Magic Aire HCA, HCA 06, HCA 08, HCA 04, HCA 12 Installation, Operation And Maintenance Manual

...
Magic Aire HCA Series units are direct drive High Efficien­cy Horizontal Air Handlers delivering nominal airflows of 400 to 4000cfm and nominal cooling capacities of 1/2 to 10 tons. Units may be specified
with chilled water or DX cooling coils and hot water or steam heating coils to meet space cooling loads or heating loads or both.
How to Use this Manual:
This manual gives instructions regarding in­stallation, operation and maintenance for the HCA Series air handling units. For more in­formation refer to:
Catalog brochure for unit dimensions, options, guide specifications and perfor­mance information. New Magic 4 software for faster selection of new equipment. Website www.magicaire.com for re­placement parts guide, software down­loads, product data and contact info for your local Magic Aire representative. Replacement Parts – Identify parts needed using the replacement parts guide available at www.magicaire.com.
HCA Series Air Handler
Installation, Operation and Maintenance
Manual
GENERAL
Installation and maintenance are to be per­formed only by qualified personnel who are fa­miliar with local codes and regulations and are experienced with HVAC equipment of this type.
WARNING: Sharp edges, coil surfaces and rotating fans are a potential injury hazard – avoid contact.
WARNING: Hazardous voltage – Discon­nect and Lock Out all incoming power sources before servicing or installing unit. ELECTRIC SHOCK CAN CAUSE DEATH.
Use these instructions in conjunction with other appropriate instructions, including but not limited to those instructions supplied with the outdoor unit (if applicable). Installation must comply with all applicable local codes.
SAFETY WARNING:
Installer should pay particular attention to the following words: NOTE–intended to clarify or make installation easier. CAUTION–given to prevent equipment dam­age. WARNING–to alert installer that personal inju-
ry and/or equipment damage may result if in­stallation procedure is not properly followed.
WARNING: This equipment may be in­stalled well above finished floor—Use ex­treme caution when working at heights.
UNPACKING-CHECK FOR DAMAGE!
Immediately inspect each unit for dam­age upon receipt.
Inspect units for external and concealed
damage immediately.
File any damage claims in accordance
with Magic Aire Freight Damage Policy and Terms and Conditions (available at
www.magicaire.com).
Do not repair damaged units without
written authorization.
Protect stored units from damage.
035-000049-001 Page 1 HCA IOM 1.1 8-28-2017
THIS PAGE INTENTIONALLY LEFT BLANK
035-000049-001 Page 2 HCA IOM 1.1 8-28-2017
HCA Series Air Handler
Installation, Operation and Maintenance
Manual
Installaon, Start-Up
and Service
Instrucons
Topic Page
Warranty Registration Form SAFETY CONSIDERATIONS
UNPACKING-Remove Shipping Screws PREINSTALLATION
Rigging Unit Weight Calculation INSTALLATION Unit Suspension External Vibration Isolators Ductwork Electrical Service Clearance Condensate Drain Steam Coil Piping Recommendations Coil Freeze-Up Protection Refrigerant Piping, Direct Expansion (DX) Coils START-UP SERVICE Water Quality Guidelines Physical Data Dimensional Drawings
27
1,4
4 5
5 5
6-18
6-7
7 8
9-11
12 13
14-16
16
17-18
19
20-23
24 25 26
035-000049-001 Page 3 HCA IOM 1.1 8-28-2017
DANGER
UNPACKING-CAUTION!
NEVER enter an enclosed fan cabinet or reach into a unit while the fan is running. LOCK OPEN AND TAG the fan motor power dis­connect switch before working on a fan. Take fuses with you and note removal on tag. Electric shock can cause personal injury or death. LOCK OPEN AND TAG the electric heat coil power disconnect switch before working on or near heat­ers. Failure to follow these warnings could lead to per­sonal injury or death.
WARNING
CHECK the assembly and component weights to be sure that the rigging equipment can handle them safely. Note also, the centers of gravity and any specific rigging instructions. CHECK for adequate ventilation so that fumes will not migrate through ductwork to occupied spaces when welding or cutting inside air­handling unit cabinet or plenum. WHEN STEAM CLEANING COILS be sure that the area is clear of personnel. DO NOT attempt to handle access covers and removable panels on outdoor units when winds are strong or gusting until you have sufficient help to control them. Make sure panels are properly secured while repairs are being made to a unit. DO NOT remove access panel fasteners or open access doors until fan is completely stopped. Pressure developed by a moving fan can cause excessive force against the panel which can in­jure personnel. DO NOT work on dampers until their operators are disconnected. BE SURE that fans are properly grounded before working on them. Failure to follow these warnings could result in personal injury or equipment damage.
After removing the outer packaging,
REMOVE RED BLOWER SHIPPING
SCREWS
from the blower discharge flanges (Fig.1) and blower supports (Fig. 2). These screws stabilize the fan assembly during shipping and need to be removed.
CAUTION! Not removing red shipping screws can result in unsatisfactory vibration or blower noise.
Figure 1
Remove Red Shipping Screws
(4 per blower discharge—single discharge
shown)
Figure 2
Remove Red Shipping Screws–
Blower (1ea per side, 2ea total)
035-000049-001 Page 4 HCA IOM 1.1 8-28-2017
PREINSTALLATION
Std
High
1R2R4R6RSteam
Component Weights (lbs)
1. Check items received against packing list.
2. Do not stack unit components or accessories during storage. Stacking can cause damage or deformation.
3. If unit is to be stored for more than 2 weeks pri­or to installation, observe the following precau­tions:
a. Choose a dry storage site that is reasona-
bly level and sturdy to prevent undue stress or permanent damage to the unit structure or components. Do not store unit on vibrating surface. Damage to stationary bearings can occur. Set unit off ground if in heavy rain area.
b. Remove all fasteners and other small parts
from jobsite to minimize theft. Tag and store parts in a safe place until needed.
c. Cover entire unit with a tarp or plastic cov-
erall. Extend cover under unit if stored on ground. Secure cover with adequate tie­downs or store indoors. Be sure all coil connections have protective shipping caps.
d. Monthly — Remove tarp from unit, enter
fan section through access door or through fan inlet, and rotate fan and motor slowly by hand to redistribute the bearing grease
and to prevent bearing corrosion. Rigging — Do not remove shipping skids or protec­tive covering until unit is ready for final placement. Use slings and spreader bars as applicable to lift unit. Do not lift unit by coil connections or headers.
Do not remove protective caps from coil piping connections until ready to connect piping. Do not remove protective cover or grease from fan shaft until ready to install sheave. Lay rigid temporary protection such as plywood walkways in unit to prevent damage to insula­tion or bottom panel during installation.
WARNING-AUXILIARY DRAIN PAN RECOMMMENDED:
This product has an auxiliary condensate drain which should be piped to a condensate overflow sensor or safe drain location or both to protect the equipment and property from damage in the case of condensate overflow.
In addition, the International Mechanical Code (IMC) section 307.2.3 requires the use of auxiliary drain pans. Many municipalities have adopted this code.
