Field Calibration Procedure 17
MACURCO GAS DETECTION PRODUCTS WARRANTY 18
2
GENERAL SAFETY INFORMATION
Intended Use
The Macurco TX-6-ND is a low voltage, dual relay Toxic Gas (TX) detector, controller and transducer for
Nitrogen Dioxide (NO2). The TX-6-ND has selectable 4-20 mA output, buzzer and digital display options. It
is an electronic detection system used to measure the concentration of Nitrogen Dioxide and provide
feedback and automatic exhaust fan control to help reduce Nitrogen Dioxide concentrations in parking
garages, maintenance facilities or other commercial applications. The TX-6-ND is a low level meter capable
of detecting from 0-20ppm of Nitrogen Dioxide. The TX-6-ND is factory calibrated and 100% tested for
proper operation, but can also be calibrated in the field.
List of Warnings and Cautions within these User Instructions
! WARNING
Each person using this equipment must read and understand the information in these User Instructions
before use. Use of this equipment by untrained or unqualified persons, or use that is not in accordance
with these User Instructions, may adversely affect product performance and result in sickness or death.
Use only for monitoring the gas which the sensor and instrument are designed to monitor. Failure to do
so may result in exposures to gases not detectable and cause sickness or death. For proper use, see
supervisor or User Instructions, or call Technical Service at 1-877-367-7891.
This equipment may not function effectively below 0F or above 125F (-18C or above 52C). Using the
detector outside of this temperature range may adversely affect product performance and result in sickness or death.
This detector helps monitor for the presence and concentration level of a certain specified airborne gas.
Misuse may produce an inaccurate reading, which means that higher levels of the gas being monitored
may be present and could result in overexposure and cause sickness or death. For proper use, see
supervisor or User Instructions, or call Technical Service at 1-877-367-7891.
High voltage relay terminals (120/240 VAC) are located within this detector, presenting a hazard to
service technicians. Only qualified technicians should open the detector case and service the internal
circuits. Ensure power is removed from the detector relays prior to servicing the unit. Failure to do so
may result in sickness or death.
Do not disassemble unit or attempt to repair or modify any component of this instrument. This instrument
contains no user serviceable parts, and substitution of components may impair product performance and
result in sickness or death.
Using a certified gas with a concentration other than the one listed for this detector when conducting a
calibration or calibration verification test (bump test) will produce inaccurate readings. This means that
higher levels of the gas being monitored may be present and could result in overexposure and cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical Service at 1877-367-7891
The following steps must be performed when conducting a calibration or calibration verification test
(bump test) to ensure proper performance of the monitor. Failure to do so may adversely affect product
performance and result in sickness or death.
When performing a calibration or calibration verification test (bump test) only use certified
calibration gas at the required concentration level. Do not calibrate with expired calibration gas.
If the instrument cannot be calibrated, do not use until the reason can be determined and
corrected.
Do not cover or obstruct display or visual alarm
Ensure sensor inlets are unobstructed and is free of debris
3
USE INSTRUCTIONS AND LIMITATIONS
! WARNING
Each person using this equipment must read a nd understand the information in these U ser Instructions before use.
Use of this equipment by untrained or unqualified persons, or use that is not in accordance with these User
Instructions, may adversely affect product performance and result in sickness or death.
Use For
The TX-6-ND provides Nitrogen Dioxide detection and automatic exhaust fan control for parking garages,
loading docks, truck and bus depots, firehouses, ambulance bays, warehouses and maintenance facilities.
Nitrogen dioxide or NO2 is a toxic chemical of concern in diesel exhaust. The higher average temperature
of combustion of diesel engines generates more nitrogen oxides than gasoline engines. The TX-6-ND
meets the requirements of the Uniform Building Code for enclosed garages and meets OSHA standards for
Nitrogen Dioxide exposure. TX-6-ND can be used stand alone, with the Macurco DVP-120 Detection and
Ventilation Control Panel, other 12 VAC or 24 VDC fire/security panels or building automation systems.
! WARNING
Use only for monitoring the gas which the sensor and instrument are designed to monitor. Failure to do so may result
in exposures to gases not detectable and cause sickness or death. For proper use, se e supervisor or User
Instructions, or call Technical Service at 1-877-367-7891.
Do Not Use For
The TX-6-ND is not intended for use in hazardous locations or industrial applications such as refineries,
chemical plants, etc. Do not mount the TX-6-ND where the normal ambient temperature is below 0°F or
exceeds 125°F (below -18C or above 52C). The TX-6-ND mounts on a 4x4 electrical box supplied by the
contractor. Do not install the TX-6-ND inside another box unless it has good air flow through it.
! WARNING
This equipment may not function effectively below 0F or above 125F (-18C or above 52C). Using the detector
outside of this temperature range may adversely affect product performance and result in sickness or death.
General Description
The TX-6-ND is a low voltage, dual relay Nitrogen Dioxide (ND) detector and automatic ventilation
controller. The TX-6-ND uses a microcomputer controlled, electronic system to measure the concentration
of Nitrogen Dioxide, actuate relays and provide a 4-20mA output. The TX-6-ND has a field replaceable,
electrochemical sensor (expected life of 2+ years) and optional gas test and calibration kits. The TX-6-ND
is a low level meter capable of displaying from 0-20ppm of Nitrogen Dioxide.
