Power-up Test setting 12
Display setting 12
Buzzer setting 12
Alarm Relay setting 13
Alarm Relay Configuration 13
Fan Relay setting 13
Fan Relay Delay setting 14
Fan Relay Minimum Runtime setting 14
Fan Relay Latching setting 14
Trouble Fan Setting 14
4-20mA Output setting 14
Operation Test 17
Manual Operation Test 18
Refrigerant Gas Test 18
Quick Gas Test 22
3
GENERAL SAFETY INFORMATION
Intended Use
The Macurco RD-6 is a low voltage, dual relay Refrigerant (REF) detector, controller and transducer. The RD-6 has selectable 4-20 mA
output, buzzer and digital display options. It is an electronic detection system used to measure the concentration of refrigerant gas and
provide feedback and automatic exhaust fan control to help reduce refrigerant gas concentrations in industrial refrigeration, cold
storage, warehouses, hockey rinks or other commercial applications. The RD-6 is a low level meter capable of detecting several
refrigerants including R-22, R-134A, R-404A, R-407C and R-410A, and displaying from 0-1,000 ppm of refrigerant gas. The RD-6 is
factory calibrated and 100% tested for proper operation.
List of Warnings and Cautions within these User Instructions
! WARNING
Each person using this equipment must read and understand the information in these User Instructions before use. Use of this
equipment by untrained or unqualified persons, or use that is not in accordance with these User Instructions, may adversely affect
product performance and result in sickness or death.
Use only for monitoring the gas which the sensor and instrument are designed to monitor. Failure to do so may result in exposures
to gases not detectable and cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical
Service at 1-877-367-7891.
This equipment may not function effectively below 0F or above 125F (-18C or above 52C). Using the detector outside of this
temperature range may adversely affect product performance and result in sickness or death.
This detector helps monitor for the presence and concentration level of a certain specified airborne gas. Misuse may produce an
inaccurate reading, which means that higher levels of the gas being monitored may be present and could result in overexposure
and cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical Service at 1-877-367-7891.
High voltage terminals (120/240 VAC) are located within this detector, presenting a hazard to service technicians. Only qualified
technicians should open the detector case and service the internal circuits. Ensure power is removed from the detector relays prior
to servicing the unit. Failure to do so may result in sickness or death.
Do not disassemble unit or attempt to repair or modify any component of this instrument. This instrument contains no user
serviceable parts, and substitution of components may impair product performance and result in sickness or death.
Using a certified gas with a concentration other than the one listed for this detector when conducting a calibration or calibration
verification test (bump test) will produce inaccurate readings. This means that higher levels of the gas being monitored may be
present and could result in overexposure and cause sickness or death. For proper use, see supervisor or User Instructions, or
call Technical Service at 1-877-367-7891
The following steps must be performed when conducting a calibration verification test (bump test) to ensure proper performance of
the monitor. Failure to do so may adversely affect product performance and result in sickness or death. When performing a calibration verification test (bump test) only use certified calibration gas at the required concentration level.
Do not test with expired calibration gas.
If the instrument cannot be tested, do not use until the reason can be determined and corrected.
Do not cover or obstruct display or visual alarm cover.
Ensure sensor inlets are unobstructed and free of debris
4
USE INSTRUCTIONS AND LIMITATIONS
! WARNING
Each person using this equipment must read and understand the information in these User Instructions before use. Use of this
equipment by untrained or unqualified persons, or use that is not in accordance with these User Instructions, may adversely affect
product performance and result in sickness or death.
Use For
The RD-6 provides refrigerant gas detection and automatic exhaust fan control for industrial refrigeration, cold storage, warehouses or
other commercial applications. The RD-6 is capable of detecting several refrigerants including R-22, R-134A, R-404A, R-407C and R410A. Refrigerants are colorless and nearly odorless liquids or gases divided into two groups according to toxicity and flammability. See
ANSI/ASHRAE Standard 34-2007 - Designation and Safety Classification of Refrigerants for details. Always review the refrigerant
MSDS and safety classifications before use. RD-6 can be used stand alone, with the Macurco DVP-120 Detection and Ventilation
Control Panel, other 12 VAC or 24 VDC fire/security panels or building automation systems.