Magic Aire holds that this practice represents the standard for professional installation whether or not this code has been adopted in a specific municipal­ity or territory. As such, water damages that would have been prevented had an auxiliary pan been deployed will not be considered for compensation. This position is taken regardless of whether the source of the moisture was specified as a potential failure mode in the applicable building code or not. A freeze burst, cracked drain pan, failed weld, or corrosion induced leak are some of the potential failure modes that are mitigated when an auxiliary pan is properly installed. Professional installers recognize the value of protecting customer assets against foreseeable events. Customers who choose to avoid the cost of common protective measures waive their right to seek damages when those foreseeable events occur. If the product is located above a living space or where damage may result from condensate overflow, install a wa­tertight pan of corrosion-resistant metal beneath the unit to catch over-flow which may result from clogged drains or from other reasons. Provide proper drain piping for this auxiliary pan. Consult local codes for additional precautions before instal­lation.
UNIT WEIGHT CALCULATION
MotorSize
Coil Weight, Dry
Cabinet
04 92 15 15 10 10 18 23 13 06 93 15 15 12 12 22 27 15 08 125 18 20 16 16 30 50 20 12 141 18 20 20 20 40 59 25 16 160 20 25 25 25 50 77 31 20 192 20 25 31 31 62 81 39 30 383 30 35 n/a 42 84 102 53 40 414 40 45 n/a 54 108 143 68
Table 1 — Unit Dry Weight
Calculation Procedure:
1. Calculate coil water weight for each water coil using the following formula:
Water Weight = Coil Volume (gal) x 8.345lb/gal (volume is from Physical Data table)
2. Calculate dry weight: Cabinet Dry Weight
+Motor Weight +Dry Coil Weight (coil 1) +Dry Coil Weight (coil 2) = Total Unit Dry Weight
3. Calculate total weight: Total Unit Dry Weight
+Water Weight (coil 1) + Water Weight (coil 2) = Total Unit Installed Weight
035-000049-001 Page 5 HCA IOM 1.1 8-28-2017
UNIT SUSPENSION
Ceiling Suspension: Acceptable forms of unit suspension are shown in Fig. 3, 4 and 5. Figure 3 shows suspension rods run through the knock­outs in top and bottom of the unit. Use strut ma­terial and hardware at bottom as shown in the details. Figure 4 shows field-supplied platform mount. Units can also be supported by suspend­ing the unit from crossbeams at the front and rear (Figure 5).
Size suspension rods to support the weight. Size any beam members to insure that they are adequate for a safe installation. Ensure that suspension rods are secured to adequately sup-
1
port the unit and that the rods extend entirely through their associated fasteners.
It is recommended that framing be construct­ed from structural steel or formed-strut mate­rials.
With Mixing Boxes: HCA units sizes 30-40 with mixing boxes should be supported with crossbeams at each end of the unit and at the duct connection side of the mixing box. Sizes 04-20 with mixing box—no additional support is required.
WARNING! INSURE THAT UNIT IS ADE­QUATELY SUPPORTED FROM STRUC­TURE TO PREVENT DAMAGE OR INJURY CAUSED BY FALLING EQUIPMENT! If un­certain about how to connect to the struc­ture, consult a qualified structural engi­neer.
Fig. 3
Ceiling Suspension—
Rods Through Unit
NOTES:
1. INSTALLATION MATERIALS ARE FIELD-SUPPLIED AND INSTALLED.
2. INSURE BUILDING STRUCTURE IS ADEQUATE FOR SUPPORTING THE EQUIPMENT.
3. INSURE AT LEAST 3 FULL THREADS ARE EXPOSED THROUGH EACH NUT WHEN LEVELING THE AHU.
4. USE NUT, WASHER, AND LOCK WASHER. ALTER­NATE: NYLOCK NUT MAY BE USED INSTAD OF
STANDARD NUT AND LOCK WASHER. WARNING!
DO NOT OMIT LOCK WASHER OR NYLOCK NUT!
035-000049-001 Page 6 HCA IOM 1.1 8-28-2017
UNIT SUSPENSION (CONT’D)
Floor mounting: Unit may be mounted on a housekeeping pad, floor or platform. CAUTION!
Make sure to allow enough elevation to permit construction of the condensate trap.
Vibration Isolators: (field supplied) If required,
install isolators in the suspension rod system. Allow clearance as needed between isolators and unit.
Fig. 4
Ceiling Suspension—
Platform Mount
WARNING! INSURE THAT UNIT IS ADE­QUATELY SUPPORTED FROM STRUCTURE TO PREVENT DAMAGE OR INJURY CAUSED BY FALLING EQUIPMENT! If uncertain about how to connect to the structure, consult a qualified structural engineer.
Fig. 5
Ceiling Suspension—
Crossbeam Mount
035-000049-001 Page 7 HCA IOM 1.1 8-28-2017
INSTALLATION—DUCTWORK
DUCTWORK CONNECTIONS
Install supply and return ductwork to the unit as required for the application. Note that free discharge or free return is ac­ceptable.
Return Ductwork: Install return ductwork by attaching one side of a field-provided flexible duct connector to the duct flange on the return side of the unit (filter side). Attach the other side of the flexible duct connector to the return ductwork. Seal the connections using duct mastic or HVAC tape.
Supply Ductwork—Unit Sizes 04-20: Install supply ductwork by attaching one side of a field­provided flexible duct to the fan discharge duct collar on the front of the unit. Attach the other side to the supply ductwork. Seal the connec­tions using duct mastic or HVAC tape. Refer to Figure 6.
NOTE: It is acceptable to omit the flexible duct connectors, but this may allow normal operating vibration or noise to transfer through the duct system leading to customer complaints.
Fig. 6 — HCA size 04 to 20
Duct Connections
Size all ductwork according to SMACNA and ASHRAE duct design standards.
MIXING BOX INSTALLATION
Mixing box accessory connects to the return (air inlet) flange on the rear of the unit. Refer to Mixing Box Installation Instructions (available at www.magicaire.com) for detailed instructions for installation along with economizer controls and damper installation.
035-000049-001 Page 8 HCA IOM 1.1 8-28-2017
INSTALLATION-ELECTRICAL
DANGER
WARNING: Hazardous voltage. Only qualified personnel must install the electrical service. Dis­connect and Lock Out all incoming power sources before connecting to electrical service.
WARNING: This appliance must be permanently grounded in accordance with the National Electrical Code and local code requirements.
WARNING: For use with copper conductors only.
INSTALLATION-ELECTRICAL
Typical wiring diagrams are shown on the fol­lowing pages FOR REFERENCE. Always re­fer to the wiring diagram on the air handling unit for actual wiring.
Connect electrical service to unit. Refer to unit wiring diagram. NOTE: CHECK MOTOR RAT­ING PLATE FOR CORRECT LINE VOLTAGE. For power supply connection, route field power wiring to Motor Start/Stop Station (MSS) dis­connect switch (if provided) or motor leads in the junction box (j-box).
DANGER
NEVER enter an enclosed fan cabinet or reach into a unit while the fan is running. LOCK OPEN AND TAG the fan motor power dis­connect switch before working on a fan. Take fuses with you and note removal on tag. Electric shock can cause personal injury or death. LOCK OPEN AND TAG the electric heat coil power disconnect switch before working on or near heat­ers. Failure to follow these warnings could lead to per­sonal injury or death.
