Macurco OX-6 Specsheet

Macurco Oxygen Detector
OX-6
GAS DETECTION
Detector, Controller and Transducer
Oxygen Detection and Control
The Macurco OX-6 is a low voltage, dual relay Oxygen (O selectable 4-20 mA output, buzzer and digital display options. It is an electronic detection system used to measure the concentration of Oxygen and provide feedback and automatic exhaust fan control to help maintain appropriate Oxygen concentrations in commercial applications. The OX-6 is a low level meter capable of detecting from 0-25% by volume of Oxygen.
Selectable options include:
• Fan relay actuation: selectable at 18, 18.1… , 20.2 (default), 20.3, 20.4 & 20.5% v/v and high 23.5 % v/v (preset)
• Output: Fan relay, Alarm relay and 4-20mA current loop
• Controls: Digital display (0-25% v/v), buzzer, fan delay, fan minimum runtime
Installation
• Mounts on a standard 4” x 4” electrical box
• 5 A SPDT fan relay controls valves, louvers or exhaust fans
• 0.5 A N.O. or N.C alarm relay connects to warning devices or control panels
• 4-20mA current loop - compatible with the Macurco DVP-120 Control Panel
• Factory calibrated
2) detector, controller and transducer. The OX-6 has
Other Features
• Supervised system design: detector problem will cause the fan & alarm relay to activate
• Optional calibration test kit allows the OX-6 to be field calibrated and tested
ETL Listed to UL 61010-1, CAN/CSA C22.2 No 61010-1
Manufactured by Aerionics, Inc. Sioux Falls, SD – Phone: 1-877-367-7891 – Email: info@aerionicsinc.com – www.macurco.com
OX-6 Specifications
• Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
• Current @ 24 VDC: 75 mA in alarm, 50 mA fan relay on and 23 mA stand by
• Shipping Weight: 1 pound (0.45 kg)
• Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
• Color: Dark gray
• Connections: plugs/terminals
• Mounting box: (not included) 4x4 electric
• Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
• Fan relay actuation: selectable at OFF, 18, 18.1… , 20.2 (default),
20.3, 20.4 & 20.5% v/v and high 23.5 % v/v (preset)
• Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
• Fan Minimum Runtime settings are OFF (default), 3, 5, 10 or 15 minutes
• Current Loop, 4-20 mA for 0-25% v/v O2
• Alarm relay: 0.5A 120 V, 60 VA
• Alarm relay actuation: selectable N.O. default or N.C.
OX-6 Rear View
• Alarm relay settings: OFF, 18.5, 19, 19.5 (default), 20, 20.5 and high 23.5 % v/v (preset)
• Operating Environment: 0°F to 125° F (-18°C to 52°C),10 to 90% RH non-condensing
Location
An OX-6 is normally mounted at breathing level, about 5 feet (1.5 meters) above the floor on a wall or column in a central area where air movement is generally good. Use the same spacing as for smoke detectors, 30-foot centers, 900 square feet per detector (84 sq. meters). The coverage depends on air movement within the room or facility.
Extra detectors may be needed near any areas where people work or where the air is stagnant. The OX-6 mounts on a 4x4 electrical box supplied by the contractor. Do not install the OX-6 inside another box unless it has good
air flow through it. Do NOT mount the OX-6 where the normal ambient temperature is below 0°F or exceeds 125°F (below -18°C or above 52°C).
TYPICAL CONNECTION OF OX-6
Alarm Control Panel
Auxiliary functions
such as dialers.
N.O. or N.C.
initiating circuit
12 or 24 V power
battery backed up
+
-
4-20 mA Loop
N.C.
POWER
12 or 24 V
N.O.
OX-6
ALARM
RELAY
SPDT fan
RELAY
TYPICAL COVERAGE 900 SQUARE FEET
Exhaust
Fan
coil
RELAY
12 or
24 V
coil