! WARNING
Use only for monitoring the gas which the sensor and instrument are designed to monitor. Failure to do so may result in exposures to
gases not detectable and cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical Service at 1877-367-7891.
Do Not Use For
The RD-6 is not intended for use in hazardous locations. Do not mount the RD-6 where the normal ambient temperature is below 0°F
or exceeds 125°F (below -18C or above 52C). The RD-6 mounts on a 4x4 electrical box supplied by the contractor. Do not install the
RD-6 inside another box unless it has good air flow through it.
! WARNING
This equipment may not function effectively below 0F or above 125F (-18C or above 52C). Using the detector outside of this
temperature range may adversely affect product performance and result in sickness or death.
General Description
The RD-6 is a low voltage, dual relay refrigerant gas detector and automatic ventilation controller. The RD-6 uses a microcomputer
controlled, electronic system to measure the concentration of refrigerant gas, actuate relays and provide a 4-20mA output. The RD-6
has a long life solid-state sensor (expected life of 7+ years). The RD-6 is a low level meter capable of displaying from 0-1,000ppm of
refrigerant gas.
5
Features
ETL Listed to UL 61010-1 and CAN/CSA C22.2 No 61010-1
Low level meter capable of displaying from 0-1,000 ppm refrigerant gas
Selectable fan and alarm relay activation
5 A SPDT fan relay controls starters of exhaust fans
0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
4-20 mA Current Loop
RD-6 mounts on a standard 4x4 electrical box and becomes cover for the box
Supervised system: any internal detector problem will cause the fan & alarm relay to activate
Calibration verification test kit is available. One screw allows access for calibration or gas test
Specifications
Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
Current @ 24 VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by
Shipping Weight: 1 pound (0.45 kg)
Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
Color: Dark gray
Connections: plugs/terminals
Mounting box: (not included) 4x4 electric
Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
Fan relay actuation: selectable at diS (disable), 100 (default), 150, 200, 250, 300, 350ppm
Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
Fan relay latching or not latching (default) selectable
Alarm relay: 0.5A 120 V, 60 VA
Alarm relay actuation: selectable N.O. (default) or N.C.
Alarm relay settings: diS, 100, 150, 200, 250, 300 (default), 350, 400, 450, 500, 550 or 600ppm
Current Loop: 4-20 mA for 0-1,000 ppm refrigerant gas, selectable to off or on (default)
Buzzer: 85 dBA at 10cm settable to on (default) or off
Digital display: 3 digit LED selectable to on (default) or off
Operating environ: 0°F to 125°F (-18C to 52C).10 to 90% RH non-condensing
6
INSTALLATION AND OPERATING INSTRUCTIONS
The following instructions are intended to serve as a guideline for the use of the Macurco RD-6 Refrigerant Detector. It is not to be
considered all-inclusive, nor is it intended to replace the policy and procedures for each facility. If you have any doubts about the
applicability of the equipment to your situation, consult an industrial hygienist or call Technical Service at 1-877-367-7891.
! WARNING
This detector helps monitor for the presence and concentration level of a certain specified airborne gas. Misuse may produce an
inaccurate reading, which means that higher levels of the gas being monitored may be present and could result in overexposure and
cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical Service at 1-877-367-7891.
Location
A RD-6 is normally mounted low in the room on a wall or column one foot above the floor in a central area where air movement is
generally good. Use the same spacing as for smoke detectors, 30-foot centers, 900 square feet per detector (84 sq. meters). The
coverage depends on air movement within the room or facility. Extra detectors may be needed near any areas where people work or
where the air is stagnant. The RD-6 mounts on a 4x4 electrical box supplied by the contractor. Do not install the RD-6 inside another
box unless it has good air flow through it. Do NOT mount the RD-6 where the normal ambient temperature is below 0°F or exceeds
125°F (below -18°C or above 52°C).
! WARNING
High voltage terminals (120/240 VAC) are located within this detector, presenting a hazard to service technicians. Only qualified
technicians should open the detector case and service the internal circuits. Ensure power is removed from the detector relays prior to
servicing the unit. Failure to do so may result in sickness or death.
Installation
1. The RD-6 mounts on a 4” square (or 4x4) electrical box supplied by the contractor. Do not mount the RD-6 inside another box,
unless it has good air flow through it.