Refer to nameplate FLA, maximum overcurrent protection device (MOPD) and minimum circuit ampacity (MCA). Also refer to wiring diagram affixed to unit to make control and power wiring connections.
NOTE: Installer is responsible for power wiring and branch circuit overcurrent protection.
NOTE: Motor provided has internal thermal overload protection. Units ordered Factory Electric Heat include fan relay or contactor and disconnect switch located inside the electric heat control box.
035-000049-001 Page 9 HCA IOM 1.1 8-28-2017
INSTALLATION-ELECTRICAL (cont’d)
TYPICAL WIRING DIAGRAMS—
Control Option “C”
Four User-Adjustable Speeds
NOTES:
1. This diagram represents the factory-installed electrical option with 4 user-adjustable speeds.
2. Typical wiring is shown. For exact wiring, refer to the wiring diagram provided with the unit.
3. Field wiring includes power wiring (upper left hand corner) and low voltage control wiring (terminal block TB1).
4. Units ordered for 208V-240V voltage selection are factory wired for 240V. Field may rewire transformer primary tap for operation at 208V.
5. Selection of field provided and installed electri­cal components is the responsibility of the in­staller, including branch circuit protection and wiring.
6. To start the fan, connect R and G1 or G2 or G3 to energize fan at each respective speed. Add connection to terminal “FLO4” on the control board (EVOECM-4SPD) to enable a fourth speed. Adjust each fan speed using potentiom­eter control on the control board. Speed adjust­ments can be made while the fan is running.
WARNING: Hazardous voltage!
7. The control power (R and C at terminal block TB1) can be used to power a stand­ard 24VAC thermostat , DX relay and up to 2ea control valves. NOTE: Factory trans­former is 40VA, so use caution when con­necting multiple loads to the 24VAC control circuit.
8. Optional condensate switch (CNS) factory option interrupts 24VAC to thermostat (R) and controls when water level rises to pre­set sensor level in the drain pan.
9. Optional current switch (CRS) factory op­tion makes upon current flow to the motor. Utilize as a dry contact for control system alarms as needed.
035-000049-001 Page 10 HCA IOM 1.1 8-28-2017
INSTALLATION-ELECTRICAL (cont’d)
0-10VDC Signal Fan Speed Control
TYPICAL WIRING DIAGRAMS—
Control Option “E”
Variable Speed
NOTES:
1. This diagram represents the factory-installed electrical option with constant CFM control us­ing the pressure transducer mounted inside the unit. Control loop logic is contained in the VFD programming. VFD keypad is mounted on out­side of unit.
2. Typical wiring is shown. For exact wiring, refer to the wiring diagram provided with the unit.
3. Field wiring includes power wiring (upper left hand corner) and low voltage control wiring (terminal block TB1).
4. Units ordered for 208V-240V voltage selection are factory wired for 240V. Field may rewire motor and transformer primary tap for opera­tion at 208V.
5. Selection of field provided and installed electri­cal components is the responsibility of the in­staller, including branch circuit protection and wiring.
6. To start the fan, apply 2.0VDC to + (plus) and—(minus) terminals. Fan speed is variable from 2.0VDC (minimum speed) to 10.0VDC (maximum speed).
7. The control power (R and C at terminal block TB1) can be used to power a stand­ard 24VAC thermostat , DX relay and up to 2ea control valves. NOTE: Factory trans­former is 40VA, so use caution when con­necting multiple loads to the 24VAC con­trol circuit.
8. Optional condensate switch (CNS) factory option interrupts 24VAC to thermostat (R) and controls when water level rises to pre­set sensor level in the drain pan.
9. Optional current switch (CRS) factory op­tion makes upon current flow to the motor. Utilize as a dry contact for control system alarms as needed.
035-000049-001 Page 11 HCA IOM 1.1 8-28-2017
SIZE
SERVICE CLEARANCES
CONTROL BOX
HC
UNIT
A B C D E
DIMENSIONS
04,06 18 36 4 30 26 08,12 20 36 4 36 31 16,20 23 36 4 30 38
CONTROL BOX CLEARANCE
NOTES:
1. NOT TO SCALE. REFER TO CATALOG DRAWINGS FOR UNIT OUTLINE DIMENSIONS.
2. MOTOR IS LOCATED ON THE SAME SIDE AS COOLING COIL CONNECTION (UNIT WITH 2 COILS) OR 2-PIPE/HEATING COIL CON­NECTION (UNIT WITH SINGLE COIL).
3. ALLOW CLEARANCE FOR FIELD PIPING AS REQUIRED BY THE PROJECT REQUIREMENTS. CONNECTIONS MAY BE ON ONE SIDE OR ON BOTH SIDES.
4. REFER TO INSTALLATION INSTRUCTIONS FOR UNIT HANGING (SUSPENSION) REQUIREMENTS.
5. COIL, DRAINPAN OR BLOWER REPLACEMETN REQUIRES UNIT TO BE REMOVED TO FLOOR FOR SAFE WORKING CONDITION. ALLOW FULL WIDTH OF UNIT FOR COIL REMOVAL. REFER TO SERVICE INSTRUCTIONS.
6. ALLOW ADEQUATE DEPTH FOR CONDENSATE DRAIN TRAP. REFER TO INSTALLATION INSTRUCTIONS FOR TRAP REQUIRE­MENTS.
035-000049-001 Page 12 HCA IOM 1.1 8-28-2017
Fig. 7 — Condensate
Drain
INSTALLATION
Condensate Drain — Install a trapped condensate
drain line at unit drain connection. HCA units have a 3/4 in. FPT condensate drain connection, or alternately a 3/4” male PVC pipe outlet for the condensate drain con­nection.
WARNING! To prevent excessive build-up of conden­sate in drain pan, adequate trap clearance (trap depth) must be provided beneath the unit as indicated in Fig. 6.
Measure maximum design negative static pressure up­stream from the fan. Referring to Fig. 7, height “H” must be 1” larger than the fan inlet static pressure Iinches w.g.) at the design operating conditions. Prime enough water in trap to prevent losing seal when starting up the unit. After the fan is running with the design fan inlet (negative) pressure, the elevation of the water on the unit side of the trap will be 1” below the drain invert.
Provide freeze-up protection as required to insure relia­ble condensate drainage. Freeze protection measures are customer-supplied and installed.
Water Coil Piping Recommendations
Water coils are piped by connecting the supply at the bottom and the return at the top. This is “counterflow” piping arrangement and is nec­essary to achieve rated thermal performance.
CAUTION! Piping the other way (parallel) will result in reduced thermal performance!
Coil Venting: Water coils are not provided with venting devices. Insure that the circulating water system has proper air venting capability. If vents are required at the coil, install them in the field piping attached to the return (upper) connection.
035-000049-001 Page 13 HCA IOM 1.1 8-28-2017
Steam Coil Piping Recommendations
GENERAL — Use straps around the coil casing to lift and place the coil.
CAUTION
To prevent damage to the coil or coil headers: Do not use the headers to lift the coil. Support the piping
and coil connections independently. Do not use the coil connections to support piping. When tightening coil connections, use a backup wrench on the coil connec­tion stub-out.
NOTE: Piping should be installed by a qualified install­er familiar with the type of piping to be installed. Per­form piping to industry best practices.
