Magic Chef JEC7430AAW, JEC7430AAB, MEC4436AAW, MEC4436AAC, MEC4436AAB Installation Instructions

...
IMPORTANT - PLEASE KEEP FOR THE USE OF THE LOCAL ELECTRICAL INSPECTOR
INSTALLATION INSTRUCTIONS
Electric Counter Mounted Surface Units
READ “SAFETY INSTRUCTIONS” IN USE & CARE BOOK BEFORE USING UNIT
Inordertoassurethe best resultsinservice, properoperationandmaximum efficiency, the original installationandadjustment shouldbemadebyyourdealer,hisauthorized agent,orbyyourlocalutility companybefore you attempttooperate thesurface unit.
LOCATION
OUTSIDE WIRING
Your local utility company will tell you whether the present electric service to your home is adequate. It may be necessary toincrease the sizeof the wiring to the houseand service switch to take care of the electrical load demanded by the surface unit and/or oven. The wattage (K.W. rating) load for the range is specified on the name plate on the unit.
HOUSE WIRING
Most local building regulations and codes require that all electrical wiring be done by licensed electricians. All wiring shouldconform to Local and National Electrical Codes. This unitrequires a singlephase threewire 120/240 or a 120/208 volt, 60 Hz, AC circuit. Wiring codes requirethat a separate circuit be run from the main entrance panel to the unit and that it be equipped with separate disconnect switch and fuses, either in the main entrance panel or in a separate switch and fuse box.
APPROVED
CONNECTOR
APPROVED
BOX
L1
RANGE GROUNDED THROUGH NEUTRAL CONDUCTOR
RANGE CONDUIT
REDBLACK
BARE
L2NEUTRAL
BRANCH CIRCUIT (POWERSUPPLY)
APPROVED INSULATED
CONNECTIONS
UNIT CONNECTIONS
This unit is supplied with a 240/208 volt wiring system consisting of 2 insulated conductors and 1 bare grounding wireforuseona3wire 120/240ora120/208volts, 60 Hz AC branch circuit. Connect only to a 3-wire, 120/240-volt power supply; the neutral conductor is not required for the operationoftheappliance.Thepotential at thepowersupply electrical connections shall be 150-volts-to-ground or less. The flexible armored conduit supplied with the unit must be connected to an approved electrical junction box by means of an approved conduit to box connector.
THEBAREWIREINTHEUNITCONDUITISCONNECTED TOTHEFRAMEOFTHEUNIT.THEFRAMEOFTHEUNIT ISGROUNDED TO NEUTRALOFTHEBRANCHCIRCUIT ONLY WHENTHISBAREWIREISCONNECTEDTOTHE NEUTRAL (WHITE) WIRE OF THE BRANCH CIRCUIT. If usedonnew branch-circuit installations(1996NEC),mobile homes, recreational vehicles, or in an area where local codes prohibit grounding through the neutral conductor, the bare wire at the end of the unit conduit must be used to ground the unit in accordance with local code. The red and black wires must be connected to two conductors (red and black) of the branch circuit. The neutral (white) wire of the branch circuit must be properly insulated. Connect all wires to the branch circuit with approved connectors. Use copper or aluminum wire. If aluminum wire is used, use connectors recognized for joining aluminum to copper.
APPROVED
CONNECTOR
BLACK
INSULATED
L1
NEUTRAL
WIRING METHOD IF CODE DOES NOT PERMIT GROUNDING THROUGH NEUTRALCONDUCTOR & ALSO REQUIRED IN MOBILE HOMES.
RANGE CONDUIT
RED
BARE
APPROVED BOX APPROVED INSULATED
CONNECTIONS
L2
BRANCH CIRCUIT
(POWERSUPPLY)
SEPARATE GROUND
WARNING: Be sure UNIT is DISCONNECTED from
POWER SUPPLY before examining any of the electrical equipment.
8101P480-60
(05-02-00)
Units shown in figures 1 and 2 may be installed in combustible countertop and must be spaced at least (1² from) combustible sides and rear wall above countertop.
Unit shown in figure 3 may be installed in combustible countertop and adjacent to (0² from) combustible sides and rear wall above countertop.
DimensionA = 30-inches minimum clearance betweentop of the cooking surface and the bottom of an unprotected wood or metal cabinet, or A = 24-inches minimum when bottom of wood or metal cabinet is protected by not less than 1/4 inch flame retardant millboard covered with not less than no. 28 msg sheet steel, .015 inch stainless steel, .024 inch aluminum or .020 inch copper.
“To eliminate the hazard of reaching over heated surface units, cabinet storage space located above the surface units should be avoided. If cabinet storage is to be provided, the hazard can be reduced by installing a range hood that projects horizontally a minimum of 5-inches beyond the bottom of the cabinets.”
CAUTION: SOME CABINETS AND BUILDING MATERIALSARENOTDESIGNEDTOWITHSTAND THE HEAT PRODUCED BY THE NORMAL SAFE OPERATION OF A LISTED APPLIANCE. DIS­COLORATIONOR DAMAGE, SUCH AS DELAMINA­TION, MAY OCCUR.
“A”
COUNTER
TOP BASE
CABINET
If cooktop is to be secured to countertop, remove main top and attach burner box to countertop at (4) corners. To remove main top from burner box, remove all (4) surface units and drip bowls. Remove the (4) mounting
screws from main top. (Tabs on side of element openings.)
CAUTION: DO NOT REMOVE GREEN GROUND WIRE FROM MAIN TOP. WHEN REPLACING MAIN TOP, USE CAUTION TO BE SURE WIRES ARE NOT PINCHED UNDER SWITCH SHIELD.
30² Cooktop with Coil Elements
3/8² FLEXIBLE CABLE 3MIN.
FURNISHED AND INSTALLED BY MANUFACTURER (CONNECT TO 240/120-VOLT ELECTRICAL SERVICE.)
FIGURE 1
2
36² Cooktop with Coil Elements
FIGURE 2
30² Smoothtop Ceramic Cooktop
3/8² FLEXIBLE CABLE 48² LONG FURNISHED AND INSTALLED BY MANUFACTURER (CONNECT TO 240/120 VOLT ELECTRICAL SERVICE)
FIGURE 3
3
Loading...
+ 6 hidden pages