2. Connect the RD-6 to Class 2 power supply only. It is suggested to use a separate transformer for powering the unit or units
because of possible interference’s from other devices on the same power supply.
3. Connect the RD-6 to the control cables with terminal plugs. When making connections, make sure the power is off.
4. There are two terminals for Power: 12 to 24 VAC or 12 to 32 VDC, with no polarity preference.
5. There are two terminals for the dry alarm relay contacts, again with no polarity preference. The alarm relay can switch up to 0.5
A 120 V, or 60 VA. The alarm relay is activated if gas reaches or exceeds the alarm settings. See OPERATION section of
these User Instructions for details on relay settings.
7
6. The alarm relay can be configured to normally open (default) (N.O.) or normally closed (N.C.) and will activate if the gas
concentration exceeds alarm set point. It will deactivate once the gas concentration drops below the alarm set point. Note that
the “disable” setting will cause the alarm relay not to engage at all.
7. The dry contact, SPDT fan relay has three terminals. The common (COM.), normally open (N.O.) and the normally closed
(N.C.) contact. The fan relay can switch up to 5.0 A up to 240 VAC. See OPERATION section of these User Instructions for
details on relay settings.
8. The Fan Relay can be configured for latching or non-latching (default) when activated (when the gas concentration exceeds fan
relay set point). Once latched in, power will need to be interrupted or the “TEST” button pressed to un-latch the relay condition.
9. The Fan Relay will engage if the fan setting refrigerant concentration is exceeded for longer than the Fan Relay Delay time.
Unless it is configured for latching, the fan relay will disengage once both of these conditions have been met:
Refrigerant gas concentration has dropped below fan setting
Fan Relay Run time has been exceeded
Note that the “disable” fan setting will cause the fan relay to not engage. The fan relay will engage in trouble fault condition (if
the Trouble Fan Setting Option is set to “On”) and will disengage once trouble fault condition is cleared.
10. The Current Loop is 4 mA in clean air and 20 mA for 1,000 ppm refrigerant gas
8
9
10
In this application (above) the Fan or primary relay is used as a low level alarm relay. The Alarm or secondary relay is used as a
supervisory relay when utilized in the normally closed configuration. The RD-6 monitors all critical functions of the unit through
software diagnostics that continually test and verify its operations. If a problem is found, the unit will switch to a fail-safe/error mode or
trouble condition. In this error mode the Fan* and Alarm relays will be activated indicating the trouble condition at panel and the RD-6
display will flash the error. *See the Trouble Fan Setting Option.
Power Up
The RD-6 steps through an internal self-test cycle for the first minute that it is powered. The unit will execute the test cycle any time
power is dropped and reapplied (i.e. power failure). During the self-test cycle the unit will display the firmware version number, then
count down from 60 to 0 (if the display option is “on”) and finally go into normal operation. The alarm relay will be activated for 10
seconds and the fan relay for 60 seconds during the power-up cycle unless the “Power Up Test” (PUt) option is OFF. The indicator light
(LED) will flash green during the self-test cycle. At the end of the 1 minute cycle, the unit will take its first sample of the air and the
indicator light will turn solid green.
Operation
1. With the display function turned “On”, the RD-6 will show the current concentration of refrigerant gas ppm or “0” (zero) in clean
air. When the gas concentration reaches the Fan Relay setting (100 ppm, for example) the display will flash back and forth
between “FAn” and “100”. With the display function turned ”OFF”, the display does not show the refrigerant gas concentration,
but will show “FAn” as long as the fan relay is activated.
2. With the display function turned “On” and the refrigerant gas concentration reaching the Alarm Relay setting, (200 ppm, for
example) the display will flash back and forth between “ALr” and “200”. The buzzer will sound indicating “Alarm” if the buzzer is
turned “On”. With the display function turned off the display does not show the refrigerant gas concentration, but will show “ALr”
when the Alarm relay is activated.
11
3. With the 4-20 mA function turned “On” and the refrigerant gas concentration climbing, the 4-20 mA signal will ramp up
corresponding to the concentration (0-300 ppm, for example). The display will show “FAn” and “ALr” and sound as outlined
above.