STEAM COILS — Position the steam supply connec­tion at the top of the coil, and the return (condensate) connection at the bottom. Figure 8 illustrates the normal piping components and the suggested locations for high, medium, or low­pressure steam coils. The low-pressure application (zero to 15 psig) can dispense with the ¼-in. petcock for continuous venting located above the vacuum breaker (check valve). Note the horizontal location of the 15-degree check valve, and the orientation of the gate/pivot. This valve is intended to relieve any vacuum forming in the con­densate outlet of a condensing steam coil, and to seal this port when steam pressure is again supplied to the coil. It must not be installed in any other position, and should not be used in the supply line. For coils used in tempering service, or to preheat outside air, install an immersion thermostat in the con­densate line ahead of the trap. This will shut down the supply fan and close the outdoor damper whenever the condensate falls to a predetermined point, perhaps 120 F. NOTE: DO NOT use an immersion thermostat to over­ride a duct thermostat and open the steam supply valve. For vacuum return systems, the vacuum break­ing check valve would be piped into the condensate line between the trap and the gate valve instead of open to the atmosphere.
Fig. 8 — Low, Medium or High
Pressure Coil Piping
NOTES:
1. Flange or union is located to facilitate coil removal.
2. Flash trap may be used if pressure differen­tial between steam and condensate return exceeds 5 psi.
3. Dirt leg may be replaced with a strainer. If so, tee on drop can be replaced by a reduc­ing ell.
4. The petcock is not necessary with a bucket trap or any trap which has provision for passing air. The great majority of high or medium pressure returns end in hot wells or deaerators which vent the air.
Figure 9 illustrates the typical piping at the end of every steam supply main. Omitting this causes many field problems and failed coils.
Figure 10 shows the typical field piping of multiple coils. Use this only if the coils are the same size and have the same pressure drop. If this is not the case, an individual trap must be provided for each coil.
Figure 11 shows a multiple coil arrangement applied to a gravity return, including the open air relief to the at­mosphere, which DOES NOT replace the vacuum breakers.
Figure 12 illustrates the basic condensate lift piping.
Fig. 9 — End of Steam Supply
Main Piping Detail
035-000049-001 Page 14 HCA IOM 1.1 8-28-2017
Steam Coil Piping Recommendations (Cont’d)
NOTES (Figure 9):
1. A bypass is necessary around trap and valves when uninterrupted operation is necessary.
2. Bypass to be the same size as trap orifice but nev­er less than 1/2 inch.
Fig. 10 — Multiple Coil High Pressure Piping
Fig. 11 — Multiple Coil Low Pressure
Piping Gravity Return
NOTES:
1. Flange or union is located to facilitate coil re­moval.
2. When control valve is omitted on multiple coils in parallel air flow.
3. When a bypass with control is required.
4. Coils with different pressure drops require in-
dividual traps. This is often caused by varying air velocities across the coil bank.
NOTES:
1. Flange or union is located to facilitate coil re­moval.
2. When a bypass with control is required.
3. Flash trap can be used if pressure differential between supply and condensate return exceeds 5 psi.
4. Coils with different pressure drops require indi­vidual traps. This is often caused by varying air velocities across the coil bank.
5. Dirt leg may be replaced with a strainer. If so, tee on drop can be replaced by a reducing ell.
6. The petcock is not necessary with a bucket trap or any trap which has provision for passing air. The great majority of high pressure return mains terminate in hot wells or deaerators which vent the air.
NOTES:
1. Flange or union is located to facilitate coil removal.
2. To avoid water hammer, drain coil before admitting steam.
3. Do not exceed one foot of lift between trap discharge and return main for each pound of pressure differential.
4. Do not use this arrangement for units handling outside air.
Fig. 12 — Multiple Coil Low Pressure Piping
Gravity Return
035-000049-001 Page 15 HCA IOM 1.1 8-28-2017
Steam Coil Piping Recommendations (Cont’d)
Following the piping diagrams in Fig. 8-12, make all connections while observing the following precau­tions:
• Install a drip line and trap on the pressure side of the inlet control valve. Connect the drip line to the return line downstream of the return line trap.
• To prevent scale or foreign matter from entering the control valve and coil, install a 3/32-in. mesh strainer in the steam supply line upstream from the control valve.
• Provide air vents for the coils to eliminate noncon­densable gases.
• Select a control valve according to the steam load, not he coils supply connection size. Do not use an oversized control valve.
• Do not use bushings that reduce the size of the header return connection. The return connection should be the same size as the return line and re­duced only at the downstream trap.
• To lift condensate above the coil return line into overhead steam mains, or pressurized mains, install a pump and receiver between the condensate trap and the pressurized main. Do not try to lift conden­sate with modulating or on-and-off steam control valves. Use only 15-degree check valves, as they open with a lower water head. Do not use 45-degree or vertical-lift check valves.
• Use float and thermostatic traps. Select the trap size according to the pressure difference between the steam supply main and the return main.
• Load variations can be caused by uneven inlet air distribution or temperature stratification.
• Drain condensate out of coils completely at the end of the heating season to prevent the formation of acid.
Coil Freeze-Up Protection
STEAM COILS — When used for preheating out­door air in pressure or vacuum systems, an immer­sion thermostat to control outdoor-air damper and fan motor is recommended. This control is actuated when steam supply fails or condensate temperature drops below an established level, such as 120 to 150 F. A vacuum breaker should also be used to equalize coil pressure with the atmosphere when steam supply throttles close. Steam should not be modulated when outdoor air is below 40 F. On low-pressure and vacuum steam-heating sys­tems, the thermostat may be replaced by a conden­sate drain with a thermal element. This element opens and drains the coil when condensate temper­ature drops below 165 F. Note that condensate drains are limited to 5 psig pressure. INNER DISTRIBUTING TUBE STEAM COILS — The inner distributing tube (IDT) steam coil used in the HHA air handling units has an inner tube pierced to facilitate the distribution of the steam along the tube's length. The outer tubes are expanded into plate fins. The completed assembly includes the supply and condensate header and side casings which are built to slant the fin/tube bundle back to­ward the condensate header. The slanting of the
assembly ensures that condensate will flow toward the drains. This condensate must be removed through the return piping to prevent premature failure of the coil. The fin/tube bun­dle is slanted vertically for horizontal airflow coils, and horizontally for vertical airflow coils. IDT Steam Coil Piping — The following piping guidelines will contribute to efficient coil oper­ation and long coil life:
1. Use full size coil outlets and return piping to the steam trap. Do not bush return out­let to the coil. Run full size to the trap, reduce at the trap.
2. Use float and thermostatic (F & T) traps only for condensate removal. Trap size selection should be based on the differ­ence in pressure between the steam sup­ply main and the condensate return main. It is good practice to select a trap with 3 times the condensate rating of the coil to which it is connected.
3. Use thermostatic traps for venting only.
4. Use only 1/2-in., 15-degree swing check valves installed horizontally, piped open to atmosphere, and located at least 12 in. above the condensate outlet. Do not use 45-degree, vertical lift and ring check valves.
5. The supply valve must be sized for the maximum anticipated steam load.
6. Do not drip steam mains into coil sec­tions. Drip them on the pressure side of the control valve and trap them into the return main beyond the trap for the coil.
