Macurco DVP-120M Specsheet

Macurco Control Panel
DVP-120M
GAS DETECTION
Addressable Detection and Control
Addressable Detection and Ventilation Control Panel
The DVP-120M exhaust fan controller provides automatic control to help maintain an acceptable environment in parking garages or other facilities. The DVP-120M system is designed to meet specifications for safety in enclosed parking garages, including the Uniform Building Code and OSHA 50ppm CO requirements. Using the Macurco MRS-485 Modbus adapter and 6-Series detectors, the DVP-120M can control up to 87 addressable gas detectors.
Features
• External keypad for user selection of the transducer/alarm display and setting the configuration
• Externally visible LCD display showing the status of each transducer and relay
• Externally visible system, alarm and relay status indicators
• Compatible with all Macurco 6-Series gas detectors and MRS-485 adapter
• Twelve analog (current loop) input channels
• Three 10A, 240 VAC SPDT fan/alarm relays
• Drivers for external Horn and Strobe
• Fail safe operation can be implemented
• Lockable NEMA 1 type enclosure
• Modular input and output connectors
• Up to three ventilation control zones can be defined
• ETL Listed to UL 508A, CAN/CSA-C22.2 No. 14-13
• Each zone can be controlled based on transducer signals and/or time of day
®
Manufactured by Aerionics, Inc. Sioux Falls, SD – Phone: 1-877-367-7891 – Email: info@aerionicsinc.com – www.macurco.com
DVP-120M Specifications
• Power Input: 90 – 250 VAC, 1 Amp, 47 – 63 Hz, single phase
• Size: 10.5” x 12.5” x 2.” (267 mm x 318 mm x 51 mm)
• Weight: 6 ½ lb (2.9 kg)
• Enclosure: NEMA 1 Type
• Operating Temperature: 32 to 104°F (0° to 40°C )
• Operating Humidity: 0% to 95% RH non-condensing
• Relay Rating (3): SPDT, 120/240 VAC, 10 A resistive
• LCD Display: 2 rows of 16 characters with backlight
• Audible indicator: Internal buzzer, 90 dBA at 1ft
• External Drivers (2): 24VDC, maximum 250 mA
• Relay On Delay: 0 – 15 minutes in 1 second increments
• Relay Off Delay: 0 – 15 minutes in 1 second increments
• RS-485 operates in the Modbus RTU Transmission Mode
• Status Indicators (LED): Power, ALARM/warning, Hush, Relay 1, Relay 2 & Relay 3
Installation & Connection
Gas detection and exhaust fan control is provided by a Macurco DVP-120M system. System wiring includes main power connection for the DVP-120M, 4-20mA current loop, RS-485 serial interface and 24VDC power connections between the remote detectors and the DVP-120M, the fan control and alarm connections from
the DVP-120M to the building ventilation and automation systems. The DVP-120M control panel has three
relays which can be used for ventilation fan control or alarm signaling. The ventilation control function operates
independently from the alarm function. It provides the ability to configure the DVP-120M for control of one to
three zones. Each zone can respond to gas levels at one or more of the sensors, with configurable rising and falling concentrations for each gas type. Each zone can also be controlled based on the time of day.
®
TYPICAL CONNECTION OF THE DVP-120M CONTROL PANEL COVERAGE UP TO 500,000 SQAURE FEET
Up to 29 Detectors per
RS-485 Channel (3)
N.C.
N.O.
COM
COM
A
B
COM
SHD
-24 VDC
-1 LOOP
+1 LOOP
+24 VDC
12 Analog Channels
24 VDC
A
B
COM
SHD
power
3 2 1
+
output
CM-6
Exhaust Fans
120VAC
Power
120VAC
ALARM
coil
coil
STARTER RELAYS
120VAC COILS
Main Fan Power
Gnd
4
1
3
2
- Horn
- Strobe
+ Horn
+ Strobe
Panel Power
120/250 VAC
LN
1 13 3 4 5 6 7 8 92
MACURCO™ DVP-120M
DETECTION AND VENTILATION
CONTROL PANEL
Relay 1
N.C.
N.O.
Relay 2 Relay 3
N.C.
N.O.
COM
Made in the U.S.A. with US and imported materials
© Aerionics 2015. All rights reserved.
Made in the USA
Macurco is a trademark of Aerionics, Inc.