Default Configuration – Factory Settings
The default Power Up Test setting is ON
The default Display setting is ON
The default Buzzer setting is ON
The default Alarm RelaySetting is activation at 300 ppm
The default Alarm RelayConfiguration setting is Normally Open
The default Fan RelaySetting is activation at 100 ppm
The default Fan Relay Delay setting is 3 minutes
The default Fan Relay Minimum Runtime setting is 0 minutes
The default Fan RelayLatching condition is OFF
The default Trouble Fan Setting condition is OFF
The default 4-20mAOutput setting is ON
To change settings, remove the Philips screw on the front of the RD-6. Pull off the front cover of the unit.
12
Selecting Default Configuration – “dEF”
To select the Default Configuration, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the Enter button to enter the Con menu. The first selection is the “dEF” or Default setting. Push Enter. If it is already in Default
configuration, there will be no action. If it is not already in Default configuration, “nO” will be displayed. Push Next to change it to “yES”
(flashing) then push Enter to confirm the change (solid) and push Enter again to return to “dEF” in the con menu. Push Next until “End”
is displayed then push Enter to get back to normal operation.
Selecting Power Up Test Option – “PUt”
To select the Power Up Test Configuration, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then
push the Enter button to enter the Con menu. Then push the Next button to get to the second selection “PUt” or Power Up Test
setting. Push Enter. If the test is “On” push Next to turn it “OFF” (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to “PUt” in the Con menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
Selecting Display Option – “dSP”
To select the Display Configuration, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the
Enter button to enter the Con menu. Then push the Next button to get to the third selection “dSP” or Display setting. Push Enter. If
the display is “On” push Next to turn it “OFF” (flashing) then push Enter to confirm the change (solid) and push Enter again to return to
“dSP” in the Con menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
Selecting Buzzer Option – “bUZ”
To select the Buzzer Configuration, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the
Enter button to enter the Con menu. The fourth selection is the “bUZ” or Buzzer setting. Push Next twice to get to “bUZ” then Enter. If
the display is “On” push Next to turn it “OFF” (flashing) then push Enter to confirm the change (solid) and push Enter again to return to
“bUZ” in the Con menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
Selecting Alarm Relay Setting – “ArS”
To select the Alarm Relay Setting, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the
Enter button to enter the Con menu. The fifth selection is the “ArS” or Alarm Relay Setting. Push Next three times to get to “ArS” then
Enter. If the display is “diS” (disabled) push Next to change it to 100, 150, 200, 250, 300 (default), 350, 400, 450, 500, 550 or 600ppm
(flashing) then push Enter to confirm the change (solid) and push Enter again to return to “ArS” in the Con menu. Push Next until “End”
is displayed then push Enter to get back to normal operation.
Selecting Alarm Relay Configuration – “Arc”
To select the Alarm Relay Configuration, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push
the Enter button to enter the Con menu. The sixth selection is the “Arc” or Alarm Relay Configuration. Push Next four times to get to
“Arc” then Enter. If the relay is “nO” (normally open) push Next to turn it to “nC” (flashing) then push Enter to confirm the change (solid)
and push Enter again to return to “Arc” in the Con menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
13
Selecting Fan Relay Settings – “FrS”
To select the Fan Relay setting, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the Enter
button to enter the Con menu. The seventh selection is the “FrS” or Fan Relay setting. Push Next five times to get to “FrS” then
Enter. If the fan relay is “diS” (disabled) push Next to change it to 100 (default), 150, 200, 250, 300, 350 ppm (flashing) then push
Enter to confirm the change (solid) and push Enter again to return to “FrS” in the Con menu. Push Next until “End” is displayed then
push Enter to get back to normal operation.
Selecting Fan Relay Delay – “Frd”
To select the Fan Relay Delay setting, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the
Enter button to enter the Con menu. The eighth selection is the “Frd” or Fan Relay Delay. Push Next six times to get to “Frd” then
Enter. If the delay is “0” (zero minutes) push Next to change it to 1, 3, 5, or 10 minutes (flashing) then push Enter to confirm the
change (solid) and push Enter again to return to “Frd” in the Con menu. Push Next until “End” is displayed then push Enter to get back
to normal operation.
Selecting Fan Relay Minimum Runtime – “Frr”
To select the Fan Relay Minimum Runtime setting, in normal mode, push the Next button to get to “Con” or the Configuration menu.