7. Do not use a single trap for two or more coils installed in series. Where two or more coils are installed in a single bank, in parallel, the use of a single trap is per­missible, but only if the load on each coil is equal. Where loads in the same coil bank vary, best practice is to use a sepa­rate trap for each coil. Variation in load on different coils in the same bank may be caused by several factors. Two of the most common are uneven airflow distribu­tion across the coil and stratification of inlet air across the coil.
8. Do not try to lift condensate above the coil return into an overhead main, or drain into a main under pressure with a modulating or on/off steam control valves. A pump and receiver should be installed between the coil condensate traps and overhead mains and return mains under pressure.
9. Use a strainer (3/32-in. mesh) on the steam supply side, as shown in the piping diagrams, to avoid collection of scale or other foreign matter in the inner tube dis­tributing orifices.
NOTE: IDT coils must be installed with the tubes draining toward the header end of the coil. The IDT steam coils are pitched toward the header end as installed in the unit.
10. Ensure the AHU (air-handling unit) is in-
035-000049-001 Page 16 HCA IOM 1.1 8-28-2017
stalled level to maintain the inherent slope. Also ensure the unit is installed high enough to allow the piping to be installed correctly, especially the traps which require long drip legs.
11. Do not fail to provide all coils with the proper air vents to eliminate noncondensable gas­ses.
12. Do not support steam piping from the coil units. Both mains and coil sections should be supported separately.
IDT Steam Coil Installation — Refer to drawings to position the coils properly with regard to the location of the supply and return connections. Ensure that the IDT coil is pitched with the tubes draining toward the header. The AHUs provide proper coil pitch when the AHU is installed level. Refer to schematic piping diagrams and piping connection notes for the recommended piping methods.
SUCTION PIPING — Connect suction piping as shown in Fig. 13 for face split coil.
Fig. 13 — Face Split Coil Suction Line Piping
(TXV — Thermostatic Expansion Valve)
Refrigerant Piping, Direct-Expansion (DX) Coils —
Direct-expansion coils are divided into 1 or 2 splits depending upon the unit size and coil circuiting. Each split requires its own distributor nozzle, ex­pansion valve, and suction piping. Suction con­nections are on the air entering side when the coil is properly installed. Matching distributor connec­tions for each coil split are on the air leaving side. See unit label or certified drawing to assure con­nection to matching suction and liquid connec­tions. The lower split of face split coils should be first on, last off (Fig. 13). Row split coils utilize special intertwined circuits; either split of these row split coils can be first on, last off.
CAUTION
Direct-expansion coils are shipped pressurized with dry nitrogen. Release pressure from each coil split through valves in protective caps before removing caps.
Do not leave piping open to the atmosphere un­necessarily. Water and water vapor are detri­mental to the refrigerant system. Until the piping is complete, recap the system and charge with nitrogen at the end of each workday. Clean all piping connections before soldering joints.
Failure to follow these procedures could result in personal injury or equipment damage.
Suction line from coil connection to end of the 15­diameter-long riser should be same tube size as coil connection to ensure proper refrigerant velocity. Size remaining suction line to compressor for a pressure drop equivalent to 2.0 F. This will provide a total suction line header pressure drop equivalent to approximately 2.5 F. Refer to Fig. 14 for piping risers to the compressor. To minimize the possibility of flooded starts and com­pressor damage during prolonged light load operation, install an accumulator in the suction line or a solenoid in the liquid line of last-on, first off split in row-split ap­plications.
Fig. 14 — Suction Line Riser Piping
035-000049-001 Page 17 HCA IOM 1.1 8-28-2017
Refrigerant Piping, Direct-Expansion (DX) Coils (Cont’d)
EXPANSION VALVE PIPING — Distributor nozzles and expansion valves sized for acceptable performance for a range of conditions are factory supplied. Use the AHU (air­handling unit) selection program in the electronic catalog to select optimal nozzle sizes. Circuiting selection should result in a circuit loading of 0.8 to 2.0 tons per circuit at design load. Circuit loading must be evaluated at minimum load to ensure that it does not drop below 0.6 tons per circuit. Solenoid valves may be used, if necessary, to shut off the refrigerant supply to indi­vidual expansion valves to maintain adequate coil circuit loading. Compressor minimum unloading and TXV quantity is nec­essary to determine minimum tonnage per circuit. Minimum Unloading Equation:
Example: Condensing Unit: 38ARS012 Minimum Unloading: 33% Coil: 6 row, 11 FPI, Half Circuit Coil Tons per Circuit: 1.68 Total TXVs: 2 In the first example we will determine the tons per circuit when both TXVs are active and the compressor is unload­ed to its minimum of 33%
There are three different options to control tons per circuit when using an unloading compressor. The first is to use drop solenoid valve control as illustrated above and let the suction cutoff unloaders “ride” with the load. The second is to use drop solenoid valve control as illustrated above with electric un­loaders and let the control algorithm deter­mine the combination of solenoid valves and unloaders to limit tons per circuit to accepta­ble limits. The third is to limit the minimum amount of unloading so that tons per circuit is within acceptable limits. TXV SENSING BULB—sensing bulb for TXV is shipped coiled up inside cabinet. Remove coil connection panel, route sens­ing bulb out through suction line hole in pan­el, reinstall panel. Locate sensing bulb on horizontal section of suction line , and attach to tubing using copper plated strap. Attach sensing bulb between but no lower than the 2-o’clock and 10-o’clock positions. Make sure that there is good contact between the bulb cylinder and tubing. INSULATE the sensing bulb to insure that it reads the tem­perature of the suction line. For dual-circuit DX coils, make sure to locate the sensing bulb on the correct suction line.
Electrical Installation
WARNING
To avoid possible injury or death due to electrical shock, open the power supply dis­connect switch and secure it in an open po­sition during installation.
= .55 tons per circuit at minimum unloading UNACCEPTA­BLE
All field-installed wiring, including the electri-
If we install a liquid line solenoid valve before one of the TXVs and close it so that only one TXV is active when the compressor is unloaded to its minimum of 33%, we see the following:
cal ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limita­tions described in the NEC. Refer to factory wiring diagrams installed in the unit.
CAUTION
Use only copper conductors for field
= 1.10 tons per circuit at minimum unloading ACCEPTABLE
-installed electrical wiring. Unit ter­minals are not designed to accept other types of conductors.
035-000049-001 Page 18 HCA IOM 1.1 8-28-2017
START-UP
Pre-Startup
BUILDING ENVELOPEAll building windows and doors should be installed and closed before starting unit. During summer construction, avoid unit sweating by allowing for gradual pull down: use elevated chilled water temperature, reduce chilled water flow rate (gpm), use maximum available airflow. HEATING FLUID TEMPERATURE-Maximum entering water temperature is 180°F, unless nameplate indicates 200°F. CAUTION: If unit is marked for 200°F maxi­mum entering water temperature, customer must en­sure that water vaporization does not occur especially at higher elevations when entering water temperatures are greater than 190°F. TEMPERATURE CONTROLS-Check that unit or wall mounted thermostat or field-supplied controller is con­nected to the unit. OUTSIDE AIR AND FREEZE PROTECTION-
WARNING: Insure that the unit is protected against freezing conditions Failure to provide freeze pro­tection may result in equipment or property dam­age. Freeze protection measures are customer-
provided and installed and include but are not limited to low-limit thermostats, automatic temperature controls, and use of glycol based heat transfer fluids (see section FREEZE PROTECTION OF WATER PIPING).