Features
ETL Listed to UL 61010-1
Low level meter capable of displaying from 0-20 ppm Nitrogen Dioxide
The TX-6-ND meets Uniform Building Code for enclosed garages and OSHA standards for gas
exposure
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of exhaust fans
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
TX-6-ND mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & alarm relay to activate
Calibration kit is available. One screw allows access for calibration or gas test
4
Specifications
Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
Current @ 24 VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
Color: Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT
Fan relay actuation: selectable at OFF, 0.2, 0.5, 0.7, 1.0, 1.2, 1.5, 1.7, 2.0, 2.2, 2.5 (default), 2.7,
3.0, 3.2, 3.5, 3.7, 4.0, 4.2, 4.5, 4.7, 5.0 ppm
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Minimum Run Time settings are OFF (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. (default) or N.C.
Alarm relay settings: OFF, 1, 2, 3, 4, 5 (default), 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20
ppm
Current Loop: 4-20 mA for 0-20ppm NO2, selectable to off (default) or on
Buzzer: 85 dBA at 10cm settable to off (default) or on
Digital display: 3 digit LED selectable to off (default) or on.
Operating environ: 0°F to 125°F (-18C to 52C).10 to 90% RH
INSTALLATION AND OPERATING INSTRUCTIONS
The following instructions are intended to serve as a guideline for the use of the Macurco TX-6-ND Nitrogen
Dioxide Detector. It is not to be considered all-inclusive, nor is it intended to replace the policy and
procedures for each facility. If you have any doubts about the applicability of the equipment to your
situation, consult an industrial hygienist or call Technical Service at 1-877-367-7891.
! WARNING
This detector helps monitor for the presence an d concentrati on level of a certain spe cified airborne gas. Misuse may
produce an inaccurate reading, which m eans that h igher le vels of the gas being monit ored may be present and coul d
result in overexposure and cause sickness or death. For pr oper use, see supervisor or User Instructions, or call
Technical Service at 1-877-367-7891.
Location
A TX-6-ND is normally mounted at breathing level, about 5 feet (1.5 meters) above the floor on a wall or
column in a central area where air movement is generally good. The unit, on average, can cover about
5,000 sq. ft. (465 sq. meters). The coverage depends on air movement within the room or facility. Extra
detectors may be needed near any areas where people work or where the air is stagnant. Do NOT mount
the TX-6-ND where the normal ambient temperature is below below 0°F or exceeds 125°F (below -18C or
above 52C).
! WARNING
High voltage relay terminals (120/240 VAC) are located within this detector, presenting a hazard to service
technicians. Only qualified technicians should open the detector case and service the internal circuits. Ensure power
is removed from the detector relays prior to servicing th e unit. Failure to do so may result in sickness or death.
5
Installation
1. The TX-6-ND mounts on a 4” square (or 4x4) electrical box supplied by the contractor. Do not mount
the TX-6-ND inside another box, unless it has good air flow through it.
2. Connect the TX-6-ND to Class 2 power supply only. It is suggested to use a separate transformer for
powering the unit or units because of possible interference’s from other devices on the same power
supply.
3. Connect the TX-6-ND to the control cables with terminal plugs. When making connections, make sure
the power is off.
4. There are two terminals for Power: 12 to 24 VAC or 12 to 32 VDC, with no polarity preference.
5. There are two terminals for the dry alarm relay contacts, again with no polarity preference. The alarm
relay can switch up to 0.5 A 120 V, or 60 VA. The alarm relay is activated if gas reaches or exceeds the
alarm settings. See OPERATION section of these User Instructions for details on relay settings.
6. The alarm relay can be configured to normally open (default) (N.O.) or normally closed (N.C.) and will
activate if the gas concentration exceeds alarm set point. It will deactivate once the gas concentration
drops below the alarm set point. Note that the “disable” setting will cause the alarm relay not to engage
at all.
7. The dry contact, SPDT fan relay has three terminals. The common (COM.), normally open (N.O.) and
the normally closed (N.C.) contact. The fan relay can switch up to 5.0 A up to 240 VAC. See
OPERATION section of these User Instructions for details on relay settings.
8. The Fan Relay can be configured for latching or non-latching (default) when activated (when the gas
concentration exceeds fan relay set point).
9. The Fan Relay will engage if the fan setting Nitrogen Dioxide concentration is exceeded for longer than
the Fan Relay Delay time. Unless it is configured for latching, the fan relay will disengage once both of
these conditions have been met:
Nitrogen Dioxide concentration has dropped below fan setting
Fan Relay Run time has been exceeded
Note that the “disable” fan setting will cause the fan relay to not engage. The fan relay will engage in
trouble fault condition and will disengage once trouble fault condition is cleared.
10. The Current Loop is 4 mA in clean air and 20 mA for 20 ppm Nitrogen Dioxide
6
Loading...
+ 12 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.