Then push the Enter button to enter the Con menu. The ninth selection is the “Frr” or Fan Relay Minimum Runtime. Push Next seven
times to get to “Frr” then Enter. If the runtime is “0” (zero minutes) push Next to change it to 3, 5, 10 or 15 minutes (flashing) then push
Enter to confirm the change (solid) and push Enter again to return to “Frr” in the Con menu. Push Next until “End” is displayed then
push Enter to get back to normal operation.
Selecting Fan Relay Latching Option – “FrL”
To select the Fan Relay Latching Option, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push
the Enter button to enter the Con menu. The tenth selection is the “FrL” or Fan Relay Latching Option. Push Next nine times to get to
“FrL” then Enter. If latching is “OFF” push Next to turn it to “On” (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to “FrL” in the Con menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
Selecting Trouble Fan Setting Option – “tFS”
To select the Trouble Fan Setting Option, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then
push the Enter button to enter the Con menu. The eleventh selection is the “tFS” or Trouble Fan Setting Option. Push Next ten times
to get to “tFS” then Enter. If Trouble Fan Setting is “OFF” push Next to turn it to “On” (flashing) then push Enter to confirm the change
(solid) and push Enter again to return to “tFS” in the Con menu. Push Next until “End” is displayed then push Enter to get back to
normal operation.
Selecting 4-20mA Output Option – “420”
To select the 4-20mA Output Option, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the
Enter button to enter the Con menu. The twelfth selection is the “420” or 4-20mA Output Option. Push Next eleven times to get to “420” then Enter. If the 4-20mA is “On” push Next to turn it to “OFF” (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to “420” in the Con menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
14
On-board Diagnostics
The RD-6 monitors all critical functions of the unit through software diagnostics that continuously test and verify unit operations. If a
problem is found, the unit will switch to a fail-safe/error mode or trouble condition. In this error mode, the Alarm relay will be activated,
the 4-20 mA current loop will go to 24 mA, the unit will display the error code, the green status indicator LED light will flash and the
buzzer will chirp intermittently. The Fan relay will also engage if the Trouble Fan Setting Option is set to “On”. This is a safety
precaution. To clear this mode, simply turn off power to the unit for a few seconds, or push the ENTER/TEST switch (inside the unit).
This will cause the unit to restart the 1 minute self-test cycle.
The 4-20 mA signal can be used for troubleshooting:
0 mA is most likely a connection problem
4-20 mA is normal gas reading range (0-1,000 ppm)
24 mA indicates a Trouble condition
Error Codes
t01 Sensor missing
t02 Temperature compensation failure
t04 EEPROM bad checksum
t10 Bad EEPROM
t20 Bad calibration
t40 Factory calibration failure
t80 Read ADC failure
t100 Under range
t200 Sensor warranty expired
Note: For trouble codes over 080 the display will alternate between t_1 and t00 for t100 and between t_2 and t00 for t200.
If the error mode repeats frequently, check for continuous power and proper voltage. If power is not the problem and a unit has
repeating error conditions, it may need to be returned to Macurco for service, per these User Instructions.
15
Sensor Poisons
The gas sensor in the detector is designed with extreme sensitivity to the environment. Alcohols, ammonia, cleaning solvents, paint
thinner, gasoline vapors, and aerosol propellants may cause nuisance alarms.
In addition, the sensing function may be deteriorated if it is exposed to a direct spray from aerosols such as paints, silicone vapors, etc.,
or to a high density of corrosive gases (such as hydrogen sulfide or sulfur dioxide) for an extended period of time.
MAINTENANCE
The RD-6 is low maintenance. The unit uses a long life solid-state sensor that has a 7+ year life expectancy (in normal conditions). The
detector’s performance should be tested regularly by using gas as detailed in the Gas Testing section. All maintenance and repair of
products manufactured by Macurco are to be performed at the appropriate Macurco manufacturing facility. Macurco does not sanction
any third-party repair facilities. Note: There is no field calibration procedure for the Macurco RD-6.