1. If “locking quadrant” manual damper operator pro­vided, set to desired position.
2. If damper actuator provided, insure that actuator opens the damper when the fan turns on, and closes when fan stops. Test mixing box controls to make sure OA damper closes on power failure or upon activation of customer-supplied and installed low limit thermostat or other freeze protection device.
Start-Up Check List — Remove all construction debris from unit interior. Remove tools and all foreign objects
before starting unit. Checklist—perform full startup checklist located on the last page of this manual, and submit to the factory to register the warranty.
FILTERS — Install unit filters in all filter sections. Pro­tect open filters from drywall dust and construction de­bris. MOTOR/FAN ASSEMBLY
1. Hand turn fan to make certain it turns freely and fan
wheel does not rub the inlet ring.
2. Check fan speed with a laser-type tachometer to
confirm operating speed (access doors must be closed to apply correct external static pressure to the fan).
3. Check direction of rotation (see Fig. 15).
4. Check vibration. If excessive vibration occurs,
check for the following:
A. Shipping screws removed. B. Inadequate airflow. C. Damaged wheel. D. Loose mounting bolts. E. Wheel or motor out of balance. F. External vibration isolators improperly ad-
justed.
G. Out-of-balance or corroded wheel
(rebalance or replace if necessary).
H. Accumulation of material on wheel (remove
excess material).
Fig. 15 — Fan Wheel Rotation
COILS
1. Make sure freeze protection measures are in place to protect water coils from freezing (see section FREEZE PROTECTION OF WATER PIPING).
2. Make sure hydronic (water based chllled water and hot water) systems are filled and have air removal devices in operation.
3. For hydronic coils with 3ea connections, make sure that the supply connection is at the bottom (air leaving side of coil) and re­turn connection is in the middle (air entering side of coil), and the top connection is capped with the factory-provided cap.
Start-Up—Run Fan, Set Airflows
CONTROLS Set up control system so that it correctly runs the fan as needed and activates control valves when required. Note that operating cooling with the fan off can cause the cabinet temperature to become too low and result in condensation in­side and outside the unit cabinet, leading to un­safe conditions. When fan is not running, cool­ing should be inactive.
START THE FAN With 4-Speed Control:
1. Using a thermostat: Route R, C and G1 connections in the HCA control box to the matching thermostat connections (include G2 and G3 if required). Set thermostat to run the fan at speed G1.
2. Without a thermostat: Jump together the R and G1 terminals in the control box.
3. While fan is running, adjust potentiometer marked “FLO1” that controls fan speed G1 using a small flat blade screwdriver. Repeat for the other speeds as needed.
With 0-10VDC Control:
1. Using a thermostat: Route R, C, + (plus) and -(minus) connections in the HCA control box to the matching thermostat connections. Set the thermostat to run the fan.
2. Without a thermostat: Provide a DC control voltage across the + (plus) and — (minus) terminals.
3. Fan starts at 2.0VDC. Fan speed varies across available range (pre-programmed at factory) from 2.0 VDC (minimum speed) to
10.0 VDC (maximum speed).
035-000049-001 Page 19 HCA IOM 1.1 8-28-2017
DANGER
NEVER enter an enclosed fan cabinet or reach into a unit while the fan is running. LOCK OPEN AND TAG the fan motor power dis­connect switch before working on a fan. Take fus­es with you and note removal on tag. Electric shock can cause personal injury or death. LOCK OPEN AND TAG the electric heat coil pow­er disconnect switch before working on or near heaters. Failure to follow these warnings could lead to per­sonal injury or death.
SERVICE
General
1. Place a suitable walkway to protect floor insula­tion whenever entering the fan section.
2. Review Safety Considerations at beginning of these instructions. Good safety habits are im­portant tools when performing service proce­dures.
3. To make speed measurements, use a laser-style tachometer and make sure the access doors are closed.
Fan Motor Replacement
Shut off motor power and lock out power supply. Procedure:
1. Disconnect motor power and control wiring har­ness(es).
2. Loosen fan inlet ring on motor side of the unit.
3. Carefully remove motor mounting bolts where they attach to the housing. WARNING: Blower motor/wheel assembly will fall, so be sure to fully support the assembly before removing the bolts.
4. Remove fan motor and wheel assembly and inlet ring from the blower housing and unit.
5. Remove the wheel from the fan motor shaft by loosening the setscrew.
6. Before removing motor mount from motor, mark the location of the motor mount for reference.
7. Attach new motor to existing or new wheel. NOTE! Install blower ring BETWEEN motor and wheel.
8. Attach existing motor mount to new motor, using mark on old motor as a reference.
9. Install motor/wheel/ring assembly in the fan housing. Ring is loose. Reinstall ring and motor mount bolts.
10. Reattach motor harness to motor.
11. Return unit to serviceInstall impeller on new mo­tor (or new impeller on motor):
Fan System Periodic Maintenance
1. Magic Aire strongly recommends use of a Pre­ventive Maintenance program to insure that the unit operates safely and efficiently.
2. Deposits of dust or other debris on the impeller can cause vibration and premature failure. Fol-
low cleaning instructions in section “Fan Maintenance & Cleaning”.
Fan Maintenance & Cleaning
1. Regular inspection, and cleaning is neces­sary to prevent imbalance due to ingress of dirt.
2. Clean the fan’s flow area - maintenance inter­val in accordance with the degree of contami­nation. Verify vibration free motion.
3. The fan wheel can be cleaned with a moist cloth.
4. Do not use any aggressive, paint solvent cleaning agents when cleaning.
5. Never use a high-pressure cleaner or water­spray for cleaning - particularly when the fan is running.
WARNING! Wet cleaning under volt­age may lead to electric shock and serious injury or death!
Coil Cleaning
DETERGENT — Spray mild detergent solution on coils with garden-type sprayer. Rinse with fresh water. Check to ensure condensate line is free. Excess water from cleaning may flood unit if con­densate line is plugged.
Winter Shutdown (Chilled Water Coil Only)
ANTIFREEZE METHODS OF COIL PROTEC­TION
1. Close coil water supply and return valves.
2. Drain coil as follows: Method I — ‘Break’ flange of coupling at each header location. Separate flange or coupling connection to facilitate coil draining. Method II — Open both valves to auxiliary drain piping.
3. After coil is drained:
Method I — Connect line with a service valve and union from upper connection to an antifreeze res­ervoir. Connect a self-priming reversible pump between the low header connection and the res­ervoir. Method II — Make connection to auxiliary drain valves.
4. Fill reservoir with any inhibited antifreeze ac­ceptable to code and underwriter authority.
5. Open service valve and circulate solution for 15 minutes; then check its strength.
6. If solution is too weak, add more antifreeze until desired strength is reached, then circu­late solution through coil for 15 minutes or until concentration is satisfactory.
7. Remove upper line from reservoir to reversi­ble pump. Drain coil to reservoir and then close service valve.
8. Break union and remove reservoir and its lines.
9. Leave coil flanges or coupling open and aux­iliary drain valves open until spring.
AIR DRYING METHOD OF COIL PROTECTION (Unit and coil must be level for this method.)
