IMPORTANT - PLEASE KEEP FOR THE USE OF THE LOCAL ELECTRICAL INSPECTOR
INSTALLATION INSTRUCTIONS
Electric Counter Mounted Surface Units
READ “SAFETY INSTRUCTIONS” IN USE & CARE BOOK BEFORE USING UNIT
Inordertoassurethe best resultsinservice, properoperationandmaximum efficiency, the original installationandadjustment
shouldbemadebyyourdealer,hisauthorized agent,orbyyourlocalutility companybefore you attempttooperate thesurface
unit.
LOCATION
Placeunit where it willbe well lighted. For proper cookingresults,it must be level. THESEELECTRIC COUNTER MOUNTED
SURFACE UNITS ARE APPROVED FOR INSTALLATION IN COMBUSTIBLE CABINETRY. SEE INSTALLATION
DIAGRAM FOR THE APPROPRIATE UNIT ON THE FOLLOWING PAGES OF THIS INSTRUCTION SHEET.
OUTSIDE WIRING
Your local utility company will tell you whether the present
electric service to your home is adequate. It may be
necessary toincrease the sizeof the wiring to the houseand
service switch to take care of the electrical load demanded
by the surface unit and/or oven. The wattage (K.W. rating)
load for the range is specified on the name plate on the unit.
HOUSE WIRING
Most local building regulations and codes require that all
electrical wiring be done by licensed electricians. All wiring
shouldconform to Local and National Electrical Codes. This
unitrequires a singlephase threewire 120/240 or a 120/208
volt, 60 Hz, AC circuit. Wiring codes requirethat a separate
circuit be run from the main entrance panel to the unit and
that it be equipped with separate disconnect switch and
fuses, either in the main entrance panel or in a separate
switch and fuse box.
APPROVED
CONNECTOR
APPROVED
BOX
L1
RANGE GROUNDED THROUGH NEUTRAL CONDUCTOR
RANGE CONDUIT
REDBLACK
BARE
L2NEUTRAL
BRANCH CIRCUIT
(POWERSUPPLY)
APPROVED INSULATED
CONNECTIONS
UNIT CONNECTIONS
This unit is supplied with a 240/208 volt wiring system
consisting of 2 insulated conductors and 1 bare grounding
wire for use on a 3 wire 120/240 or a 120/208 volts, 60 Hz,
AC branch circuit. The flexible armored conduit supplied
with the unit must be connected to an approved electrical
junction box by means of an approved conduit to box
connector.
THEBAREWIREINTHEUNITCONDUITISCONNECTED
TOTHEFRAMEOFTHEUNIT.THEFRAMEOFTHEUNIT
ISGROUNDED TO NEUTRALOFTHEBRANCHCIRCUIT
ONLY WHENTHISBAREWIREISCONNECTEDTOTHE
NEUTRAL (WHITE) WIRE OF THE BRANCH CIRCUIT. If
usedonnew branch-circuit installations(1996NEC),mobile
homes, recreational vehicles, or in an area where local
codes prohibit grounding through the neutral conductor, the
bare wire at the end of the unit conduit must be used to
ground the unit in accordance with local code. The red and
black wires must be connected to two conductors (red and
black) of the branch circuit. The neutral (white) wire of the
branch circuit must be properly insulated. Connect all wires
to the branch circuit with approved connectors. Use copper
or aluminum wire. If aluminum wire is used, use connectors
recognized for joining aluminum to copper.
APPROVED
CONNECTOR
BLACK
INSULATED
L1
NEUTRAL
WIRING METHOD IF CODE DOES NOT PERMIT GROUNDING
THROUGH NEUTRALCONDUCTOR & ALSO REQUIRED IN MOBILE
HOMES.
RANGE CONDUIT
RED
BARE
APPROVED BOX
APPROVED INSULATED
CONNECTIONS
L2
BRANCH CIRCUIT
(POWERSUPPLY)
SEPARATE GROUND
WARNING: Be sure UNIT is DISCONNECTED from
POWER SUPPLY before examining any of the electrical
equipment.
8101P408-60
(05-02-01)
Units shown in figures 1 and 2 may be installed in
combustible countertop and must be spaced at least (1²
from) combustible sides and rear wall above countertop.
Unit shown in figure 3 may be installed in combustible
countertop and adjacent to (0² from) combustible sides
and rear wall above countertop.
DimensionA = 30-inches minimum clearance betweentop
of the cooking surface and the bottom of an unprotected
wood or metal cabinet, or A = 24-inches minimum when
bottom of wood or metal cabinet is protected by not less
than 1/4 inch flame retardant millboard covered with not
less than no. 28 msg sheet steel, .015 inch stainless steel,
.024 inch aluminum or .020 inch copper.
“To eliminate the hazard of reaching over heated surface
units, cabinet storage space located above the surface
units should be avoided. If cabinet storage is to be
provided, the hazard can be reduced by installing a range
hood that projects horizontally a minimum of 5-inches
beyond the bottom of the cabinets.”
CAUTION: SOME CABINETS AND BUILDING
MATERIALSARENOTDESIGNEDTOWITHSTAND
THE HEAT PRODUCED BY THE NORMAL SAFE
OPERATION OF A LISTED APPLIANCE. DISCOLORATIONOR DAMAGE, SUCH AS DELAMINATION, MAY OCCUR.
“A”
COUNTER
TOP BASE
CABINET
If cooktop is to be secured to countertop, remove main top and attach burner box to countertop at (4) corners.
To remove main top from burner box, remove all (4) surface units and drip bowls. Remove the (4) mounting
screws from main top. (Tabs on side of element openings.)
CAUTION: DO NOT REMOVE GREEN GROUND WIRE FROM MAIN TOP. WHEN REPLACING MAIN
TOP, USE CAUTION TO BE SURE WIRES ARE NOT PINCHED UNDER SWITCH SHIELD.
30² Cooktop with Coil Elements
3/8² FLEXIBLE CABLE 3′ MIN.
FURNISHED AND
INSTALLED BY MANUFACTURER
(CONNECT TO 240/120-VOLT
ELECTRICAL SERVICE.)
FIGURE 1
2
36² Cooktop with Coil Elements
FIGURE 2
30² Smoothtop Ceramic Cooktop
3/8² FLEXIBLE CABLE 48² LONG
FURNISHED AND INSTALLED BY
MANUFACTURER (CONNECT TO
240/120 VOLT ELECTRICAL SERVICE)
FIGURE 3
3