End-of-Life Signal
The RD-6 has a long life, non-replaceable solid-state sensor. Seven (7) years after the RD-6 is installed the sensor end-of-life signal will
be activated indicating that the RD-6 has reached the end of its typical usable life. The end-of-life signal will cause an error code t200
“Sensor expired”. See Error Codes section. The end-of-life signal can be silenced for 48 hours by pressing the "ENTER/TEST" button
or by temporarily dropping power to the unit. The end-of-life signal provides the user an opportunity to test the sensor assuring that it is
still performing within acceptable parameters though the sensor is nearing the end of its expected life. The silence function will continue
to be available for 29 days after the RD-6 initiates the initial end-of-life signal. After this 29 day period the RD-6 can no longer be
silenced and the sensor life must be reset or the RD-6 detector replaced.
Sensor Life Reset
1. Remove the Philips screw on the front of the RD-6. Pull the front cover of the unit off.
2. To reset the sensor life (rSt), from normal or warm-up mode, press the Next button four times to get to “SEn” or Sensor Mode.
3. Then press the Enter button to get to “rSt” - Reset Sensor Mode.
4. Press the Enter button again to see the sensor reset status. If the sensor life has already been reset, done “don” will be
displayed. If it has not already been reset, “nO” will be displayed. Push Next to change it to “ yES” (flashing) then push Enter to
confirm the change (solid) and push Enter again to return to "rSt” in the “SEn” menu. Push Next until “End” is displayed then
push Enter to get back to normal operation. Note: The sensor life will be reset for 1 year.
Note: If the sensor is reset and the detector not replaced, it is necessary to test the sensor to assure that it is still performing within
acceptable specifications though the sensor is nearing the end of its expected life. There will be no other indication of sensor
performance.
16
! WARNING
Do not disassemble unit or attempt to repair or modify any component of this instrument. This instrument contains no user serviceable
parts, and substitution of components may impair product performance and result in sickness or death.
CAUTION
Avoid the use of harsh cleaning materials, abrasives and other organic solvents. Such materials may permanently scratch the surfaces
and damage the display window, labels, sensor or instrument housing. High voltage terminals (100-240VAC) are located within this
detector, presenting a hazard to service technicians. Only qualified technicians should open the detector case and service the internal
circuits. Ensure power is removed from the detector prior to cleaning the unit. Failure to do so may result in sickness or death.
Cleaning
Cleaning of the external surfaces is best carried out using a damp cloth with a mild detergent or soap. Use a vacuum cleaner with soft
brush to remove dust or contamination under the cover. Do not blow out the sensor with compressed air.
TESTING
! WARNING
Using a certified gas with a concentration other than the one listed for this detector when conducting a calibration or calibration
verification test (bump test) will produce inaccurate readings. This means that higher levels of the gas being monitored may be present
and could result in overexposure and cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical
Service at 1-877-367-7891.
General
All RD-6 units are factory calibrated and 100% tested for proper operation. During normal operation the green status indicator LED light
will be on steady, the fan & alarm relay will be in standby mode and the 4-20 mA output will be at 4mA (in clean air).The unit also
performs a regular automatic self-test during normal operation. If the unit detects an improper voltage or inoperable component, it will
default into Error mode. In this error mode, the Alarm relay will be activated, the 4-20 mA current loop will go to 24 mA, the unit will
display the error code, the green status indicator LED light will flash and the buzzer will chirp intermittently. The Fan relay will also
engage if the Trouble Fan Setting Option is set to “On”.
Operation Test
Check that the green RD-6 status indicator LED light is illuminated continuously. If not, do not proceed with the tests. If the unit is in
error mode contact your local representative or Macurco technical service representative for information on resolving the problem.
1. Remove the single screw in the middle of the front cover of the RD-6.
2. Remove the front cover.
17
3. Observe the LED light on the front of the RD-6.
4. If the light is solid green proceed to step 6.
5. If the green status indicator LED light is off or flashing, refer to the General section above.
6. Locate the switch labeled ENTER/TEST on the left side of the printed circuit board. Press the Test switch once.
7. The RD-6 will step through a cycle test:
a. The display progresses through the BUZ (Buzzer Test) Art (alarm relay test), Frt (fan relay test) then 42t (4-20 mA output
test). Make sure that the settings are “On” or not disabled “diS”.
b. During the first 10 seconds of the test cycle, the display will show BUZ and set off the audible buzzer
c. The alarm relay will be closed, so any devices connected to that relay will be tested.
d. The Fan relay will be activated for the next 1 minute of the test, so if the fan circuits are wired in the normal manner, the fan
should run.
e. The 4-20mA output will then ramp up from 4 to 16 mA over the next 130 seconds of the test, so if the circuit is wired in the
normal manner, the control panel or building automation system should respond.
f. At the end of the test cycle, the light will turn green and be on steady (Normal Operation), the fan & alarm relay will be in
standby mode and the 4-20 mA output will return to 4 mA (in clean air).
