimum and 13” W.C. maximum. A regulator is also required on the propane tank.
Loading...
+ 15 hidden pages