1. Close coil water supply and return main valves.
035-000049-001 Page 20 HCA IOM 1.1 8-28-2017
SERVICE—Fan Motor Replacement (cont’d)
2. Drain coil as described in procedures for Anti­freeze Methods of Coil Protection.
3. Connect air supply or air blower to inlet header connection and close its drain connection.
4. Circulate air and check for air dryness by hold­ing mirror in front of open vent in outlet header drain connection. Mirror will fog if water is still present.
5. Allow coil to stand for a few minutes; repeat Step 4 until coil is dry.
PIPING — Direct expansion, chilled water, and hot water coils should always be piped for counterflow. (Fluid should enter the coil at the leaving-air side.) Steam coils must have the condensate connection at bottom of coil. To determine intervals for cleaning coils in contami­nated air operations, pressure taps should be in­stalled across the coils and checked periodically. Abnormal air pressure drop will indicate a need for cleaning the coils.
Steam Systems
Annual steam system maintenance should include:
1. Clean the line strainers.
2. Blow down the dirt leg.
3. Clean and check operation of steam traps.
4. Check operation of control valves.
5. Check the operation of check valves to prevent condensate flowback.
6. Check operation of thermostatic air vents, if used. A float and thermostatic trap will contain a thermostatic air vent. When the bellows is ruptured, it will fail closed.
7. Check operation of vacuum breakers.
8. Check operation of the thermal protection devic-
es used for freeze-up protection.
9. Steam or condensate should not be allowed to
remain in the coil during the off season. This will prevent the formation and build up of acids. There are additional precautions and control strate­gies, as found in various catalogues and in the ASHRAE Fundamentals Handbook when the enter­ing-air temperature to the coil falls below 35 F. These conditions occur when IDT coils are used for pre-heat and/or face and bypass applications. Freeze up protection:
1. Use a strainer in the supply line and the dirt leg
ahead of the trap.
2. Use a vacuum breaker in the return.
3. Do not use overhead returns from the coil. A
floodback can occur.
4. An immersion thermostat to control outdoor-air
dampers and the fan motor is recommended. This control is activated when the steam supply fails or the condensate temperature drops below a prede­termined temperature, usually 120 F.
5. On low pressure and vacuum systems, the im-
mersion thermostat may be replaced by a conden­sate drain with a thermal element. This element opens and drains the coil when the condensate
temperature drops below 165 F. Note the ther­mal condensate drain is limited to 5 psig pres­sure. At greater coil pressures they will not open. In spite of the precautions listed above, a coil may still freeze up. An oversize capacity coil, at partial load, with a modulating steam control valve will occasionally freeze. Freezing occurs in the 20 F to 35 F range of entering-air tem­peratures. A better installation would be an un­dersize coil, with an on/off control valve with thermostatic control in the outside air, set at 35 F air temperature, installed downstream of the first coil; or setting the minimum steam pres­sure at 5 psig.
Filters
FILTER SECTIONS — Open or remove filter panel to replace old filter with a new filter. See physical data tables for filter data.
035-000049-001 Page 21 HCA IOM 1.1 8-28-2017
SERVICE-Coil & Drainpan Removal and Reinstallation Procedure
1. Perform procedure on the ground for safety. If working at heights USE EXTREME CAUTION observe all FALL SAFETY considerations. Under all conditions, LOCK OUT all power supplies before performing this procedure.
2. Isolate and drain coil from heating/cooling fluid and/or reclaim refrigerant. Disconnect unit from piping. Remove supply piping to allow access into the coil section from the side. Re­fer to Service Clearance drawing to determine required clear space.
3. Remove the flat coil stubout panel. Refer to Figure 16 and 17. Note that there is another coil access panel on the opposite side of the unit.
Coil Stubout Panel
4. Remove filter door and filter (Figure 17 and 18).
5. Remove coil retaining screws (4ea sizes 04-20, up to 6ea sizes 30-40). Screws attach the first coil to the coil panel. Screws are visible from the coil side (Figure 19) and are accessible from the filter side of the unit (Figure 20).
Filter Door
Figure 16
Figure 19
Coil Retaining Screws
Figure 17
Coil Stubout Panel shown removed
Figure 20
Coil Retaining Screws-filter side view (filter
removed)
Figure 18
Filter removal
035-000049-001 Page 22 HCA IOM 1.1 8-28-2017
SERVICE-Coil & Drainpan Removal and Reinstallation Procedure
6. Remove top panel screws at sides and rear
(rear leg and coil panel) to allow top to be lifted up. Front screws can remain. Remove top filter rail. (Figure 21 and 22). WARN-
ING! Insure unit is adequately supported
before removing top panel screws!
Top Panel
Top Panel
Flange
Top Filter Rail
Rear Leg
Figure 21
Figure 24
Figure 22
7. Remove screws at bottom of coil panel. Re­move coil panel. (Figure 23 and 24)
Plastic
Drainpan
Figure 25
Stainless
Steel
Drainpan
Figure 23
Figure26
8. Remove coils from unit along with drainpan. Drainpan will slide out of unit (Figure 25 or
26). To remove coils and drainpan, top will need to be lifted up as shown in Figure 21.
10. Follow instructions in reverse to reassemble the unit.
9. At this point, the drainpan or one or more coils may be replaced.
035-000049-001 Page 23 HCA IOM 1.1 8-28-2017
Magic Aire Water Quality Guidelines
For Heat Exchanger Coils with Copper Tubes
Introduction:
Poor cooling/heating water quality can cause serious problems. Ground source or open loop water quality varies and therefore should be tested to determine suitability for use with Magic Aire equipment. Test water for hardness, acidity and iron content before the equipment is installed. Poor water quality can cause one or more of the following problems: mineral deposits, sediment deposits or corrosion. These problems will result in fouling, contamination or damage to water coils and may render them inoperable or inefficient. It is the responsibility of the customer to insure that the water quality meets or exceeds water quality specifications prescribed in Table 1.
Table 1
Condition
pH 7 to 9 Total Hardness Iron Oxides < 1 ppm.
Iron Bacteria No level allowable. Brackish
Sediment/Solids
Corrosion
1
Calcium and magnesium carbonate should not exceed 20 grains per gallon (350 ppm).
Calcium or sodium chloride concentrations ≤ 125 ppm.
(Seawater is approximately 25,000 ppm)
Provide ≤ 800 micron filtration on open loop or ground
source systems. Ammonia, Ammonium Hydroxide 0.5 ppm max. Ammonium Chloride, Ammonium Nitrate 0.5 ppm max. Ammonium Sulfate 0.5 ppm max. Chlorine/Chlorides 0.5 ppm max. Hydrogen Sulfide
2
Acceptable Level
None Allowable
NOTES:
1. If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion problems exists.
2. Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0.