8. When testing is completed reassemble the unit or units.
Manual Operation Test
This option gives the user the opportunity to manually initiate an individual test for each relay, the analog output and the sensor
response to gas. From normal operation mode press the Next button 2 times to get to the Test Mode (tSt). Press the Enter button once
to get into the Test Menu. Press the Next button to scroll through the five test options and press Enter to initiate the selected test. Note
that if the relay or 4–20 mA output has been disabled, the test selection will not be displayed in the test menu.
bUZ – Buzzer Test, 3 seconds
Art - Alarm Relay Test, 5 seconds
Frt - Fan Relay Test, 60 seconds
42t - 420 loop test, 130 seconds
gtS - Gas Test, 3 minutes (no output to the panel during the gas test)
The display will flash during the test, or in the case of the gas test, the gas level will alternate with gtS. Once the test is complete, the
display will return to steady display. To exit the test menu, press the Next button until “End” is displayed then press Enter to return to
normal mode.
18
Refrigerant Gas Test
! WARNING
The following steps must be performed when conducting a calibration verification test (bump test) to ensure proper performance of the
monitor. Failure to do so may adversely affect product performance and result in sickness or death.
When performing a calibration verification test (bump test) only use certified calibration gas at the required concentration level.
Do not test with expired calibration gas.
If the instrument cannot be tested, do not use until the reason can be determined and corrected.
Do not cover or obstruct display or visual alarm cover.
Ensure sensor inlets are unobstructed and free of debris
General
The RD-6 calibration can be verified or bump-tested with the RD-FTK with R-134a refrigerant gas, regulator and test hood, available
through your local representative or from Macurco.
Note: For optimum test results it is suggested that the unit be in clean air (green light on steady) and be in a low ambient air flow.
Contents of the FTK
RD-FTK: (1) Gas Cylinder, 300 ppm R-134a refrigerant gas in air
Gas regulator with about two feet of plastic tubing
Humidifier
Test hood
FTK Information
Several detectors can be tested with one FTK. The only limitation is the amount of gas in the cylinder and the flow of the regulator. The
34 liter cylinder for example with a 0.2LPM regulator has approximately 170 minutes of continuous calibration run time. Replacement
cylinders are available. The gas cylinder should be replaced when the pressure gauge on the regulator shows 25-psi or less.
Note: Gas testing results can vary depending upon temperature, humidity, test duration and other variables. For optimum results it is
suggested that the unit be in continuous operation for a minimum of 72 hours, in a stable environment and at standard conditions
before proceeding with testing.
Gas Testing
Preparing the Humidifier
1. Open the two plastic halves of the humidifier by holding one half steady and turning the other one counterclockwise. Then pull them
apart.
2. Pull out the orange sponge and wet it.
3. Squeeze the sponge such that there are not any visible drops of water on the sponge (it should only be damp).
4. Put the sponge back into the humidifier housing and close it.
19
Assembling the Regulator, Hose and Test Hood
1. Open the FTK. Connect the 300 ppm gas cylinder to the regulator.
2. Connect a 6 inch piece of tubing from the non-sponge end of the humidifier to the test hood.
3. Connect the sponge end of the humidifier to the tubing from the regulator
Testing the Fan Relay
1. Remove the Philips screw on the front of the RD-6. Remove the front cover.
2. Check the pressure gauge on the regulator. If you have 25-psi or less you will need to replace the gas canister.
3. Place the Test Hood over the gas sensor.
Note: The time to activate the Fan relay depends on the delay setting.
4. Turn on the regulator to start the gas flow and wait with the gas applied continuously.
5. With the display function turned “On”, the RD-6 will show the current concentration of gas or “0” (zero) in clean air. When the gas
concentration reaches the Fan Relay setting (100 ppm, for example) the display will flash back and forth between “FAn” and “100”.
With the display function turned ”OFF”, the display does not show the gas concentration, but will show “FAn” as long as the fan
relay is activated.
20
Note: If the Fan relay does not change state within 2 minutes, there are four possibilities:
a. Gas cylinder is empty, check the pressure gauge. Replace the gas cylinder if 25psi or less.
b. Detector has fan relay set to disable (diS) or higher than 300 ppm. Set fan relay to 100 ppm and repeat the test.
c. Detector has fan relay delay set to 3 or more minutes. Set fan relay to 0 minutes and repeat the test.
d. Detector is in need of servicing (return unit to factory for servicing).
6. Remove the gas from the sensor. Proceed to Test the Alarm relay or replace the top cover. Fan relay test is complete.
Testing the Alarm Relay
Note: The gas concentration to activate the Alarm relay depends on the setting.
1. Connect the 300 ppm cylinder of Refrigerant to the regulator.
2. Check the pressure gauge. If there is 25psi or less the cylinder should be replaced.
3. Place the test hood over the gas sensor. Turn on the regulator to start the gas flow.
4. The Fan relay should activate according to the settings.
5. With the display function turned “On” and the gas concentration reaching the Alarm Relay setting, (150 ppm, for example) the
display will flash back and forth between “ALr” and “150”. The buzzer will sound indicating “Alarm” if the buzzer is turned “On”.
With the display function turned off the display does not show the gas concentration, but will show “ALr” when the Alarm relay
is activated.
Note: If the Alarm relay fails to operate within 2 minutes, there are three possibilities:
a. Gas cylinder is empty, check the pressure gauge. Replace the gas cylinder if 25-psi or less.
b. Detector has Alarm relay set to disable (diS) or higher than 300 ppm. Set Alarm relay to 150 ppm and repeat the test.
c. Detector is in need of servicing (return unit to factory for servicing).
6. Remove the gas from the sensor after Test. Proceed to Test the 4-20mA output or replace the top cover. Alarm relay test is
complete.
Testing the 4-20mA current loop
1. Connect the 300 ppm cylinder of Refrigerant to the regulator.
2. Check the pressure gauge. If there is 25-psi or less the cylinder should be replaced.
3. Place the test hood from the regulator over the gas sensor. Turn on the regulator to start the gas flow.
4. The Fan relay should activate according to the settings.
5. The Alarm relay should activate according to the settings.
6. The 4-20 mA output should ramp up from 4mA in clean air to 9 mA at 300 ppm. See 4-20 mA diagram on page 7.
Note: If the 4-20mA output does not ramp up within 2 minutes, there are three possibilities:
21
a. Gas cylinder is empty, check the pressure gauge. Replace the gas cylinder if 25-psi or less.
b. Detector has 4-20 mA option set to “OFF”. Set 4-20mA option to “On” and repeat the test.
c. Detector is in need of servicing (return unit to factory for servicing).
7. Remove the gas from the sensor. Re-assemble the RD-6 (make sure the LED is aligned with the front case hole). 4-20 current
loop test is complete.
Quick Gas Test
A butane cigarette lighter can be used to perform a functionality test of the RD-6. This test allows installers to do a quick functionality
test of the gas sensor.
1. Units to be tested must be powered continuously for a minimum of 3 minutes before proceeding.
2. For optimum test results, the unit should be in clean air and be in a low ambient air flow.
3. Check that the RD-6 status indicator light is illuminated, green continuously. If not, do not proceed with tests. See RD-6 Trouble
Indicator section in these User Instructions.
4. The display option should be set to “On” and reading 0 ppm in clean air.
5. With the RD-6 cover on, aim the lighter into the sensor grate area (under “DO NOT PAINT”) on the front cover and release the
gas (without igniting the flame) for 1 second or less
6. Wait for a few seconds. The digital display should climb indicating the increased gas concentration at the sensor confirming a
pass of the quick test.
Note: If the Display does not change within 10 seconds, consider these possibilities:
a. Lighter is empty.
b. Detector is in need of servicing (return unit to factory for servicing).
7. Wait for the display to return to 0 ppm and configure options to desired settings.
22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.