3. To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.
035-000049-001 Page 24 HCA IOM 1.1 8-28-2017
0406081216
20
1- Row
1.58
1.79
1.50
2.39
4.03
5.00
2- Row
1.58
1.79
1.56
2.39
3.52
4.38
4- Row
1.58
1.79
2.00
3.06
4.03
5.00
6- Row
1.58
1.79
2.00
3.06
3.94
5.00
4-Row
0.875
6-Row
1.125
(note 2)
(dua l ckt)
(dua l ckt)
Unit Size
Actua l size
Note 1)
Model HCA
2" Pl ea te d (MERV 8)
4" Pl ea te d (MERV 13)
Su cti on (OD Sw e a t) 2ea
Su cti on (OD Sw e a t) 2ea
Tube)
PHYSICAL DATA
Nomi na l Capa city (Tons ) Nomi na l Capa city (BTU/H R) Nomi na l Airfl ow (CFM) Fa n Fa n Si ze Pre-Fil ter
Qua nti ty /
Coi l Fa ce Are a
Fa ce Area -Hydroni c (s q ft.)
Fa ce Area -DX (s q ft.) Fa ce Area -Stea m He ati ng (s q ft.) Coi l Ro ws /FPI Chi l le d Wate r/2-Pi p e - 4 row Chi l le d Wate r/2-Pi p e - 6 row Std Ca paci ty Stea m 2/8 2/8 2/6 2/6 2/6 2/6 Hi gh Capa ci ty Stea m - - 2/14 2/14 2/14 2/14 Std Ca paci ty DX Hi gh Capa ci ty DX Ma x Coil Rows Coi l Conne cti ons (i n )
Chi l le d Wa te r (OD Coppe r
(See
1 1.5 2 3 4 5
12000 18000 24000 36000 48000 60000
400 600 800 1200 1600 2000
97-6T 90-6R 120-11R
12 x 24 16 x 32
1.19 1.79 2.00 3.06 4.03 5.00
1.13 1.13 1.88 2.86 3.63 4.50
4/10 4/10 4/10 4/10 4/10 4/10 6/10 6/10 6/10 6/10 6/10 6/10
3/10 3/10 3/12 3/10 3/12 3/12 6/10 6/10 6/10 6/10 6/10 6/10
10 Rows Tota l (note 1)
0.75 0.75 0.75
0.875
20 x 20
1.125
Ho t Wa ter (OD Copper Tu b e ) Ste am-Std Ca p -Sup p l y/Return (MPT) Ste am-Hi gh Ca p-Supply/Return (MPT)
Std Ca p DX
Std Ca p DX
Hi gh Ca p DX
Hi gh Ca p DX
Conde n s ate Dra in Li ne Prima ry & Au xi li ary Coi l Vol u me Hot Wa te r - 1 row (ga l) Hot Wa te r - 2 row (ga l) Chi l le d Wate r/2-Pi p e - 4 row (ga l) Chi l le d Wate r/2-Pi p e - 6 row (ga l) Std Ca paci ty DX 68 103 115 175 231 286 Hi gh Capa ci ty DX 136 205 229 350 461 573
Notes:
1. Ste a m coil s a re 1-row, 5/8" tube -i n -tube s tea m di stributi n g type con s truction. Wh e n ca l cua ti ng tota l
rows of coi l for th e uni t, thes e cou n t a s 2 rows .
2. For dua l circui t coi ls , vol u me pe r ci rcuit i s ha l f of tha t li s ted.
3. Not a ll combi na tio ns equa li ng 10 rows are a ll owe d. Pl ea se re fer to Ne w Ma gic 4 Softwa re for
pe rmi ss ibl e se l ecti ons.
Li qui d (OD Swe a t) Su cti on (OD Sw e a t) Li qui d (OD Swe a t) 2ea
Li qui d (OD Swe a t) Su cti on (OD Sw e a t) Li qui d (OD Swe a t) 2ea
(cu i n)
0.75 0.625 0.625 0.625 0.875 0.875
1.50/1.00 1.50/1.00 1.50/1.00 1.50/1.00 1.50/1.00 1.50/1.00
- - 1.50/1.00 1.50/1.00 1.50/1.00 1.50/1.00
0.375 0.375 0.375 0.375 0.375 0.625
0.625 0.625 0.75 0.75 0.75 1.125
- - 0.375 0.375 0.375 0.375
- - 0.75 0.75 0.75 0.75
0.375 0.375 0.375 0.5 0.625 0.625
0.75 0.75 0.75 0.875 0.875 1.125
- - 0.375 0.375 0.5 0.5
- - 0.75 0.75 0.875 0.875
3/4" FPT
0.1 0.2 0.2 0.3 0.5 0.6
0.3 0.3 0.3 0.7 0.7 0.9
0.5 0.6 0.6 0.8 1.1 1.4
0.8 0.9 0.8 1.3 1.7 2.1
035-000049-001 Page 25 HCA IOM 1.1 8-28-2017
035-000049-001 Page 26 HCA IOM 1.1 8-28-2017
AIR HANDLERS AND FAN
COILS
Warranty Registraon and Start-up Report
Warranty Registration Form: Complete and submit this form within ten (10) days of start-up to comply with the terms of the Magic Aire warranty. Form must be com­pleted to clearly indicate startup for each
Mail form(s) to Magic Aire Warranty Department 501 Galveston St. Wichita Falls, TX, 76301 or
Email customer.service@MagicAire.com
unit being registered.
Job Name City
Sales Order # Unit Tag
Model Number Serial Number
Installer Quantity of Units
STARTUP REPORT
Group Checklist Item Yes No
Have red shipping screws been removed from pallet and blower rails?
Electrical/Operational
Does electrical service correspond to unit nameplate?
-Nameplate Supply Voltage/Phase: Rated_________ Measured___________
-Nameplate Rated FLA motor current: Rated_______ Measured__________ Does all field wiring conform to unit wiring diagram? Is field-provided freeze protection present? (for DX and hydronic coils) Is fan wheel turning the correct direction? Are mixing box dampers operating properly?
Is the filter clean? Is unit properly supported?
Structural
Is unit installed level (necessary for proper condensate drainage)? Is properly sized condensate trap present? Is the condensate disposal system operating correctly? Is auxiliary external condensate drain pan installed as recommended by IOM? (not
required for valid warranty)
DX Sys-
tems
Check
Systems
Is expansion valve sensing bulb properly installed and insulated? Is Heat Pump Bypass Kit (HPK) present if required?
Is the DX system charged per the condensing unit mfr’s instructions? Is unit piping correct and insulated to prevent condensation?
Piping
Are the control valve packages piped correctly? Are Valve packages properly insulated? Are there any leaks detected: interior to unit, at connections, or at valve packages? Have customer-provided Freeze Protection measures been taken, such as Low
Limit Thermostats and glycol (antifreeze) heat transfer fluids?
Hydronic
Does the hydronic system include a pressure relief valve or other pressure relief device to protect the coil from operating pressures beyond the nameplate design working pressure rating?
Are coils equipped with control valves to stop fluid flow to save energy and prevent cabinet condensation (wild coil in cooling) when heating/cooling is not required?
035-000049-001 Page 27 HCA IOM 1.1 8-28-2017
THIS PAGE INTENTIONALLY LEFT BLANK
035-000049-001 Page 28 HCA IOM 1.1 8-28-2017
THIS PAGE INTENTIONALLY LEFT BLANK
035-000049-001 Page 29 HCA IOM 1.1 8-28-2017
HCA Series Air Handler
Installation, Operation and Maintenance Manual
035-000049-001 Page 30 HCA IOM 1.1 8-28-2017
Loading...